The Most Trusted Name In Measurement
Coriolis Mass Flowmeter
Proline Promass 80
Operating Instructions
Issue/Rev. 0.0 (5/09) Bulletin MN0M028
Valid as of version
V 3.05.XX (device software)
Brief operating instructions Proline Promass 80 PROFIBUS PA
2
Brief operating instructions
These brief operating instructions show you how to configure your measuring device quickly and
easily:
!Note!
Always start troubleshooting with the checklist on Page 69 if faults occur after commissioning or
during operation. The routine takes you directly to the cause of the problem and the appropriate
remedial measures.
Safety instructions Page 7
Installation Page 13
Wiring Page 26
Switching on the measuring device Page 46
Display and operating elements Page 37
Basic configuration (device parameters, automation functions) Page 46 ff.
Configuration programs from various manufacturers can be used to configure device-specific parameters and to specify
automation functions for the PROFIBUS interface.
!Note!
If the measuring device is equipped with a local display, device-specific parameters and functions can be configured easily
and quickly using the "Commissioning" Quick Setup menu, e.g. language of the UI, measured variables, engineering
units, signal type etc. see next page
System integration
and cyclic data transmission
Page 50 ff.
Use of the device master files (GSD files)
Cyclic data transmission, configuration examples
Application-specific commissioning Page 39
Device functions, zero point adjustment, density adjustment
Customer-specific configuration Page 39 ff.
Complex measuring operations necessitate additional functions that you can select and configure as necessary with the
aid of the function matrix, and customize to suit your process parameters.
!Note!
All functions are described in detail, as is the function matrix itself, in the "Description of Device Functions" manual
which is a separate part of these Operating Instructions.
Proline Promass 80 PROFIBUS PA Brief operating instructions
3
QUICK SETUP "Commissioning"
!Note!
More detailed information on running Quick Setup menus, especially for devices without a local
display, can be found in the "Commissioning" section. Page 47 ff.
a0004749-en
Fig. 1: Quick Setup "Commissioning"
+
++
EE
HOME-POSITION
Esc
E
+
-
XXX.XXX.XX
Yes
Yes
No
No
Mass flow Volume flow Density
Selection System Units
Configuration another unit ?
Automatically configuration display ?
Temperature Quit
Unit
Mass flow
Unit
flowVolume
Unit
Density
Unit
Temperature
Unit
Totalizer
Unit
Totalizer
Automatically
parameterization
of the display
Language
Pre-setting
Quick Setup Quick Setup
Commission
n
o
Corr. Vol. flow
Unit
Corr. Vol. flow
Unit
Ref. Density
Fix
Ref. Density
p
Selection pre-settings
Actual SettingsDeliver Settingsy
m
Set Unit to Bus
SET UNITSOFF
m
Brief operating instructions Proline Promass 80 PROFIBUS PA
4
Proline Promass 80 PROFIBUS PA Table of contents
5
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 7
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Installation, commissioning and operation . . . . . . . . 7
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5 Notes on safety conventions and icons . . . . . . . . . . . 8
2 Identification . . . . . . . . . . . . . . . . . . . . 9
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.1 Nameplate of the transmitter . . . . . . . . . . . . 9
2.1.2 Nameplate of the sensor . . . . . . . . . . . . . . 10
2.1.3 Nameplate for connections . . . . . . . . . . . . 11
2.2 Certificates and approvals . . . . . . . . . . . . . . . . . . . 12
2.3 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 12
3 Installation . . . . . . . . . . . . . . . . . . . . . 13
3.1 Incoming acceptance, transport and storage . . . . . . 13
3.1.1 Incoming acceptance . . . . . . . . . . . . . . . . . 13
3.1.2 Transport . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 14
3.2.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.2 Mounting location . . . . . . . . . . . . . . . . . . . 14
3.2.3 Orientation . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.4 Special installation instructions . . . . . . . . . 18
3.2.5 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.6 Thermal insulation . . . . . . . . . . . . . . . . . . 21
3.2.7 Inlet and outlet runs . . . . . . . . . . . . . . . . . 21
3.2.8 Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.2.9 Limiting flow . . . . . . . . . . . . . . . . . . . . . . . 21
3.3 Installation instructions . . . . . . . . . . . . . . . . . . . . . 22
3.3.1 Turning the transmitter housing . . . . . . . . 22
3.3.2 Installing the wall-mount housing . . . . . . . 23
3.3.3 Turning the local display . . . . . . . . . . . . . . 25
3.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 25
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 26
4.1 PROFIBUS PA cable specifications . . . . . . . . . . . . . 26
4.1.1 Cable type . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.1.2 Maximum overall cable length . . . . . . . . . . 27
4.1.3 Maximum spur length . . . . . . . . . . . . . . . . 27
4.1.4 Number of field devices . . . . . . . . . . . . . . . 27
4.1.5 Bus termination . . . . . . . . . . . . . . . . . . . . . 27
4.1.6 Further information . . . . . . . . . . . . . . . . . . 27
4.2 Shielding and grounding . . . . . . . . . . . . . . . . . . . . 28
4.3 Connecting the remote version . . . . . . . . . . . . . . . 29
4.3.1 Connecting connecting cable for sensor/
transmitter . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.2 Cable specification for connecting cable . . . 29
4.4 Connecting the measuring unit . . . . . . . . . . . . . . . 30
4.4.1 Terminal assignment . . . . . . . . . . . . . . . . . 30
4.4.2 Transmitter connection . . . . . . . . . . . . . . . 30
4.4.3 Fieldbus connector . . . . . . . . . . . . . . . . . . 32
4.5 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . 34
4.6 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 35
5 Operation . . . . . . . . . . . . . . . . . . . . . . 36
5.1 Quick operation guide . . . . . . . . . . . . . . . . . . . . . . 36
5.2 Local display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2.1 Display and operating elements . . . . . . . . . 37
5.2.2 Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.3 Brief operating instructions on the
function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.1 General notes . . . . . . . . . . . . . . . . . . . . . . 40
5.3.2 Enabling the programming mode . . . . . . . . 40
5.3.3 Disabling the programming mode . . . . . . . . 40
5.4 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.4.1 Type of error . . . . . . . . . . . . . . . . . . . . . . . 40
5.4.2 Error message type . . . . . . . . . . . . . . . . . . . 41
5.5 Operating options . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.5.1 FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.5.2 Operating program "SIMATIC PDM"
(Siemens) . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.5.3 Device description files for
operating programs . . . . . . . . . . . . . . . . . . 43
5.6 PROFIBUS PA hardware settings . . . . . . . . . . . . . 44
5.6.1 Hardware write protection . . . . . . . . . . . . . 44
5.6.2 Configuring the device address . . . . . . . . . . 45
6 Commissioning . . . . . . . . . . . . . . . . . . 46
6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.2 Switching on the measuring device . . . . . . . . . . . . 46
6.3 Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.3.1 Quick Setup "Commissioning" . . . . . . . . . . 47
6.4 Commissioning the PROFIBUS PA interface . . . . . 48
6.5 PROFIBUS PA system integration . . . . . . . . . . . . . . 50
6.5.1 Device master file (GSD file) . . . . . . . . . . . 50
6.5.2 Selecting the GSD file in the
measuring device . . . . . . . . . . . . . . . . . . . . 52
6.5.3 imum number of writes . . . . . . . . . . . . . . 52
6.6 Cyclic data transmission PROFIBUS PA . . . . . . . . . 53
6.6.1 Block model . . . . . . . . . . . . . . . . . . . . . . . 53
6.6.2 Modules for cyclic data transmission . . . . . 53
6.6.3 Description of the modules . . . . . . . . . . . . 54
6.6.4 Configuration examples with Simatic S7
HW-Konfig . . . . . . . . . . . . . . . . . . . . . . . . 60
6.7 Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.7.1 Zero point adjustment . . . . . . . . . . . . . . . . 62
6.7.2 Density adjustment . . . . . . . . . . . . . . . . . . 64
6.8 Rupture disk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.9 Purge and pressure monitoring connections . . . . . . 65
6.10 Data storage device (HistoROM) . . . . . . . . . . . . . . 65
6.10.1 HistoROM/S–DAT (sensor–DAT) . . . . . . . 65
Proline Promass 80 PROFIBUS PA Table of contents
6
7 Maintenance . . . . . . . . . . . . . . . . . . . . 66
7.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.2 Cleaning with pigs (Promass H, I, S, P) . . . . . . . . . . 66
7.3 Replacing seals . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8 Accessories . . . . . . . . . . . . . . . . . . . . . 67
8.1 Device-specific accessories: . . . . . . . . . . . . . . . . . . 67
8.2 Measuring principle-specific accessories: . . . . . . . . 67
8.3 Service-specific accessories: . . . . . . . . . . . . . . . . . . 68
9 Troubleshooting . . . . . . . . . . . . . . . . . 69
9.1 Troubleshooting instructions . . . . . . . . . . . . . . . . . 69
9.2 System error messages . . . . . . . . . . . . . . . . . . . . . . 71
9.2.1 Displaying the device status on
PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . 71
9.2.2 List of system error messages . . . . . . . . . . 72
9.3 Process error messages . . . . . . . . . . . . . . . . . . . . . . 77
9.3.1 Displaying the device status on
PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . 77
9.3.2 List of process error messages . . . . . . . . . . 77
9.4 Process errors without messages . . . . . . . . . . . . . . 79
9.5 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.5.1 Removing and installing
printed circuit boards . . . . . . . . . . . . . . . . . 81
9.5.2 Replacing the device fuse . . . . . . . . . . . . . . 85
9.6 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.7 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.8 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . 86
10 Technical data . . . . . . . . . . . . . . . . . . . 88
10.1 Technical data at a glance . . . . . . . . . . . . . . . . . . . 88
10.1.1 Applications . . . . . . . . . . . . . . . . . . . . . . . . 88
10.1.2 Function and system design . . . . . . . . . . . . 88
10.1.3 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
10.1.4 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
10.1.5 Power supply . . . . . . . . . . . . . . . . . . . . . . . 91
10.1.6 Performance characteristics . . . . . . . . . . . . 92
10.1.7 Operating conditions: Installation . . . . . . . . 98
10.1.8 Operating conditions: Environment . . . . . . 99
10.1.9 Operating conditions: Process . . . . . . . . . . 99
10.1.10 Mechanical construction . . . . . . . . . . . . . 109
10.1.11 Human interface . . . . . . . . . . . . . . . . . . . 114
10.1.12 Certificates and approvals . . . . . . . . . . . . 115
10.1.13 Ordering information . . . . . . . . . . . . . . . 116
10.1.14 Accessories . . . . . . . . . . . . . . . . . . . . . . . 116
10.1.15 Documentation . . . . . . . . . . . . . . . . . . . 116
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Proline Promass 80 PROFIBUS PA Safety instructions
7
1 Safety instructions
1.1 Designated use
The measuring device described in these Operating Instructions is to be used only for measuring the
mass flow rate of liquids and gases. At the same time, the system also measures fluid density and
fluid temperature. These parameters are then used to calculate other variables such as volume flow.
Fluids with widely differing properties can be measured.
Examples:
• Chocolate, condensed milk, liquid sugar
• Oils, fats
• Acids, alkalis, lacquers, paints, solvents and cleaning agents
• Pharmaceuticals, catalysts, inhibitors, suspensions
• Gases, liquefied gases, etc.
Resulting from incorrect use or from use other than that designated the operational safety of the
measuring devices can be suspended. The manufacturer accepts no liability for damages being
produced from this.
1.2 Installation, commissioning and operation
Note the following points:
• Installation, connection to the electricity supply, commissioning and maintenance of the device
must be carried out by trained, qualified specialists authorized to perform such work by the
facility's owner-operator. The specialist must have read and understood these Operating
Instructions and must follow the instructions they contain.
The device must be operated by persons authorized and trained by the facility's owner-operator.
Strict compliance with the instructions in the Operating Instructions is mandatory.
• FMC Technologies is willing to assist in clarifying the chemical resistance properties of parts
wetted by special fluids, including fluids used for cleaning. However small changes in
temperature, concentration or the degree of contamination in the process can result in changes
of the chemical resistance properties. Therefore, FMC Technologies can not guarantee or accept
liability for the chemical resistance properties of the fluid wetted materials in a specific application.
The user is responsible for the choice of fluid wetted materials in regards to their in-process
resistance to corrosion.
• If carrying out welding work on the piping, the welding unit may not be grounded by means of
the measuring device.
• The installer must ensure that the measuring system is correctly wired in accordance with the
wiring diagrams. The transmitter must be grounded, except in cases where
special protective measures have been taken (e.g. galvanically isolated power supply SELV
or PELV).
• Invariably, local regulations governing the opening and repair of electrical devices apply.
1.3 Operational safety
Note the following points:
• Measuring systems for use in hazardous environments are accompanied by separate
"Ex documentation", which is an integral part of these Operating Instructions. Strict compliance
with the installation instructions and ratings as stated in this supplementary documentation is
mandatory.
The symbol on the front of this supplementary Ex documentation indicates the approval and the
certification body (e.g. 0Europe, 2 USA, 1 Canada).
• The measuring device complies with the general safety requirements in accordance with
EN 61010-1, the EMC requirements of IEC/EN 61326, and NAMUR recommendation NE 21,
NE 43 and NE 53.
Safety instructions Proline Promass 80 PROFIBUS PA
8
For measuring systems used in SIL 2 applications, the separate manual on functional safety must
be observed.
• Due to the performance rate in the electronic components, the maximum heating of the outer
housing surfaces is 10 K. When hot media are passed through the measuring tube, the surface
temperature of the housing increases. With regard to the sensor, in particular, you should expect
temperatures that can be close to the temperature of the medium. If the temperature of the
medium is high, ensure staff are protected against burns and scalds.
• The manufacturer reserves the right to modify technical data without prior notice. Your FMC
Technologies distributor will supply you with current information and updates to this Operating
Instructions.
1.4 Return
The following procedures must be carried out before a flowmeter requiring repair or calibration, for
example, is returned to FMC Technologies:
• Always enclose a duly completed "Declaration of contamination" form. Only then can FMC
Technologies transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as per
Regulation (EC) 1907/2006 REACH.
• Remove all residues. Pay special attention to the grooves for seals and crevices which could
contain residues. This is particularly important if the substance is hazardous to health, e.g.
flammable, toxic, caustic, carcinogenic, etc.
With Promass A and Promass M the threaded process connections must first be removed from the
sensor and then cleaned.
!Note!
You will find a preprinted "Declaration of contamination" form at the back of this manual.
#Warning!
• Do not return a measuring device if you are not absolutely certain that all traces of hazardous
substances have been removed, e.g. substances which have penetrated crevices or diffused
through plastic.
• Costs incurred for waste disposal and injury (burns, etc.) due to inadequate cleaning will be
charged to the owner-operator.
1.5 Notes on safety conventions and icons
The devices are designed to meet state-of-the-art safety requirements, have been tested, and left the
factory in a condition in which they are safe to operate. The devices comply with the applicable
standards and regulations in accordance with EN 61010-1 "Protection Measures for Electrical
Equipment for Measurement, Control, Regulation and Laboratory Procedures". The devices can,
however, be a source of danger if used incorrectly or for anything other than the designated use.
Consequently, always pay particular attention to the safety instructions indicated in these Operating
Instructions by the following icons:
#Warning!
"Warning" indicates an action or procedure which, if not performed correctly, can result in injury
or a safety hazard. Comply strictly with the instructions and proceed with care.
"Caution!
"Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect
operation or destruction of the device. Comply strictly with the instructions.
!Note!
"Note" indicates an action or procedure which, if not performed correctly, can have an indirect
effect on operation or trigger an unexpected response on the part of the device.
Proline Promass 80 PROFIBUS PA Identification
9
2 Identification
2.1 Device designation
The "Promass 80/83" flow measuring system consists of the following components:
• Promass 80 or 83 transmitter.
• Promass F, Promass M, Promass E, Promass A, Promass H, Promass I, Promass S or Promass P
sensor.
Two versions are available:
• Compact version: transmitter and sensor form a single mechanical unit.
• Remote version: transmitter and sensor are installed separately.
2.1.1 Nameplate of the transmitter
a0004708
Fig. 2: Nameplate specifications for the "Promass 80" transmitter (example)
1 Order code/serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits.
2 Power supply/frequency: 16 to 62 V DC / 20 to 55 V AC / 50 to 60 Hz
Power consumption: 15 VA / W
3 Available inputs/outputs:
PROFIBUS-PA
4 Reserved for information on special products
5 Please refer to operating instructions / documentation
6 Reserved for additional information on device version (approvals, certificates)
7 Degree of protection
8 Ambient temperature range
N12895
Order Code:
Ser.No.:
TAG No.:
16-62VDC/20-55VAC
50-60Hz 15VA/W
IP67/NEMA/Type4X80F25-XXXXXXXXXXXX
12345678901
ABCDEFGHJKLMNPQRST
–20°C (–4°F) < Tamb < +60°C (+140°F)
i
1
2
3
4
Pat. US 5,479,007
Pat. US 4,768,384
Pat. UK 261 435
5,648,616
4,801,897
EP 262 573 EP 618 680
PROFIBUS-PA Profile 3.0
R
Promass 80
5
6
7
8
Identification Proline Promass 80 PROFIBUS PA
10
2.1.2 Nameplate of the sensor
a0004688
Fig. 3: Nameplate specifications for the "Promass F" sensor (example)
1 Order code / Serial number: See the specifications on the order confirmation for the meanings of the individual
letters and digits.
2 Calibration factor with zero point
3 Device nominal diameter/nominal pressure
4 Flange nominal diameter/nominal pressure
5 Measuring tube material
6 Max. fluid temperature
7 Secondary containment pressure range
8 Density accuracy
9 Additional information (examples):
5P-CAL: with 5-point calibration
3.1: with 3.1 certificate for wetted materials
10 Reserved for information on special products
11 Ambient temperature range
12 Please refer to operating instructions / documentation
13 Degree of protection
14 Flow direction
15 Reserved for additional information on device version (approvals, certificates)
DN25 / 1"
Size:
-20°C (-4°F) < Tamb < +60°C (+140°F)
Pat. US 5,796,011
i
NEMA/Type 4X
ABCDEFGHJKLMNPQRST
12345678901
2.5100 / -11
83F25-XXXXXXXXXXXX
DN25 DIN/EN PN100 pnom =PS= 100bar
1.4404 / 316L, 1.4539 / 904L
-50°C...+200°C / -58°F...+392°F
40bar / 600psi Container
5P-CAL, 3.1
+/- 0.001g/cc
K-factor:
TM:
Materials:
Density cal.:
Ser.No.:
TAG No.:
Order Code:
5,610,342
IP67
N12895
PROMASS F
1
2
4
5
6
7
8
9
13
14
3
11
10
12
15
Proline Promass 80 PROFIBUS PA Identification
11
2.1.3 Nameplate for connections
a0001665
Fig. 4: Nameplate specifications for Proline sensor (example)
1 Serial number
2 Possible configuration of current output
3 Possible configuration of relay contacts
4 Terminal assignment, cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC
5 Pending signals at the inputs and outputs Page 91 ff.
possible configuration and terminal assignment
6 Version of device software currently installed (inclusive language group)
7 Installed communication type
8PROFIBUS ID No.
9 Date of installation
10 Language group
11 Current updates to data specified in points 6 to 9
Communication:
Drivers:
Device SW:
ID XXXX (HEX)
XX.XX.XX
PROFIBUS PA
Date: DD MMM YYYY
Ex works / ab Werk / réglages usine:
26(+) / 27(-)
NC:
Versorgung /
Tension d'alimentation
Observer manuel d'instruction
See operating manual
Betriebsanleitung beachten
26=PA+
27=PA-
PROFIBUS PA (Profile 3.0)
XXXXXXXXXXXSer.No.:
Supply /
24(+) / 25(-)
22(+) / 23(-)
20(+) / 21(-)
N/L-
PE
A:
NO:
P:
L1/L+
12
FEK1512–2
X
active
passive
normally open contact
normally closed contact
Update 1 Update 2
2
3
1
4
5
6
7
8
9
10
(WEA)
Identification Proline Promass 80 PROFIBUS PA
12
2.2 Certificates and approvals
The devices are designed in accordance with good engineering practice to meet state-of-the-art
safety requirements, have been tested, and left the factory in a condition in which they are safe to
operate. The devices comply with the applicable standards and regulations in accordance with
EN 61010-1 "Protection Measures for Electrical Equipment for Measurement, Control, Regulation
and Laboratory Procedures" and with the EMC requirements of IEC/EN 61326.
The measuring system described in these Operating Instructions thus complies with the statutory
requirements of the EC Directives. Endress+Hauser confirms successful testing of the device by
affixing to it the CE mark.
The measuring system complies with the EMC requirements of the "Australian Communications
and Media Authority (ACMA)".
The flowmeter has successfully passed all the test procedures carried out and is certified and
registered by the PNO (PROFIBUS User Organization).
The device thus meets all the requirements of the following specifications:
• Certified to PROFIBUS Specification Profile 3.0 version
(Device certification number: provided upon request)
• The measuring device can also be operated with certified devices of other manufacturers
(interoperability).
2.3 Registered trademarks
KALREZ® and VITON®
Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA
TRI-CLAMP®
Registered trademark of Ladish & Co., Inc., Kenosha, USA
SWAGELOK®
Registered trademark of Swagelok & Co., Solon, USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, D
HistoROM™, S-DAT®, FieldCare®, Fieldcheck®, Applicator®
Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH
Proline Promass 80 PROFIBUS PA Installation
13
3 Installation
3.1 Incoming acceptance, transport and storage
3.1.1 Incoming acceptance
On receipt of the goods, check the following points:
• Check the packaging and the contents for damage.
• Check the shipment, make sure nothing is missing and that the scope of supply matches your
order.
3.1.2 Transport
The following instructions apply to unpacking and to transporting the device to its final location:
• Transport the devices in the containers in which they are delivered.
• The covers or caps fitted to the process connections prevent mechanical damage to the sealing
faces and the ingress of foreign matter to the measuring tube during transportation and storage.
Consequently, do not remove these covers or caps until immediately before installation.
Do not lift measuring devices of nominal diameters > DN 40 (> 1½") by the transmitter housing
or the connection housing in the case of the remote version (Fig. 5). - Use webbing slings slung
round the two process connections. Do not use chains, as they could damage the housing.
• In the case of the Promass M / DN 80 sensor, use only the lifting eyes on the flanges to lift the
assembly!
#Warning!
Risk of injury if the measuring device slips. The center of gravity of the assembled measuring device
might be higher than the points around which the slings are slung.
At all times, therefore, make sure that the device does not unexpectedly turn around its axis or slip.
a0004294
Fig. 5: Instructions for transporting sensors with > DN 40 (> 1½")
Installation Proline Promass 80 PROFIBUS PA
14
3.1.3 Storage
Note the following points:
• Pack the measuring device in such a way as to protect it reliably against impact for storage (and
transportation). The original packaging provides optimum protection.
• The permissible storage temperature is –40 to +80 °C (–40 °F to +176 °F), preferably +20 °C
(+68 °F).
• Do not remove the protective covers or caps on the process connections until you are ready to
install the device.
• The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
3.2 Installation conditions
Note the following points:
• No special measures such as supports are necessary. External forces are absorbed by the
construction of the instrument, for example the secondary containment.
• The high oscillation frequency of the measuring tubes ensures that the correct operation of the
measuring system is not influenced by pipe vibrations.
• No special precautions need to be taken for fittings which create turbulence (valves, elbows,
T-pieces, etc.), as long as no cavitation occurs.
• For mechanical reasons and in order to protect the pipe, it is advisable to support heavy sensors.
3.2.1 Dimensions
All the dimensions and lengths of the sensor and transmitter are provided in the separate
documentation "Technical Information"
3.2.2 Mounting location
Entrained air or gas bubbles forming in the measuring tube can result in an increase in measuring
errors.
Avoid the following locations in the pipe installation:
• Highest point of a pipeline. Risk of air accumulating.
• Directly upstream of a free pipe outlet in a vertical pipeline.
a0003605
Fig. 6: Mounting location
The proposed configuration in the following diagram, however, permits installation in a vertical
pipeline. Pipe restrictors or the use of an orifice plate with a smaller cross-section than the nominal
diameter prevent the sensor from running empty during measurement.
Proline Promass 80 PROFIBUS PA Installation
15
a0003597
Fig. 7: Installation in a vertical pipe (e.g. for batching applications)
1 = Supply tank , 2 = Sensor, 3 = Orifice plate, pipe restrictions (see Table), 4 = Valve, 5 = Batching tank
System pressure
It is important to ensure that cavitation does not occur, because it would influence the oscillation
of the measuring tube. No special measures need to be taken for fluids which have properties similar
to water under normal conditions.
In the case of liquids with a low boiling point (hydrocarbons, solvents, liquefied gases) or in suction
lines, it is important to ensure that pressure does not drop below the vapor pressure and that the
liquid does not start to boil. It is also important to ensure that the gases that occur naturally in many
liquids do not outgas. Such effects can be prevented when system pressure is sufficiently high.
For this reason, the following installation locations are preferred:
• Downstream from pumps (no danger of vacuum)
• At the lowest point in a vertical pipe.
1
2
3
4
5
DN
Ø Orifice plate, pipe
restrictor
DN
Ø Orifice plate, pipe
restrictor
mm inch mm inch
1 1/24" 0.8 0.03 40 1½" 22 0.87
2 1/12" 1.5 0.06 40 FB 1½" 35 1.38
4 1/8" 3.0 0.12 50 2" 28 1.10
8 3/8" 6 0.24 50 FB 2" 54 2.00
15 ½" 10 0.40 80 3" 50 2.00
15 FB ½" 15 0.60 100 4" 65 2.60
25 1" 14 0.55 150 6" 90 3.54
25 FB 1" 24 0.95 250 10" 150 5.91
FB = Full bore versions of Promass I
Installation Proline Promass 80 PROFIBUS PA
16
3.2.3 Orientation
Make sure that the direction of the arrow on the nameplate of the sensor matches the direction of
flow (direction in which the fluid flows through the pipe).
Orientation Promass A
Vertical:
Recommended orientation with upward direction of flow. When fluid is not flowing, entrained
solids will sink down and gases will rise away from the measuring tube. The measuring tubes can
be completely drained and protected against solids buildup.
Horizontal:
When installation is correct the transmitter housing is above or below the pipe. This arrangement
means that no gas or solid deposits can accumulate in the curved measuring tube (single-tube
system).
Do not install the sensor in such a way that it is suspended in the pipe, in other words without
support or attachment. This is to avoid excessive strain at the process connection. The base plate of
the sensor housing is designed for mounting on a tabletop, wall or post.
a0003606
Fig. 8: Vertical and horizontal orientation (Promass A)
Orientation Promass F, M, E, H, I, S, P
Make sure that the direction of the arrow on the nameplate of the sensor matches the direction of
flow (direction in which the fluid flows through the pipe).
Vertical:
Recommended orientation with upward direction of flow (View V). When fluid is not flowing,
entrained solids will sink down and gases will rise away from the measuring tube. The measuring
tubes can be completely drained and protected against solids buildup.
Horizontal (Promass F, M, E):
The measuring tubes of Promass F, M and E must be horizontal and beside each other. When
installation is correct the transmitter housing is above or below the pipe (View H1/H2). Always
avoid having the transmitter housing in the same horizontal plane as the pipe.
Proline Promass 80 PROFIBUS PA Installation
17
Horizontal (Promass H, I, S, P):
Promass H, I, S and P can be installed in any orientation in a horizontal pipe run.
In order to ensure that the maximum permissible ambient temperature for the transmitter
(–20 to +60 °C (–4 to +140° F), optional –40 to +60 °C (–40 to +140 °F)) is not exceeded, we
recommend the following orientations:
m = For fluids with very high temperatures > 200 °C (392 °F), we recommend the horizontal
orientation with the transmitter head pointing downwards (Fig. H2) or the vertical orientation
(Fig. V).
n = For fluids with low temperatures, we recommend the horizontal orientation with the
transmitter head pointing upwards (Fig. H1) or the vertical orientation (Fig. V).
Promass F, M, E
Standard, compact
Promass F, M, E
Standard, remote
Promass F
High-temperature,
compact
Promass F
High-temperature,
remote
Promass H, I, S, P
Standard, compact
Promass H, I, S, P
Standard, compact
Abb. V:
Vertical orientation
a0004572
ÐÐ ÐÐ ÐÐ ÐÐ ÐÐ ÐÐ
Abb. H1:
Horizontal
orientation
Transmitter head up
a0004576
ÐÐ ÐÐ
TM > 200 °C
( 392 °F)
m
Ð
TM > 200 °C
( 392 °F)
m
ÐÐ ÐÐ
Abb. H2:
Horizontal
orientation
Transmitter head
down a0004580
ÐÐ
n
ÐÐ
n
ÐÐ
n
ÐÐ
n
ÐÐ
n
ÐÐ
n
Abb. H3:
Horizontal
orientation
Transmitter head to
the side a0007558
✘✘ ÐÐ ÐÐ
ÐÐ = Recommended orientation
Ð = Orientation recommended in certain situations
= Impermissible orientation
Installation Proline Promass 80 PROFIBUS PA
18
3.2.4 Special installation instructions
Promass F, E, H, S and P
"Caution!
If the measuring tube is curved and the unit is installed horizontally, adapt the sensor position to
the fluid properties.
a0004581
Fig. 9: Horizontal installation of sensors with curved measuring tube.
1 Not suitable for fluids with entrained solids. Risk of solids accumulating.
2 Not suitable for outgassing fluids. Risk of air accumulating.
Promass I and P with Eccentric Tri-clamps
Eccentric Tri-Clamps can be used to ensure complete drainability when the sensor is installed in a
horizontal line. When lines are pitched in a specific direction and at a specific slope, gravity can be
used to achieve complete drainability. The sensor must be installed in the correct position with the
tube bend facing to the side, to ensure full drainability in the horizontal position. Markings on the
sensor show the correct mounting position to optimize drainability.
a0007396-ae
Fig. 10: Promass P: When lines are pitched in a specific direction and at a specific slope: as per hygienic guidelines
(21 mm/m or approximatley 2%). Gravity can be used to achieve complete drainability.
1 The arrow indicates the direction of flow (direction of fluid flow through the pipe).
2 The label shows the installation orientation for horizontal drainability.
3 The underside of the process connection is indicated by a scribed line. This line indicates the lowest point of the
eccentric process connection.
12
1
2
321 mm/m (¼ in/ft) ~2%
Proline Promass 80 PROFIBUS PA Installation
19
A0010011-ae
Fig. 11: Promass I: When lines are pitched in a specific direction and at a specific slope: as per hygienic guidelines
(21 mm/m or approximatley 2%). Gravity can be used to achieve complete drainability.
1 The arrow indicates the direction of flow (direction of fluid flow through the pipe).
2 The label shows the installation orientation for horizontal drainability.
3 The underside of the process connection is indicated by a scribed line. This line indicates the lowest point of the
eccentric process connection.
Promass I and P with hygienic connections
(mounting clamp with lining between clamp and instrument)
It is not necessary to support the sensor under any circumstances for operational performance. If the
requirement exists to support the sensor the following recommendation should be followed.
A0007397
Fig. 12: Promass P, mounted with mounting clamp
Esc
Esc
E
-
+
1
2
3
0.83 in/3.28 ft ( 2%)~
A
B
C
DN 8 15 25 40 50
A 298 402 542 750 1019
B 33 33 33 36.5 44.1
C 2828385675
Installation Proline Promass 80 PROFIBUS PA
20
A0010008
Fig. 13: Promass I, mounted with mounting clamp
3.2.5 Heating
Some fluids require suitable measures to avoid loss of heat at the sensor. Heating can be electric,
e.g. with heated elements, or by means of hot water or steam pipes made of copper or heating
jackets.
"Caution!
• Risk of electronics overheating! Make sure that the maximum permissible ambient temperature
for the transmitter is not exceeded. Consequently, make sure that the adapter between sensor and
transmitter and the connection housing of the remote version always remain free of insulating
material. Note that a certain orientation might be required, depending on the fluid temperature.
Page 16
• With a fluid temperature between 200 °C to 350 °C (392 to 662 °F) the remote version of the
high-temperature version is preferable.
When using electrical heat tracing whose heat is regulated using phase control or by pulse packs,
it cannot be ruled out that the measured values are influenced by magnetic fields which may
occur, (i.e. at values greater than those permitted by the EC standard (Sinus 30 A/m)). In such
cases, the sensor must be magnetically shielded (except for Promass M).
The secondary containment can be shielded with tin plates or electric sheets without privileged
direction (e.g. V330-35A) with the following properties:
Relative magnetic permeability μr 300
Plate thickness d 0.35 mm (0.0011")
• Information on permissible temperature ranges Page 99
Special heating jackets which can be ordered as accessories from FMC Technologies are available
for the sensors.
Esc
Esc
E
-
+
1
2
3
0.83 in/3.28 ft ( 2%)~
DN 8 15 15FB 25 25FB 40 40FB 50 50FB 50FB 80 80
Tri-Clamp ½" 3/4" 1" 1" 1 ½" 1 ½" 2" 2" 2 ½" 3" 2 ½" 3"
A 373 409 539 539 668 668 780 780 1152 1152 1152 1152
B 202030302828353557575757
C 404044.544.56060808090909090
Proline Promass 80 PROFIBUS PA Installation
21
3.2.6 Thermal insulation
Some fluids require suitable measures to avoid loss of heat at the sensor. A wide range of materials
can be used to provide the required thermal insulation.
a0004614-ae
Fig. 14: In the case of the Promass F high-temperature version, a maximum insulation thickness of 60 mm (2.4") must
be observed in the area of the electronics/neck.
If the device is installed horizontally (with transmitter head pointing upwards), an insulation
thickness of min. 10 mm (0.4") is recommended to reduce convection. The maximum insulation
thickness of 60 mm (2.4") must be observed.
3.2.7 Inlet and outlet runs
There are no installation requirements regarding inlet and outlet runs. If possible, install the sensor
well clear of fittings such as valves, T-pieces, elbows, etc.
3.2.8 Vibrations
The high oscillation frequency of the measuring tubes ensures that the correct operation of the
measuring system is not influenced by pipe vibrations. Consequently, the sensors require no special
measures for attachment.
3.2.9 Limiting flow
Relevant information can be found in the "Technical Data" section under Measuring range
Seite 88
Esc
E
-
+
mm (inch)
max. 60 (2.4)
max. 60 (2.4)
Installation Proline Promass 80 PROFIBUS PA
22
3.3 Installation instructions
3.3.1 Turning the transmitter housing
Turning the aluminum field housing
#Warning!
The turning mechanism in devices with EEx d/de or FM/CSA Cl. I Div. 1 classification is not the
same as that described here. The procedure for turning these housings is described in the Ex-specific
documentation.
1. Loosen the two securing screws.
2. Turn the bayonet catch as far as it will go.
3. Carefully lift the transmitter housing as far as it will go.
4. Turn the transmitter housing to the desired position (max. 2 x 90° in either direction).
5. Lower the housing into position and reengage the bayonet catch.
6. Retighten the two securing screws.
a0004302
Fig. 15: Turning the transmitter housing (aluminum field housing)
Turning the stainless steel field housing
1. Loosen the two securing screws.
2. Carefully lift the transmitter housing as far as it will go.
3. Turn the transmitter housing to the desired position (max. 2 x 90° in either direction).
4. Lower the housing into position.
5. Retighten the two securing screws.
a0004303
Fig. 16: Turning the transmitter housing (stainless steel field housing)
3
5
6
1
24
12
3
4
5
Proline Promass 80 PROFIBUS PA Installation
23
3.3.2 Installing the wall-mount housing
There are various ways of installing the wall-mount housing:
• Mounted directly on the wall
• Installation in control panel (separate mounting set, accessories) Page 24
• Pipe mounting (separate mounting set, accessories) Page 24
"Caution!
• At the mounting location, make sure that the ambient temperature does not go beyond the
permissible range – 20 to +60 °C (–4 to + °140 F), optional – 40 to +60 °C (–40 to +140 °F).
Install the device in a shady location. Avoid direct sunlight.
• Always install the wall-mount housing in such a way that the cable entries are pointing down.
Mounted directly on the wall
1. Drill the holes as illustrated in the diagram.
2. Remove the cover of the connection compartment (a).
3. Push the two securing screws (b) through the appropriate bores (c) in the housing.
Securing screws (M6): max. Ø 6.5 mm (0.26")
Screw head: max. Ø 10.5 mm (0.41")
4. Secure the transmitter housing to the wall as indicated.
5. Screw the cover of the connection compartment (a) firmly onto the housing.
a0001130-ae
Fig. 17: Mounted directly on the wall
a
bcc
90 (3.54)
35 (1.38)
192 (7.56)
81.5 (3.2)
mm (inch)
Installation Proline Promass 80 PROFIBUS PA
24
Panel mounting
1. Prepare the opening in the panel as illustrated in the diagram.
2. Slide the housing into the opening in the panel from the front.
3. Screw the fasteners onto the wall-mount housing.
4. Screw threaded rods into holders and tighten
until the housing is solidly seated on the panel wall. Afterwards, tighten the locking nuts.
Additional support is not necessary.
a0001131-ae
Fig. 18: Panel installation (wall-mount housing)
Pipe mounting
The assembly should be performed by following the instructions in the diagram.
"Caution!
If a warm pipe is used for installation, make sure
that the housing temperature does not exceed the max. permitted value of +60 °C (+140 °F).
a0001132-ae
Fig. 19: Pipe mounting (wall-mount housing)
245 (9.65)
~110 (~4.33)
210 (8.27)
+0.5 (+0.019)
–0.5 (–0.019)
+0.5 (+0.019)
–0.5 (–0.019)
mm (inch)
Ø 20…70
(Ø 0.79…2.75)
~ ~ 6.1)155 (
mm (inch)
Proline Promass 80 PROFIBUS PA Installation
25
3.3.3 Turning the local display
1. Unscrew cover of the electronics compartment from the transmitter housing.
2. Press the side latches on the display module and remove the module from the electronics
compartment cover plate.
3. Rotate the display to the desired position (max. 4 x 45 ° in both directions), and reset it onto
the electronics compartment cover plate.
4. Screw the cover of the electronics compartment firmly back onto the transmitter housing.
a0003236
Fig. 20: Turning the local display (field housing)
3.4 Post-installation check
Perform the following checks after installing the measuring device in the pipe:
4 x 45°
Device condition and specifications Notes
Is the device damaged (visual inspection)? -
Does the device correspond to specifications at the measuring point, including
process temperature and pressure, ambient temperature, measuring range, etc.?
Page 7 ff.
Installation Notes
Does the arrow on the sensor nameplate match the direction of flow through the
pipe?
-
Are the measuring point number and labeling correct (visual inspection)? -
Is the orientation chosen for the sensor correct, in other words suitable for sensor
type, fluid properties (outgassing, with entrained solids) and fluid temperature?
Page 14 ff.
Process environment / process conditions Notes
Is the measuring device protected against moisture and direct sunlight? -
Wiring Proline Promass 80 PROFIBUS PA
26
4 Wiring
#Warning!
When connecting Ex-certified devices, see the notes and diagrams in the Ex-specific supplement to
these Operating Instructions. Please do not hesitate to contact your FMC Technologies sales office
if you have any questions.
!Note!
The device does not have an internal power switch. For this reason, assign the device a switch or
power-circuit breaker which can be used to disconnect the power supply line from the power grid.
4.1 PROFIBUS PA cable specifications
4.1.1 Cable type
Twin-core cables are recommended for connecting the device to the fieldbus. Following
IEC 61158-2 (MBP), four different cable types (A, B, C, D) can be used with the fieldbus, only two
of which (cable types A and B) are shielded.
• Cable types A or B are particularly preferable for new installations. Only these types have cable
shielding that guarantees adequate protection from electromagnetic interference and thus the
most reliable data transfer. In the case of type B multi-pair cables, it is permissible to operate
multiple fieldbuses with the same degree of protection on one cable. No other circuits are
permissible in the same cable.
• Practical experience has shown that cable types C and D should not be used due to the lack of
shielding, since the freedom from interference generally does not meet the requirements
described in the standard.
The electrical data of the fieldbus cable have not been specified but determine important
characteristics of the design of the fieldbus, such as distances bridged, number of users,
electromagnetic compatibility, etc.
Suitable fieldbus cables from various manufacturers for non-hazardous areas are listed below:
• Siemens: 6XV1 830-5BH10
• Belden: 3076F
• Kerpen: CeL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL
Type A Type B
Cable structure Twisted pair,
shielded
One or more twisted pairs, fully shielded
Wire cross-section 0.8 mm2 (AWG 18) 0.32 mm2 (AWG 22)
Loop-resistance (DC) 44 Ω/km 112 Ω/km
Characteristic impedance at 31.25 kHz 100 Ω ± 20% 100 Ω ± 30%
Attenuation constant at 39 kHz 3 dB/km 5 dB/km
Capacitive asymmetry 2 nF/km 2 nF/km
Envelope delay distortion (7.9 to 39 kHz) 1.7 μs/km *
Shield coverage 90% *
Max. cable length (incl. spurs >1 m) 1900 m (6200 ft) 1200 m (4000 ft)
* Not specified
Proline Promass 80 PROFIBUS PA Wiring
27
4.1.2 Maximum overall cable length
The maximum network expansion depends on the type of protection and the cable specifications.
The overall cable length combines the length of the main cable and the length of all the spurs
(>1 m (>3 ft)).
Note the following points:
• The maximum permissible overall cable length depends on the cable type used:
• If repeaters are used, the maximum permissible cable length is doubled.
A maximum of three repeaters are permitted between user and master.
4.1.3 Maximum spur length
The line between the distribution box and field device is described as a spur.
In the case of non-Ex applications, the max. length of a spur depends on the number of spurs
(>1 m) (>3 ft):
4.1.4 Number of field devices
In systems that meet FISCO with EEx ia type of protection, the line length is limited to
max. 1000 m (3280 ft). A maximum of 32 users per segment in non-Ex areas or a maximum of
10 users in an Ex-area (EEx ia IIC) is possible. The actual number of users must be determined
during configuration.
4.1.5 Bus termination
The start and end of each fieldbus segment are always to be terminated with a bus terminator. With
various junction boxes (non-Ex), the bus termination can be activated via a switch. If this is not the
case, a separate bus terminator must be installed.
Note the following points:
• In the case of a branched bus segment, the device furthest from the segment coupler represents
the end of the bus.
• If the fieldbus is extended with a repeater then the extension must also be terminated at both
ends.
4.1.6 Further information
General information and further notes regarding the wiring are contained in BA034S/04:
"Guidelines for planning and commissioning, PROFIBUS DP/PA, field communication."
Type A 1900 m 6200 ft
Type B 1200 m 4000 ft
Number of spurs 1 to 12 13 to 14 15 to 18 19 to 24 25 to 32
Max. length per spur
[m] 120 90 60 30 1
[ft] 400 300 200 100 3
Wiring Proline Promass 80 PROFIBUS PA
28
4.2 Shielding and grounding
When planning the shielding and grounding for a fieldbus system, there are three important points
to consider:
• Electromagnetic compatibility (EMC)
• Explosion protection
• Safety of the personnel
To ensure the optimum electromagnetic compatibility of systems, it is important that the system
components and above all the cables, which connect the components, are shielded and that no
portion of the system is unshielded. Ideally, the cable shields are connected to the normally metal
housings of the connected field devices. Since these are generally connected to the protective earth,
the shield of the bus cable is grounded many times. Keep the stripped and twisted lengths of cable
shield to the terminals as short as possible.
This approach, which provides the best electromagnetic compatibility and personal safety, can be
used without restriction in systems with good potential matching.
In the case of systems without potential matching, a power supply frequency (50 Hz) equalizing
current can flow between two grounding points which, in unfavorable cases, e.g. when it exceeds
the permissible shield current, may destroy the cable.
To suppress the low frequency equalizing currents on systems without potential equalization, it is
therefore recommended to connect the cable shield directly to the building ground (or protective
earth) at one end only and to use capacitive coupling to connect all other grounding points.
"Caution!
The legal EMC requirements are fulfilled only when the cable shield is grounded on both sides!
Proline Promass 80 PROFIBUS PA Wiring
29
4.3 Connecting the remote version
4.3.1 Connecting connecting cable for sensor/transmitter
#Warning!
• Risk of electric shock. Switch off the power supply before opening the device.
Do not install or wire the device while it is connected to the power supply.
Failure to comply with this precaution can result in irreparable damage to parts of the electronics.
• Risk of electric shock. Connect the protective ground to the ground terminal on the housing
before the power supply is applied.
You may only connect the sensor to the transmitter with the same serial number. Communication
errors can occur if this is not observed when connecting the devices.
1. Remove the cover (d) from the connection compartment or the sensor housing.
2. Feed the connecting cable (e) through the appropriate cable runs.
3. Establish the connections between sensor and transmitter in accordance with the wiring
diagram (see Fig. 21 or wiring diagram inside cover).
4. Seal the connection compartment or the transmitter housing again.
a0003681
Fig. 21: Connecting the remote version
a Wall-mount housing: non-hazardous area and ATEX II3G / Zone 2 see separate Ex documentation
b Wall-mount housing: ATEX II2G / Zone 1 /FM/CSA see separate Ex documentation
c Remote version, flange version
d Cover of the connection compartment or connection housing
e Connecting cable
Terminal No.: 4/5 = gray; 6/7 = green; 8 = yellow; 9/10 = pink; 11/12 = white; 41/42 = brown
4.3.2 Cable specification for connecting cable
The specifications of the cable connecting the transmitter and the sensor of the remote version are
as follows:
• 6 x 0.38 mm2 PVC cable with common shield and individually shielded cores
• Conductor resistance: 50 Ω/km
• Capacitance core/shield: 420 pF/m
• Cable length: max. 20 m (3.28 ft)
• Permanent operating temperature: max. +105 °C (+221 °F)
!Note!
The cable must be installed securely, to prevents movement.
4 5 6 7 8 9 10 11 12 41 42
4 5 6 7 8 9 10 11 12 41 42
S1 S1 S2 S2 GND TM TM TT TT
++ ++
++ ++
S1 S1 S2 S2 GND TM TM TT TT
ab
c
d
d
d
e
Wiring Proline Promass 80 PROFIBUS PA
30
4.4 Connecting the measuring unit
4.4.1 Terminal assignment
Electrical values of the inputs Page 91
Electrical values of the outputs Page 91
4.4.2 Transmitter connection
#Warning!
• Risk of electric shock. Switch off the power supply before opening the device. Do not install or
wire the device while it is connected to the power supply. Failure to comply with this precaution
can result in irreparable damage to parts of the electronics.
Risk of electric shock. Connect the protective earth to the ground terminal on the housing before
the power supply is applied (not required for galvanically isolated power supply).
• Compare the specifications on the nameplate with the local supply voltage and frequency. The
national regulations governing the installation of electrical equipment also apply.
1. Remove the cover (a) from the connection compartment.
2. Route the power supply cable (b) and fieldbus cable (d) through the appropriate cable entries.
!Note!
The measuring devices can also be supplied with the option of a ready-mounted fieldbus
connector. Further information: Page 32
3. Perform wiring: wiring diagram (aluminum housing, stainless steel housing or wall-mount
housing) Fig. 17.
"Caution!
Risk of damaging the fieldbus cable!
If the shielding of the cable is grounded at more than one point in systems without additional
potential equalization, power supply frequency equalization currents can occur that damage
the cable or the shielding.
In such cases the shielding of the cable is to be grounded on only one side, i.e. it must not
be connected to the ground terminal of the housing. The shield that is not connected should
be insulated!
We recommend that the fieldbus cable not be looped using conventional cable glands. If you
later replace even just one measuring device, the bus communication will have to be
interrupted.
!Note!
The terminals for the PROFIBUS PA connection (26/27) have integrated reverse polarity
protection. This ensures correct signal transmission via the fieldbus even if lines are mixed
up.
Conductor cross-section: max. 2.5 mm2
Observe the grounding concept of the plant.
Connection values Chap. 4.4.1
4. Seal the connection compartment again.
Order version
Terminal No. (outputs/inputs)
26: PA + / 27: PA – (with integrated reverse polarity
protection)
80***-***********H PROFIBUS-PA
PROFIBUS-PA connection data
Ui = 30 V AC; Ii = 500 mA; Pi = 5.5 W; Li = 10.0 μH; Ci = 5.0 nF
Proline Promass 80 PROFIBUS PA Wiring
31
a0002593
Fig. 22: Connecting the transmitter, cable cross-section: max. 2.5 mm² (AWG 14)
A View A (field housing)
B View B (stainless steel field housing)
C View C (wall-mount housing)
a Connection compartment cover
b Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L for DC
c Ground terminal for protective earth
d Fieldbus cable:
Terminal No. 26: PA + (with reverse polarity protection)
Terminal No. 27: PA – (with reverse polarity protection)
e Ground terminal for fieldbus cable shield
Observe the following:
the shielding and grounding of the fieldbus cable Page 28
that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare)
d
c
e
b
27
25
23
21
2
1
26
24
22
20
L1 (L+)
PA +
N (L-)
PA –
f
PA –
PA +
12
ce
f
bd
22 2320 21 24 25 26 27
L1 (L+)
N (L–)
C
a
d
b
a
A
B
d
b
d
b
Wiring Proline Promass 80 PROFIBUS PA
32
4.4.3 Fieldbus connector
!Note!
The connector can only be used for PROFIBUS PA devices.
The connection technology of PROFIBUS PA allows measuring devices to be connected to the
fieldbus via uniform mechanical connections such as T-boxes, distribution modules etc.
This connection technology using prefabricated distribution modules and plug-in connectors offers
substantial advantages over conventional wiring:
• Field devices can be removed, replaced or added at any time during normal operation.
Communication is not interrupted.
• Installation and maintenance are significantly easier.
• Existing cable infrastructures can be used and expanded instantly, e.g. when constructing new
star distributors using 4-channel or 8-channel distribution modules.
The device can therefore be supplied with the option of a ready-mounted fieldbus connector.
Fieldbus connectors for retrofitting can be ordered from Endress+Hauser as a spare part. Page 67
a0005999
Fig. 23: Connectors for connecting to the PROFIBUS PA
A Aluminum field housing
B Stainless steel field housing
C Protection cap for connector
D Fieldbus connector
E Adapter PG 13.5 / M 20.5
F Connector at housing (male)
G Female connector
Pin assignment / color codes:
1 Brown wire: PA + (terminal 26)
2 Not connected
3 Blue wire: PA – (terminal 27)
4 Black wire: ground (instructions for connection Seite 31 ff.)
5 Middle female connector not assigned
6 Positioning groove
7 Positioning key
PG 13.5
M12x1
150/300
(5.91/11.81)
45.0 (1.77)
mm (inch)
CD E
34
21
G
5
6
4
12
F3
7
B
C
D
E
A
Esc
E
-
+
Proline Promass 80 PROFIBUS PA Wiring
33
Technical data (fieldbus connector):
Shielding of the cable connection/T-box
Use cable glands with good EMC properties, with surrounding contact of the cable gland (iris
spring). This requires small differences in potential, and possibly potential matching.
• Do not interrupt the shielding of the PA cable.
• Always keep the connection of the shielding as short as possible.
Ideally, cable glands with iris springs should be used for the connection of the shielding. The shield
is placed on the T-box via the iris spring that is inside the cable gland. The shielding mesh is located
under the iris spring. When the PG thread is screwed closed, the iris spring is pressed onto the
shield, making a conductive connection between the shielding and the metal housing.
A junction box or connection is to be considered part of the shielding (Faraday cage). This is
particularly true for offset boxes when these are connected to a PROFIBUS PA measuring device
using a plug-in cable. In such a case, use a metallic plug in which the cable shielding is attached to
the plug housing (such as prefabricated cables).
Connection cross section 0.75 mm2
Connector thread PG 13.5
Degree of protection IP 67 in accordance with DIN 40 050 IEC 529
Contact surface CuZnAu
Housing material Cu Zn, surface Ni
Flammability V - 2 in accordance with UL - 94
Operating temperature –40 to +85 °C (–40 to +185 °F)
Ambient temperature –40…+150 °C, (–40… +302 °F)
Nominal current per
contact
3 A
Nominal voltage 125 to 150 V DC in accordance with the VDE Standard 01 10/ISO Group 10
Resistance to tracking KC 600
Volume resistance 8 mΩ in accordance with IEC 512 Part 2
Insulation resistance 1012 Ω in accordance with IEC 512 Part 2
Wiring Proline Promass 80 PROFIBUS PA
34
4.5 Degree of protection
The devices fulfill all the requirements for IP 67.
Compliance with the following points is mandatory following installation in the field or servicing,
in order to ensure that IP 67 protection is maintained:
The housing seals must be clean and undamaged when inserted into the sealing groove. The seals
must be dried, cleaned or replaced if necessary.
• All the housing screws and screw covers must be firmly tightened.
• The cables used for connection must be of the specified outer diameter. Page 29
• Firmly tighten the cable entry.
• The cable must loop down in front of the cable entry ("water trap"). This arrangement prevents
moisture penetrating the entry. Always install the measuring device in such a way that the cable
entries do not point upwards.
• Remove all unused cable entries and insert plugs instead.
• Do not remove the grommet from the cable entry.
a0001914
Fig. 24: Installation instructions, cable entries
"Caution!
Do not loosen the screws of the sensor housing, as otherwise the degree of protection guaranteed
by FMC Technologies no longer applies.
ab
Proline Promass 80 PROFIBUS PA Wiring
35
4.6 Post-connection check
Perform the following checks after completing electrical installation of the measuring device:
Device condition and specifications Notes
Are cables or the device damaged (visual inspection)? -
Electrical connection Notes
Does the supply voltage match the specifications on the nameplate? 85 to 260 V AC (45 to 65 Hz)
20 to 55 V AC (45 to 65 Hz)
16 to 62 V DC
Do the cables comply with the specifications? PROFIBUS PA Page 26
Sensor cable Page 29
Do the cables have adequate strain relief? -
Cables correctly segregated by type?
Without loops and crossovers?
-
Are the power supply and signal cables correctly connected? See the wiring diagram inside
the cover of the terminal
compartment
Are all screw terminals firmly tightened? -
Are all cable entries installed, firmly tightened and correctly sealed?
Cables looped as "water traps"?
Page 34
Are all housing covers installed and firmly tightened? -
Electrical connection of PROFIBUS Notes
Are all the connecting components (T-boxes, junction boxes, connectors, etc.)
connected with each other correctly?
-
Has each fieldbus segment been terminated at both ends with a bus terminator? -
Has the max. length of the fieldbus cable been observed in accordance with the
PROFIBUS specifications?
Page 27
Has the max. length of the spurs been observed in accordance with the PROFIBUS
specifications?
Page 27
Is the fieldbus cable fully shielded and correctly grounded? Page 33
Operation Proline Promass 80 PROFIBUS PA
36
5 Operation
5.1 Quick operation guide
The user has a number of options for configuring and commissioning the device:
1. Local display (option) Page 37
The local display enables you to read all important variables directly at the measuring point,
configure device-specific parameters in the field and perform commissioning.
2. Operating programs Page 42
The configuration of profile and device-specific parameters is primarily done via the PROFIBUS
interface. You can obtain special configuration and operating programs from various
manufacturers for these purposes.
3. Jumpers/miniature switches for hardware settings
Configuring the device address Page 45
Hardware write protection Page 44
You can make the following hardware settings using a jumper or miniature switches on the
I/O board:
• Device bus address configuration (for hardware addressing)
• Hardware write protection enabling/disabling
a0001318
Fig. 25: Methods of operating PROFIBUS PA
1 Local display for device operation in the field (option)
2A Configuration/operating programs (e.g. FieldCare) for operation via PROFIBUS PA
2B Configuration/operating program for operating by means of the FXA193 service interface (e.g. FieldCare)
3 Jumper/miniature switches for hardware settings (write protection, device address)
2A
3
1
Esc
E
-
+
Esc
E
+
-
XXX.XXX.XX
Esc
E
-
+
FXA193
2B
Proline Promass 80 PROFIBUS PA Operation
37
5.2 Local display
5.2.1 Display and operating elements
The local display enables you to read all important parameters directly at the measuring point and
configure the device using the "Quick Setup" or the function matrix.
The display consists of four lines; this is where measured values and/or status variables (direction
of flow, empty pipe, bar graph, etc.) are displayed. You can change the assignment of display lines
to different variables to suit your needs and preferences ( "Description of Device Functions"
manual).
A0001141
Fig. 26: Display and operating elements
1 Liquid crystal display
The two-line liquid crystal display shows measured values, dialog texts, fault messages and notice messages. The
display as it appears when normal measuring is in progress is known as the HOME position (operating mode).
Top line: shows main measured values, e.g. volume flow, [e.g. in ml/min]
Bottom line: shows the totalizer reading [e.g. in m3]
Bargraph display, tag name
2O/ S keys
HOME position Direct access to totalizer values and actual values of inputs/outputs
Enter numerical values, select parameters
Select different function groups within the function matrix
Press the +/- keys (X) simultaneously to trigger the following functions:
Exit the function matrix step by step HOME position
Press and hold down +/– keys for longer than 3 seconds Return directly to HOME position
Cancel data entry
3F key (Enter key)
HOME position Entry into the function matrix
Save the numerical values you input or settings you changed
Esc
E
+
-
1
32
+48.25 xx/yy
+3702.6 x
Operation Proline Promass 80 PROFIBUS PA
38
5.2.2 Icons
The icons which appear in the field on the left make it easier to read and recognize measured
variables, device status, and error messages.
Icons Meaning
S System error
! Notice message
P Process error
$Fault message
(scrolling display)
Cyclic communication via PROFIBUS active, for example via PLC (Class 1 master)
a0001206
Acyclic communication via PROFIBUS active,
e.g. via FieldCare
Proline Promass 80 PROFIBUS PA Operation
39
5.3 Brief operating instructions on the function matrix
!Note!
• See the general notes Page 40
• Function descriptions see the "Description of Device Functions" manual"
1. HOME position F Entry into the function matrix
2. Select a function group (e.g. CURRENT OUTPUT 1)
3. Select a function (e.g. TIME CONSTANT)
Change parameter / enter numerical values:
OS Select or enter release code, parameters, numerical values
F Save your entries
4. Exit the function matrix:
Press and hold down Esc key (X) for longer than 3 seconds HOME position
Repeatedly press Esc key (X) Return step-by-step to HOME position
a0001142
Fig. 27: Selecting functions and configuring parameters (function matrix)
>3s
-+E
Esc
E
E
E
E
E E E E E
+
+
Esc
+
Esc
+
Esc
E
m
n
o
p
Operation Proline Promass 80 PROFIBUS PA
40
5.3.1 General notes
The Quick Setup menu contains the default settings that are adequate for commissioning.
Complex measuring operations on the other hand necessitate additional functions that you can
configure as necessary and customize to suit your process parameters. The function matrix,
therefore, comprises a multiplicity of additional functions which, for the sake of clarity, are arranged
in a number of function groups.
Comply with the following instructions when configuring functions:
• You select functions as described earlier. Page 39
You can switch off certain functions (OFF). If you do so, related functions in other function groups
will no longer be displayed.
• Certain functions prompt you to confirm your data entries. Press P to select "SURE [ YES ]" and
press F to confirm. This saves your setting or starts a function, as applicable.
• Return to the HOME position is automatic if no key is pressed for 5 minutes.
• Programming mode is disabled automatically if you do not press a key within 60 seconds
following automatic return to the HOME position.
"Caution!
All functions are described in detail, as is the function matrix itself, in the "Description of Device
Functions" manual which is a separate part of these Operating Instructions.
!Note!
• The transmitter continues to measure while data entry is in progress, i.e. the current measured
values are output via the signal outputs in the normal way.
• If the power supply fails all preset and configured values remain safely stored in the EEPROM.
5.3.2 Enabling the programming mode
The function matrix can be disabled. Disabling the function matrix rules out the possibility of
inadvertent changes to device functions, numerical values or factory settings. A numerical code
(factory setting = 80) has to be entered before settings can be changed.
If you use a code number of your choice, you exclude the possibility of unauthorized persons
accessing data (see the "Description of Device Functions" manual).
Comply with the following instructions when entering codes:
• If programming is disabled and the P operating elements are pressed in any function, a prompt
for the code automatically appears on the display.
• If "0" is entered as the customer's code, programming is always enabled!
• The Endress+Hauser service organization can be of assistance if you mislay your personal code.
"Caution!
Changing certain parameters such as all sensor characteristics, for example, influences numerous
functions of the entire measuring system, particularly measuring accuracy.
There is no need to change these parameters under normal circumstances and consequently, they
are protected by a special code known only to the FMC Technologiesservice organization. Please
contact FMC Technologies if you have any questions.
5.3.3 Disabling the programming mode
Programming mode is disabled if you do not press an operating element within 60 seconds following
automatic return to the HOME position.
You can also disable programming in the "ACCESS CODE" function by entering any number (other
than the customer's code).
5.4 Error messages
5.4.1 Type of error
Errors that occur during commissioning or measuring are displayed immediately. If two or more
system or process errors occur, the error with the highest priority is the one shown on the display.
Proline Promass 80 PROFIBUS PA Operation
41
The measuring system distinguishes between two types of error:
System error: This group includes all device errors, e.g. hardware errors, etc. Page 71
Process error: This group includes all application errors, e.g. fluid not homogeneous, etc.
Page 77
a0000991
Fig. 28: Error messages on the display (example)
1 Error type: P = process error, S = system error
2 Error message type: $ = fault message, ! = notice message, definition
3 Error designation: e.g. MEDIUM INHOM. = fluid is not homogeneous
4 Error number: e.g. #702
5 Duration of last error to occur (in hours, minutes and seconds)
5.4.2 Error message type
The measuring device always assigns system and process errors which occur to two types of error
messages (fault or notice messages), resulting in different weightings Page 69.
Serious system errors, e.g. module defects, are always identified and classed as "fault messages" by
the measuring device.
Notice message (!)
• The error in question has no effect on the current operation
• Displayed as Exclamation mark (!), type of error (S: system error, P: process error)
• PROFIBUS device status display, error display Page 71
Fault message ( $)
• The error in question interrupts or stops the current operation
• Displayed as Lightning flash ( $ ), type of error (S: system error, P: process error)
• PROFIBUS device status display, error display Page 71
1
2453
XXXXXXXXXX
#000 00:00:05
P
Operation Proline Promass 80 PROFIBUS PA
42
5.5 Operating options
For the complete operation of the measuring device, including device-specific commands, device
description (DD) files are available to the user to provide the following operating aids and programs:
5.5.1 FieldCare
FieldCare is Endress+Hauser’s FDT-based plant asset management tool and allows the configuration
and diagnosis of intelligent field devices. By using status information, you also have a simple but
effective tool for monitoring devices. The Proline flowmeters are accessed via a service interface or
via the service interface FXA193.
5.5.2 Operating program "SIMATIC PDM" (Siemens)
SIMATIC PDM is a standardized, manufacturer-independent tool for the operation, configuration,
maintenance and diagnosis of intelligent field devices.
Proline Promass 80 PROFIBUS PA Operation
43
5.5.3 Device description files for operating programs
The following table illustrates the suitable device description file for the operating program in
question and then indicates where these can be obtained.
!Note!
The Fieldcheck tester/simulator is used for testing flowmeters in the field. When used in
conjunction with the "FieldCare" software package, test results can be imported into a database,
printed and used for official certification. Contact your FMC Technologies representative for more
information.
Valid for device software: 3.05.XX DEVICE SOFTWARE function
Device data PROFIBUS PA:
Profile Version:
Promass 80 ID No.:
Profile ID No.:
3.0
1528hex
9742 (Hex)
PROFILE VERSION function
DEVICE ID function
GSD file information:
Promass 80 GSD file: Extended Format
(recommended):
Standard Format:
eh3x1528.gsd
eh3_1528.gsd
!Note!
Before configuring the PROFIBUS network, read and follow the information
for using the GSD file Page 50 ff.
Bitmaps: EH_1528_d.bmp/.dib
EH_1528_n.bmp/.dib
EH_1528_s.bmp/.dib
Profile GSD file: PA139742.gsd
Software release: 12.2007
Operating program/device description: Sources for obtaining device descriptions/program updates:
Promass 80 GSD file www.endress.com Download
Profile GSD file www.profibus.com
FieldCare/DTM www.endress.com Download
CD–ROM (Endress+Hauser order number: 56004088)
DVD (Endress+Hauser order number: 70100690)
SIMATIC PDM www.endress.com Download
Tester/simulator: How to acquire:
Fieldcheck Update by means of FieldCare with the Flow Device FXA193/291 DTM
in the Fieldflash Module
Operation Proline Promass 80 PROFIBUS PA
44
5.6 PROFIBUS PA hardware settings
5.6.1 Hardware write protection
A jumper on the I/O board provides the means of switching hardware write protection on or off.
When hardware write protection is switched on, it is not possible to write to the device functions
via PROFIBUS (acyclic data transmission, e.g. via the operating program "FieldCare").
#Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
1. Switch off power supply.
2. Remove the I/O board. Page 81 ff.
3. Configure the hardware write protection accordingly with the aid of the jumpers (see Figure).
4. Installation is the reverse of the removal procedure.
a0001359
Fig. 29: Switching write protection on and off with the aid of a jumper on the I/O board
1 Jumper for switching write protection on and off
1.1 Write protection switched off (factory setting) = it is possible to write to the device functions via PROFIBUS
(acyclic data transmission, e.g. via the operating program "FieldCare")
1.2 Write protection switched on = it is not possible to write to the device functions via PROFIBUS (acyclic data
transmission, e.g. via the operating program "FieldCare")
2 Jumper without function
LED Overview of LED states:
Lit continuously Ready for operation
Not lit Not ready for operation
Flashing System or process error present Page69ff.
1
1.21.1
2
LED
Proline Promass 80 PROFIBUS PA Operation
45
5.6.2 Configuring the device address
The address must always be configured for a PROFIBUS PA device. The valid device addresses are
in the range from 1 to 126. In a PROFIBUS PA network, each address can only be assigned once. If
an address is not configured correctly, the device is not recognized by the master. All measuring
devices are delivered from the factory with the address 126 and with software addressing.
Addressing via local operation/operating program Page 42
Addressing via miniature switches
#Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
1. Loosen the Allen screw (3 mm) of the securing clamp.
2. Unscrew cover of the electronics compartment from the transmitter housing.
3. Remove the local display (if present) by loosening the set screws of the display module.
4. Set the position of the miniature switches on the I/O board using a sharp pointed object.
5. Installation is the reverse of the removal procedure.
a0002590
Fig. 30: Addressing with the aid of miniature switches on the I/O board
a Miniature switches for setting the device address (illustrated: 1 + 16 + 32 = device address 49)
b Miniature switches for the address mode (method of addressing):
OFF = software addressing via local operation/operating program (factory setting)
ON = hardware addressing via miniature switches
c Miniature switches not assigned
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
161
3
322
4
643
4
1
2
b
OFF ON
11
22
43
84 a
OFF ON
c
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
Commissioning Proline Promass 80 PROFIBUS PA
46
6 Commissioning
6.1 Function check
Make sure that the following function checks have been performed successfully before switching on
the supply voltage for the measuring device:
• Checklist for "Post-installation check" Page 25
• Checklist for "Post-connection check" Page 91 Page 35
6.2 Switching on the measuring device
Once the function check has been performed successfully, the device is operational and can be
switched on via the supply voltage. The device then performs internal test functions and the
following messages are shown on the local display:
Normal measuring mode commences as soon as startup completes.
Various measured value and/or status variables appear on the display (HOME position).
!Note!
If startup fails, an error message indicating the cause is displayed.
PROMASS 80
START UP… Start-up message
DEVICE SOFTWARE
V XX.XX.XX Current software version
SYSTEM OK
OPERATION Beginning of normal measuring mode
Proline Promass 80 PROFIBUS PA Commissioning
47
6.3 Quick Setup
In the case of measuring devices without a local display, the individual parameters and functions
must be configured via the operating program, e.g. FieldCare.
If the measuring device is equipped with a local display, all the important device parameters for
standard operation, as well as additional functions, can be configured quickly and easily by means
of the following Quick Setup menus.
6.3.1 Quick Setup "Commissioning"
a0004749-en
Fig. 31: Quick Setup "Commissioning"
+
++
EE
HOME-POSITION
Esc
E
+
-
XXX.XXX.XX
Yes
Yes
No
No
Mass flow Volume flow Density
Selection System Units
Configuration another unit ?
Automatically configuration display ?
Temperature Quit
Unit
Mass flow
Unit
flowVolume
Unit
Density
Unit
Temperature
Unit
Totalizer
Unit
Totalizer
Automatically
parameterization
of the display
Language
Pre-setting
Quick Setup Quick Setup
Commission
n
o
Corr. Vol. flow
Unit
Corr. Vol. flow
Unit
Ref. Density
Fix
Ref. Density
p
Selection pre-settings
Actual SettingsDeliver Settingsy
m
Set Unit to Bus
SET UNITSOFF
m
!Note!
The display returns to the cell SETUP COMMISSIONING (1002) if you the press X key combination during
parameter interrogation. The stored parameters remain valid.
The "Commissioning" Quick Setup must be carried out before one of the Quick Setups explained below is run.
mThe "DELIVERY SETTINGS" option sets every selected unit to the factory setting.
The "ACTUAL SETTINGS" accepts the units you configured beforehand.
nOnly units not yet configured in the current Setup are offered for selection in each cycle. The unit for mass, volume
and corrected volume is derived from the corresponding flow unit.
oThe "YES" option remains visible until all the units have been configured. "NO" is the only option displayed when
no further units are available.
pThe “automatic parameterization of the display” option contains the following basic settings/factory settings:
YES: line 1= mass flow; line 2 = totalizer 1
NO: The existing (selected) settings remain.
Commissioning Proline Promass 80 PROFIBUS PA
48
6.4 Commissioning the PROFIBUS PA interface
!Note!
• All functions required for commissioning are described in detail in the "Description of Device
Functions" manual which is a separate part of these Operating Instructions.
• A code (factory setting: 80) must be entered to change device functions, numerical values or
factory settings.
The following steps must be carried out in the sequence specified:
1. Check the hardware write protection:
The WRITE PROTECT parameter indicates whether it is possible to write to the device via
PROFIBUS communication (e.g. via FieldCare).
!Note!
This check is not needed if operating via the local display.
COMMUNICATION WRITE PROTECT…
OFF displayed (factory setting): write access via PROFIBUS possible
ON displayed: write access via PROFIBUS not possible
Deactivate the write protection if necessary Page 44
2. Enter the tag name (optional):
COMMUNICATION TAG NAME
3. Configuring the fieldbus address:
Set the bus address:
Software addressing using the local display:
COMMUNICATION BUS ADDRESS
Hardware addressing via miniature switches Page 45
4. Select the system units:
• Via the system units group:
SYSTEM UNITS UNIT VOL. FLOW UNIT VOLUME UNIT…
In the SET UNIT TO BUS function, select the SET UNITS function to transfer the cyclically
transmitted volume flow to the PROFIBUS master (Class 1) with the system unit set in the
measuring device.
COMMUNICATION SET UNIT TO BUS
!Note!
The configuration of the engineering units for the totalizers is described separately see
Point 6
If a system unit is altered via local operation, this initially does not affect the unit that is used
to transfer the volume flow to the automation system.
The SET UNIT TO BUS function has to be activated in the COMMUNICATION block before
the altered system unit of the measured value is transmitted to the automation system.
5. Setting the measuring mode:
SYSTEM PARAMETER MEASURING MODE
Select the flow components that should be recorded by the measuring device:
UNIDIRECTIONAL (factory setting) = only the positive flow portions
BIDIRECTIONAL = the positive and negative flow components
6. Configuration of the totalizer:
The measuring device has one totalizer.
• You can assign a measured variable to the totalizer via the CHANNEL parameter:
TOTALIZER CHANNEL …
VOLUME FLOW option (CHANNEL = 273), factory setting: the volume flow is
totalized as the measured variable
OFF option (CHANNEL = 0): no totalizing, the value 0 is displayed as the totalizer
value
Proline Promass 80 PROFIBUS PA Commissioning
49
!Note!
If the module or the TOTAL function was integrated when configuring the PROFIBUS
network, the measured variable selected in the CHANNEL parameter is cyclically
transmitted to the PROFIBUS master (Class 1) (for further information, see Page 53).
• Enter the desired totalizer units:
TOTALIZER UNIT TOTALIZER (factory setting: m³)
• Configure totalizer status (e.g. totalize):
TOTALIZER SET TOTALIZER…
Select: TOTALIZE
• Configure the totalizer mode:
TOTALIZER TOTALIZER MODE…
BALANCE option (factory setting): calculates the positive and negative flow
components
POSITIVE option: calculates the positive flow components only
NEGATIVE option: calculates the negative flow components only
HOLD VALUE option: the totalizer remains at the last value
!Note!
For the calculation of the positive and negative flow components (BALANCE) or the negative
flow components only (NEGATIVE) to be carried out correctly, the option BIDIRECTIONAL
must be active in the SYSTEM PARAMETER MEASURING MODE function.
7. Select the operating mode:
Select the operating mode (GSD file) which should be used for cyclic data transmission to the
PROFIBUS master.
COMMUNICATION SELECTION GSD…
MANUFACT. SPEC. option (factory setting): the complete device functionality is
available
PROFILE-GSD option: the device is operated in the PROFIBUS Profile mode
!Note!
For PROFIBUS network configuration, make sure that the right device master file (GSD file) of
the measuring device is used for the selected operating mode Page 50.
8. Configuration of cyclic data transmission in the PROFIBUS master
A detailed description of the system integration can be found on Page 50.
Commissioning Proline Promass 80 PROFIBUS PA
50
6.5 PROFIBUS PA system integration
6.5.1 Device master file (GSD file)
For PROFIBUS network configuration, the device master file (GSD file) is needed for every bus user
(PROFIBUS slave). The GSD file contains a description of the properties of a PROFIBUS device, such
as supported data transmission rate and number of input and output data.
Before configuration takes place, a decision should be made as to which GSD file should be used to
operate the measuring device in the PROFIBUS DP master system.
The measuring device supports the following GSD files:
• Promass 80 GSD file (manufacturer-specific GSD file, complete device functionality)
• PROFIBUS Profile GSD file.
Below you will find a detailed description of the GSD files supported.
Promass 80 GSD file (manufacturer-specific GSD file, complete device functionality)
Use this GSD file to access the complete functionality of the measuring device. In this way, device-
specific measured variables and functionalities are thus completely available in the PROFIBUS
master system. An overview of the modules available (input and output data) is contained on the
following pages:
PROFIBUS PA Page 53 ff.
GSD file with standard or extended format
The GSD file with either the standard or the extended format must be used depending on the
configuration software used. When installing the GSD file, the GSD file with the extended format
(EH3x15xx.gsd) should always be used first.
However, if the installation or the configuration of the measuring device fails with this format, then
use the standard GSD (EH3_15xx.gsd). This differentiation is the result of different implementation
of the GSD formats in the master systems. Note the specifications of the configuration software.
Name of the Promass 80 GSD file
How to acquire
• Internet (Endress+Hauser) www.endress.com ( Download Software Device Driver)
• CD-ROM with all GSD files for Endress+Hauser devices Order No.: 56003894
Contents of the download file from the Internet and the CD-ROM:
• All Endress+Hauser GSD files (standard and extended format)
• Endress+Hauser type files
• Endress+Hauser bitmap files
• Information on the devices
ID No. GSD file Type file Bitmaps
PROFIBUS PA 1528 (Hex) Extended Format
(recommended):
Standard Format:
EH3x1528.gsd
EH3_1528.gsd
EH_1528.200 EH_1528_d.bmp/.dib
EH_1528_n.bmp/.dib
EH_1528_s.bmp/.dib
Proline Promass 80 PROFIBUS PA Commissioning
51
PROFIBUS Profile GSD file:
The function scope of the profile GSD file is defined by the PROFIBUS Profile Specification 3.0. The
function scope is restricted compared to the manufacturer-specific GSD file (complete device
functionality). However, similar devices from different manufacturers can be interchanged with the
profile GSD file without the need to reconfigure (interchangeability).
Profile GSD (multivariable) with the ID number 9760 (Hex): This GSD contains all the function
blocks such as AI, DO, DI etc. This GSD is not supported by Promass.
!Note!
• Before configuration takes place, a decision should be made as to which GSD should be used to
operate the system.
• The setting can be changed via the local display or using a Class 2 master. Setting via the local
display. Page 48
GSD files supported: Page 43
Each device receives an identification number (ID No.) from the Profibus User Organization (PNO).
The name of the device master file (GSD) is derived from this.
For Endress+Hauser, this ID No. starts with the manufacturer ID 15xx.
In order to ensure clarity and make assignment easier, the GSD names (with the exception of type
files) at Endress+Hauser are as follows:
Name of the PROFIBUS Profile GSD file
Source
Internet (GSD library of the PROFIBUS User Organization) www.PROFIBUS.com
EH3_15xx EH = Endress + Hauser
3 = Profile 3.0
_ = Standard ID
15xx = ID No.
EH3x15xx EH = Endress + Hauser
3 = Profile 3.0
x = Extended ID
15xx = ID No.
ID No. Profile GSD file
PROFIBUS PA 9742 (Hex) PA139742.gsd
Commissioning Proline Promass 80 PROFIBUS PA
52
6.5.2 Selecting the GSD file in the measuring device
Depending on which GSD file is used in the PROFIBUS master system, the corresponding GSD file
has to be configured in the device by means of the SELECTION GSD function.
COMMUNICATION SELECTION GSD
Example
Before configuration takes place, a decision should be made as to which GSD file should be used to
configure the measuring device in the PROFIBUS master system. Below, the use of the
manufacturer-specific GSD file (complete device functionality) is shown using PROFIBUS PA as an
example:
Select the manufacturer-specific GSD file in the measuring device by means of the SELECTION
GSD function.
COMMUNICATION SELECTION GSD Select: MANUFACT. SPEC. (factory setting)
1. Before configuring the network, load the corresponding GSD file into the configuration
system/master system.
!Note!
When installing the GSD file, always first use the GSD file with the extended format
(EH3x1528.gsd). However, if the installation or the configuration of the device fails with this
format, then use the standard GSD (EH3_1528.gsd).
Example for the configuration software Siemens STEP 7 of the Siemens PLC family
S7-300/400:
Use the GSD file with the extended format (EH3x1528.gsd). Copy the file to the subdirectory
"…\siemens\step7\s7data\gsd". The GSD files also include bitmap files. These bitmap files
are used to display the measuring points in image form. The bitmap files must be saved to the
directory "…\siemens\step7\s7data\nsbmp".
If you are using configuration software other than that referred to above, ask your PROFIBUS
master system manufacturer which directory you should use.
2. The measuring device is a modular PROFIBUS slave, i.e. the desired module configuration
(input and output data) must be performed in the next step. This can be done directly by means
of the configuration software.
6.5.3 imum number of writes
If a nonvolatile device parameter is modified via the cyclic or acyclic data transmission, this change
is saved in the EEPROM of the measuring device.
The number of writes to the EEPROM is technically restricted to a maximum of 1 million. Attention
must be paid to this limit since, if exceeded, it results in data loss and measuring device failure. For
this reason, avoid constantly writing nonvolatile device parameters via the PROFIBUS!
Promass 80 GSD file Select: MANUFACT. SPEC. (factory setting)
Profile GSD file Select: PROFILE-GSD
Proline Promass 80 PROFIBUS PA Commissioning
53
6.6 Cyclic data transmission PROFIBUS PA
Below is a description of the cyclic data transmission when using the Promass 80 GSD file (complete
device functionality).
6.6.1 Block model
The block model illustrated shows which input and output data Promass 80 provides for cyclic data
exchange via PROFIBUS PA.
a0004774-en
Fig. 32: Block model for Promass 80 PROFIBUS PA Profile 3.0
6.6.2 Modules for cyclic data transmission
The measuring device is a so-called modular PROFIBUS slave. In contrast to a compact slave, the
structure of a modular slave is variable - it consists of several individual modules. In the GSD file,
the individual modules (input and output data) are described with their individual properties. The
modules are permanently assigned to the slots, i.e. the sequence or arrangement of the modules
must be observed when configuring the modules (see following table). Gaps between configured
modules have to be assigned the EMPTY_MODULE module.
To optimize the data throughput rate of the PROFIBUS network, it is recommended to only
configure modules that are processed in the PROFIBUS master system.
Esc
E
+
-
XXX.XXX.XX
PROFIBUS PA
Analog Input 1
Output value AI
Output value AI
Output value AI
Output value AI
Analog Input 2
Analog Input 3
Analog Input 4
Measured variable 1
Measured variable 2
Measured variable 3
Measured variable …
Signal
processing
PROFIBUS
PROFILE
Parameter
Manufacturer
specific
Parameter
Control (CONTROL_BLOCK)
Display value (DISPLAY_VALUE)
Transducer
block
Totalizer Configuration SETTOT, MODETOT
Measured variable 1
Measured variable 2
Measured variable 3
Measured variable …
Out value TOTAL
Local
Display
Physical
Block
Commissioning Proline Promass 80 PROFIBUS PA
54
It is essential to adhere to the following sequence/assignment when configuring the modules in the
PROFIBUS master system:
!Note!
• The assignment of the measured variables for the Analog Input function blocks 1 to 4 and the
Totalizer function block 1 can be changed by means of the CHANNEL function. A detailed
description of the individual modules is contained in the following section.
• The device has to be reset once a new configuration has been loaded to the automation system.
This can be effected as follows:
By means of the local display
By means of an operating program (e.g. FieldCare)
By switching the supply voltage off and on again.
6.6.3 Description of the modules
AI module (Analog Input)
The corresponding measured variable, including the status, is cyclically transmitted to the
PROFIBUS master (Class 1) by means of the AI module (slots 1 to 4). The measured variable is
represented in the first four bytes in the form of floating point numbers in accordance with the
IEEE 754 standard. The fifth byte contains standardized status information corresponding to the
measured variable.
Further information on the device status Page 71
Input data
Slot
sequence Module Description
1AIAnalog Input function block 1
Output variable mass flow (factory setting)
2AIAnalog Input function block 2
Output variable volume flow (factory setting)
3AIAnalog Input function block 3
Output variable corrected volume flow (factory setting)
4AIAnalog Input function block 4
Output variable density (factory setting)
5
TOTAL or
SETTOT_TOTAL or
SETTOT_MODETOT_TOTAL
Totalizer function block 1
TOTAL output variable = totalized mass flow (factory
setting)
SETTOT totalizer control
MODETOT totalizer configuration
6 DISPLAY_VALUE Default value for local display
7 CONTROL_BLOCK Control of device functions
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Measured variable (IEEE 754 floating point
number)
Status
Proline Promass 80 PROFIBUS PA Commissioning
55
Assignment of the measured variables to the AI module
The AI module can transmit different measured variables to the PROFIBUS master (Class 1).
The measured variables are assigned to the Analog Input function blocks 1 to 4 by means of the local
display or with the aid of an operating program (e.g. FieldCare) in the CHANNEL function:
COMMUNICATION BLOCK SELECTION: select an Analog Input function block
CHANNEL: select a measured variable
Possible settings
Factory setting:
Example:
You want to cyclically transmit the mass flow to the PROFIBUS master (Class 1) by means of the
Analog Input function block 1 (module AI, slot 1) and the temperature by means of the Analog Input
function block 2 (module AI, slot 2).
1. COMMUNICATION BLOCK SELECTION: select ANALOG INPUT 1, then select
CHANNEL = MASS FLOW
2. COMMUNICATION BLOCK SELECTION: select ANALOG INPUT 2, then select
CHANNEL = TEMPERATURE
Measured variable ID for CHANNEL function
MASS FLOW 277
VOLUME FLOW 273
CORRECTED VOLUME FLOW 398
DENSITY 281
REFERENCE DENSITY 402
TEMPERATURE 285
Module Analog Input
function block
Measured variable Unit ID for CHANNEL
function
AI (slot 1) 1 MASS FLOW kg/s 277
AI (slot 2) 2 VOLUME FLOW m/h 273
AI (slot 3) 4 DENSITY kg/l 281
AI (slot 4) 6 TEMPERATURE K 285
Commissioning Proline Promass 80 PROFIBUS PA
56
TOTAL module
The measuring device has one totalizer function block. The totalizer values can be cyclically
transmitted to the PROFIBUS master (Class 1) via the TOTAL module (slot 5). The totalizer value
is represented in the first four bytes in the form of a floating point number in accordance with the
IEEE 754 standard. The fifth byte contains standardized status information corresponding to the
totalizer value.
Further information on the device status Page 71
Input data
Assignment of the measured variables to the TOTAL module
The TOTAL module can transmit different totalizer variables to the PROFIBUS master (Class 1).
The measured variables are assigned to the Totalizer function block by means of the local display or
with the aid of an operating program (e.g. FieldCare) in the "CHANNEL" function:
TOTALIZER TOTALIZER option: select a totalizer
CHANNEL: select a measured variable
Possible settings
Factory setting
Example:
You want to cyclically transmit the totalized volume flow as totalizer value 1 to the PROFIBUS
master (Class 1) by means of the TOTAL module (slot 5):
TOTALIZER TOTALIZER option: select TOTALIZER 1, then select CHANNEL = VOLUME
FLOW
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Totalizer value (IEEE 754 floating point number) Status
Totalizer value/measured variable ID for CHANNEL function
MASS FLOW 277
VOLUME FLOW 273
CORRECTED VOLUME FLOW 398
OFF 0
Module Totalizer
function block
Totalizer value/
Measured variable
Unit ID for CHANNEL
function
TOTAL (slot 5) 1 MASS FLOW kg/s 277
Proline Promass 80 PROFIBUS PA Commissioning
57
SETTOT_TOTAL module
The module combination SETTOT_TOTAL (slot 5) consists of the functions SETTOT and TOTAL.
With this module combination:
• The totalizer can be controlled via the automation system (SETTOT).
• The totalizer value is transmitted including the status (TOTAL)
SETTOT function
In the SETTOT function, the totalizer can be controlled via control variables.
The following control variables are supported:
• 0 = Totalize (factory setting)
• 1 = Reset totalizer (the totalizer value is reset to 0)
• 2 = Accept totalizer preset
!Note!
After the totalizer value has been reset to 0 or set to the preset value, the totalizing continues
automatically. The control variable does not have to be changed to 0 again to restart totalizing.
Stopping totalizing is controlled in the SETTOT_MODETOT_TOTAL module via the MODETOT
function. Page 57
TOTAL function
For a description of the TOTAL function, refer to TOTAL module Page 56
Data structure of the SETTOT_TOTAL module combination
SETTOT_MODETOT_TOTAL module
The module combination SETTOT_MODETOT_TOTAL (slot 5) consists of the functions SETTOT,
MODETOT and TOTAL.
With this module combination:
• The totalizer can be controlled via the automation system (SETTOT).
• The totalizer can be configured via the automation system (MODETOT).
• The totalizer value is transmitted including the status (TOTAL)
SETTOT function
For a description of the SETTOT function, refer to SETOT_TOTAL module. Page 57
MODETOT function
In the MODETOT function, the totalizer can be configured via control variables.
The following settings are possible:
• 0 = Balance (factory setting), calculates the positive and negative flow portions
• 1 = calculates the positive flow portions
• 2 = calculates the negative flow portions
• 3 = Totalizing is stopped
!Note!
For the calculation of the positive and negative flow components (control variable 0) or the negative
flow components only (control variable 2) to be carried out correctly, the option BIDIRECTIONAL
must be active in the MEASURING MODE function.
Output data Input data
SETTOT TOTAL
Byte 1 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Control Totalizer value (IEEE 754 floating point number) Status
Commissioning Proline Promass 80 PROFIBUS PA
58
TOTAL function
For a description of the TOTAL function, refer to TOTAL module Page 56
Data structure of the SETTOT_MODETOT_TOTAL module combination
Example of using the SETTOT_MODETOT_TOTAL module
If the SETTOT function is set to 1 (= reset the totalizer), the value for the aggregated total is reset
to 0.
If the aggregated total of the totalizer should constantly retain the value 0, the MODETOT function
must first be set to 3 (= totalizing is stopped) and then the SETTOT function must be set to 1 (= reset
the totalizer).
DISPLAY_VALUE module
Any value (IEEE 754 floating point number), including status, can be cyclically transmitted via the
PROFIBUS master (Class 1) directly to the local display using the DISPLAY_VALUE module (slot 6).
Display value assignment to the main line, additional line or info line can be configured via the local
display itself or an operating program (e.g. FieldCare).
Output data
Status
The measuring device interprets the status in accordance with PROFIBUS Profile Specification
Version 3.0. The statuses OK, BAD and UNCERTAIN are indicated on the local display by a
corresponding symbol. Page 38
Output data Input data
SETTOT MODETOT TOTAL
Byte 1 Byte 2 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Control Configuration Totalizer value (IEEE 754 floating point number) Status
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Displayed value (IEEE 754 floating point
number)
Status
Proline Promass 80 PROFIBUS PA Commissioning
59
CONTROL_BLOCK module
By means of the CONTROL_BLOCK module (slot 7), the measuring device is able to process device-
specific control variables from the PROFIBUS master (Class 1) in cyclic data transmission (e.g.
switching on positive zero return).
Supported control variables of the CONTROL_BLOCK module
The following device-specific control variables can be activated by changing the output byte from
0 x:
Example (change the output byte)
Output data
EMPTY_MODULE module
The measuring device is a so-called modular PROFIBUS slave. In contrast to a compact slave, the
structure of a modular slave is variable - it consists of several individual modules. In the GSD file,
the individual modules are described with their individual properties. The modules are permanently
assigned to the slots, i.e. the sequence or arrangement of the modules must be observed when
configuring the modules. Gaps between configured modules have to be assigned the
EMPTY_MODULE module.
For a more detailed description, see Page 54
Module Control variables
CONTROL_BLOCK
0 2: Positive zero return ON
0 3: Positive zero return OFF
0 4: Run zero point adjustment
0 8: UNIDIRECTIONAL measuring mode
0 9: BIDIRECTIONAL measuring mode
0 24: Run UNIT TO BUS function
!Note!
The control (e.g. switching on positive zero return) is executed by cyclic data transmission if the output byte switches from
"0" to the bit pattern in question. The output byte must always switch from "0". A switchback to "0" does not have any
effect.
From To Result
02 Positive zero return is switched on.
20No effect
03 Positive zero return is switched off.
32No effect
Byte 1
Control
Commissioning Proline Promass 80 PROFIBUS PA
60
6.6.4 Configuration examples with Simatic S7 HW-Konfig
Example 1:
a0004775
Fig. 33: Complete configuration using the Promass 80 GSD file.
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS master (Class 1):
Slot
sequence Module Byte length
input data
Byte length
output data Description
1AI 5Analog Input function block 1
Output variable mass flow (factory setting)
2AI 5Analog Input function block 2
Output variable volume flow (factory setting)
3AI 5Analog Input function block 3
Output variable corrected volume flow (factory setting)
4AI 5Analog Input function block 4
Output variable density (factory setting)
5 SETTOT_MODETOT_TOTAL 5 2
Totalizer function block 1
TOTAL output variable = totalized mass flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
6 DISPLAY_VALUE 5 Default value for local display
7 CONTROL_BLOCK 1 Control of device functions
Proline Promass 80 PROFIBUS PA Commissioning
61
Example 2:
a0004791
Fig. 34: In this configuration example, modules that are not needed are replaced by the module EMPTY_MODULE.
The Promass 80 GSD file is used.
With this configuration, the Analog Input function block 1 (slot 1), the totalizer value TOTAL
(slot 5) and the cyclic control of device functions CONTROL_BLOCK (slot 8) are activated. The
mass flow (factory setting) is read out cyclically by the measuring device by means of the Analog
Input function block 1. The totalizer is configured "without configuration". In other words, in this
example it only returns the totalizer value for the mass flow (factory setting) by means of the TOTAL
module and cannot be controlled by the PROFIBUS master (Class 1).
Slot sequence Module Byte length
input data
Byte length
output data Description
1AI5Analog Input function block 1
Output variable mass flow (factory setting)
2 EMPTY_MODULE – Empty
3 EMPTY_MODULE – Empty
4 EMPTY_MODULE – Empty
5TOTAL5
Totalizer function block 1
TOTAL output variable = totalized mass flow (factory setting)
6 EMPTY_MODULE – Empty
7 CONTROL_BLOCK 1 Control of device functions
Commissioning Proline Promass 80 PROFIBUS PA
62
6.7 Adjustment
6.7.1 Zero point adjustment
All measuring devices are calibrated with state-of-the-art technology. The zero point obtained in
this way is printed on the nameplate.
Calibration takes place under reference operating conditions. Page 92 ff.
Consequently, the zero point adjustment is generally not necessary!
Experience shows that the zero point adjustment is advisable only in special cases:
• To achieve highest measuring accuracy also with very small flow rates.
Under extreme process or operating conditions (e.g. very high process temperatures or very high
viscosity fluids).
Preconditions for a zero point adjustment
Note the following before you perform a zero point adjustment:
• A zero point adjustment can be performed only with fluids that have no gas or solid contents.
• Zero point adjustment is performed with the measuring tubes completely filled and at zero flow
(v = 0 m/s). This can be achieved, for example, with shutoff valves upstream and/or downstream
of the sensor or by using existing valves and gates.
Normal operation valves 1 and 2 open
Zero point adjustment with pump pressure Valve 1 open / valve 2 closed
Zero point adjustment without pump pressure Valve 1 closed / valve 2 open
a0003601
Fig. 35: Zero point adjustment and shutoff valves
"Caution!
• If the fluid is very difficult to measure (e.g. containing entrained solids or gas) it may prove
impossible to obtain a stable zero point despite repeated zero point adjustments. In instances of
this nature, please contact your E+H service center.
• You can view the currently valid zero point value using the ZERO POINT function (see the
"Description of Device Functions" manual).
1
2
Proline Promass 80 PROFIBUS PA Commissioning
63
Performing a zero point adjustment
1. Operate the system until operating conditions have settled.
2. Stop the flow (v = 0 m/s).
3. Check the shutoff valves for leaks.
4. Check that operating pressure is correct.
5. Now perform the adjustment as follows:
Key Procedure Display text
FHOME position enter the operating matrix > GROUP SELECTION <
MEASURED VALUES
PSelect the "PROCESS PARAMETER" function group > GROUP SELECTION <
PROCESS PARAMETER
NSelect the desired function "ZERO ADJUST". ZERO ADJUST CANCEL
PWhen you press P you are automatically prompted to enter the access code if
the function matrix is still disabled.
CODE ENTRY
***
PEnter code (80 = factory setting) CODE ENTRY
80
F
Confirm code entry.
The "ZERO ADJUST" function then appears again on the display.
PROGRAMMING
ENABLED
ZERO ADJUST.
CANCEL
PSelect "START" ZERO ADJUST.
START
FConfirm entry with the E-key.
A security query appears on the display.
SURE? NO
PSelect "YES" SURE? YES
F
Confirm entry with the E-key. Zero point adjustment is now started. The
message on the right appears on the display for 30 to 60 seconds while zero
point adjustment is in progress.
If the flow in the pipe exceeds 0.1 m/s, the following error message appears on
the display: "ZERO ADJUST NOT POSSIBLE".
When the zero point adjustment is completed, the "ZERO ADJUST." function
reappears on the display.
ZERO ADJUST.
RUNNING
ZERO ADJUST.
CANCEL
FThe new zero point value is displayed when the Enter key is pressed. ZERO POINT
QPress P simultaneously HOME position
Commissioning Proline Promass 80 PROFIBUS PA
64
6.7.2 Density adjustment
Accuracy when determining the density has a direct effect on volume flow calculation. Density
adjustment is thus necessary under the following conditions:
• The sensor does not measure exactly the density value that the user expects on the basis of
laboratory analyses.
The fluid properties are outside the measuring points set at the factory, or the reference operating
conditions used to calibrate the measuring device.
• The system is used exclusively to measure a fluid’s density which must be registered to a high
degree of accuracy under constant conditions.
Performing a 1-point density adjustment
"Caution!
• Onsite density adjustment can be performed only if the user has detailed knowledge of the fluid
density, obtained for example from detailed laboratory analyses.
• The target density value specified in this way must not deviate from the measured fluid density
by more than ±10%.
• An error in defining the target density affects all calculated density and volume functions.
Density adjustment changes the factory density calibration values or the calibration values set by
the service technician.
The functions outlined in the following instructions are described in detail in the "Description of
Device Functions" manual.
1. Fill the sensor with fluid. Make sure that the measuring tubes are completely filled and that
liquids are free of gas bubbles.
2. Wait until the temperature difference between fluid and measuring tube has equalized. The
time you have to wait for equalization depends on the fluid and the temperature level.
3. Select the density adjustment function:
HOME F R PROCESS PARAMETERS F DENSITY SET POINT
When you press P you are automatically prompted to enter the access code if the function
matrix is still disabled. Enter the code.
–Now use P to enter the target density of your fluid and press F to save this value (input
range = actual density value ±10%).
4. Press F to select the "MEASURE FLUID" function.
With P, select the "START" setting and press F. The message "DENSITY ADJUST RUNNING"
then appears on the display for approx. 10 seconds. During this time Promass measures the
current density of the fluid (actual density value).
5. Press F to select the "DENSITY ADJUST" function.
With P, now select the "DENSITY ADJUST" setting and press F. Promass now compares the
target and actual density values and uses this information to calculate the new density
coefficients.
"Caution!
If the density adjustment does not complete correctly, you can select the RESTORE ORIGINAL
function to reactivate the default density coefficients.
6. Back to HOME position with Q (press P simultaneously).
Proline Promass 80 PROFIBUS PA Commissioning
65
6.8 Rupture disk
Sensor housings with integrated rupture disks are optionally available.
#Warning!
• Make sure that the function and operation of the rupture disk is not impeded through the
installation. Triggering overpressure in the housing as stated on the indication label. Take
adequate precautions to ensure that no damage occurs, and risk to human life is ruled out, if the
rupture disk is triggered.
Rupture disk: Burst pressure 10 to 15 bar.
Please note that the housing can no longer assume a secondary containment function if a rupture
disk is used.
• It is not permitted to open the connections or remove the rupture disk.
"Caution!
• Rupture disks can not be combined with separately available heating jacket (except Promass A).
• The existing connection nozzles are not designed for a rinse or pressure monitoring function.
!Note!
• Before commissioning, please remove the transport protection of the rupture disk.
• Please note the indication labels.
6.9 Purge and pressure monitoring connections
The sensor housing protects the inner electronics and mechanics and is filled with dry nitrogen.
Beyond that, up to a specified measuring pressure it additionally serves as secondary containment.
#Warning!
For a process pressure above the specified containment pressure, the housing does not serve as an
additional secondary containment. In case a danger of measuring tube failure exists due to process
characteristics, e.g. with corrosive process fluids, we recommend the use of sensors whose housing
is equipped with special pressure monitoring connections (ordering option). With the help of these
connections, fluid collected in the housing in the event of tube failure can be drained off. This
diminishes the danger of mechanical overload of the housing, which could lead to a housing failure
and accordingly is connected with an increased danger potential. These connections can also be
used for gas purging (gas detection).
The following instructions apply to handling sensors with purge or pressure monitoring connections:
• Do not open the purge connections unless the containment can be filled immediately with a dry
inert gas.
• Use only low gauge pressure to purge. Maximum pressure 5 bar (73 psi).
6.10 Data storage device (HistoROM)
The term HistoROM refers to various types of data storage modules on which process and measuring
device data are stored. By plugging and unplugging such modules, device configurations can be
duplicated onto other measuring devices to cite just one example.
6.10.1 HistoROM/S–DAT (sensor–DAT)
The S-DAT is an exchangeable data storage device in which all sensor relevant parameters are
stored, i.e., diameter, serial number, calibration factor, zero point.
Maintenance Proline Promass 80 PROFIBUS PA
66
7 Maintenance
No special maintenance work is required.
7.1 Exterior cleaning
When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the
surface of the housing and the seals.
7.2 Cleaning with pigs (Promass H, I, S, P)
If pigs are used for cleaning, it is essential to take the inside diameters of measuring tube and process
connection into account. See also Technical Information. Page 116
7.3 Replacing seals
Under normal circumstances, fluid wetted seals of the Promass A and Promass M sensors do not
require replacement. Replacement is necessary only in special circumstances, for example if
aggressive or corrosive fluids are incompatible with the seal material.
!Note!
• The period between changes depends on the fluid properties and on the frequency of cleaning
cycles in the case of CIP/SIP cleaning.
• Replacement seals (accessories)
Proline Promass 80 PROFIBUS PA Accessories
67
8 Accessories
Various accessories , which can be ordered separately from FMC Technologies, are available for the
transmitter and the sensor. The FMC Technologies service organization can provide detailed
information on the order code of your choice.
8.1 Device-specific accessories:
8.2 Measuring principle-specific accessories:
Accessory Description Order code
Proline Promass 80
transmitter
Transmitter for replacement or for stock. Use the order
code to define the following specifications:
– Approvals
Degree of protection / version
Cable entries
Display / power supply / operation
– Software
Outputs / inputs.
80XXX – XXXXX * * * * * *
Accessory Description Order code
Mounting set for
transmitter
Mounting kit for wall-mount housing (remote version).
Suitable for:
Wall mounting
Pipe mounting
Panel mounting
Mounting set for aluminum field housing:
Suitable for pipe mounting (¾" to 3")
DK8WM – *
Post mounting set for the
Promass A sensor
Post mounting set for the Promass A DK8AS – * *
Mounting set for the
Promass A sensor
Mounting set for Promass A, comprising:
2 process connections
–Seals
DK8MS – * * * * * *
Set of seals for sensor For regular replacement of the seals of the Promass M and
Promass A sensors.
Set consists of two seals.
DKS – * * *
Accessories Proline Promass 80 PROFIBUS PA
68
8.3 Service-specific accessories:
Accessory Description Order code
Applicator Software for selecting and configuring flowmeters.
Applicator can be downloaded from the Internet or
ordered on CD-ROM for installation on a local PC.
Contact your Endress+Hauser representative for more
information.
DKA80 - *
Fieldcheck Tester/simulator for testing flowmeters in the field.
When used in conjunction with the "FieldCare" software
package, test results can be imported into a database,
printed and used for official certification.
Contact your Endress+Hauser representative for more
information.
50098801
FieldCare FieldCare is Endress+Hauser’s FDT-based plant asset
management tool. It can configure all intelligent field
units in your system and helps you manage them. By
using the status information, it is also a simple but
effective way of checking their status and condition.
See the product page on the
Endress+Hauser Web site:
www.endress.com
FXA193 The FXA193 service interface connects the device to the
PC for configuration via FieldCare.
FXA193 – *
Proline Promass 80 PROFIBUS PA Troubleshooting
69
9 Troubleshooting
9.1 Troubleshooting instructions
Always start troubleshooting with the following checklist if faults occur after commissioning or
during operation. The routine takes you directly to the cause of the problem and the appropriate
remedial measures.
Check the display
No display visible and no
output signals present.
1. Check the supply voltage Terminals 1, 2
2. Check device fuse Page 85
85 to 260 V AC: 0.8 A slow-blow / 250 V
20 to 55 V AC and 16 to 62 V DC:2 A slow-blow / 250 V
3. Measuring electronics defective order spare parts Page 80
No display visible, but
output signals are present.
1. Check whether the ribbon-cable connector of the display module is correctly plugged
into the amplifier board Page 80 ff.
2. Display module defective order spare parts Page 80
3. Measuring electronics defective order spare parts Page 80
Display texts are in a
foreign language.
Switch off power supply. Press and hold down both the P keys and switch on the
measuring device. The display text will appear in English (default) and is displayed at
maximum contrast.
Measured value indicated,
but no signal at the current
or pulse output
Measuring electronics defective order spare parts Page 80
Error messages on display
Errors that occur during commissioning or measuring are displayed immediately. Error messages consist of a variety of
icons. The meanings of these icons are as follows (example):
Error type: S = system error, P = process error
Error message type: $ = fault message, ! = notice message
MEDIUM INHOM. = error designation (e.g. fluid is not homogeneous)
03:00:05 = duration of error occurrence (in hours, minutes and seconds)
#702 = error number
"Caution!
Also refer to the information on Page 40
System error (device error) has occurred Page 71
Process error (application error) has occurred Page 77
Faulty connection to control system
No connection can be made between the control system and the device.
Check the following points:
Supply voltage
Transmitter
Check the supply voltage Terminals 1/2
Device fuse Check device fuse Page 85
85 to 260 V AC: 0.8 A slow-blow / 250 V
20 to 55 V AC and 16 to 62 V DC: 2 A slow-blow / 250 V
Fieldbus connection Check the data cable
Terminal 26 = PA +
Terminal 27 = PA
Fieldbus connector Check pin assignment/wiring Page 25
Check connection between connector/fieldbus port.
Is the coupling ring tightened correctly?
Fieldbus voltage Check that a min. bus voltage of 9 V DC is present at terminals 26/27. Permissible range: 9
to 32 V DC
Troubleshooting Proline Promass 80 PROFIBUS PA
70
Network structure Check permissible fieldbus length and number of spurs. Page 26
Basic current Is there a basic current of min. 11 mA?
Bus address Check bus address: make sure there are no double assignments
Bus termination
(Termination)
Has the PROFIBUS network been terminated correctly?
Each bus segment must always be terminated with a bus terminator at both ends (start and
finish). Otherwise there may be interference in communication.
Current consumption,
permissible feed current
Check the current consumption of the bus segment:
The current consumption of the bus segment in question (= total of basic currents of all bus
users) must not exceed the max. permissible feed current of the bus power supply.
System or process error messages
System or process errors which occur during commissioning or operation can be displayed via the local display or an
operating program (e.g. FieldCare) in the ACTUAL SYSTEM CONDITION function.
Other error (without error message)
Some other error has
occurred.
Diagnosis and rectification Seite 79
Proline Promass 80 PROFIBUS PA Troubleshooting
71
9.2 System error messages
Serious system errors are always recognized by the instrument as "Fault message" and are shown
as a lightning flash ($) on the display! Fault messages immediately affect the outputs. Simulations
and positive zero return, on the other hand, are classed and displayed as "Notice messages".
"Caution!
In the event of a serious fault, a flowmeter might have to be returned to the manufacturer for repair.
Important procedures must be carried out before you return a flowmeter to FMC Technologies.
Page 8
Always enclose a duly completed "Declaration of contamination" form. You will find a preprinted
blank of this form at the back of this manual.
!Note!
See the information on Page 40
9.2.1 Displaying the device status on PROFIBUS PA
Display in the operating program (acyclic data transmission)
The device status can be queried using an operating program (e.g. FieldCare):
Function block SUPERVISION SYSTEM OPERATION ACTUAL SYSTEM CONDITION
Display in the PROFIBUS master system (cyclic data transmission)
If the AI or TOTAL modules are configured for cyclic data transmission, the device status is coded
in accordance with PROFIBUS Profile Specification 3.0 and transmitted with the measured value to
the PROFIBUS master (Class 1) by means of the quality byte (byte 5). The quality byte is split into
the "quality status", "quality substatus" and "limits" segments.
a0002707-en
Fig. 36: Structure of the quality byte
The content of the quality byte depends on the failsafe mode error behavior configured in the
corresponding Analog Input function block. Depending on which failsafe mode has been set in the
FAILSAFE_TYPE function, the following status information is transmitted to the PROFIBUS master
(Class 1) via the quality byte:
• For FAILSAFE_TYPE FSAFE VALUE:
Quality
Code
Measuring value
Limits
Quality Substatus
Quality
Status
Byte 5
Quality code (HEX) Quality status Quality substatus Limits
0x48
0x49
0x4A
UNCERTAIN Substitute set
OK
Low
High
Troubleshooting Proline Promass 80 PROFIBUS PA
72
• For FAILSAFE_TYPE LAST GOOD (factory setting):
If a valid output value was available before the failure:
If no valid output value was available before the failure:
• For FAILSAFE_TYPE WRONG VALUE:
For status information, see the table in the following section.
!Note!
The FAILSAFE_TYPE function can be configured in the corresponding Analog Input function block
1 to 6 or Totalizer function block 1 to 3 by means of an operating program (e.g. FieldCare).
9.2.2 List of system error messages
Quality code (HEX) Quality status Quality substatus Limits
0x44
0x45
0x46
UNCERTAIN Last usable value
OK
Low
High
Quality code (HEX) Quality status Quality substatus Limits
0x4C
0x4D
0x4E
UNCERTAIN Initial Value
OK
Low
High
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy (spare part Page 80 ff.)
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits
Depicted on the local display:
S = System error
$ = Fault message (with an effect on the outputs)
! = Notice message (without any effect on the outputs)
001 S: CRITICAL FAILURE
$: # 001
0x0F BAD Device Failure Constant ROM / RAM
failure
Cause:
ROM/RAM error. Error when accessing the
program memory (ROM) or random access
memory (RAM) of the processor.
Remedy:
Replace the amplifier board.
011 S: AMP HW EEPROM
$: # 011
0x0F BAD Device Failure Constant Amplifier EEPROM
failure
Cause:
Amplifier with faulty EEPROM
Remedy:
Replace the amplifier board.
012 S: AMP SW EEPROM
$: # 012
0x0F BAD Device Failure Constant Amplifier EEPROM
data inconsistent
Cause:
Error when accessing data of the measuring
amplifier EEPROM
Remedy:
Perform a "warm start" (= start the measuring
system without disconnecting main power).
Access:
SUPERVISION SYSTEM OPERATION
SYSTEM RESET ( RESTART)
Proline Promass 80 PROFIBUS PA Troubleshooting
73
031 S: SENSOR HW DAT
$: # 031
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
S-DAT failure /
S-DAT not inserted
Cause:
1. S-DAT is not plugged into the amplifier board
correctly (or is missing).
2. S-DAT is defective.
Remedy:
1. Check whether the S-DAT is correctly plugged
into the amplifier board.
2. Replace the S-DAT if it is defective.
Check that the new, replacement DAT is
compatible with the measuring electronics.
Check the:
- Spare part set number
- Hardware revision code
3. Replace measuring electronics boards if
necessary.
4. Plug the S-DAT into the amplifier board.
032 S: SENSOR SW DAT
$: # 032
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
S-DAT data
inconsistent
121 S: A/C COMPATIB.
!: # 121
0x0F BAD Device Failure Constant Amplifier and I/O
board only partially
compatible
Cause:
Due to different software versions, I/O board and
amplifier board are only partially compatible
(possibly restricted functionality).
!Note!
This message is only listed in the error history.
Nothing is displayed on the display.
Remedy:
Module with lower software version has either to
be actualized by FieldCare with the required
software version or the module has to be replaced.
261 S: COMMUNICAT. I/O
$: # 261
0x18
0x19
0x1A
BAD No
Communicati
on
O.K.
Low
High
Communication
failure
Cause:
Communication error. No data reception between
amplifier and I/O board or faulty internal data
transfer.
Remedy:
Check whether the electronics boards are correctly
inserted in their holders
379 S: LOW FREQ. LIM
$: # 379
0x0F BAD Device Failure Constant Frequence limit 1 Cause:
The measuring tube oscillation frequency is outside
the permitted range.
Causes:
Measuring tube damaged
Sensor defective or damaged
Remedy:
Contact your Endress+Hauser service organization.
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy (spare part Page 80 ff.)
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits
Troubleshooting Proline Promass 80 PROFIBUS PA
74
380 S: UPPER FREQ. LIM
$: # 380
0x0F BAD Device Failure Constant Frequence limit 2 Cause:
The measuring tube oscillation frequency is outside
the permitted range.
Causes:
Measuring tube damaged
Sensor defective or damaged
Remedy:
Contact your Endress+Hauser service organization.
381 S: FLUIDTEMP.MIN.
$: # 381
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Fluid Temperature
Min.
Cause:
The temperature sensor on the measuring tube is
likely defective.
Remedy:
Check the following electrical connections before
you contact your Endress+Hauser service
organization:
Verify that the sensor signal cable connector is
correctly plugged into the amplifier board
Remote version: Check sensor and transmitter
terminal connections No. 9 and 10
Page 29 ff.
382 S: FLUIDTEMP.MAX.
$: # 382
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Fluid Temperature
Max.
383 S: CARR.TEMP.MIN
$: # 383
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Carrier
Temperature Min.
Cause:
The temperature sensor on the carrier tube is likely
defective.
Remedy:
Check the following electrical connections before
you contact your Endress+Hauser service
organization:
Verify that the sensor signal cable connector is
correctly plugged into the amplifier board
Remote version: Check sensor and transmitter
terminal connections No. 11 and 12
Page 29 ff.
384 S: CARR.TEMP.MAX
$: # 384
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Carrier
Temperature Max.
385 S: INL.SENS.DEF.
$: # 385
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Inlet Sensor Defect Cause:
One of the measuring tube sensor coils (inlet or
outlet) is likely defective.
Remedy:
Check the following electrical connections before
you contact your Endress+Hauser service
organization:
Verify that the sensor signal cable connector is
correctly plugged into the amplifier board
Remote version: Check sensor and transmitter
terminal connections No. 4, 5, 6, 7.
386 S: OUTL.SENS.DEF.
$: # 386
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Outlet Sensor
Defect
387 S: SEN.ASY.EXCEED
$: # 387
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Sensor Asymmetry
Exceeded
388 S: AMP. FAULT
$: # 388
0x0F BAD Device Failure Constant Amplifier failure Cause:
Amplifier error
Remedy:
Contact your Endress+Hauser service organization.
389 S: AMP. FAULT
$: # 389
0x0F BAD Device Failure Constant Amplifier failure
390 S: AMP. FAULT
$: # 390
0x0F BAD Device Failure Constant Amplifier failure
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy (spare part Page 80 ff.)
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits
Proline Promass 80 PROFIBUS PA Troubleshooting
75
501 S: SW.-UPDATE ACT.
!: # 501
0x48
0x49
0x4A
UNCERTAIN Substitute set
(Substitute set
of failsafe
status)
O.K.
Low
High
New amplifier
software loaded
Cause:
New amplifier or communication software version
is loaded.
Currently no other functions are possible.
Remedy:
Wait until process is finished. The device will
restart automatically.
502 S: UP-/DOWNLO. ACT.
!: # 502
0x48
0x49
0x4A
UNCERTAIN Substitute set
(Substitute set
of failsafe
status)
O.K.
Low
High
Upload/download
of device data
active
Cause:
Up- or downloading the device data via operating
program. Currently no other functions are possible.
Remedy:
Wait until process is finished.
586 P: OSC. AMP. LIMIT
$: # 586
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Oscillation
amplitude too low
Cause:
The fluid properties do not allow a continuation of
the measurement.
Causes:
Extremely high viscosity
Fluid is very inhomogeneous (gas or solid content)
Remedy:
Change or improve process conditions.
587 P: TUBE NOT OSC
$: # 587
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
No oscillation
possible
Cause:
Extreme process conditions exist. The measuring
system can therefore not be started.
Remedy:
Change or improve process conditions.
588 P: GAIN RED.IMPOS
$: # 588
0x10
0x11
0x12
BAD Sensor Failure O.K.
Low
High
Gain reduction
impossible
Cause:
Overdriving of the internal analog to digital
converter.
A continuation of the measurement is no longer
possible!
Causes:
Cavitation
Extreme pressure shock
High gas flow velocity
Remedy:
Change or improve process conditions, e.g. by
reducing the flow velocity.
601 S: POS. ZERO-RETURN
!: # 601
0x53 UNCERTAIN Sensor
conversion
not accurate
(measured
value from
sensor not
accurate)
Constant Positive zero return
active
Cause:
Positive zero return is active
Remedy:
Switch off positive zero return:
Access:
BASIC FUNCTIONS SYSTEM PARAMETER
CONFIGURATION POS. ZERO RETURN
(OFF)
691 S: SIM. FAILSAFE
!: # 691
0x48
0x49
0x4A
UNCERTAIN Substitute set
(Substitute set
of failsafe
status)
O.K.
Low
High
Simulation failsafe
active
Cause:
Simulation of response to error is active.
Remedy:
Switch off simulation:
Access:
SUPERVISION SYSTEM OPERATION
SIM. FAILSAFE MODE ( OFF)
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy (spare part Page 80 ff.)
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits
Troubleshooting Proline Promass 80 PROFIBUS PA
76
692 S: SIM. MEASURAND
!: # 692
0x60
0x61
0x62
UNCERTAIN Simulated
Value
(manually
specified
value)
O.K.
Low
High
Simulation
measured value
active
Cause:
Simulation is active
Remedy:
Switch off simulation:
Access:
SUPERVISION SYSTEM OPERATION
SIM. MEASURAND ( OFF)
698 S: DEV. TEST ACT.
!: # 698
0x60
0x61
0x62
UNCERTAIN Simulated
Value
(manually
specified
value)
O.K.
Low
High
Device test via
Fieldcheck active
Cause:
The measuring device is being checked on site via
the test and simulation device.
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy (spare part Page 80 ff.)
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits
Proline Promass 80 PROFIBUS PA Troubleshooting
77
9.3 Process error messages
!Note!
See the information on Page 40
9.3.1 Displaying the device status on PROFIBUS PA
Further information Page 71
9.3.2 List of process error messages
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits
P = Process error
$ = Fault message (with an effect on the outputs)
! = Notice message (without any effect on the outputs)
700 P: EMPTY PIPE
!: # 700
0x53 UNCERT
AIN
Sensor
conversion
not accurate
(measured
value from
sensor not
accurate)
Constant Empty pipe
detected
Cause:
The process fluid density is outside the upper or lower
limit values set for empty pipe detection.
Causes:
Air in the measuring tube Partly filled measuring tube
Remedy:
1. Ensure that there is no gas content in the process
liquid.
2. Adjust the upper or lower limit value for empty
pipe detection to the current process conditions.
Access:
BASIC FUNCTIONS PROCESS PARAMETER
EPD PARAMETER EPD VALUE LOW or EPD
VALUE HIGH
701 P: EXC. CURR. LIM
!: # 701
0x40
0x41
0x42
UNCERT
AIN
Non specific
(uncertain
status)
O.K.
Low
High
Excitation too high Cause:
The maximum current value for the sensor coils has
been reached, since certain process fluid characteristics
are extreme, e.g. high gas or solid content.
The instrument continues to work correctly.
Remedy:
In particular with outgassing fluids and/or increased
gas content, the following measures are recommended
to increase system pressure:
Install the instrument at the outlet side of a pump.
Install the instrument at the lowest point of an
ascending pipeline.
Install a flow restriction, e.g. reducer or orifice plate,
downstream from the instrument.
Troubleshooting Proline Promass 80 PROFIBUS PA
78
702 P: MEDIUM INHOM.
!: # 702
0x43 UNCERT
AIN
Non specific
(uncertain
status)
Constant Fluid
inhomogeneous
Cause:
Frequency control is not stable, due to inhomogeneous
process fluid, e.g. gas or solid content.
Remedy:
In particular with outgassing fluids and/or increased
gas content, the following measures are recommended
to increase system pressure:
Install the instrument at the outlet side of a pump.
Install the instrument at the lowest point of an
ascending pipeline.
Install a flow restriction, e.g. reducer or orifice plate,
downstream from the instrument.
703 P: NOISE LIM. CH0
!: # 703
0x40
0x41
0x42
UNCERT
AIN
Non specific
(uncertain
status)
O.K.
Low
High
Noise Limit
Channel 0
Cause:
Overdriving of the internal analog to digital converter.
Causes:
Cavitation
Extreme pressure pulses
High gas flow velocity
A continuation of the measurement is still possible!
Remedy:
Change or improve process conditions, e.g. by
reducing the flow velocity.
704 P: NOISE LIM. CH1
!: # 704
0x40
0x41
0x42
UNCERT
AIN
Non specific
(uncertain
status)
O.K.
Low
High
Noise Limit
Channel 1
705 P: FLOW LIMIT
$: # 705
0x42 UNCERT
AIN
Non specific
(uncertain
status)
High
Limited
Flow limit Cause:
The mass flow is too high. The electronics' measuring
range will be exceeded.
Remedy:
Reduce flow
731 P: ADJ. ZERO FAIL
!: # 731
0x43 UNCERT
AIN
Non specific
(uncertain
status)
Constant Zero point
adjustment failure
Cause:
The zero point adjustment is not possible or has been
canceled.
Remedy:
Make sure that zero point adjustment is carried out at
"zero flow" only (v = 0 m/s). Page 62
No. Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits
Proline Promass 80 PROFIBUS PA Troubleshooting
79
9.4 Process errors without messages
Symptoms Rectification
!Note!
You may have to change or correct certain settings of the function matrix in order to rectify faults. The functions outlined below are described in detail in the
"Description of Device Functions" manual.
Measured value reading fluctuates even
though flow is steady.
1. Check the fluid for presence of gas bubbles.
2. Increase the following values:
Analog Input function block RISING TIME
BASIC FUNCTIONS SYSTEM PARAMETER CONFIGURATION FLOW DAMPING
3. Increase the value for display damping:
HOME USER INTERFACE CONTROL BASIC CONFIG. DISPLAY DAMPING
Measured value reading shown on
display, even though the fluid is at a
standstill and the measuring tube is full.
1. Check the fluid for presence of gas bubbles.
2. Enter a value for the low flow cutoff or increase this value:
BASIC FUNCTION PROCESS PARAMETER CONFIGURATION ON-VALUE LF CUTOFF
The fault cannot be rectified or some
other fault not described above has
occurred.
In these instances, please contact your
Endress+Hauser service organization.
The following options are available for tackling problems of this nature:
Request the services of an Endress+Hauser service technician
If you contact our service organization to have a service technician sent out, please be ready with the following
information:
Brief description of the fault
Nameplate specifications: order code and serial number Page 9
Return devices to Endress+Hauser
You can return a measuring device to Endress+Hauser for repair or calibration.
Always enclose the duly completed "Declaration of contamination" form with the flowmeter. You will find a preprinted
blank of this form at the back of this manual.
Replace transmitter electronics
Parts of the measuring electronics defective Order spare parts Page 80 ff.
Troubleshooting Proline Promass 80 PROFIBUS PA
80
9.5 Spare parts
The previous sections contain a detailed troubleshooting guide. Page 69 ff.
The measuring device, moreover, provides additional support in the form of continuous self-
diagnosis and error messages.
Fault rectification can entail replacing defective components with tested spare parts. The illustration
below shows the available scope of spare parts.
!Note!
You can order spare parts directly from your FMC Technologies service organization by providing
the serial number printed on the transmitter's nameplate.
Spare parts are shipped as sets comprising the following parts:
• Spare part
• Additional parts, small items (screws, etc.)
• Mounting instructions
•Packaging
A0005400
Fig. 37: Spare parts for PROFIBUS PA transmitters (field and wall-mount housing)
1 Power unit board (85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC)
2 Amplifier board
3 I/O board (COM module)
4 S-DAT (sensor data storage device)
5 Display module
6 Fieldbus connector consisting of protection cap, connector, adapter PG 13.5/M20.5
(order No. 50098037)
1
2
3
5
4
6
Proline Promass 80 PROFIBUS PA Troubleshooting
81
9.5.1 Removing and installing printed circuit boards
Field housing
#Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
Risk of damaging electronic components (ESD protection). Static electricity can damage electronic
components or impair their operability. Use a workplace with a grounded working surface
purpose-built for electrostatically sensitive devices!
• If you cannot guarantee that the dielectric strength of the device is maintained in the following
steps, then an appropriate inspection must be carried out in accordance with the manufacturer’s
specifications.
"Caution!
Use only original FMC Technologies parts.
Fig. 38, installation and removal:
1. Unscrew cover of the electronics compartment from the transmitter housing.
2. Remove the local display (1) as follows:
Press in the latches (1.1) at the side and remove the display module.
Disconnect the ribbon cable (1.2) of the display module from the amplifier board.
3. Remove the screws and remove the cover (2) from the electronics compartment.
4. Remove power unit board (4) and I/O board (6):
Insert a thin pin into the hole provided (3) for the purpose and pull the board clear of its holder.
5. Remove amplifier board (5):
Disconnect the plug of the sensor signal cable (5.1) including S-DAT (5.3) from the board.
Gently disconnect the plug of the excitation current cable (5.2) from the board, i.e. without
moving it back and forth.
Insert a thin pin into the hole provided (3) for the purpose and pull the board clear of its
holder.
6. Installation is the reverse of the removal procedure.
Troubleshooting Proline Promass 80 PROFIBUS PA
82
a0004769
Fig. 38: Field housing: removing and installing printed circuit boards
1 Local display
1.1 Latch
1.2 Ribbon cable (display module)
2 Screws of electronics compartment cover
3 Aperture for installing/removing boards
4 Power unit board
5 Amplifier board
5.1 Signal cable (sensor)
5.2 Excitation current cable (sensor)
5.3 S-DAT (sensor data storage device)
6 I/O board
3
4
5
2
2
2
4.1
4.3
4.2
1.1
1
1.2
Proline Promass 80 PROFIBUS PA Troubleshooting
83
Wall-mount housing
#Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
Risk of damaging electronic components (ESD protection). Static electricity can damage electronic
components or impair their operability. Use a workplace with a grounded working surface
purpose-built for electrostatically sensitive devices!
• If you cannot guarantee that the dielectric strength of the device is maintained in the following
steps, then an appropriate inspection must be carried out in accordance with the manufacturer’s
specifications.
"Caution!
Use only original FMC Technologies parts.
Fig. 39, installation and removal:
1. Loosen the screws and open the hinged cover (1) of the housing.
2. Loosen the screws securing the electronics module (2). Then push up electronics module and
pull it as far as possible out of the wall-mount housing.
3. Disconnect the following cable plugs from amplifier board (7):
Sensor signal cable plug (7.1) including S-DAT (7.3)
Plug of excitation current cable (7.2). Gently disconnect the plug, i.e. without moving it back
and forth.
Ribbon cable plug (3) of the display module
4. Remove the cover (4) from the electronics compartment by loosening the screws.
5. Remove the boards (6, 7, 8):
Insert a thin pin into the hole provided (5) for the purpose and pull the board clear of its holder.
6. Installation is the reverse of the removal procedure.
Troubleshooting Proline Promass 80 PROFIBUS PA
84
a0004770
Fig. 39: Field housing: removing and installing printed circuit boards
1 Housing cover
2 Electronics module
3 Ribbon cable (display module)
4 Screws of electronics compartment cover
5 Aperture for installing/removing boards
6 Power unit board
7 Amplifier board
7.1 Signal cable (sensor)
7.2 Excitation current cable (sensor)
7.3 S-DAT (sensor data storage device)
8 I/O board
6
7
8
5
5
5
34
7.1
7.3
7.2
1
2
3
Proline Promass 80 PROFIBUS PA Troubleshooting
85
9.5.2 Replacing the device fuse
#Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
The main fuse is on the power unit board. Fig. 38
The procedure for replacing the fuse is as follows:
1. Switch off power supply.
2. Remove the power unit board. Page 81 Page 83
3. Remove the protection cap (1) and replace the device fuse (2).
Only use the following fuse type:
20 to 55 V AC / 16 to 62 V DC 2.0 A slow-blow / 250 V; 5.2 x 20 mm
Power supply 85 to 260 V AC 0.8 A slow-blow / 250 V; 5.2 x 20 mm
Ex-rated devices see the Ex documentation
4. Installation is the reverse of the removal procedure.
"Caution!
Use only original FMC Technologies parts.
a0001148
Fig. 40: Replacing the device fuse on the power unit board
1 Protective cap
2Device fuse
9.6 Return
Page 8
9.7 Disposal
Observe the regulations applicable in your country!
1
2
Troubleshooting Proline Promass 80 PROFIBUS PA
86
9.8 Software history
!Note!
Uploading/downloading between different software versions is normally only possible with special
service software.
Date Software version Changes to software Operating
Instructions
12.2007 3.05.XX Introduction of a new PROFIBUS PA I/O board BA072D/06/en/12.07
71066150
12.2006 2.03.XX New Sensor:
Promass S
Promass P
BA072D/06/en/12.06
71036013
12.2005 Software expansion:
Promass I DN80, DN50FB
General device functions
BA072D/06/en/12.05
71008415
11.2004 Software expansion:
New sensor DN 250
New functionalities:
Empty pipe detection via excitation current
(EPD EXC.CURR. (6426))
DEVICE SOFTWARE (8100) Device software
displayed (NAMUR recommendation 53)
BA072D/06/en/11.04
50100101
10.2003 Amplifier:
1.06.XX
Communication module:
2.03.XX
Software expansion:
Language groups
Corrected volume measurement
Adjustments to Fieldcheck and Simubox
New error messages
SIL2 support
The totalizer values are also updated without
integration in cyclic data exchange
Support for corrected volume flow and standard
density process variables
New functionalities:
Operation hours counter
Intensity of background illumination adjustable
Pulse output simulation
Counter for access code
Upload/download via ToF Tool - Fieldtool package
Compatible with service protocol:
ToF Tool - Fieldtool Package
(the latest SW version can be downloaded under:
www.tof-fieldtool.endress.com)
PROFIBUS operation via:
Commuwin II version 2.08-1 (update C) and higher
BA072D/06/en/10.03
50100101
12.2002 Amplifier:
2.02.00
Software expansion:
Extended functions of Promass E
BA072D/06/en/09.02
50100101
04.2002 Amplifier:
1.02.01
Software adjustment: BA072D/06/en/04.02
50100101
03.2002 Communication module:
2.00.01
Software expansion:
New error messages:
061, 121, 501
Extension of control systems in cyclic data exchange
Control variables (measuring mode):
–0 8: Unidirectional
–0 9: Bidirectional
Communication software update possible via service
protocol
11.2001 Amplifier:
1.02.01
Software adjustment
Proline Promass 80 PROFIBUS PA Troubleshooting
87
07.2001 Amplifier:
1.02.00
Communication module:
1.01.00
Original software
Compatible with:
– Fieldtool
Commuwin II (version 2.07.02 and higher)
PROFIBUS DP/PA Profile Version 3.0
BA072D/06/en/06.01
50100101
Date Software version Changes to software Operating
Instructions
Technical data Proline Promass 80 PROFIBUS PA
88
10 Technical data
10.1 Technical data at a glance
10.1.1 Applications
Page 7
10.1.2 Function and system design
Measuring principle Mass flow measurement by the Coriolis principle
Measuring system Page 9
10.1.3 Input
Measured variable • Mass flow (proportional to the phase difference between two sensors mounted on the measuring
tube to register a phase shift in the oscillation)
• Fluid density (proportional to resonance frequency of the measuring tube)
• Fluid temperature (measured with temperature sensors)
Measuring range Measuring ranges for liquids (Promass F, M):
Measuring ranges for liquids (Promass E, H, S, P):
DN Range for full scale values (liquids) gmin(F) to gmax(F)
[mm] [inch]
8 3/8" 0 to 2000 kg/h 0 to 73.5 lb/min
15 1/2" 0 to 6500 kg/h 0 to 238 lb/min
25 1" 0 to 18000 kg/h 0 to 660 lb/min
40 1 ½" 0 to 45000 kg/h 0 to 1650 lb/min
50 2" 0 to 70000 kg/h 0 to 2570 lb/min
80 3" 0 to 180000 kg/h 0 to 6600 lb/min
100* 4"* 0 to 350000 kg/h 0 to 12860 lb/min
150* 6"* 0 to 800000 kg/h 0 to 29400 lb/min
250* 10"* 0 to 2200000 kg/h 0 to 80860 lb/min
*) only Promass F
DN Range for full scale values (liquids) gmin(F) to gmax(F)
[mm] [inch]
8 3/8" 0 to 2000 kg/h 0 to 73.5 lb/min
15 1/2" 0 to 6500 kg/h 0 to 238 lb/min
25 1" 0 to 18000 kg/h 0 to 660 lb/min
40 1 ½" 0 to 45000 kg/h 0 to 1650 lb/min
50 2" 0 to 70000 kg/h 0 to 2570 lb/min
Proline Promass 80 PROFIBUS PA Technical data
89
Measuring ranges for liquids (Promass A):
Measuring ranges for liquids (Promass I):
Measuring ranges for gases, generell, (except Promass H)
The full scale values depend on the density of the gas. Use the formula below to calculate the full
scale values:
gmax(G) = gmax(F) ρ(G) : x [kg/m3 (lb/ft3)]
gmax(G) = Max. full scale value for gas [kg/h (lb/min)]
gmax(F) = Max. full scale value for liquid [kg/h (lb/min)]
ρ(G) = Gas density in [kg/m3 (lb/ft3)] for process conditions
Here, gmax(G) can never be greater than gmax(F)
Measuring ranges for gases (Promass F, M):
DN Range for full scale values (liquids) gmin(F) to gmax(F)
[mm] [inch]
1 1/24" 0 to 20 kg/h 0 to 0.7 lb/min
2 1/12" 0 to 100 kg/h 0 to 3.7 lb/min
4 1/8" 0 to 450 kg/h 0 to 16.5 lb/min
DN Range for full scale values (liquids) gmin(F) to gmax(F)
[mm] [inch]
8 3/8" 0 to 2000 kg/h 0 to 73.5 lb/min
15 1/2" 0 to 6500 kg/h 0 to 238 lb/min
15 FB 1/2" FB 0 to 18000 kg/h 0 to 660 lb/min
25 1" 0 to 18000 kg/h 0 to 660 lb/min
25 FB 1" FB 0 to 45000 kg/h 0 to 1650 lb/min
40 1 ½" 0 to 45000 kg/h 0 to 1650 lb/min
40 FB 1 ½" FB 0 to 70000 kg/h 0 to 2570 lb/min
50 2" 0 to 70000 kg/h 0 to 2570 lb/min
50 FB 2" FB 0 to 180000 kg/h 0 to 6600 lb/min
80 3" 0 to 180000 kg/h 0 to 6600 lb/min
FB = Full bore versions of Promass I
DN x
[mm] [inch]
83/8" 60
15 ½" 80
25 1" 90
40 1½" 90
50 2" 90
80 3" 110
100 4" 130
150 6" 200
250 10" 200
Technical data Proline Promass 80 PROFIBUS PA
90
Measuring ranges for gases (Promass E)
Measuring ranges for gases (Promass P, S)
Measuring ranges for gases (Promass A)
Measuring ranges for gases (Promass I)
DN x
[mm] [inch]
83/8" 85
15 ½" 110
25 1" 125
40 1½" 125
50 2" 125
DN x
[mm] [inch]
83/8" 60
15 ½" 80
25 1" 90
40 1½" 90
50 2" 90
DN x
[mm] [inch]
11/24" 32
21/12" 32
41/8" 32
DN x
[mm] [inch]
83/8" 60
15 1/2" 80
15 FB 1/2" FB 90
25 1" 90
25 FB 1" FB 90
40 1 ½" 90
40 FB 1 ½" FB 90
50 2" 90
50 FB 2" FB 110
80 3" 110
FB = Full bore versions of Promass I
Proline Promass 80 PROFIBUS PA Technical data
91
Calculation example for gas:
•Sensor type: Promass F, DN 50
• Gas: air with a density of 60.3 kg/m³ (at 20 °C and 50 bar)
• Measuring range (liquid): 70000 kg/h
• x = 90 (for Promass F DN 50)
Max. possible full scale value:
gmax(G) = gmax(F) · ρ(G) ÷ x [kg/m³] = 70000 kg/h · 60.3 kg/m³ ÷ 90 kg/m³ = 46900 kg/h
Recommended full scale values
See information on Page 101 ff. ("Limiting flow")
Operable flow range Greater than 1000 : 1. Flows above the preset full scale value do not overload the amplifier, i.e.
totalizer values are registered correctly.
Input signal Status input (auxiliary input):
U = 3 to 30 V DC, Ri = 5 kΩ, galvanically isolated.
Configurable for: positive zero return, error message reset, zero point adjustment start, batching
start/stop (optional), totalizer reset for batching (optional).
10.1.4 Output
Output signal • PROFIBUS PA in accordance with IEC 61158 (MBP), galvanically isolated
• Profile Version 3.0
• Data transmission rate: 31.25 kBaud
• Current consumption: 11 mA
• Permitted supply voltage: 9 to 32 V
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Signal coding: Manchester II
Bus address can be configured via miniature switches, via the local display (optional) or operating
program
Signal on alarm PROFIBUS PA interface:
Status and alarm messages in accordance with PROFIBUS Profile Version 3.0
10.1.5 Power supply
Electrical connections Page 26 ff.
Supply voltage 85 to 260 V AC, 45 to 65 Hz
20 to 55 V AC, 45 to 65 Hz
16 to 62 V DC
Cable entries Power supply and signal cables (inputs/outputs):
• Cable entry M20 x 1.5 (8 to 12 mm)
• Threads for cable entries, ½" NPT, G ½"
Connecting cable for remote version:
• Cable entry M20 x 1.5 (8 to 12 mm)
• Threads for cable entries, ½" NPT, G ½"
Technical data Proline Promass 80 PROFIBUS PA
92
Cable specifications Remote version Page 29 Page 26 ff.
PROFIBUS seePage29
Power consumption AC: <15 VA (including sensor)
DC: <15 W (including sensor)
Switch-on current:
• max. 13.5 A (< 50 ms) at 24 V DC
• max. 3 A (< 5 ms) at 260 V AC
Power supply failure Lasting min. 1 power cycle:
• EEPROM saves measuring system data if power supply fails
HistoROM/S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal
diameter, serial number, calibration factor, zero point, etc.)
Potential equalization No measures necessary.
10.1.6 Performance characteristics
Reference operating
conditions
Error limits following ISO/DIS 11631:
• 20 to 30 °C (68 to 86 °F); 2 to 4 bar (30 to 60 psi)
• Accuracy based on accredited calibration rigs according to ISO 17025
• Zero point calibrated under operating conditions
• Field density calibrated (or special density calibration)
Maximum measured error The following values refer to the pulse/frequency output. The measured error at the current output
is typically also ±5 μA.
o.r. = of reading
Mass flow (liquid)
Promass F, Premium Cal:
±0.10% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass F, M, A, I, S, P:
±0.15% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass E:
±0.30% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass H:
±0.175% ± [(zero point stability ÷ measured value) · 100]% o.r.
Mass flow (gas)
Promass F:
±0.35% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass M, A, I, S, P:
±0.50% ± [(zero point stability ÷ measured value) · 100]% o.r.
Proline Promass 80 PROFIBUS PA Technical data
93
Promass E:
±0.75% ± [(zero point stability ÷ measured value) · 100]% o.r.
Volume flow (liquid)
Promass F:
±0.20% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass M, A:
±0.25% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass E:
±0.45% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass H, I:
±0.50% ± [(zero point stability ÷ measured value) · 100]% o.r.
Promass S, P:
±0.30% ± [(zero point stability ÷ measured value) · 100]% o.r.
Zero point stability (Promass A):
Zero point stability (Promass F, M):
DN
Max. full scale value Zero point stability
[kg/h] [lb/min] [kg/h] [lb/min]
1 1/24" 0 to 20 0 to 0.7 0.0010 0.00004
2 1/12" 0 to 100 0 to 3.7 0.0050 0.0002
4 1/8" 0 to 450 0 to 16.5 0.0225 0.0008
DN
Max. full scale value Zero point stability
[kg/h] [lb/min]
Promass F Promass F
(high-temperature)
Promass M
[kg/h] [lb/min] [kg/h] [lb/min] [kg/h] [lb/min]
8 3/8" 2000 73.5 0.030 0.001 −−0.100 0.004
15 ½" 6500 238 0.200 0.007 −−0.325 0.012
25 1" 18000 660 0.540 0.019 1.80 0.066 0.90 0.033
40 1½" 45000 1650 2.25 0.083 −−2.25 0.083
50 2" 70000 2570 3.50 0.129 7.00 0.257 3.50 0.129
80 3" 180000 6600 9.00 0.330 18.00 0.661 9.00 0.330
100 4" 350000 12860 14.00 0.514 −−−−
150 6" 800000 29400 32.00 1.17 −−−−
250 10" 2200000 80860 88.00 3.23 −−−−
Technical data Proline Promass 80 PROFIBUS PA
94
Zero point stability (Promass E, H, S, P):
Zero point stability (Promass I):
Sample calculation
a0004604
Fig. 41: Maximum measured error in % of reading (example: Promass 80 F, M / DN 25)
Calculation example (mass flow, liquid):
Given: Promass 80 F / DN 25, flow = 8000 kg/h
Max. measured error: ±0.10% ± [(zero point stability ÷ measured value) · 100]% o.r.
Max. measured error ±0.10% ±0.54 kg/h ÷ 8000 kg/h · 100% = ±0.107%
DN
Max. full scale value Zero point stability
[kg/h] [lb/min] [kg/h] [lb/min]
8 3/8" 2000 73.5 0.200 0.007
15 ½" 6500 238 0.650 0.024
25 1" 18000 660 1.80 0.066
40 1½" 45000 1650 4.50 0.165
50 2" 70000 2570 7.00 0.257
DN
Max. full scale value Zero point stability
[kg/h] [lb/min] [kg/h] [lb/min]
8 3/8" 2000 73.5 0.150 0.006
15 1/2" 6500 238 0.488 0.018
15 FB 1/2" FB 18000 660 1.350 0.050
25 1" 18000 660 1.350 0.050
25 FB 1" FB 45000 1650 3.375 0.124
40 1 ½" 45000 1650 3.375 0.124
40 FB 1 ½" FB 70000 2570 5.250 0.193
50 2" 70000 2570 5.250 0.193
50 FB 2" FB 180000 6600 13.500 0.495
80 3" 180000 6600 13.500 0.495
FB = Full bore versions of Promass I
0
±0.5
±0.2
±1.0
[%]
0 2 4 6 8 10 12 14 16 18 t/h
Proline Promass 80 PROFIBUS PA Technical data
95
Density (liquid)
1 g/cc = 1 kg/l
After field density calibration or under reference conditions:
Promass F, S, P:
±0.0005 g/cc
Promass M, E, A, H:
±0.0010 g/cc
Promass I:
±0.0020 g/cc
Special density calibration (optional), not for high-temperature version
(calibration range = 0.8 to 1.8 g/cc, 5 to 80 °C (41 to 176 °F)):
Promass F:
±0.001 g/cc
Promass M, A, H, S, P:
±0.002 g/cc
Promass I:
±0.004 g/cc
Standard calibration:
Promass F, S, P:
±0.01 g/cc
Promass M, E, A, H, I:
±0.02 g/cc
Temperature
±0.5 °C ±0.005 · T (T = fluid temperature in °C)
±1 °F ±0.003 · (T–32) (T = fluid temperature in °F)
Repeatability Mass flow (liquid):
Promass F, A, H, I, S, P
±0.05% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
Promass E:
±0.10% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
Technical data Proline Promass 80 PROFIBUS PA
96
Mass flow (gas):
Promass F, M, A, I, S, P:
±0.25% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
Promass E:
±0.35% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
Volume flow (liquid):
Promass F:
±0.05% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
Promass M, A:
±0.10% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
Promass E, H, I, S, P:
±0.20% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
o.r. = of reading
Zero point stability: see "Max. measured error" Page 92 ff.
Calculation example (mass flow, liquid):
Given: Promass 80 F / DN 25, flow = 8000 kg/h
Repeatability: ±0.05% ± [½ · (zero point stability ÷ measured value) · 100]% o.r.
Repeatability ±0.05% ± ½ · 0.54 kg/h ÷ 8000 kg/h · 100% = ±0.053%
Density measurement (liquid)
1 g/cc = 1 kg/l
Promass F:
±0.00025 g/cc
Promass M, H, E, A, S, P:
±0.0005 g/cc
Promass I:
±0.001 g/cc
Temperature measurement
±0.25 °C ± 0.0025 · T (T = fluid temperature in °C)
(±0.5 °F ± 0.0015 · (T – 32), T = fluid temperature in °F)
Influence of medium
temperature
When there is a difference between the temperature for zero point adjustment and the process
temperature, the typical measured error of the Promass sensor is ±0.0002% of the full scale
value / °C (±0.0001% of the full scale value / °F). The typical measured error of the Promass E
sensor is ±0.0003% of the full scale value / °C (±0.0002% of the full scale value / °F).
Proline Promass 80 PROFIBUS PA Technical data
97
Influence of medium pressure The following section shows the effect on accuracy of mass flow due to a difference between
calibration pressure and process pressure.
Promass F, M:
Promass E:
With nominal diameters DN 8 to 40 (3/8" to 1½"), the effect on accuracy of mass flow due to a
difference between calibration pressure and process pressure is negligible.
At DN 50 (2"), the effect is –0.009% o.r. / bar (–0.006% v.M. / psi) (o.r. = of reading).
Promass A:
A difference between calibration pressure and process pressure has no effect on measuring accuracy.
Promass H:
DN
Promass F,
Promass F high-temperature Promass M Promass M, high pressure
[% o.r./bar] [% o.r./psi] [% o.r./bar] [% o.r./psi] [% o.r./bar] [% o.r./psi]
8 3/8" No influence 0.009 0.0006 0.006 0.0004
15 ½" No influence 0.008 0.0005 0.005 0.0003
25 1" No influence 0.009 0.0006 0.003 0.0002
40 1½" 0.003 0.0002 0.005 0.0003 −−
50 2" 0.008 0.0005 No influence −−
80 3" 0.009 0.0006 No influence −−
100 4" 0.012 0.0008 −−−−
150 6" 0.009 0.0006 −−−−
250 10" 0.009 0.0006 −−−−
o.r. = of reading
DN [% o.r./bar] [% o.r./psi]
8 3/8" –0.017 –0.0012
15 ½" –0.021 –0.0014
25 1" –0.013 –0.0019
40 1½" –0.018 –0.0012
50 2" –0.020 –0.0014
Technical data Proline Promass 80 PROFIBUS PA
98
Promass I:
Promass S, P:
10.1.7 Operating conditions: Installation
Installation instructions Page 14 ff.
Inlet and outlet runs There are no installation requirements regarding inlet and outlet runs.
Length of connecting cable Max. 20 meters (66 feet) (remote version)
System pressure Page 15
DN
Promass I
[% o.r./bar] [% o.r./psi]
8 3/8" 0.006 0.0004
15 ½" 0.004 0.0003
15 FB ½" FB 0.006 0.0004
25 1" 0.006 0.0004
25 FB 1" FB No influence
40 1½" No influence
40 FB 1½" FB –0.0002 –0.0003
50 2" –0.0002 –0.0003
50 FB 2" FB 0.003 0.0002
80 3" 0.003 0.0002
FB = Full bore versions of Promass I
DN
Promass S
[% o.r./bar] [% o.r./psi]
8 3/8" –0.002 –0.0001
15 ½" –0.006 –0.0004
25 1" –0.005 –0.0003
40 1½" –0.005 –0.0003
50 2" –0.005 –0.0003
Proline Promass 80 PROFIBUS PA Technical data
99
10.1.8 Operating conditions: Environment
Ambient temperature range Standard: –20 to +60 °C (-4 to +140°F) (sensor, transmitter)
Optional: –40 to +60 °C (-40 to +140°F) (sensor, transmitter)
!Note!
Install the device at a shady location. Avoid direct sunlight, particularly in warm climatic regions.
• At ambient temperatures below –20 °C (–4 °F) the readability of the display may be impaired.
Storage temperature –40 to +80 °C (–40 to +175 °F) (preferably +20 °C (+68 °F))
Degree of protection Standard: IP 67 (NEMA 4X) for transmitter and sensor
Shock resistance According to IEC 68-2-31
Vibration resistance Acceleration up to 1 g, 10 to 150 Hz, following IEC 68-2-6
CIP cleaning Yes
SIP cleaning Yes
Electromagnetic compatibility
(EMC)
To IEC/EN 61326 and NAMUR Recommendation NE 21
10.1.9 Operating conditions: Process
Medium temperature range Sensor:
Promass F, A, H, P:
–50 to +200 °C (–58 to +392 °F)
Promass F (high-temperature version):
–50 to +350 °C (–58 to +662 °F)
Promass M, I, S:
–50 to +150 °C (–58 to +302 °F)
Promass E:
–40 to +140 °C (–40 to +284 °F)
Technical data Proline Promass 80 PROFIBUS PA
100
Seals:
Promass F, E, H, I, S, P:
No internal seals
Promass M:
Viton: –15 to +200 °C ( –5 to +392 °F)
EPDM: –40 to +160 °C (–40 to +320 °F)
Silicon: –60 to +200 °C (–76 to +392 °F)
Kalrez: –20 to +275 °C (–4 to +527 °F);
FEP sheathed (not for gas applications): –60 to +200 °C (–76 to +392 °F)
Promass A
No inside seals.
Only for mounting sets with threaded connections:
Viton: –15 to +200 °C ( –5 to +392 °F)
EPDM: –40 to +160 °C (–40 to +320 °F)
Silicon: –60 to +200 °C (–76 to +392 °F)
Kalrez: –20 to +275 °C (–4 to +527 °F)
Limiting medium pressure
range (rated pressure)
The material load diagrams (pressure-temperature diagrams) for the process connections are
provided in the separate "Technical Information" document on the device in question. This can be
downloaded as a PDF file from www.endress.com.
A list of the "Technical Information" documents available is provided on Page 116
Pressure ranges of secondary containment:
Promass F:
DN 8 to 50: 40 bar (580 psi)
DN 80: 25 bar (362 psi)
DN 100 to 150: 16 bar (232 psi)
DN 250: 10 bar (145 psi)
Promass M:
100 bar (1450) psi
Promass E:
No secondary containment
Promass A:
25 bar (362) psi
Promass H, P:
DN 8 to 15: 25 bar (362 psi)
DN 25 to 50: 16 bar (232 psi)
Promass I:
40 bar (580 psi)
Promass S:
DN 8 to 40: 16 bar (232 psi)
DN 50: 10 bar (145 psi)
Proline Promass 80 PROFIBUS PA Technical data
101
Limiting flow See the "Measuring range" section Page 88 ff.
Select nominal diameter by optimizing between required flow range and permissible pressure loss.
See the "Measuring range" section for a list of max. possible full scale values.
• The minimum recommended full scale value is approx. 1/20 of the max. full scale value.
• In most applications, 20 to 50% of the maximum full scale value can be considered ideal.
• Select a lower full scale value for abrasive substances such as liquids with entrained solids (flow
velocity < 1 m/s (3 ft/s)).
• For gas measurement the following rules apply:
Flow velocity in the measuring tubes should not be more than half the sonic velocity
(0.5 Mach).
The maximum mass flow depends on the density of the gas: formula Page 91
Pressure loss (SI units) Pressure loss depends on the properties of the fluid and on its flow. The following formulas can be
used to approximately calculate the pressure loss:
Pressure loss formulas for Promass F, M, E
Pressure loss formulas for Promass H, I, S, P
Reynolds number
a0004623
Re 2300 *
a0004626
Re < 2300
a0004628
Δp = pressure loss [mbar]
ν = kinematic viscosity [m2/s]
g = mass flow [kg/s]
ρ = fluid density [kg/m3]
d = inside diameter of measuring tubes [m]
K to K2 = constants (depending on nominal diameter)
* To compute the pressure loss for gases, always use the formula for Re 2300.
Reynolds number
a0003381
Re 2300 *
a0004631
Re < 2300
a0004633
Δp = pressure loss [mbar]
ν = kinematic viscosity [m2/s]
g = mass flow [kg/s]
ρ = fluid density [kg/m3]
d = inside diameter of measuring tubes [m]
K to K3 = constants (depending on nominal diameter)
* To compute the pressure loss for gases, always use the formula for Re 2300.
Re =
g
pnr·d· ·
Drp=K· · ·
0.25 1.85 –0.86
gn
Dp=K1· · +
g
nK2 · ·
0.25 2
g
n
r
Re =
pnr·d· ·
g
Dnrp=K· · ·
0.25 1.75 –0.75
g
K3 · g2
r
+
Dp=K1· ·gnK3 · g2
r
+
Technical data Proline Promass 80 PROFIBUS PA
102
Pressure loss formulas for Promass A
Pressure loss coefficient for Promass F
a0001396
Fig. 42: Pressure loss diagram for water
Reynolds number
a0003381
Re 2300 *
a0003380
Re < 2300
a0003379
Δp = pressure loss [mbar]
ν = kinematic viscosity [m2/s]
g = mass flow [kg/s]
ρ = density [kg/m³]
d = inside diameter of measuring tubes [m]
K to K1 = constants (depending on nominal diameter)
* To compute the pressure loss for gases, always use the formula for Re 2300.
DN d[m] KK1 K2
8 5.35 10–3 5.70 1079.60 1071.90 107
15 8.30 10–3 5.80 1061.90 10710.60 105
25 12.00 10–3 1.90 1066.40 1064.50 105
40 17.60 10–3 3.50 1051.30 1061.30 105
50 26.00 10–3 7.00 1045.00 1051.40 104
80 40.50 10–3 1.10 1047.71 1041.42 104
100 51.20 10–3 3.54 1033.54 1045.40 103
150 68.90 10–3 1.36 1032.04 1046.46 102
250 102.26 10–3 3.00 1026.10 1031.33 102
Re =
pnr·d· ·
g
Dn rp=K· · ·
0.25 1.75 –0.75
g
Dnp=K1· ·g
DN 50
DN 40
DN 25
DN 8
10000
1000
100
10
1
0.1
0.001 0.01 0.1 110 100 1000
DN 15
DN 80
DN 100
[mbar]
[t/h]
DN 150
DN 250
Proline Promass 80 PROFIBUS PA Technical data
103
Pressure loss coefficient for Promass M
a0004605
Fig. 43: Pressure loss diagram for water
1 Promass M
2 Promass M (high pressure version)
DN d[m] KK1 K2
8 5.53 10–3 5.2 1078.6 1071.7 107
15 8.55 10–3 5.3 1061.7 1079.7 105
25 11.38 10–3 1.7 1065.8 1064.1 105
40 17.07 10–3 3.2 1051.2 1061.2 105
50 25.60 10–3 6.4 1044.5 1051.3 104
80 38.46 10–3 1.4 1048.2 1043.7 104
High pressure version
8 4.93 10–3 6.0 1071.4 1082.8 107
15 7.75 10–3 8.0 1062.5 1071.4 106
25 10.20 10–3 2.7 1068.9 1066.3 105
DN 50
DN 40
DN 25
DN 8
10000
1000
100
10
1
0.1
0.001 0.01 0.1 110 100 1000
DN 15
DN 80
[mbar]
[t/h]
1
2
Technical data Proline Promass 80 PROFIBUS PA
104
Pressure loss coefficient for Promass E
a0004606
Fig. 44: Pressure loss diagram for water
DN d[m] KK1 K2
8 5.35 10–3 5.70 1077.91 1072.10 107
15 8.30 10–3 7.62 1061.73 1072.13 106
25 12.00 10–3 1.89 1064.66 1066.11 105
40 17.60 10–3 4.42 1051.35 1061.38 105
50 26.00 10–3 8.54 1044.02 1052.31 104
DN 50
DN 40
DN 25
DN 8
10000
1000
100
10
1
0.1
0.001 0.01 0.1 110 100 1000
DN 15
[mbar]
[t/h]
Proline Promass 80 PROFIBUS PA Technical data
105
Pressure loss coefficient for Promass A
a0003595
Fig. 45: Pressure loss diagram for water
1 Standard version
2 High pressure version
DN d[m] KK1
11.1 10–3 1.2 1011 1.3 1011
21.8 10–3 1.6 1010 2.4 1010
43.5 10–3 9.4 1082.3 109
High pressure version
21.4 10–3 5.4 1010 6.6 1010
43.0 10–3 2.0 1094.3 109
[mbar]
[kg/h]
1
DN 2
10000
1000
100
10
1
0.1 110
100 1000
DN 4
DN 1
2
Technical data Proline Promass 80 PROFIBUS PA
106
Pressure loss coefficient for Promass H
a0004607
Fig. 46: Pressure loss diagram for water
DN d[m] KK1 K3
8 8.51 10–3 8.04 1063.28 1071.15 106
15 12.00 10–3 1.81 1069.99 1061.87 105
25 17.60 10–3 3.67 1052.76 1064.99 104
40 25.50 10–3 8.75 1048.67 1051.22 104
50 40.50 10–3 1.35 1041.72 1051.20 103
Pressure loss data includes interface between measuring tube and piping
1000
100
10
1
0.1
0.01 0.1 110
100
[mbar]
[t/h]
DN 40
DN 50DN 25
DN 15
DN 8
Proline Promass 80 PROFIBUS PA Technical data
107
Pressure loss coefficient for Promass I
a0004608
Fig. 47: Pressure loss diagram for water
1 Standard versions
2 Full bore versions (*)
DN d[m] KK1 K3
8 8.55 10–3 8.1 1063.9 107129.95 104
15 11.38 10–3 2.3 1061.3 10723.33 104
15 FB 17.07 10–3 4.1 1053.3 1060.01 104
25 17.07 10–3 4.1 1053.3 1065.89 104
25 FB 26.40 10–3 7.8 1048.5 1050.11 104
40 26.40 10–3 7.8 1048.5 1051.19 104
40 FB 35.62 10–3 1.3 1042.0 1050.08 104
50 35.62 10–3 1.3 1042.0 1050.25 104
50 FB 54.8 10–3 2.3 1035.5 1041.0 102
80 54.8 10–3 2.3 1035.5 1043.5 102
Pressure loss data includes interface between measuring tube and piping
FB = Full bore versions of Promass I
1000
100
10
1
0.1
0.01 0.1 110 100
DN 40
DN 25 *
DN 50
DN 40 *
DN 25
DN 15 *
DN 15
[mbar]
[t/h]
1
DN 8
DN 80
DN 50 *
2
Technical data Proline Promass 80 PROFIBUS PA
108
Pressure loss coefficient for Promass S, P
a0004607
Fig. 48: Pressure loss diagram for water
Pressure loss (US units) Pressure loss is dependent on fluid properties nominal diameter. Consult FMC Technologies for
Applicator PC software to determine pressure loss in US units. All important instrument data is
contained in the Applicator software program in order to optimize the design of measuring system.
The software is used for following calculations:
• Nominal diameter of the sensor with fluid characteristics such as viscosity, density, etc.
• Pressure loss downstream of the measuring point.
• Converting mass flow to volume flow, etc.
• Simultaneous display of various meter size.
• Determining measuring ranges.
The Applicator runs on any IBM compatible PC with windows.
DN d[m] KK1 K3
8 8.31 10–3 8.78 1063.53 1071.30 106
15 12.00 10–3 1.81 1069.99 1061.87 105
25 17.60 10–3 3.67 1052.76 1064.99 104
40 26.00 10–3 8.00 1047.96 1051.09 104
50 40.50 10–3 1.41 1041.85 1051.20 103
Pressure loss data includes interface between measuring tube and piping
1000
100
10
1
0.1
0.01 0.1 110
100
[mbar]
[t/h]
DN 40
DN 50DN 25
DN 15
DN 8
Proline Promass 80 PROFIBUS PA Technical data
109
10.1.10 Mechanical construction
Design / dimensions The dimensions and lengths of the sensor and transmitter are provided in the separate "Technical
Information" document on the device in question. This can be downloaded as a PDF file from
www.endress.com.
A list of the "Technical Information" documents available is provided on Page 116
Weight (SI units) Compact version: see table below
• Remote version
Sensor: see table below
Wall-mount housing: 5 kg
All values (weight) refer to devices with EN/DIN PN 40 flanges.
Weight data in [kg].
Promass F / DN 815 25 40 50 80 100 150 250*
Compact version 11 12 14 19 30 55 96 154 400
Compact version, high-temperature −−14.7 30.7 55.7 −−−
Remote version 9 10 12 17 28 53 94 152 398
Remote version, high-temperature −−13.5 29.5 54.5 −−−
* With 10" according to ASME B16.5 Cl 300 flanges
Promass M / DN 815 25 40 50 80
Compact version 11 12 15 24 41 67
Remote version 9 10 13 22 39 65
Promass E / DN 815 25 40 50
Compact version 8 8 10 15 22
Remote version 6 6 8 13 20
Promass A / DN 1 2 4
Compact version 10 11 15
Remote version 8 9 13
Promass H / DN 815 25 40 50
Compact version 12 13 19 36 69
Remote version 10 11 17 34 67
Promass I / DN 815 15FB 25 25FB 40 40FB 50 50FB 80
Compact version 13 15 21 22 41 42 67 69 120 124
Remote version 11 13 19 20 39 40 65 67 118 122
"FB" = Full bore versions of Promass I
Technical data Proline Promass 80 PROFIBUS PA
110
Weight (US units) Compact version: see table below
• Remote version
Sensor: see table below
Wall-mount housing: 11 lb
All values (weight) refer to devices with EN/DIN PN 40 flanges.
Weight data in [lb].
Promass S / DN 815 25 40 50
Compact version 13 15 21 43 80
Remote version 11 13 19 41 78
Promass P / DN 815 25 40 50
Compact version 13 15 21 43 80
Remote version 11 13 19 41 78
Promass F / DN 3/8" ½" 1" 1½" 2" 3" 4" 6" 10"*
Compact version 24 26 31 42 66 121 212 340 882
Compact version, high-temperature 32 68 123
Remote version 20 22 26 37 62 117 207 335 878
Remote version, high-temperature – 30 65 120
* With 10" according to ASME B16.5 Cl 300 flanges
Promass M / DN 3/8" ½" 11½" 2" 3"
Compact version 24 26 33 53 90 148
Remote version 20 22 29 49 86 143
Promass E / DN 3/8" ½" 11½" 2"
Compact version 1818223349
Remote version 1313182944
Promass A / DN 1/24" 1/12" 1/8"
Compact version 22 24 33
Remote version 18 20 29
Promass H / DN 3/8" ½" 11½" 2"
Compact version 26 29 42 79 152
Remote version 22 24 37 75 148
Proline Promass 80 PROFIBUS PA Technical data
111
Material Transmitter housing:
• Compact housing: stainless steel 1.4301/304
• Compact housing: powder coated die-cast aluminum
• Wall-mount housing: powder coated die-cast aluminum
• Remote field housing: powder-coated die-cast aluminum
Sensor housing / containment:
Promass F:
• Acid- and alkali-resistant outer surface
• Stainless steel 1.4301/1.4307/304L
Promass M:
• Acid- and alkali-resistant outer surface
• DN 8 to 50 (3/8" to 2"): steel, chemically nickel-plated
• DN 80 (3"): stainless steel
Promass E, A, H, I, S, P:
• Acid- and alkali-resistant outer surface
• Stainless steel 1.4301/304
Connection housing, sensor (remote version):
• Stainless steel 1.4301/304 (standard)
• Powder coated die-cast aluminum (high-temperature version and version for heating)
Promass I / DN 3/8" 1/2" 1/2"FB 1 ½" 1 ½"FB 3/8" 3/8"FB 11FB 2"
Compact version 29 33 46 49 90 93 148 152 265 273
Remote version 24 29 42 44 86 88 143 148 260 269
"FB" = Full bore versions of Promass I
Promass S / DN 3/8" ½" 11½" 2"
Compact version 29 33 46 95 176
Remote version 24 29 42 90 172
Promass P / DN 3/8" ½" 11½" 2"
Compact version 29 33 46 95 176
Remote version 24 29 42 90 172
Technical data Proline Promass 80 PROFIBUS PA
112
Process connections
Promass F:
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4404/316L
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
Alloy C-22 2.4602/N 06022
• DIN 11864-2 Form A (flat flange with groove) stainless steel 1.4404/316L
• Threaded hygienic connections DIN 11851/ DIN 11864-1, Form A / ISO 2853 / SMS 1145
stainless steel 1.4404/316L
•Tri-Clamp (OD-tubes) stainless steel 1.4404/316L
•VCO connection stainless steel 1.4404/316L
Promass F (high-temperature version):
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4404/316L
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
Alloy C-22 2.4602 (N 06022)
Promass M:
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4404/316L, titanium grade 2
• DIN 11864-2 Form A (flat flange with groove) stainless steel 1.4404/316L
• PVDF connection to DIN / ASME / JIS
• Threaded hygienic connections DIN 11851/ DIN 11864-1, Form A / ISO 2853 / SMS 1145
stainless steel 1.4404/316L
•Tri-Clamp (OD-tubes) stainless steel 1.4404/316L
Promass M (high pressure version):
•Connector stainless steel 1.4404/316L
•Couplings stainless steel 1.4401/316
Promass E:
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4404/316L
• DIN 11864-2 Form A (flat flange with groove) stainless steel 1.4404/316L
•VCO connection stainless steel 1.4404/316L
• Threaded hygienic connections DIN 11851/ DIN 11864-1, Form A / ISO 2853 / SMS 1145
stainless steel 1.4404/316L
•Tri-Clamp (OD-tubes) stainless steel 1.4404/316L
Promass A:
• Mounting set for flanges to EN 1092-1 (DIN 2501) / ASME B16.5 / JIS B2220
stainless steel 1.4539/904L, Alloy C-22 2.4602/N 06022.
Loose flanges stainless steel 1.4404/316L
•VCO connection stainless steel 1.4539/904L, Alloy C-22 2.4602/N 06022
• Tri-Clamp (OD-tubes) (1/2") stainless steel 1.4539/904L
• Mounting set for SWAGELOK (1/4", 1/8") stainless steel 1.4401/316
• Mounting set for NPT-F (1/4") stainless steel 1.4539/904L,
Alloy C-22 2.4602/N 06022
Promass H:
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4301/304, parts in contact with medium: zirconium 702
Proline Promass 80 PROFIBUS PA Technical data
113
Promass I:
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4301/304
• DIN 11864-2 Form A (flat flange with groove) titanium grade 2
• Threaded hygienic connections DIN 11851/ DIN 11864-1, Form A / ISO 2853 / SMS 1145
titanium grade 2
•Tri-Clamp (OD-tubes) titanium grade 2
Promass S
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4404/316/316L
• DIN 11864-2 Form A (flat flange with groove) stainless steel 1.4435/316L
• Threaded hygienic connections DIN 11851/ DIN 11864-1, Form A / ISO 2853 / SMS 1145
stainless steel 1.4435/316L
•Tri-Clamp (OD-Tubes) stainless steel 1.4435/316L
• Clamp aseptic connection DIN 11864-3, Form A stainless steel 1.4435/316L
• Clamp pipe connection DIN 32676 / ISO 2852 stainless steel 1.4435/316L
Promass P
• Flanges according to EN 1092-1 (DIN 2501) / according to ASME B16.5 / JIS B2220
stainless steel 1.4404/316/316L
• DIN 11864-2 Form A (flat flange with groove), BioConnect® stainless steel 1.4435/316L
• Threaded hygienic connections DIN 11851/ DIN 11864-1, Form A / ISO 2853 / SMS 1145
stainless steel 1.4435/316L
•Tri-Clamp (OD-Tubes) stainless steel 1.4435/316L
• Clamp aseptic connection DIN 11864-3, Form A stainless steel 1.4435/316L
• Clamp pipe connection DIN 32676/ISO 2852, BioConnect® stainless steel 1.4435/316L
Measuring tube(s):
Promass F:
• DN 8 to 100 (3/8" to 4"): stainless steel 1.4539/904L
• DN 150 (6"): stainless steel 1.4404/316L
• DN 250 (10"): stainless steel 1.4404/316L; manifold: CF3M
• DN 8 to 150 (3/8" to 6"): Alloy C-22 2.4602/N 06022
Promass F (high-temperature version):
• DN 25, 50, 80 (1", 2", 3"): Alloy C-22 2.4602/N 06022
Promass M:
• DN 8 to 50 (3/8" to 2"): titanium grade 9
• DN 80 (3"): titanium grade 2
Promass M (high pressure version):
• Titanium grade 9
Promass E, S:
• Stainless steel 1.4539/904L
Promass A:
• Stainless steel 1.4539/904L, Alloy C-22 2.4602/N 06022
Technical data Proline Promass 80 PROFIBUS PA
114
Promass H:
• Zirconium 702/R 60702
Promass I:
• Titanium grade 9
• Titanium grade 2 (flange disks)
Promass P:
Stainless steel 1.4435/316L
Seals:
Promass F, E, H, I, S, P:
Welded process connections without internal seals
Promass M:
Viton, EPDM, silicon, Kalrez 6375, FEP sheathing (not for gas applications)
Promass A:
Welded process connections without internal seals.
Only for mounting sets with threaded connections: Viton, EPDM, silicon, Kalrez
Material load diagram The material load diagrams (pressure-temperature diagrams) for the process connections are
provided in the separate "Technical Information" document on the device in question. This can be
downloaded as a PDF file from www.endress.com.
A list of the "Technical Information" documents available is provided on Page 116
Process connections see Page 112 ff.
10.1.11 Human interface
Display elements • Liquid crystal display: illuminated, two lines with 16 characters per line
• Selectable display of different measured values and status variables
• At ambient temperatures below –20 °C (–4 °F) the readability of the display may be impaired.
Operating elements • Local operation with three keys (–, +, E)
• Quick Setup menus for straightforward commissioning
Language groups Language groups available for operation in different countries:
• Western Europe and America (WEA):
English, German, Spanish, Italian, French, Dutch and Portuguese
• Eastern Europe and Scandinavia (EES):
English, Russian, Polish, Norwegian, Finnish, Swedish and Czech.
• South and East Asia (SEA):
English, Japanese, Indonesian
!Note!
You can change the language group via the operating program "FieldCare".
Remote operation Operation via PROFIBUS
Proline Promass 80 PROFIBUS PA Technical data
115
10.1.12 Certificates and approvals
CE mark The measuring system is in conformity with the statutory requirements of the EC Directives.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
C-tick mark The measuring system is in conformity with the EMC requirements of the "Australian
Communications and Media Authority (ACMA)".
Ex approval Information about currently available Ex versions (ATEX, FM, CSA, IECEx, NEPSI) can be supplied
by your Endress+Hauser Sales Center on request. All information relevant to explosion protection
is available in separate Ex documents that you can order as necessary.
Sanitary compatibility • 3A authorization (all measuring systems, except Promass H)
• EHEDG-tested (all measuring systems, except Promass H and E)
Pressure device approval Flowmeters with a nominal diameter smaller or equal DN 25 are covered by Art. 3(3) of the
European directive 97/23/EC (Pressure Equipment Directive) and are designed according to sound
engineer practice. For larger nominal diameters, optional approvals according to Cat. II/III are
available when required (depends on fluid and process pressure).
Optionally flowmeters in accordance to the guidelines AD 2000 are available on request (Promass
F and M only).
Functional safety SIL -2:
In accordance with IEC 61508/IEC 61511-1 (FDIS)
Other standards and
guidelines
• EN 60529
Degrees of protection by housing (IP code)
• EN 61010-1
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and
Laboratory Procedures
• IEC/EN 61326
"Emission in accordance with requirements for Class A".
Electromagnetic compatibility (EMC requirements).
•NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.
•NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal.
•NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics
Technical data Proline Promass 80 PROFIBUS PA
116
10.1.13 Ordering information
The FMC Technologies service organization can provide detailed ordering information and
information on the order codes on request.
10.1.14 Accessories
Various accessories, which can be ordered separately from FMC Technologies, are available for the
transmitter and the sensor. Page 67
10.1.15 Documentation
• Flow measuring technology (FA005D/06/en)
• Technical Information Promass 80F, 80M, 83F, 83M (TI053D/06/en)
• Technical Information Promass 80E, 83E (TI061D/06/en)
• Technical Information Promass 80A, 83A (TI 054D/06/en)
• Technical Information Promass 80H, 83H (TI074D/06/en)
• Technical Information Promass 80I, 83I (TI075D/06/en)
• Technical Information Promass 80S, 83S (TI076D/06/en)
• Technical Information Promass 80P, 83P (TI078D/06/en)
• Description of Device Functions Promass 80 PROFIBUS PA (BA073D/06/en)
• Supplementary documentation on Ex-ratings: ATEX, FM, CSA, IECEx, NEPSI
• Functional Safety Manual Promass 80, 83 (SD077D/06/en)
Proline Promass 80 PROFIBUS PA Index
117
Index
A
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Ambient temperature range. . . . . . . . . . . . . . . . . . . . . . . . 99
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Applicator (selection and configuration software) . . . . . . . . 68
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C
Cable entries
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Cable specifications (remote version) . . . . . . . . . . . . . . . . . 29
CE mark (declaration of conformity) . . . . . . . . . . . . . . . . . 12
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CIP cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Cleaning
CIP cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66, 99
Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
SIP cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Code entry (function matrix) . . . . . . . . . . . . . . . . . . . . . . . 40
Commissioning
Zero point adjustment . . . . . . . . . . . . . . . . . . . . . . . . . 62
Commubox FXA193 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Connection
See Electrical connection
C-tick mark. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cyclic data transmission PROFIBUS PA
AI module (Analog Input) . . . . . . . . . . . . . . . . . . . . . . 54
CONTROL_BLOCK. . . . . . . . . . . . . . . . . . . . . . . . . . . 59
DISPLAY_VALUE module . . . . . . . . . . . . . . . . . . . . . . 58
EMPTY_MODULE . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
SETTOT_MODETOT_TOTAL module . . . . . . . . . . . . . 57
SETTOT_TOTAL module. . . . . . . . . . . . . . . . . . . . . . . 57
TOTAL module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
D
Data transmission - cyclic PROFIBUS PA . . . . . . . . . . . . . . 53
Declaration of conformity (CE mark) . . . . . . . . . . . . . . . . . 12
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 99
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Device address, PROFIBUS PA configuration . . . . . . . . . . . 45
Device description files . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Device functions
See function descriptions
Device status, display . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Display
Display and operating elements . . . . . . . . . . . . . . . . . . 37
Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Local display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
See Display
Turning the display . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Display and operating elements . . . . . . . . . . . . . . . . . . . . . 37
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
E
Electrical connection
Cable specifications (remote version) . . . . . . . . . . . . . . 29
Degree of protection. . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Error limits
See Performance characteristics
Error messages
Confirming error messages . . . . . . . . . . . . . . . . . . . . . . 40
Process error (application error) . . . . . . . . . . . . . . . . . . 77
System error (device error) . . . . . . . . . . . . . . . . . . . . . . 71
Error types (system and process errors). . . . . . . . . . . . . . . . 41
European Pressure Equipment Directive. . . . . . . . . . . . . . 115
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
F
Fault message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
FieldCare. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Fieldcheck (tester and simulator) . . . . . . . . . . . . . . . . . . . . 68
Flow direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Function descriptions
See "Description of Device Functions" manual
Function groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Function matrix
Brief operating instructions. . . . . . . . . . . . . . . . . . . . . . 39
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Fuse, replacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
H
Hazardous substances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
HOME position (display operating mode) . . . . . . . . . . . . . . 37
I
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Inlet runs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Installation
See Installation conditions
Installation conditions
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Inlet and outlet runs. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Orientation (vertical, horizontal). . . . . . . . . . . . . . . . . . 16
System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Vertical pipe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Special instructions for
Promass F, E, H, P and S . . . . . . . . . . . . . . . . . . . . . . . 18
Special instructions for
Promass I and P with Eccentric Tri-clamps . . . . . . . . . . 18
Special instructions for
Promass I and P with hygienic connections. . . . . . . . . . 19
Installing the wall-mount housing . . . . . . . . . . . . . . . . . . . 23
Insulation of sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Proline Promass 80 PROFIBUS PA Index
118
L
Language groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Length of connecting cable . . . . . . . . . . . . . . . . . . . . . . . . 98
Limiting flow
See Measuring range
Local display
See Display
M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Material load diagram . . . . . . . . . . . . . . . . . . . . . . . 100, 114
Measured value status, display. . . . . . . . . . . . . . . . . . . . . . 71
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Measuring principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88–90
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Medium pressure range . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . . 99
Module
AI (Analog Input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
DISPLAY_VALUE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
EMPTY_MODULE. . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
SETTOT_MODETOT_TOTAL . . . . . . . . . . . . . . . . . . . 57
SETTOT_TOTAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
TOTAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
N
Nameplate
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Nameplate specifications
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Nominal pressure
See Medium pressure range
Notice message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
O
Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 98–99
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Operation
Device description files. . . . . . . . . . . . . . . . . . . . . . . . . 43
Display and operating elements
FieldCare. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Order code
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9–10
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Output signal
PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
P
Performance characteristics
Influence of medium pressure . . . . . . . . . . . . . . . . . . . 97
Influence of medium temperature . . . . . . . . . . . . . . . . 96
Maximum measured error. . . . . . . . . . . . . . . . . . . . . . 92
Reference operating conditions . . . . . . . . . . . . . . . . . . 92
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95–96
Post-installation check (checklist) . . . . . . . . . . . . . . . . . . . 25
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Power supply (supply voltage) . . . . . . . . . . . . . . . . . . . . . . 91
Pressure device approval. . . . . . . . . . . . . . . . . . . . . . . . . 115
Pressure loss (formulas, pressure loss diagrams) . . . . 101, 108
Pressure monitoring connections. . . . . . . . . . . . . . . . . . . . 65
Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Process error
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Process error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
PROFIBUS PA
Cable specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Cable type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Configuration examples. . . . . . . . . . . . . . . . . . . . . . . . 60
Cyclic data exchange. . . . . . . . . . . . . . . . . . . . . . . . . . 53
Device address, configuring . . . . . . . . . . . . . . . . . . . . . 45
Device description data . . . . . . . . . . . . . . . . . . . . . . . . 43
Hardware write protection . . . . . . . . . . . . . . . . . . . . . 44
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Spur . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
PROFIBUS PA block model. . . . . . . . . . . . . . . . . . . . . . . . 53
PROFIBUS PA cable specifications. . . . . . . . . . . . . . . . . . . 26
PROFIBUS PA cable type . . . . . . . . . . . . . . . . . . . . . . . . . 26
PROFIBUS PA cyclic data exchange . . . . . . . . . . . . . . . . . 53
PROFIBUS PA device description data. . . . . . . . . . . . . . . . 43
PROFIBUS PA hardware write protection . . . . . . . . . . . . . 44
PROFIBUS PA spur . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Programming mode
Disabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Enabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Pumps, mounting location, system pressure. . . . . . . . . . . . 15
Purge connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
R
Registered trademarks. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Repeatability (performance characteristics) . . . . . . . . . 95–96
Replacing
Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Returning devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
S
Safety icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Sanitary compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
S–DAT (HistoROM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Seals
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Medium temperature range . . . . . . . . . . . . . . . . . . . . 100
Replacing, replacement seals . . . . . . . . . . . . . . . . . . . . 66
Secondary containment
Gas purging, pressure monitoring connections . . . . . . . 65
Pressure range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Sensor heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Proline Promass 80 PROFIBUS PA Index
Endress+Hauser 119
Sensor mounting
See Sensor installation
Serial number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9–11
Service interface
Commubox FXA193 . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Shielding of the cable connection/T-box . . . . . . . . . . . . . . 33
SIL (functional safety) . . . . . . . . . . . . . . . . . . . . . . . . . 8, 115
SIP cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Software
Amplifier display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Versions (history). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Standards, guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Status input
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Supplementary Ex documentation . . . . . . . . . . . . . . . . . . . . 7
Supply voltage (power supply) . . . . . . . . . . . . . . . . . . . . . . 91
System error
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
System error messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
T
Temperature ranges
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . 99
Medium temperature range . . . . . . . . . . . . . . . . . . . . . 99
Storage temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Thermal insulation, general notes . . . . . . . . . . . . . . . . . . . 21
Transmitter
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installing the wall-mount housing . . . . . . . . . . . . . . . . 23
Turning the field housing (aluminum) . . . . . . . . . . . . . 22
Turning the field housing (stainless steel) . . . . . . . . . . . 22
Transporting the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Troubleshooting and remedy . . . . . . . . . . . . . . . . . . . . . . . 69
V
Vertical pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21, 99
W
Wall-mount housing, installing . . . . . . . . . . . . . . . . . . . . . 23
Weight
SI units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
US units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Wiring
See Electrical connection
Writes (max.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Z
Zero point adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Proline Promass 80 PROFIBUS PA Index
120
P/SF/Konta XIV
Because of legal regulations and for the safety of our employees and operating equipment, we need the "Declaration of Hazardous Material
and De-Contamination", with your signature, before your order can be handled. Please make absolutely sure to attach it to the outside of the
packaging.
Aufgrund der gesetzlichen Vorschriften und zum Schutz unserer Mitarbeiter und Betriebseinrichtungen, benötigen wir die unterschriebene
"Erklärung zur Kontamination und Reinigung", bevor Ihr Auftrag bearbeitet werden kann. Bringen Sie diese unbedingt außen an der
Verpackung an.
Serial number
Seriennummer ________________________
Type of instrument / sensor
Geräte-/Sensortyp ____________________________________________
Process data/Prozessdaten Temperature _____ [°F] [°C]
Conductivity / ________
_____
Leitfähigkeit
/
[μS/cm]
Temperatur Pressure _____ [psi] [ Pa ]
Viscosity _____ [cp] [mm /s]
_____
_____
/
/
Druck
Viskosität
2
corrosive
ätzend
harmless
unbedenklich
other *
sonstiges*
toxic
giftig
Process
medium
Identification
CAS No.
flammable
entzündlich
harmful/
irritant
gesundheits-
schädlich/
reizend
Medium /concentration
Medium /Konzentration
Returned part
cleaned with
Medium for
process cleaning
Medium and warnings
Warnhinweise zum Medium
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
*explosiv; brandfördernd; umweltgefährlich; biogefährlich; radioaktiv
Please tick should one of the above be applicable, include safety data sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifft einer der Warnhinweise zu, Sicherheitsdatenblatt und ggf. spezielle Handhabungsvorschriften beilegen.
Description of failure / Fehlerbeschreibung __________________________________________________________________________
______________________________________________________________________________________________________________
______________________________________________________________________________________________________________
“We hereby certify that this declaration is filled out truthfully and completely to the best of our knowledge.We further certify that the returned
parts have been carefully cleaned. To the best of our knowledge they are free of any residues in dangerous quantities.”
“Wir bestätigen
w
bestätigen, die vorliegende Erklärung nach unserem besten Wissen wahrheitsgetreu und vollständig ausgefüllt zu haben. Wir
eiter, dass die zurückgesandten Teile sorgfältig gereinigt wurden und nach unserem besten Wissen frei von Rückständen in gefahrbringen-
der Menge sind.”
(place, date / Ort, Datum)
Company data /Angaben zum Absender
Company / ________________________________
_________________________________________________
Address /
_________________________________________________
_________________________________________________
Firma ___
Adresse
Phone number of contact person /
____________________________________________
Fax / E-Mail ____________________________________________
Your order No. / ____________________________
Telefon-Nr. Ansprechpartner:
Ihre Auftragsnr.
Medium zur
Endreinigung
Medium zur
Prozessreinigung
Medium im
Prozess
Used as SIL device in a Safety Instrumented System / Einsatz als SIL Gerät in Schutzeinrichtungen
RA No.
Erklärung zur Kontamination und Reinigung
Declaration of Hazardous Material and De-Contamination
Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA#
clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
Bitte geben Sie die von E+H mitgeteilte Rücklieferungsnummer (RA#) auf allen Lieferpapieren an und vermerken Sie diese
auch außen auf der Verpackung. Nichtbeachtung dieser Anweisung führt zur Ablehnung ihrer Lieferung.
Name, dept./Abt.
(please print / )bitte Druckschrift
Signature / Unterschrift
Printed in U.S.A. © 5/09 FMC Technologies Measurement Solutions, Inc. All rights reserved. MN0M028 Issue/Rev. 0.0 (5/09)
Visit our website at www.fmctechnologies.com/measurementsolutions
The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently
in effect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.
Headquarters:
500 North Sam Houston Parkway West, Suite 100, Houston, TX 77067 USA, Phone: +1 (281) 260-2190, Fax: +1 (281) 260-2191
Gas Measurement Products:
Erie, PA USA +1 (814) 898-5000
Ellerbek, Germany +49 (4101) 304-0
Thetford, England +44 (1842) 82-2900
Kongsberg, Norway +47 (32) 286-700
Buenos Aires, Argentina +54 (11) 4312-4736
Integrated Measurement Systems:
Corpus Christi, TX USA +1 (361) 289-3400
Kongsberg, Norway +47 (32) 286-700
San Juan, Puerto Rico +1809 (787) 274-3760
United Arab Emirates, Dubai +971 (4) 331-3646
Liquid Measurement Products:
Erie, PA USA +1 (814) 898-5000
Los Angeles, CA USA +1 (310) 328-1236
Slough, England +44 (1753) 57-1515
Ellerbek, Germany +49 (4101) 304-0
Barcelona, Spain +34 (93) 201-0989
Moscow, Russia +7 (495) 564-8705
Melbourne, Australia +61 (3) 9807-2818
Beijing, China +86 (10) 6500-2251
Singapore +65 6861-3011
Chennai, India +91 (44) 450-4400

Navigation menu