HOLD
Tactile
Barrier
®
T5-600/T5-1000
Electrical Tester
Instruction Card
Voltage Indicator
V
T5-600 max: 600 V CAT III
T5-1000 max: 1000 V CAT III, 600 V CAT IV
HOLD
V
45 Hz - 66 Hz
T5-600 max: 600 V rms CAT III
T5-1000 max: 1000 V rms CAT III, 600 V rms CAT IV
HOLD
V
AC/DC
Automatic
Selection
V
AC/DC
Automatic
Selection
Continuity & Resistance
1000 Ω
Range
Greater than
400 Ω
Open Short
Less than
25 Ω
A
0.5"(12.9 mm)
maximum
OK
OK OK
Sensor
Zone 1 Wire
only
Display HOLD
1
2
3
HOLD
HOLD
HOLD
HOLD
AC
AC
A
AC
December 2001, Rev.3, 1/13
(Czech, Polish, Russian, Turkish, Arabic)
2001 - 2013 Fluke Corporation. All rights reserved.
Warning
Read the T5-600/T5-1000 Safety Sheet before
using this tester.
Bu test cihazını kullanmadan önce
T5-600/T5-1000 Güvenlik Broşürü'nü okuyun.
Перед использованием данного
измерительного прибора прочтите
Инструкции по технике безопасности
T5-600/T5-1000.
Przed użyciem próbnika należy przeczytać
instrukcje dotyczące bezpieczeństwa
zamieszczone w dokumencie T5-600/T5-1000.
Před použitím této zkoušečky si přečtete
bezpečnostní informace k modelu
T5-600/T5-1000.
Auto Off
45 min
LO
+
+
Do not
overtighten
screw
OFF
2 AA
+
+
Specifications
Specifications subject to change without notice.
Calibration 1-year calibration cycle
Temperature
Operating:
Storage:
-10 °C to +50 °C (14 °F to 122 °F)
-30 °C to +60 °C (-22 °F to +140 °F)
Altitude
Operating:
Storage:
2000 m (6562 ft)
10,000 m (32808 ft)
Relative
Humidity
0 % to 95 %, 5 °C to 30 °C
(41 °F to 86 °F); 0 % to 75 %,
30 °C to 40 °C
(86 °F to 104 °F); 0 % to 45 %,
40 °C to 50 °C
(104 °F to 122 °F)
Battery Type
and Life
AA (2); 360 hours continuous with
alkaline; 125 hours continuous with
zinc chloride
RF Field
Specification
0.5 % full scale + (specified accuracy)
at 3 V / m
Enclosure
Rating
IP 52 per IEC 60529, no vacuum
applied
Temperature
coefficient
0.1 x (specified accuracy) / °C for <18
°C or >28 °C (< 64.4 °F or > 82.4 °F)
Accuracy ± ( [ % of reading] + [number of least
significant digits] )
Accuracy is specified for 1 year after
calibration, at 18 °C to 28 °C
(64 °F to 82 °F) with relative humidity
to 90 %. AC conversions are ac-
coupled, average responding, and
calibrated to the rms value of a sine
wave input.
Function
T5-600
Range
(600 V
CAT III)
T5-1000
Range
(1000 V
CAT III)
Reso-
lution Accuracy
600 V
rms
1000 V
rms
1 V ±(1.5 % + 2 digits)
45 Hz - 66 Hz
600 V 1000 V 1 V ±(1 % + 1 digit)
100.0 A 100.0 A 0.1 A ±(3 % + 3 digits)
45 Hz - 66 Hz
1000 Ω1000 Ω1 Ω±(1 % + 2 digits)
Replacement Parts
Test Lead Assembly.
Replace only with Fluke double-insulated
leads ( ) See "Accessories" for available
probes.
PN 648029
PN 2091779
rooD yrettaB
PN 8758161
wercS rooD yrettaB
Accessories
H
Use only specified replacement parts.
5 Belt Holster
TP1 Probe Set, Flat-Blade
AC285 SureGrip™ Alligator Clips
AC220 SureGrip™ Alligator Clips
Service Information Sheet, PN 686953
To contact Fluke, call:
USA: 1-800-44-FLUKE (1-800-443-5853)
Canada: 1-800-36-FLUKE (1-800-363-5853)
Europe: +31 402-675-200
Japan: +81-67143114
Singapore: +65-738-5655
Anywhere in the world: +1-425-446-5500
Visit Fluke's Web site at www.fluke.com.
Safety ......................... IEC 61010-1: Pollution Degree 2
Electromagnetic
Environment ................ IEC 61326-1: Portable
Warning
Disconnect test leads from power source
before opening battery door.