Friedrich Air Conditioner Cp06E10 Users Manual CP06F10 Service And Parts | Sylvane
CP08E10 to the manual 846afde1-a07f-4607-a732-84ff724a0651
2015-02-02
: Friedrich Friedrich-Friedrich-Air-Conditioner-Cp06E10-Users-Manual-428231 friedrich-friedrich-air-conditioner-cp06e10-users-manual-428231 friedrich pdf
Open the PDF directly: View PDF .
Page Count: 30
Download | |
Open PDF In Browser | View PDF |
www.sylvane.com 1-800-934-9194 Room Air Conditioner Service and Parts Manual 0F hr Fan Speed Money Fan Cool Saver ® Only Dry Timer 0n/0ff CP08E10 CP06 CP08 SVC PARTS 2008(07/08) CP06E10 Mode Auto Swing Temp Power www.sylvane.com 1-800-934-9194 Air Conditioner Service Manual TABLE OF CONTENTS Safety Precautions..........................................................................................................................................3 Dimensions .....................................................................................................................................................6 Outside Dimensions ...................................................................................................................................6 Product Specifications ..................................................................................................................................7 Operation ...................................................................................................................................................... 8 How to Operate Your Friedrich CP........................................................................................................... 9 Disassembly ..................................................................................................................................................10 Mechanical Parts..................................................................................................................................... 10 Air H andling Parts ...................................................................................................................................11 Electrical Parts .........................................................................................................................................12 Refrigerating Cycle...................................................................................................................................13 Schematic Diagram.......................................................................................................................................16 Wiring Diagram.........................................................................................................................................16 Electronic Control Device .........................................................................................................................17 Components Location(For Main P.W.B ASM)...........................................................................................18 Troubleshooting Guide .................................................................................................................................19 Piping System ........................................................................................................................................19 Troubleshooting Guide .............................................................................................................................20 Exploded View ..............................................................................................................................................28 Replacement Parts List ................................................................................................................................29 2 Room Air Conditioner www.sylvane.com 1-800-934-9194 Safety Precautions Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instructions will cause harm or damage. The seriousness is classified by the following indications. WARNING This symbol indicates the possibility of death or serious injury. CAUTION This symbol indicates the possibility of injury or damage to property only. Meanings of symbols used in this manual are as shown below. Be sure not to do. Be sure to follow the instruction. WARNING Always install the expansion panel(s). • Improper assembly or installation may cause incorrect operation, including injury, fire, and electric shock hazards. Do not use the power cord near flammable gas or combustibles such as gasoline, benzene, thinner, etc. • It may cause explosion or fire. Do not place the power cord near a heater. • It may cause fire and electric shock. Do not disassemble or modify products. • It may cause failure and electric shock. Service Manual 3 www.sylvane.com 1-800-934-9194 Safety Precautions Plug in the power plug properly. • Otherwise, it will cause electric shock or fire. Do not modify po power wer cord length. • It will cause electric shock or fire. Ventilate before operating air conditionerwhen gas goes out. • It may cause explosion, fire, and burn. 4 Room Air Conditioner Do not operate or stop the unit by inserting or pulling out the power plug. Do not damage or use an unspecified power cord. • It will cause electric shock or fire. • It will cause electric shock or fire. Use the air conditioner on a single outlet circuit.(see page 7.) Do not share the outlet with other appliances. • It will cause electric shock or fire. Do not use the socket if it is loose or damaged. • It may cause fire and electric shock. Always plug into a grounded outlet. • No grounding may cause electric shock. Do not operate with wet hands or in damp environment. • It will cause electric shock. www.sylvane.com 1-800-934-9194 Safety Precautions If water enters the product, turn off the the power switch of the main body of appliance. Contact service center after taking the powerplug out from the socket. • It will cause electric shock or failure of machine. Do not clean the air conditioner with water. • Water may enter the unit and degrade the insulation. It may cause an electric shock. CAUTION Never touch the metal parts of the unit when removing the filter. Do not block the inlet or outlet. • They are sharp and may cause injury. • It may cause failure of appliance or performance deteriorate. Ensure that the outer caseis not damaged by age orwear. Be cautious not to touch the sharp edges • installing. when • Leaving it damaged couldresult in the air conditioner falling out of the window, creating a safety hazard. • It may cause injury. Sharp edges Service Manual 5 www.sylvane.com 1-800-934-9194 Dimensions Dimensions Symbols Used in this Manual This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the air conditioner. NOTICE This symbol indicates special notes. Outside Dimensions 11/ 16") 470(18 1/2") 353(13 7/8") 525(20 6 Room Air Conditioner www.sylvane.com 1-800-934-9194 Specfications Product Specifications MODLES ITEMS CP06E10 CP08E10 POWER SUPPLY 1Ø, 115, 60Hz COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (BTU/W.h) OPERATING INDOOR ( C) OUTDOOR ( C) REFRIGERANT (R-22) CHARGE 7,800 6,000 720 560 6.8 5.1 10.8 10.7 26.7(DB)* 19.4(WB)** 35(DB)* 23.9(WB)** 490g(17.3 oz) 285g(10.1 oz) EVAPORATOR Ø7.0, 2ROW 14STACKS CONDENSER Ø5.0, 2ROW 16STACKS FAN, INDOOR TURBO FAN FAN, OUTDOOR PROPELLER TYPE FAN WITH SLINGER RING FAN SPEEDS, FAN/COOLING 3/3 FAN MOTOR 6 POLES OPERATION CONTROL REMOTE CONTROLLER ROOM TEMP. CONTROL THERMISTOR AIR DIRECTION CONTROL HORIZONTAL LOUVER (UP & DOWN), AUTOSWING LOUVER (RIGHT&LEFT) CONSTRUCTION PROTECTOR SLIDE IN-OUT CHASSIS COMPRESSOR FAN MOTOR OVERLOAD PROTECTOR INTERNAL THERMAL PROTECTOR 3 WIRE WITH GROUNDING POWER CORD ATTACHMENT PLUG (CORD-CONNECTED TYPE) DRAIN SYSTEM DRAIN PIPE OR SPLASHED BY FAN SLINGER OUTSIDE DIMENSION (inch) 18 1/2 x 13 7/8 x 20 11/16 (W x H x D) (mm) 469 x 353 x 526 * DB:Dry Bulb ** WB:Wet Bulb Service Manual 7 Ser www.sylvane.com 1-800-934-9194 Operation Operation • • • • • • DESIGNED FOR COOLING ONLY POWERFUL AND INCREDIBLE COOLING TOP-DOWN CHASSIS FOR THE SIMPLE INSTALLATION AND SERVICE BUILT-IN ADJUSTABLE THERMOSTAT WASHABLE ONE-TOUCH FILTER COMPACT SIZE Location and Function of Controls Service Manual 8 www.sylvane.com 1-800-934-9194 4 6 7 A ir P urifier Power 0F 1 Temp hr Fan Speed 2 Fan S peed Money Saver ® Fan Cool Only Dry Timer 0n/0ff Mode 5 3 4 Auto Swing 5 Temp 6 Power 2 dry operation. (dehumidify operation) Auto Swing Mode A S wing 3 1 6. AUTO SWING This button can automatically control the air flow direction(left+right). 7 9 Room Air Conditioner T imer To receive the signal from remote controller. www.sylvane.com 1-800-934-9194 Disassembly Disassembly — Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord. Mechanical Parts 1. FRONT GRILLE 1. Open the lnlet grille upward or downward. 2. Remove the screw which fastens the front grille. 3. Pull the front grille from the right side. 4. Remove the front grille. 5. Re-install the component by referring to the removal procedure, above.(See Figure 17) Figure 17 2. CABINET 1. After disassembling the FRONT GRILLE, remove the 2 screws which fasten the cabinet at both sides. 2. Remove the 2 screws which fasten the cabinet at back. 3. Pull the base pan forward. (See Figure 18) 4. Remove the cabinet. 5. Re-install the component by referring to the removal procedure, above. Figure 18 3. CONTROL BOX 1. Disconnect the unit from the power source. 2. Remove the front grille. 3. Remove the cabinet. 4. Remove the screw which fastens the control box cover. 5. Remove the housing which connects motor wire in the control box. 6. Remove the 3 leads from the compressor. 7.Discharge the capacitor by placing a 20,000 ohmresistor across the capacitor terminals. 8. Remove the 2 screws which fasten the control box.(See Figure 19) 9. Pull the control box forward completely. 10. Re-install the components by referring to the removal procedure, above. (See Figure 19) Figure 19 Service Manual 10 www.sylvane.com 1-800-934-9194 Disassembly Air Handling Parts 1. AIR GUIDE AND BLOWER 1. Remove the front grille. 2. Remove the cabinet. 3. Remove the control box. 4. Remove the 3 screws which fasten the brace. 5. Remove the brace. 6. Remove the 2 screws which fasten the evaporator. 7. Move the evaporator forward and pulling it upward slightly. (See Figure 20) 8. Move the evaporator to the left carefully. 9. Pull out the hook of orifice by pushing the tabs and remove it. (See Figure 21) 10. Remove the clamp with a hand plier which secures the blower. 11. Remove the blower. 12. Remove the 4 screws which fasten the air guide from the barrier. 13. Move the air guide backward, pulling out from the base pan. 14. Re-install the components by referring to the removal procedure, above. Figure 20 Figure 21 2. FAN AND SHROUD 1. Remove the cabinet. 2. Remove the brace. 3. Remove the 3 screws which fasten the condenser. 4. Move the condenser to the left carefully. 5. Remove the clamp which secures the fan. 6. Remove the fan and then pull out the shroud. (See Figure 22) 7. Re-install by referring to the removal procedure. Figure 22 11 Room Air Conditioner —7— www.sylvane.com 1-800-934-9194 Disassembly 3. MOTOR 1. Remove the cabinet. 2. Remove the evaporator. 3. Remove the orifice. 4. Remove the blower. 5. Remove the fan. 6. Remove the control box cover and housing of the motor in the control box. 7. Remove the 2 screws which fasten the motor from the mount motor. (See Figure 23) 8. Remove the motor. 9. Re-install the components by referring to the removal procedure, above.(See Figure 23) Figure 23 Electrical Parts 1. OVERLOAD PROTECTOR 1. Remove the cabinet. 2. Remove the nut which fastens the terminal cover. 3. Remove the terminal cover. (See Figure 24) 4. Remove all the leads from the overload protector. 5. Remove the overload protector. 6. Re-install the component by referring to the removal procedure, above. Figure 24 2. COMPRESSOR 1. Remove the cabinet. 2. Discharge the refrigerant system using a FreonTM Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system. 3. Remove the overload protector. 4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections. 5. Remove the 3 nuts and the 3 washers which fasten the compressor. 6. Remove the compressor. (See Figure 25) 7. Re-install the components by referring to the removal procedure, above. Figure 25 Service Manual 12 www.sylvane.com 1-800-934-9194 Disassembly 3. CAPACITOR 1. Remove the control box. 2. Remove the screw which fasten control panel from control box. 3. Remove the screw which located in the front. 4. Open the bottom side of control box. 5. Remove the screw and the clamp which fastens the capacitor. 6. Disconnect all the leads of capacitor terminals. 7. Re-install the components by referring to the removal procedure, above. (See Figure 26) Figure 26 4. POWER CORD 1. Remove the control box. 2. Open the control box. 3. Disconnect the grounding screw from the control box. 4. Disconnect the 2 receptacles. 5. Remove a screw which fastens the clip cord. (See Figure 27) 6. Remove the power cord. 7. Re-install the component by referring to the above removal procedure, above. (Use only one ground-marked hole for ground connection.) 8. If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord which has the same specification marked on the supply cord attached at the unit.) Figure 27 Refrigerating Cycle CAUTION: Discharge the refrigerant system using a FreonTM Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system. 1. CONDENSER 1. Remove the cabinet. 2. Remove the 3 screws which fasten the brace. 3. Remove the 3 screws which fasten the condenser and shroud. 4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections. 5. Remove the condenser carefully. 6. Re-install the component by referring to notes. (See Figure 28) Figure 28 Service Manual 13 www.sylvane.com 1-800-934-9194 Disassembly 2. EVAPORATOR 1. Remove the cabinet. 2. Remove the 2 screws which fasten the evaporator. 3. Move the evaporator sideways carefully. 4. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections. 5. Remove the evaporator carefully. 6. Re-install the component by referring to notes. (See Figure 29) 3. CAPILLARY TUBE 1. Remove the cabinet. 2. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube. 3. Remove the capillary tube. 4. Re-install the component by referring to notes. NOTICE — Replacement of the refrigeration cycle. 1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system. 2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes. 3. Solder service valves into the pinch-off tube ports, leaving the valves open. 4. Solder the pinch-off tubes with Service valves. 5. Evacuate as follows. 1) Connect the vacuum pump, as illustrated figure 30A. 2) Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system. CAUTION: If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump. 3) Operate the vacuum pump vaccum for 20 to 30 minutes, until 600 microns of vaccum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture 14 Room Air Conditioner Figure 29 remaining in the system. With valves A and B closed, stop the vacuum pump. 4) Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 37B. Open valve C. Discharge the line at the manifold connection. 5) The system is now ready for final charging. 6. Recharge as follows : 1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened. 2) Connect the charging cylinder as shown in figure 30B. With valve C open, discharge the hose at the manifold connection. 3) Open valve A and allow the proper charge to enter the system. Valve B is still closed. 4) If more charge is required, the high-side will not take it. Close valve A. 5) With the unit running, open valve B and add the balance of the charge. a. Do not add the liquid refrigerant to the Low-side. b. Watch the Low-side gauge; allow pressure to rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps b. and c. until the balance of the charge is in the system. 6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos braze and braze pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection. www.sylvane.com 1-800-934-9194 Disassembly Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve. COMPOUND GAUGE CONDENSER (HIGH PRESSURE SIDE) MANIFOLD GAUGE A B CAPILLARY TUBE SEE INSETS BELOW EVAPORATOR (LOW PRESSURE SIDE) COMPRESSOR LOW HI A B B A EXTERNAL VACUUM PUMP CHARGING CYLINDER C Figure 30A-Pulling Vacuum Figure 30B-Charging Service Manual 15 www.sylvane.com 1-800-934-9194 Schematic Diagram Circuit Diagram 1 6 2 4 7 5 3 8 LOCATION NO. DESCRIPTION Q'TY PER SET 1 POWER CORD ASSEMBLY 1 2 FAN MOTOR 1 3 COMPRESSOR 1 4 DISPLAY P.W.B ASSEMBLY 1 5 MAIN P.W.B ASSEMBLY 1 6 THERMISTOR 1 7 CAPACITOR 1 8 OWERLOAD PROTECTOR 1 Service Manual 16 www.sylvane.com 1-800-934-9194 Schematic Diagram Electronic Control Device 17 Room Air Conditioner www.sylvane.com 1-800-934-9194 Schematic Diagram Components Location(For Main P.W.B ASM) Service Manual 18 www.sylvane.com 1-800-934-9194 Troubleshooting Guide Troubleshooting Guide Piping System CONDENSER COIL FAN CAPILLARY TUBE MOTOR COMPRESSOR BLOWER EVAPORATOR COIL Figure 38 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle. ROOM AIR CONITIONER CYCLE OF REFRIGERATION EVAPORATOR COILS CONDENSER COILS COMPLETE LIQUID BOIL OFF POINT COOLED AIR SUCTION LINE COOL LOW PRESSURE VAPOR VAPOR INLET HOT DISCHARGED AIR ROOM AIR HEAT LOAD MOTOR OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH COMPRESSOR OIL LIQUID PRESSURE DROP LIQUID OUTLET (LIQUID REFRIGERANT) HIGH PRESSURE VAPOR LIQUID REFRIGERANT CAPILLARY TUBE LOW PRESSURE VAPOR Figure 34 19 Room Air Conditioner www.sylvane.com 1-800-934-9194 Troubleshooting Guide Troubleshooting Guide In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but poor cooling. Ineffective Cooling Check cold air circulation for smooth flow. Check outdoor coil (heat exchanger) and fan operation. Dirty indoor coil (heat exchanger) Check gas leakage. Check heat load increase. Clean condenser. Not on separate circuit Repair gas leak. Malfunction of fan. Clogging of air filter. Replacement of unit if the unit is beyond repair. Check inside gas pressure. Adjust refrigerant charge. Obstruction at air outlet. Remove obstruction. Malfunction of compressor. Check clogging in refrigeration circuit. Replacement of compressor. Repair clogging in refrigeration circuit. Satisfactory operation with temperature difference of inlet & outlet air; 44~50°F (7~10°C) Service Manual 20 www.sylvane.com 1-800-934-9194 Troubleshooting Guide Fails to Start Check of power source. Check of circuit breaker and fuse. Check of control panel setting. Check control panel. Compressor fails only to start. Fan only fails to start. Drop of power voltage. Defect of compressor capacitor. Capacitor check. Improper thermistor setting Loose terminal connection Improper wiring Improper wiring. Defect of fan motor capacitor. Irregular motor resistance (Ω) Irregular motor insulation (Ω) Replacement. Replacement of fan motor. Irregular motor resistance (Ω) Irregular motor insulation (Ω) Replacement of compressor (Motor damaged). 21 Room Air Conditioner Regular but fails to start. Replacement of compressor. (Locking of piston, metal.) www.sylvane.com 1-800-934-9194 Troubleshooting Guide ELECTRIC PARTS TROUBLESHOOTING GUIDE: Possible Trouble 1 Is the Trans input power AC 115V? • The unit does not operate. NO • Check the Fuse. • Check the wiring diagram. YES Is the Trans output power about AC 14V? NO YES Is output Voltage of IC01D DC 12V? Is shorted the Trans. output? YES NO NO • Check the Main P.W.B pattern. • Exchange the Trans. • Exchange D02D~D05D. • Exchange IC01D. YES Is output Voltage of IC02D DC 5V? NO • Exchange IC02D. YES Is the reset circuit all right? (The No.14 of Micom is 5V.) NO • Exchange IC01A. YES Is the connection between Main and Display all right? NO • Connect connector exactly. NO • Check the P.W.B pattern. YES Is the voltage No.18 of Micom DC 5V? YES Exchange Main P.W.B Ass'y. Service Manual 22 www.sylvane.com 1-800-934-9194 Troubleshooting Guide Possible Trouble 2 • The compressor does not operate. Is Temp. NO setting set lower than Room Temp.-0.5°C? • Set the Temp. setting to lower Temp. YES Is the voltage No.10 of IC01M 0V? NO Is the voltage N0.7 of IC01M DC 5V? NO YES YES • Check the RY-COMP. • Check the wiring Diagram. • Exchange IC01M. Is the Unit for 3 minutes delay? NO YES • Wait 3 Minutes • Exchange MAIN P.W.B Ass'y. Possible Trouble 3 Is the wire connection of RY-COMP all right? • The compressor always operate. • Connect LEAD Wire to RY-COMP again. NO YES • Check the RY-COMP. Possible Trouble 4 Is the voltage NO.1 or 4 of IC01M DC 5V? • Fan does not operate. NO • Exchange IC01M. YES Is the voltage NO.13 or 16 of IC01M 0V? YES • Check the RY-Hi or RY-Lo. • Check the wiring diagram. 23 Room Air Conditioner NO • Exchange IC01M. www.sylvane.com 1-800-934-9194 Troubleshooting Guide • Romote controller does not operate. Possible Trouble 5 Is the voltage of Battery about over 2.3V? NO • Exchange the battery. YES Is the voltage No.16 of CN-DISP1 on Main P.W.B Ass'y DC 5V? NO • Check the P.W.B pattern. YES NO Is the connection of CN-DISP1 all right? • Connect connector to CN-DISP1 exactly. YES • Exchange Receiver Ass'y. Possible Trouble 6 Is the IC01G all right? • It displays abnormally on Display P.W.B Ass'y. NO • Exchange IC01G. YES NO Is the connection of CN-DISP1 all right? NO • Connect connector to CN-DISP1 exactly. YES Does the Q01G, Q02G, Q03G Q04G operate normally on main P.W.B Ass'y? NO • Exchange Q01G, Q02G, Q03G, Q04G YES • Exchange the display P.W.B Ass'y. Service Manual 24 www.sylvane.com 1-800-934-9194 Troubleshooting Guide ROOM AIR CONDITIONER VOLTAGE LIMITS NAME PLATE RATING MINIMUM MAXIMUM 115V ± 10% 103.5V 126.5V COMPLAINT Fan motor will not run. CAUSE REMEDY No power Check voltage at outlet. Correct if none. Power supply cord Check voltage to rotary switch. If none, check power supply cord. Replace cord if circuit is open. Rotary switch Check switch continuity. Refer to wiring diagram for terminal identification. Replace switch if defective. Wire disconnected or connection loose Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal. Capacitor (Discharge capacitor before testing.) Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged. Will not rotate Fan blade hitting shroud or blower wheel hitting scroll. Re-align assembly. Units using slinger ring condenser fans must have 0.22~0.25 inch clearance to the base. If necessary, shim up the bottom of the fan motor with mounting screw(s). Check fan motor bearings; if motor shaft will not rotate, replace the motor. Fan motor runs. Revolves on overload Check voltage. See limits on this page. If not within limits, call an electrician. Test capacitor. Check bearings. Does the fan blade rotate freely? If not, replace fan motor. Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor. 25 Room Air Conditioner www.sylvane.com 1-800-934-9194 Troubleshooting Guide COMPLAINT Fan motor noise. Compressor will not run, fan motor runs. CAUSE REMEDY Fan If cracked, out of balance, or partially missing, replace it. Blower If cracked, out of balance, or partially missing, replace it. Loose set screw Tighten it. Worn bearings If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor. Voltage Check voltage. See the limits on the preceding page. If not within limits, call an electrician. Wiring Check the wire connections; if loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires. Check the wire connections; If not according to the wiring diagram, correct the connections. Thermistor Check the TEMP control. If not at the lowest number, set TEMP control to this setting and restart the unit. Check the continuity of the thermistor. Replace the thermistor if the circuit is open. Rotary Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if the circuit is open. Thermostat Check the position of knob. If not at the coldest setting, advance the knob to this setting and restart the unit. Check the continuity of the thermostat. Replace the thermostat if the circuit is open. Capacitor (discharge capacitor before servicing.) Check the capacitor. Replace if not within ±10% of manufacturer’s rating, replace if shorted, open, or damaged. Compressor Check the compressor for open circuit or ground. If open or grounded, replace the compressor. Overload Check the compressor overload if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.) Service Manual 26 www.sylvane.com 1-800-934-9194 Troubleshooting Guide COMPLAINT Compressor cycles on overload. Compressor cycles on overload. Insufficient cooling Excessive noise 27 Room Air Conditioner CAUSE REMEDY Voltage Check the voltage. See the limits on the preceding page. If voltage is not within these limits, call an electrician. Overload Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.) Fan motor If not running, determine the cause. Replace if required. Condenser air flow restriction Remove the cabinet, inspect the interior surface of the condenser. If restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before re-assembling. Condenser fins (damaged) If the condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to cycle. Straighten the fins or replace the coil. Capacitor Test the capacitor. Wiring Check the terminals. If loose, repair or replace. Refrigeration system Check the system for a restriction. Air filter If restricted, clean or replace. Unit undersized Determine if the unit is properly sized for the area to be cooled. Blower or fan Check the set screw, or clamp. If loose or missing, correct. If the blower or fan is hitting scroll or barrier, rearrange the air handling parts. Copper tubing Remove the cabinet and carefully rearrange the tubing not to contact the cabinet, compressor, shroud, and barrier. www.sylvane.com 1-800-934-9194 Exploded View Exploded View 554030 130910 731273 148000 559010 346811 352380 W48602 749740 349600 149980 359012 267110 354210 349001 349480 567502 135314 159830 130410 554160 550140 147581 135312 352115-1 352115-2 249950 567480 W0CZZ 268711-1 552102 552113 238310 352113 146812 264110 237200 268711-2 135510 35211A Ser vice Man ual 28 www.sylvane.com 1-800-934-9194 Replacement Parts list LocNo CP06E10 CP08E10 DESCRIPTION REMARK 130410 67302912 67302905 Base Assy Single R 349001 67303502 67303502 Damper Assembly R 130910 67303714 67303714 Cabinet Assy Single R 135312 67306017 67306017 Grille Assy Front R 135314 67306110 67306110 Grille Assy Inlet R 135510 67400148 67400148 Cover R 147581 67306208 67306208 Louver,Horizontal R 147582 67306264 67306264 Louver,Vertical R 149980 67303108 67303104 Shroud R 159830 67304309 238310 67500142 67500142 Escutcheon R 567480 67307806 67307806 Thermistor R 264110 67300020 67300020 Power Cord Assy R 267110 67307704 67307704 Remote Controller R 249950 67305511 67305513 Case Assembly,Control R 237200 67305512 67305512 Panel,Control R 268711-1 67307621 67307621 PWB(PCB) Assy Display R 268711-2 67307622 67307622 PWB(PCB) Assy Main R 146812 67300902 349600 67303604 67303604 Bracket,Motor R 346811 67303013 67303005 Motor Assy Single R 349480 67303412 67303412 Orifice R 352380 67302736 67302736 Duct Assembly R 552102 67400188 67400190 Tube Assy Capillary R 550140 67301900 67301901 Isolator Comp R 559010 67303203 67303203 Fan Assy Axial R 359012 67302609 67302609 Fan Turbo R 148000 67303901 67303901 Supporter R 567502 W0CZZ 67301405 67300718 67301406 67302726 O.L.P. Overload Protect Capacitor R R 731273 67306312 67306312 installation Kit w/Curtain R W48602 67302500 67302500 Clamp Spring R 749740 67304002 67304002 Upper Guide Cabinet R 29 Room Air Conditioner 67304309 67300902 Filter (Mech) Swing Louver Motor R R www.sylvane.com 1-800-934-9194 Use Factory Certified Parts... FRIEDRICH AIR CONDITIONING CO. Visit our web site at www.friedrich.com Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540 • (210) 357-4400 • FAX (210) 357-4490 CP06 CP08 SVC PARTS 2008(07/08)
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 4.05 for Macintosh Create Date : 2004:02:05 16:23:32Z Modify Date : 2008:07:09 16:57:27+08:00 Metadata Date : 2008:07:09 16:57:27+08:00 Creator Tool : Adobe Illustrator CS2 Thumbnail Width : 200 Thumbnail Height : 256 Thumbnail Format : JPEG Thumbnail Image : (Binary data 2103 bytes, use -b option to extract) Instance ID : uuid:b962d1e8-7608-484e-82e9-19cf8cf93a2c Document ID : uuid:415984a1-6c3d-4ec5-bf52-104cb5a4601a Format : application/pdf Has XFA : No Page Count : 30 Creator : Adobe Illustrator CS2 Title : Friedrich CP06F10 Service and Parts Manual | Sylvane Subject : Information on servicing and parts for Friedrich CP06F10 window AC Keywords : Friedrich, CP06F10, Window, AC, Service, and, Parts, ManualEXIF Metadata provided by EXIF.tools