Gallagher Group C30047XA Prox Readers T15 Mifare and T15 Mifare PIV User Manual

Gallagher Group Ltd Prox Readers T15 Mifare and T15 Mifare PIV Users Manual

Users Manual

Page 1
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
Gallagher
T15 Terminal
Installaon Note
T15 Mifare Reader Black: C300470
T15 Mifare Reader White: C300471
T15 Mul Tech Reader Black: C300480
T15 Mul Tech Reader White: C300481
T15 PIV Mifare Reader Black: C305470
T15 PIV Mifare Reader White: C305471
T15 PIV Mul Tech Reader Black: C305480
T15 PIV Mul Tech Reader White: C305481
Page 2
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
Disclaimer
This document gives certain informaon about products and/or services provided by Gallagher Group Limited
or its related companies (referred to as "Gallagher Group").
The informaon is indicave only and is subject to change without noce meaning it may be out of date at any
given me. Although every commercially reasonable eort has been taken to ensure the quality and accuracy
of the informaon, Gallagher Group makes no representaon as to its accuracy or completeness and it should
not be relied on as such. To the extent permied by law, all express or implied, or other representaons or
warranes in relaon to the informaon are expressly excluded.
Neither Gallagher Group nor any of its directors, employees or other representaves shall be responsible
for any loss that you may incur, either directly or indirectly, arising from any use or decisions based on the
informaon provided.
Except where stated otherwise, the informaon is subject to copyright owned by Gallagher Group and you may
not sell it without permission. Gallagher Group is the owner of all trademarks reproduced in this informaon.
All trademarks which are not the property of Gallagher Group, are acknowledged.
Copyright © Gallagher Group Ltd 2016. All rights reserved.
Page 3
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
Contents
1 Introducon ..................................................................................................................................... 4
2 Before you begin .............................................................................................................................. 4
3 Distance between proximity readers ............................................................................................... 7
4 Installaon ....................................................................................................................................... 8
5 LED indicaons ............................................................................................................................... 10
6 Accessories .................................................................................................................................... 10
7 Technical specicaons .................................................................................................................. 11
8 Approvals and standards ................................................................................................................ 12
9 Mounng dimensions .................................................................................................................... 13
Page 4
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
1 Introducon
The Gallagher T15 Reader is a smart card proximity reader. It can be installed as either an entry reader
or exit reader. The reader contains an NXP chip for improved read range performance and supports
Bluetooth® technology for hands-free access.
The reader sends informaon to the Gallagher Controller and acts upon informaon sent from the
Gallagher Controller. The reader itself does not make any access decisions.
The reader is available in eight variants. The card technologies for each variant are shown below.
Reader Product code Supported card technologies
T15 Mifare Reader Black
T15 Mifare Reader White
C300470
C300471
Mifare DESFire EV1, Mifare Plus and Mifare Classic
T15 Mul Tech Reader Black
T15 Mul Tech Reader White
C300480
C300481
Mifare DESFire EV1, Mifare Plus, Mifare Classic and
125 KHz cards
T15 PIV Mifare Reader Black
T15 PIV Mifare Reader White
C305470
C305471
PIV, PIV-I, Mifare DESFire EV1, Mifare Plus and
Mifare Classic
T15 PIV Mul Tech Reader Black
T15 PIV Mul Tech Reader White
C305480
C305481
PIV, PIV-I, Mifare DESFire EV1, Mifare Plus, Mifare
Classic and 125 KHz cards
The reader can be connected as an HBUS Reader or Cardax IV Reader. An HBUS Reader uses the HBUS
communicaons protocol to communicate with the Gallagher Controller 6000. A Cardax IV Reader uses
the Cardax IV communicaons protocol to communicate with a Gallagher Controller.
HBUSReaderCompability
HBUS communicaons are only supported for sites running Command Centre v7.00 soware (or later).
GallagherMulTechReaders
Gallagher strongly recommends against using dual technology 125/Mifare cards with Gallagher Mul
Tech readers for sites running pre-Command Centre v7.00 soware. From Command Centre v7.00, a
site may specify which technology a Mul Tech reader should read o a dual technology card.
Gallagher PIV Readers
Gallagher PIV Readers connect to the Gallagher Controller 6000 High Spec PIV (C305101) only (referred
to as the Controller). Gallagher PIV Readers can only be used with sites running Gallagher Command
Centre vEL7.10 soware (or later). Gallagher PIV Readers are connected as HBUS Readers only.
2 Beforeyoubegin
2.1 Shipment contents
Check the shipment contains the following items:
1 x Gallagher T15 Reader facia assembly
1 x Gallagher T15 Reader base
1 x M3 Torx Post Security screw
2 x 25 mm No.6 self tapping, pan head, Phillips drive xing screws
2 x 40 mm No.6 self tapping, pan head, Phillips drive xing screws
Page 5
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
2.2 Powersupply
The Gallagher T15 Reader is designed to operate over a supply voltage range of 9 - 16 Vdc
measured at the reader terminals. The operang current draw is dependant on the supply
voltage at the reader. The power source should be linear or a good quality switched-mode
power supply. The performance of the reader may be aected by a low quality, noisy power
supply.
2.3 Cabling
The Gallagher T15 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm2) stranded
security cable. This cable allows the transmission of data (2 wires) and power (2 wires). When
using a single cable to carry both power supply and data, both the power supply voltage drop
and data requirements must be considered. Although the reader is specied to operate at 9
Vdc, for good engineering design it is recommended that the voltage at the reader should be
approximately 12 Vdc.
 HBUScablingtopology
The HBUS communicaons protocol is based on the RS485 standard and allows the reader to
communicate over a distance of up to 500 m (1640 ).
The cabling between HBUS devices should be done in a "daisy chain" topology, (i.e. A "T" or
"Star" topology should not be used between devices). Should "Star" or "Home-Run" wiring be
required, the HBUS 4H/8H Modules and the HBUS Door Module allow mulple HBUS devices to
be individually wired to the one physical locaon.
The end devices on the HBUS cable should be terminated using 120 ohms resistance. To
terminate the Gallagher Controller 6000, connect the supplied on-board terminaon jumpers
to the Controller. To terminate a reader, connect the orange (terminaon) wire to the green
(HBUS A) wire. Terminaon is already included at the HBUS Module, (i.e. each HBUS port is
permanently terminated at the module).
Connect the on-board
terminaon jumper
Controller 6000
RS485 1
HBUS
Device
"T" or "Star" circuits are
not permied between
HBUS devices
HBUS
Device
Terminate
HBUS
Device
HBUS
Device
HBUS
Device
Page 6
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
HBUS
Device
HBUS
Device
HBUS
Device
Terminate
Remove the on-board
terminaon jumper
RS485 1
"T" or "Star" circuits are
not permied between
HBUS devices
HBUS
Device
Terminate
HBUS
Device Controller 6000
HBUS
Device
"T" or "Star" circuits are
not permied between
HBUS devices
Controller 6000
H1 H4
H8
H5
HBUS
Device
Terminate
HBUS
Device
Terminate
HBUS Module
HBUS
Device
HBUS
Device
Terminate
HBUS
Device
Terminate
HBUS
Device
 Cabledistance
Cabletype Cableformat* HBUS
single reader
connected using
dataonlyina
singlecable
Cardax IV
single reader
connected using
dataonlyina
singlecable
HBUS/Cardax IV
single reader
connected using
power and data
inasinglecable
CAT 5e or
beer**
4 twisted pair
Each 2 x 0.2 mm2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
BELDEN 9842**
(shielded)
2 twisted pair
Each 2 x 0.2 mm2
(24 AWG)
500 m (1640 ) 200 m (650 ) 100 m (330 )
SEC472 4 x 0.2 mm2
Not twisted
pairs (24 AWG)
400 m (1310 ) 200 m (650 ) 100 m (330 )
SEC4142 4 x 0.4 mm2
Not twisted
pairs (21 AWG)
400 m (1310 ) 200 m (650 ) 150 m (500 )
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for opmal HBUS RS485 performance.
Page 7
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
Notes:
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
If other cable types are used, operang distances and performance may be reduced
depending on the cable quality.
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to funcon correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.
3 Distancebetweenproximityreaders
The distance separang any two proximity readers must not be less than 200 mm (8 in) in all direcons.
200 mm
When mounng a proximity reader on an internal wall, check that any reader xed to the other side of
the wall is not less than 200 mm (8 inches) away.
200 mm
Page 8
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
4 Installaon
ATTENTION: This equipment contains components that can be damaged by
electrostac discharge. Ensure both you and the equipment are earthed before
beginning any servicing.
The Gallagher T15 Reader is designed to be mounted on any solid at surface. However installaon on
metal surfaces, parcularly those with a large surface area will reduce read range. The extent to which
the range is reduced will depend upon the type of metal surface.
The recommended mounng height for the reader is 1.1 m (3.6 ) from the oor level to the centre of
the reader device. However this may vary in some countries and you should check local regulaons for
variaons to this height.
1. Use the reader base as a guide to drill all three holes. Drill the 13 mm (1/2 inch) diameter centre
hole (this is the centre hole for which the building cable will exit the mounng surface) and the
two xing holes.
2. Run the building cabling out through the centre hole and through the reader base.
3. Secure the base to the mounng surface using the two xing screws provided. It is important the
base of the reader is ush with and ght against the mounng surface. Three screw locaons
have been provided. Gallagher recommend using the outer screw locaons.
Note: It is strongly recommended that you use the screws provided. If an alternave screw is
used, the head must be no larger nor deeper than that of the screw provided.
Note: Ensure the centre hole allows the cable to run freely out through the mounng surface, so
that the reader facia can clip into the base.
Base
Building cable
No. 6 pan head screw
No. 6 pan head screw
4. Connect the reader tail extending from the facia assembly to the building cable. Connect the
wires for the appropriate reader you wish to interface, either an HBUS Reader or a Cardax IV
Reader, as shown. T15 PIV Readers must be connected as HBUS Readers.
An HBUS Reader connects to a Gallagher Controller 6000, Gallagher 4H/8H Module (aached to
a Controller 6000) or a Gallagher HBUS Door Module (connected to a Controller 6000).
Page 9
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
A Cardax IV Reader connects to a Gallagher Controller 6000, Gallagher 4R/8R Module (aached
to a Controller 6000), Gallagher GBUS Universal Reader Interface (Gallagher GBUS URI), Gallagher
Controller 3000-8R or 3000-4R, Gallagher Local Bus Universal Reader Interface (Gallagher URI) or
a Gallagher Local Bus Reader I/O Interface.
HBUS Reader connecon: HBUS Reader terminated:
Posive Red
Negave Black
HBUS Terminaon Orange
HBUS A Green
HBUS B Brown
CDXIV TX White
CDXIV RX Blue
HBUS Reader
Posive Red
Negave Black
HBUS Terminaon Orange
HBUS A Green
HBUS B Brown
CDXIV TX White
CDXIV RX Blue
HBUS Reader
Note: To terminate an HBUS Reader, connect the Orange (HBUS Terminaon) wire to the Green
(HBUS A) wire.
Cardax IV Reader connecon:
Posive Red
Negave Black
HBUS Terminaon Orange
HBUS A Green
HBUS B Brown
CDXIV TX White
CDXIV RX Blue
Cardax IV Reader
5. Fit the facia assembly into the base by clipping the small lip, into the top of the base and holding
the top, press the boom of the facia assembly down into the base.
6. Insert the M3 Torx Post Security screw (using a T10 Torx Post Security screwdriver) through the
hole at the boom of the base to secure the facia assembly.
Note: The Torx Post Security screw needs only to be lightly ghtened.
Building cable
Facia
Reader tail
Connecon
Fit screw to secure facia to base
Page 10
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
7. Removal of the facia assembly is a simple reversal of these steps.
8. Congure the reader in Command Centre. If the reader is connected as an HBUS Reader, refer to
the topic "Conguring HBUS Devices" in the Command Centre Conguraon Client Online Help.
If the reader is connected as a Cardax IV Reader, refer to the topic "Creang Readers" in the
Command Centre Conguraon Client Online Help.
5 LEDindicaons
LED(squiggle) HBUSindicaon
3 Flash (Amber) No communicaons with the Controller.
2 Flash (Amber) Communicaons with the Controller, but reader is not congured.
1 Flash (Amber) Congured to a Controller, but reader is not assigned to a door or elevator car.
On (Green or Red) Fully congured and funconing normally.
Green = Access mode is Free
Red = Access mode is Secure
Flashes Green Access has been granted.
Flashes Red Access has been denied.
Flashes (Blue) Reading and validang a PIV card.
LED(squiggle) CardaxIVindicaon
3 Flash (Amber) No communicaons with the Controller.
On (Green or Red) Fully congured and funconing normally.
Green = Access mode is Free
Red = Access mode is Secure
Flashes Green Access has been granted.
Flashes Red Access has been denied.
6 Accessories
Accessory Product code
T15 Bezel, Black, Pk 10
T15 Bezel, White, Pk 10
T15 Bezel, Silver, Pk 10
T15 Bezel, Gold, Pk 10
T10 Dress Plate, Black, Pk 10 C300320
T10 Spacer, Black, Pk 10 C300300
T10 Spacer, White, Pk 10 C300301
T10 Protecve Cover Spacer C300310
Page 11
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
7 Technicalspecicaons
Roune maintenance: Not applicable for this reader
Cleaning: This reader should only be cleaned with a clean, lint free, damp cloth
Voltage: 9 Vdc - 16 Vdc
Current: Mifare Reader Mul Tech Reader
Idle 1Maximum 2Idle 1Maximum 2
at 9 Vdc 124 mA 175 mA 115 mA 164 mA
at 13.6 Vdc 84 mA 113 mA 100 mA 124 mA
Temperature range: -35 °C to +70 °C
Note: Direct sunlight may increase the internal reader temperature
above the ambient temperature level
Humidity: 0 - 95% non-condensing 3
Environmental protecon: IP68
Impact rang: IK07
Unit dimensions: Height 139 mm (5.47 inches)
Width 44 mm (1.73 inches)
Depth 23 mm (0.9 inches)
Maximum number of readers
on one HBUS cable:
20
1 The reader is idle.
2 Peak current during card read.
3 Gallagher T Series readers are UL humidity tested and cered to 85% and have been independently
veried to 95%.
Note: The current values stated above have been reported using the default conguraon for a reader
in Command Centre. Changing the conguraon may vary the current value.
Page 12
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
8 Approvals and standards
This symbol on the product or its packaging indicates that this product must not be disposed
of with other waste. Instead, it is your responsibility to dispose of your waste equipment by
handing it over to a designated collecon point for the recycling of waste electrical and electronic
equipment. The separate collecon and recycling of your waste equipment at the me of disposal
will help conserve natural resources and ensure that it is recycled in a manner that protects human
health and the environment. For more informaon about where you can drop o your waste
equipment for recycling, please contact your local city recycling oce or the dealer from whom
you purchased the product.
This product complies with the environmental regulaons for the Restricon of Hazardous
Substances in electrical and electronic equipment (RoHS). The RoHS direcve prohibits the use of
electronic equipment containing certain hazardous substances in the European Union.
FCC This device complies with part 15 of the FCC Rules. Operaon is subject to the following two
condions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operaon.
Note: Changes or modicaons not expressly approved by Gallagher Limited could void the user's
authority to operate this equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protecon against harmful interference in a residenal installaon. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instrucons, may cause harmful interference to radio communicaons. However, there is no
guarantee that interference will not occur in a parcular installaon. If this equipment does cause
harmful interference to radio or television recepon, which can be determined by turning the
equipment o and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
Reorient or relocate the receiving antenna.
Increase the separaon between the equipment and receiver.
Connect the equipment into an outlet on a circuit dierent from that to which the receiver is
connected.
Consult the dealer or an experienced radio/TV technician for help.
Industry
Canada
This device complies with Industry Canada licence-exempt RSS standard(s). Operaon is subject to
the following two condions: (1) this device may not cause interference, and (2) this device must
accept any interference, including interference that may cause undesired operaon of the device.
Industrie
Canada
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio
exempts de licence. L'exploitaon est autorisée aux deux condions suivantes : (1) l'appareil
ne doit pas produire de brouillage, et (2) l'ulisateur de l'appareil doit accepter tout brouillage
radioélectrique subi, même si le brouillage est suscepble d'en compromere le fonconnement.
ETSI EN 300 330-2 V1.5.1:2010
EN50130-4:1996
Please refer to the document “3E2793 Gallagher Command Centre UL Conguraon Requirements” for a guide
to conguring the Gallagher system to the appropriate UL Standard.
US - Equipment: com, burg and acc reader
CA - Equipment: com, burg reader
Page 13
3E4237 Gallagher T15 Reader | Edion 1 | June 2016
Copyright © Gallagher Group Limited
9 Mounngdimensions
IMPORTANT
This picture is not to scale, therefore use the measurements provided.
44 mm (1.73")
139 mm (5.47")
13 mm (1/2") diameter
hole for cable
16 mm (0.63") 67 mm (2.64")
44 mm (1.73")

Navigation menu