Fluke Cv400 Clirvu Application Note UL Recognized And Listed

2015-09-09

: Fluke Fluke-Cv400-Clirvu-Application-Note-808408 fluke-cv400-clirvu-application-note-808408 fluke pdf

Open the PDF directly: View PDF PDF.
Page Count: 1

From the Fluke Digital Library @ www.fluke.com/library
Application Note
UL Recognized and UL Listed:
What’s the difference?
Thermal imaging or infrared
imaging has become com-
monplace in most daily plant
operations. As the number of
infrared scans increases, so too
does the exposure to and risk
of arc flash. Enclosures must
be opened to scan with infra-
red (IR) and doing so greatly
increases the likelihood of an
arc flash explosion. IR windows
can mitigate this risk by allowing
infrared scans to be performed
without opening enclosures,
virtually eliminating the risk of
an arc flash.
While the reasons to install
IR Windows are quite clear, a
common question posed by those
considering the installation of IR
Windows into UL Listed switch-
gear is ‘Won’t the UL Recognized
IR Window de-rate my UL Listed
switchgear?’ The misconception
is that UL Recognized products
are somehow inferior to UL Listed
products. This is not true.
UL Listed products are ‘end
products’ or products that stand
alone and are not designed to
be included as a component in
another product. A computer or
electrical switchgear are exam-
ples of end products that you buy
and use as-is.
In contrast, UL Recognized
products are considered to be
components of an end product.
A UL Recognized product is not
considered to be an end prod-
uct in and of itself, as it must
be incorporated into an end
product in order to be used with
any real purpose. For instance,
a computer micro-chip is UL
Recognized because it would
never be used on its own; it
would always be installed in to
a computer. Similarly, electrical
fuses are UL Recognized because
they are designed to be used in
electrical control systems.
IR Windows are UL Rec-
ognized instead of UL Listed
because IR Windows serve no
real purpose by themselves.
They need to be installed into
an electrical enclosure, or onto
something, to be used for their
intended purpose. All Fluke IR
Windows are tested to meet
the UL50V Infrared Viewport
Standard. This standard outlines
the necessary testing criteria to
achieve UL Recognition.
To further this point, let’s
take a look at how electrical
switchgear manufacturers use IR
Windows.
A switchgear manufacturer
has various types of UL Listed
switchgear. In order to maintain
that UL Listing, the IR Window is
added to the switchgear manu-
facturer’s UL Listing or file as a
©2012 Fluke Corporation. Specifications subject to change without notice.
Printed in U.S.A. 3/2012 4161283A A-EN-N
Modification of this document is not permitted without written permission
from Fluke Corporation.
Fluke. Not just infrared. Infrared you can use.
UL Recognized component. This
allows the manufacturer to install
IR Windows into their switchgear
during assembly, prior to delivery
to the customer without violating
their UL Listing. As long as the
IR Window is installed according
to the IR Window manufacturer’s
instructions (instructions that
are approved by UL during the
UL50V testing), the UL Listing of
the switchgear is maintained.