Generac 37Kw Ng Owners Manual 0E9042RevE

37kW NG to the manual 575f314d-9125-453b-a9da-afa287943d32

2015-01-05

: Generac Generac-37Kw-Ng-Owners-Manual-166149 generac-37kw-ng-owners-manual-166149 generac pdf

Open the PDF directly: View PDF PDF.
Page Count: 48

DownloadGenerac Generac-37Kw-Ng-Owners-Manual- 0E9042RevE  Generac-37kw-ng-owners-manual
Open PDF In BrowserView PDF
Owner’s Manual
Liquid-cooled, Prepackaged
Standby Generators
Model No: 005012-0
37kW NG, 40kW LP

This manual should remain with the unit.

ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION!!

INTRODUCTION
Thank you for purchasing this model of the
QuietSource standby generator set product line by
Generac Power Systems.
Every effort was expended to make sure that the
information and instructions in this manual are both
accurate and current at the time the manual was written. However, the manufacturer reserves the right to
change, alter or otherwise improve this product(s) at
any time without prior notice.

‹ READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest Generac Authorized Service Dealer
for starting, operating and servicing procedures.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular service or
operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:

DANGER
After this heading, read instructions that, if not
strictly complied with, will result in personal injury
or property damage.

After this heading, read instructions that, if not
strictly complied with, may result in personal injury
or property damage.

After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:

The operator is responsible for proper and safe use
of the equipment. Generac strongly recommends that
the operator read this Owner's Manual and thoroughly understand all instructions before using this
equipment. Generac also strongly recommends
instructing other users to properly start and operate
the unit. This prepares them if they need to operate
the equipment in an emergency.

‹ OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by a Generac
Authorized Service Dealer. Normal maintenance service and replacement of parts are the responsibility of
the owner/operator and, as such, are not considered
defects in materials or workmanship within the terms
of the warranty. Individual operating habits and usage
contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures
a minimum number of problems and keep operating
expenses at a minimum. See the Generac Authorized
Service Dealer for service aids and accessories.
Operating instructions presented in this manual
assume that the standby electric system has been
installed by a Generac Authorized Service Dealer or
other competent, qualified contractor. Installation of
this equipment is not a “do-it-yourself” project.

‹ HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs,
contact a Generac Authorized Service Dealer for
assistance. Service technicians are factory-trained
and are capable of handling all service needs.
When contacting a Generac Authorized Service
Dealer about parts and service, always supply the
complete model number of the unit as given on the
front cover of this manual or on the DATA CARD
affixed to the unit.

After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compliance with the special instructions while performing the
service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates is as follows:

!

This symbol points out important safety information that, if not followed, could endanger personal
safety and/or property of others.
This symbol points out potential explosion hazard.

AUTHORIZED SERVICE
DEALER LOCATION
To locate the nearest GENERAC AUTHORIZED
SERVICE DEALER, please call this number:

This symbol points out potential fire hazard.

1-800-333-1322

This symbol points out potential electrical shock
hazard.

OR
Locate us on the web at:

www.generac.com
Generac® Power Systems, Inc.

Table of Contents
QUIETSOURCE™ 40kW Liquid-cooled Generators

INTRODUCTION ................................................IFC

Section 3 — OPERATION ................................12

Read this Manual Thoroughly......................................IFC

3.1

Using an Engineered “GTS” Transfer Switch ......12

Operation and Maintenance ........................................IFC

3.2

Control Console Components..............................13

How to Obtain Service ................................................IFC

3.3

Manual Transfer and Startup ..............................14

3.4

Engine Governor Adjustments ............................14

SAFETY RULES ....................................................2

3.5

Retransfer and Shutdown....................................14

Section 1 — GENERAL INFORMATION ............4

3.6

Automatic Operation ..........................................14

3.7

Weekly Exercise Cycle..........................................14

Authorized Service Dealer Location ............................IFC

1.1

Generator ..............................................................4

1.2

Transfer Switch ....................................................4

1.3

Automatic System Operation ................................4

1.4

Generator AC Connection Systems........................4

1.5

Main Circuit Breaker ............................................4

1.6

Generator Fuel System ..........................................5

1.7

Section 4 — MAINTENANCE ..........................15
4.1

Maintenance Performed by Authorized
Service Facilities ..................................................15

4.2

Cooling System....................................................15

4.3

Overload Protection for Engine DC
Electrical System ................................................15

Engine Protective Devices ......................................5

4.4

Checking Fluid Levels ........................................16

1.8

Unpacking ............................................................6

4.5

1.9

Lifting the Generator ............................................6

Maintenance Owner/Operator
Can Perform ........................................................16

1.10 Specifications ........................................................7

4.6

Miscellaneous Maintenance ................................18

1.11 Fuel Consumption ................................................7

4.7

Scheduled Maintenance ......................................19

1.12 Reconfiguring the Fuel System ..............................7

Section 5 — TROUBLESHOOTING ..................22

1.13 Torque Specifications ............................................8
1.14 Engine Oil Recommendations ..............................8
1.15 Coolant Recommendations....................................8
1.16 Before Installation ................................................8

Section 2 — INSTALLATION ............................8
2.1

Standby Generator Installation ............................8

2.2

Generator Location................................................9

2.3

Generator Mounting and Support ........................9

2.4

Basic Standby Electric System ..............................9

2.5

Emergency Circuit Isolation Method....................10

2.6

Total Circuit Isolation Method ............................10

2.7

Grounding the Generator ....................................10

2.8

Generator AC Neutral Connections......................10

2.9

Transfer Switch Start Signal Connections ..........10

Section 6 — INSTALLATION DIAGRAM ..........23
Section 7 — ELECTRICAL DATA ....................24
Section 8 — EXPLODED VIEWS AND
PARTS LISTS ..............................28
Section 9 — NOTES ........................................43
Section 10 — WARRANTY .................Back Cover

2.10 Battery Installation ..............................................11
2.11 Preparation Before Start-Up ................................12

Generac® Power Systems, Inc.

1

IMPORTANT SAFETY INSTRUCTIONS
QUIETSOURCE™ 40kW Liquid-cooled Generators

!

SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators, potential operators, and service and repair technicians for this equipment.

!

SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.

!

!

WARNING:
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.

!

WARNING:

!

This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing,
operating or servicing this equipment. Become familiar
with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is
properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work
method or operating technique that Generac does not
specifically recommend, ensure that it is safe for others.
Also make sure the procedure, work method or operating technique chosen does not render the generator
unsafe.

DANGER

!

Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to install, operate or maintain this equipment.
Potentially lethal voltages are generated by these
machines. Ensure all steps are taken to render the
machine safe before attempting to work on the
generator.

!

2

Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.

Generac® Power Systems, Inc.

!
!

! GENERAL HAZARDS !
• For safety reasons, Generac recommends that this
equipment be installed, serviced and repaired by a
Generac Authorized Service Dealer or other competent, qualified electrician or installation technician
who is familiar with applicable codes, standards and
regulations. The operator also must comply with all
such codes, standards and regulations.
• Installation, operation, servicing and repair of this
(and related) equipment must always comply with
applicable codes, standards, laws and regulations.
Adhere strictly to local, state and national electrical
and building codes. Comply with regulations the
Occupational Safety and Health Administration
(OSHA) has established. Also, ensure that the generator is installed, operated and serviced in accordance
with the manufacturer’s instructions and recommendations. Following installation, do nothing that might
render the unit unsafe or in noncompliance with the
aforementioned codes, standards, laws and regulations.
• The engine exhaust fumes contain carbon monoxide
gas, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. For that reason, adequate ventilation must be provided. Exhaust gases
must be piped safely away from any building or
enclosure that houses the generator to an area where
people, animals, etc., will not be harmed. This
exhaust system must be installed properly, in strict
compliance with applicable codes and standards.
• Keep hands, feet, clothing, etc., away from drive belts,
fans, and other moving or hot parts. Never remove
any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is critical to prevent buildup of explosive gases
and to ensure correct generator operation. Do not
alter the installation or permit even partial blockage
of ventilation provisions, as this can seriously affect
safe operation of the generator.
• Keep the area around the generator clean and uncluttered. Remove any materials that could become hazardous.
• When working on this equipment, remain alert at all
times. Never work on the equipment when physically
or mentally fatigued.

IMPORTANT SAFETY INSTRUCTIONS
QUIETSOURCE™ 40kW Liquid-cooled Generators

• Inspect the generator regularly, and promptly repair
or replace all worn, damaged or defective parts using
only factory-approved parts.
• Before performing any maintenance on the generator,
disconnect its battery cables to prevent accidental
start-up. Disconnect the cable from the battery post
indicated by a NEGATIVE, NEG or (–) first.
Reconnect that cable last.
• Never use the generator or any of its parts as a step.
Stepping on the unit can stress and break parts, and
may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.

ELECTRICAL HAZARDS
• All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical
shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as well as the
standby generator. Avoid contact with bare wires, terminals, connections, etc., on the generator as well as
the transfer switch, if applicable. Ensure all appropriate covers, guards and barriers are in place before
operating the generator. If work must be done around
an operating unit, stand on an insulated, dry surface
to reduce shock hazard.
• Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
• If people must stand on metal or concrete while
installing, operating, servicing, adjusting or repairing
this equipment, place insulative mats over a dry
wooden platform. Work on the equipment only while
standing on such insulative mats.
• The National Electrical Code (NEC), Article 250
requires the frame and external electrically conductive parts of the generator to be connected to an
approved earth ground and/or grounding rods. This
grounding will help prevent dangerous electrical
shock that might be caused by a ground fault condition in the generator set or by static electricity. Never
disconnect the ground wire.
• Wire gauge sizes of electrical wiring, cables and cord
sets must be adequate to handle the maximum electrical current (ampacity) to which they will be subjected.
• Before installing or servicing this (and related) equipment, make sure that all power voltage supplies are
positively turned off at their source. Failure to do so
will result in hazardous and possibly fatal electrical
shock.
• Connecting this unit to an electrical system normally
supplied by an electric utility shall be by means of a
transfer switch so as to isolate the generator electric
system from the electric utility distribution system
when the generator is operating. Failure to isolate the
two electric system power sources from each other by
such means will result in damage to the generator
and may also result in injury or death to utility power
workers due to backfeed of electrical energy.

• Generators installed with an automatic transfer
switch will crank and start automatically when NORMAL (UTILITY) source voltage is removed or is below
an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, disable
the generator’s automatic start circuit (battery cables,
etc.) before working on or around the unit. Then,
place a “Do Not Operate” tag on the generator control
panel and on the transfer switch.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If this
is not possible, attempt to free the victim from the
live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement, such
as a dry rope or board, to free the victim from the live
conductor. If the victim is unconscious, apply first aid
and get immediate medical help.
• Never wear jewelry when working on this equipment.
Jewelry can conduct electricity resulting in electric
shock, or may get caught in moving components
causing injury.

FIRE HAZARDS
• Keep a fire extinguisher near the generator at all
times. Do NOT use any carbon tetra-chloride type
extinguisher. Its fumes are toxic, and the liquid can
deteriorate wiring insulation. Keep the extinguisher
properly charged and be familiar with its use. If there
are any questions pertaining to fire extinguishers,
consult the local fire department.

EXPLOSION HAZARDS
• Properly ventilate any room or building housing the
generator to prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel
or oil spills immediately. Ensure that no combustible
materials are left in the generator compartment, or
on or near the generator, as FIRE or EXPLOSION
may result. Keep the area surrounding the generator
clean and free from debris.
• Generac generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled
with care. Comply with all laws regulating the storage
and handling of fuels. Inspect the unit’s fuel system
frequently and correct any leaks immediately. Fuel
supply lines must be properly installed, purged and
leak tested according to applicable fuel-gas codes
before placing this equipment into service.
• Diesel fuels are highly FLAMMABLE. Gaseous fluids
such as natural gas and liquid propane (LP) gas are
extremely EXPLOSIVE. Natural gas is lighter than air,
and LP gas is heavier than air; install leak detectors
accordingly.

Generac® Power Systems, Inc.

3

Section 1 - General Information
QUIETSOURCE™ 40kW Liquid-cooled Generators

1.1

GENERATOR

1.3

This equipment is a liquid-cooled, engine-driven generator set. The generator is designed to supply electrical power that operates critical electrical loads
during utility power failure. The unit has been factory-installed in a weather resistant, all metal enclosure
and is intended for outdoor installation only. Use this
generator as a source of electrical power for the operation of 120 and/or 240VAC, single-phase loads.

!

1.2

If this generator is used to power electrical
load circuits normally powered by a utility
power source, it is required by code to install
a transfer switch. The transfer switch must
effectively isolate the electric system from the
utility distribution system when the generator
is operating (NEC 701). Failure to isolate an
electrical system by such means results in
damage to the generator and may also result
in injury or even death to utility power workers due to backfeed of electrical energy.

TRANSFER SWITCH

This generator system is intended to be used with a
Generac transfer switch. It will be available in either
a NEMA 1 enclosure or a NEMA 3R enclosure. The
NEMA 1 enclosure is intended for indoor use only.
The NEMA 3R enclosure is weather proof and can be
used indoors or outdoors. Follow these rules:
• Install the transfer switch on a firm, sturdy supporting structure.
• To prevent switch distortion, level the switch if necessary. This can be done by placing washers
between the switch enclosure and the mounting
surface.
• Never install the switch where water or any corrosive substance might drip onto the enclosure.
• Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and corrosive vapors.
A Generac Authorized Dealer can supply an appropriate transfer switch for the generator.

AUTOMATIC SYSTEM OPERATION

When this generator, along with a transfer switch, has
been installed and interconnected, a circuit board in
the generator panel constantly monitors UTILITY
power source voltage. Should that voltage drop below
a preset value, and remain at such a low state for a
preset amount of time, the generator cranks and
starts. After the generator starts, the transfer switch
transfers load circuits so the generator can power
them.
When utility source voltage has been restored, the
switch re-transfers back to the UTILITY source voltage and the generator then shuts down.
Please reference the transfer switch manual for specific information.

1.4

GENERATOR AC CONNECTION
SYSTEMS

The generator was shipped from the factory with its
stator AC output leads connected in a single-phase,
three-wire generator AC connection system (Figure
1.1). The stator assembly in this system consists of a
pair of stationary windings, with two leads brought
out of each winding. Each single winding can supply
120VAC, 60 Hertz. When the two windings are connected in series, a 240VAC, 60 Hertz AC output
results. Typically the two HOT leads in the circuit are
wires 11 and 44. The NEUTRAL leads are the junction of Wires 22 and 33. The NEUTRAL is not
grounded.

Figure 1.1 - Generator AC Connection System

1.5

MAIN CIRCUIT BREAKER

The generator’s main circuit breaker is included with
the unit as shipped from the factory. The breaker for
this unit is described in Figure 1.2.

Figure 1.2 - Main Circuit Breaker

4

Model

Rating

005012-0

37,000 NG
40,000 LP

Phase

Generac® Power Systems, Inc.

Actual Current

C/B Rating*

1
154.2
1
166.7
* Amp Rating of C/B structured under model.

200
200

Circuit Breaker
200A QN2
200A QN2

Section 1 - General Information
QUIETSOURCE™ 40kW Liquid-cooled Generators

1.6

NOTE:

GENERATOR FUEL SYSTEM

The unit has been factory tested and adjusted using a
natural gas fuel system. If propane (LP) gas is necessary, refer to Section 1.12 for conversion instructions.

The Low Oil Pressure, High Coolant Temperature
and Low Coolant Level are not monitored for the
first 10 seconds of engine run time.

Fuel pressure for a natural gas set up should be five
inches to 14 inches of water column (0.18 to 0.5
psi) at all load ranges.

Figure 1.4 - Low Oil Pressure Switch

Fuel pressure for an LP vapor set up should be 11
inches to 14 inches of water column (0.4 to 0.5
psi) at all load ranges.
NOTE:
A seperate gas line and regulator may be needed
to assure proper gas pressure to the generator.
Improper gas pressure can cause hard starting and
affect engine durability.

!

1.7

Gaseous fuels such as natural and LP
(propane) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.

ENGINE PROTECTIVE DEVICES

The engine has several safety switches which cause
the engine to automatically shut down under the following conditions: low oil pressure, high coolant temperature, engine overspeed, low coolant level or overcrank (Figure 1.3).

‹ 1.7.2

HIGH COOLANT TEMPERATURE
SWITCH

This normally open (N.O.) thermostatic switch has
sensing tip which is immersed in captive coolant.
Should coolant temperature exceed about 230°F
(110°C), the switch contacts close. This causes the
engine to shut down automatically and turns on the
high coolant temperature/low coolant level LED
(Figure 1.5).

Figure 1.5- High Coolant Temperature Switch

Figure 1.3 - Engine Protective Devices
Low Oil Pressure Switch
High Coolant
Temperature Switch

Low Coolant
Level Sensor

‹ 1.7.3
‹ 1.7.1

LOW OIL PRESSURE SWITCH

This switch is normally-closed (N.C.) but is held open
by engine oil pressure during engine running. Should
operating oil pressure drop below about 8-10 psi
(55-68 kPa), the switch contacts close, the engine
shuts down automatically, and the low oil pressure
LED is turned ON (Figure 1.4).

LOW COOLANT LEVEL SWITCH

Should engine coolant level drop below the level of
the high coolant temperature switch, it is possible for
the engine to overheat without automatic shutdown.
To prevent such overheating without automatic shut
down, the engine has a low coolant level sensor. If the
engine coolant drops too low, the engine automatically shuts down and turns on the high coolant temperature/low coolant level LED (Figure 1.6 on page 6).
Generac® Power Systems, Inc.

5

Section 1 — General Information
QUIETSOURCE™ 40kW Liquid-cooled Generators

Figure 1.6 - Low Coolant Level Sensor

‹ 1.7.7

LOW BATTERY

The engine control board continually monitors the
battery voltage and turns on the low battery LED if
the battery voltage falls below 11.0 VDC for one
minute. Low battery voltage is a non-latching alarm,
which will automatically clear if the battery voltage
rises above 11.0 VDC.

‹ 1.7.4

The control system will not attempt to start the
engine if there is a low battery condition, however, if
the engine is already running when the low battery
condition occurs, the engine will continue to run as
long as possible.

OVERSPEED SHUTDOWN

The engine control board receives AC frequency signals from an engine run winding in the alternator.
Should AC frequency exceed about 72 Hertz for three
seconds or 75 Hertz instantaneously, the engine
shuts down and the overspeed LED turns on. Should
AC frequency exceed about 72 Hertz, circuit board
action will automatically shutdown the engine (Figure
1.7).

Figure 1.7 - Printed Circuit Board Assembly
R44

LED1
C27

Q2

2

C9

J2
C26

U7
C4
D10

Battery voltage is NOT monitored during the crank
cycle.

‹ 1.7.8

ALARM RESET

If the engine control board shuts down the generator
for any of the above reasons, the engine remains
stopped until the alarm is cleared by placing the
AUTO/OFF/MANUAL switch into the OFF position.

‹ 1.7.9

DC FUSE

These fuses are located on the front panel of the control system. They protect the panel wiring and components from damaging overload. Always remove the
15 amp main fuse before working on the generator.
The unit will not start or crank if this fuse is blown.
Replace the fuse with one of the same size, type, and
rating (main AGC-15, battery charger AG4).

C21

1.8

C30

UNPACKING

C2

RL1

‹ 1.8.1

RL2

UNPACKING PRECAUTIONS

R25

R1

Handle shipping cartons and crates with care. Use
care to avoid damage from dropping, bumping, collision, etc..

R48
D17

R49

U1

J1
L3

. V E R 6 0 94 E 0 # B C P

D19

‹ 1.8.2

INSPECTION

If the engine control board does not receive a proper
rpm signal from the starter during cranking or running, it shuts down the engine on rpm sensor loss
and flashes the overspeed LED.

After unpacking, carefully inspect the generator for
any damage that may have occurred during shipment. If loss or damage is noted at the time of delivery, have the person(s) making delivery note all damage on the freight bill or affix their signature under
the consignor’s memo of loss or damage.

‹ 1.7.6

1.9

‹ 1.7.5

RPM SENSOR LOSS

OVERCRANK SHUTDOWN

The engine control board uses a cyclic cranking
process when attempting to start the engine. The first
crank cycle is a 15-second crank followed by a sevensecond rest. This is followed by five more crank
cycles each with a seven-second crank followed by a
seven-second rest.
If the engine fails to start after all six attempts, the
start attempt is stopped and the overcrank LED
turned on.
6

Generac® Power Systems, Inc.

!

LIFTING THE GENERATOR
When lifting or hoisting equipment is used,
be careful not to touch overhead power lines.
The generators weight of more than 900
pounds requires proper tools, equipment, and
qualified personnel to be used in all phases of
handling and unpacking.

Section 1 — General Information
QUIETSOURCE™ 40kW Liquid-cooled Generators

NOTE:

1.10 SPECIFICATIONS
‹ 1.10.1 GENERATOR SPECIFICATIONS
Single-phase
005012-0
37 (NG), 40 (LP)

Model
Rated Max. Cont.
AC Power Output (kW)
Rated voltage (volts)
120/240
No. of Rotor Poles
4
Driven Speed of Rotor
1800
Rotor Excitation System Direct excited brush type
Type of Stator
4 Wire
Rotor/Stator Insulation
Class F/H

‹ 1.10.2 ENGINE SPECIFICATIONS
Make ................................................................................Chrysler
Displacement ..................................................................3.9 liters
Cylinder Arrangement ..............................................................V-6
Valve Arrangement ..............................................Overhead Valve
Firing Order ................................................................1-6-5-4-3-2
Number of Main Bearings............................................................4
Compression Ratio............................................................9.1 to 1
No. of Teeth on Flywheel ........................................................164
Ignition Timing at 1800 rpm..............................30 degrees BTDC
Spark Plug Gap ..............................................1.01mm (0.040 in.)
Recommended Spark Plugs
Champion ....................................................................RC12LC4
Oil Pressure....................................................................30-80 psi
Crankcase Oil Capacity........................4.0 U.S. quarts (3.8 liters)
Recommended Engine Oil........................................SAE 15W-40
Type of Cooling System ..................Pressurized, closed recovery
Cooling Fan ..............................................................Pusher Type
Cooling System Capacity..................5.0 U.S. gallons (19.3 liters)
Recommended Coolant ............................Use a 50-50 mixture of
ethylene glycol base
and de-ionized water.

1.11 FUEL CONSUMPTION
Natural Gas:
% of Load
m3/hr
ft3/hr
LP Vapor:
% of Load
m3/hr
ft3/hr

Fuel consumption is given at rated maximum continuous power output when using natural gas
rated at 1000 Btu per cubic foot. LP gas is rated
at 2520 Btu per cubic foot. Actual fuel consumption obtained may vary depending on such variables as applied load, ambient temperature,
engine conditions and other environmental factors.
Fuel pressure for a natural gas set up should be five
inches to 14 inches of water column (0.18 to 0.5
psi) at all load ranges.
Fuel pressure for an LP vapor set up should be 11
inches to 14 inches of water column (0.4 to 0.5
psi) at all load ranges.

1.12 RECONFIGURING THE FUEL
SYSTEM
NOTE:
All models are configured for natural gas from the
factory.
To reconfigure the fuel system from NG to LP vapor,
follow these steps:
1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet
port (Port 1) of the demand regulator (Figure
1.8).

Figure 1.8 — Reconfigure the Fuel System
Port 2

Port 1

PLUG

50%
7.7
271.1

75%
11.0
388.5

100%
14.2
502.0

25%
1.7
60.7

50%
3.3
115.0

75%
4.7
164.9

100%
6.0
213.0

FUEL HOSE

BRASS HOSE
FITTING
OUT
PORT 1

BRASS HOSE
FITTING

HOUSING
PORTS

NG FUEL SYSTEM

25%
4.1
143.1

FUEL HOSE

PLUG

OUT
PORT 2
HOUSING
PORTS

LP FUEL SYSTEM

3. Remove the brass hose fitting from the outlet port
(Port 1) of the demand regulator.
4. Remove pipe plug from Port 2.
5. Install brass hose fitting into Port 2.
6. Install pipe plug into Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure
and type for configuration.
10. Reverse the procedure to convert back to natural
gas.
Generac® Power Systems, Inc.

7

Section 2 — Installation
QUIETSOURCE™ 40kW Liquid-cooled Generators

NOTE:
Port 1 is for NG only and Port 2 is for LP vapor
only. No provision for dual fuel has been made.

!

DANGER

!

Serious injury or damage may occur if not configured properly. Please consult an authorized
Generac Service Dealer with any questions.

1.13 TORQUE SPECIFICATIONS
Tighten the bolts from the middle out, in a crisscross pattern.

Cylinder Head ....................................50 ft.lb./105 ft.lb./105 ft.lb.
Intake Manifold ....................................48 in.lb./84 in.lb./84 in.lb.
Exhaust Manifold..............................................................25 ft.lb.

1.14 ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at the
factory. Use a high-quality detergent oil classified “For
Service CC, SD, SE, SF.” Detergent oils keep the
engine cleaner and reduce carbon deposits. Use oil
having the following SAE viscosity rating, based on
the ambient temperature range anticipated before the
next oil change:
Temperature
Above 80° F (27° C)
32° to 80° F (-1° to 27° C)
Below 32° F (0° C)

Oil Grade (Recommended)
SAE 15W-40
SAE 15W-40
SAE 15W-40

NOTE:
5W-30 full synthetic oil is highly recommended in
any element with temperatures above 90° F or
below 30° F.

!

Any attempt to crank or start the engine before
it has been properly serviced with the recommended oil may result in an engine failure.

1.15 COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol base
anti-freeze and half de-ionized water. Cooling system
capacity is about 20 U.S. quarts (19.3 liters). Use
only de-ionized water and only low silicate antifreeze. If desired, add a high quality rust inhibitor to
the recommended coolant mixture. When adding
coolant, always add the recommended 50-50 mixture.

8

Generac® Power Systems, Inc.

Do not use any chromate base rust inhibitor
with ethylene glycol base anti-freeze or chromiumhydroxide (“green slime”) forms and will
cause overheating. Engines that have been
operated with a chromate base rust inhibitor
must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high
silicate anti-freeze boosters or additives will
also cause overheating. It is also recommend
that any soluble oil inhibitor is NOT USED for
this equipment.

1.16 BEFORE INSTALLATION
Before installing this equipment, check the ratings of
both the generator and the transfer switch. Read
“Emergency Isolation Method” and “Total Circuit
Isolation Method” Sections 2.5 and 2.6.
The generator’s rated wattage/amperage capacity
must be adequate to handle all electrical loads that
the unit will power. The critical (essential) loads may
need to be grouped together and wired into a separate “emergency” distribution panel.
This generator can be installed in conjunction with
an engineered Generac “GTS” type transfer switch, if
necessary.
The standard transfer switch has no sensing or controlling circuit boards. Instead, the generator control
console houses a “Printed Circuit Board Assembly”,
which controls all phases of operation, including
engine start up and load transfer.

2.1

STANDBY GENERATOR
INSTALLATION
DANGER
Connecting this generator to an electrical system normally supplied by an electric utility
shall be by means of a transfer switch, so as to
isolate the electric system from the utility distribution system when the generator is operating.
Failure to isolate the electric system by these
means will result in damage to the generator
and may also result in injury or death to utility
workers due to backfeed of electrical energy.
If an open bottom is used, the engine-generator is to be installed over non-combustible
materials and should be located such that combustible materials are not capable of accumulating under the generator set.

Section 2 — Installation
QUIETSOURCE™ 40kW Liquid-cooled Generators

Only qualified, competent installation contractors or
electricians thoroughly familiar with applicable
codes, standards and regulations should install this
standby electric power system. The installation must
comply strictly with all codes, standards and regulations pertaining to the installation.

!

After the system has been installed, do nothing
that might render the installation in noncompliance with such codes, standards and regulations.

‹ 2.1.1

NFPA STANDARDS

The following published standards booklets pertaining to standby electric systems are available form the
National Fire Protection Association (NFPA),
Batterymarch Park, Quincy, MA 02269:
• NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES.
• NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES.
• NFPA No. 220, STANDARD TYPES OF BUILDING
CONSTRUCTION
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING
• NFPA No. 70, NATIONAL ELECTRICAL CODE.
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE.
• NFPA No. 10, INSTALLATION, MAINTENANCE AND
USE OF PORTABLE FIRE EXTINGUISHERS.

‹ 2.1.2

OTHER PUBLISHED STANDARDS

In addition to NFPA standards, the following information pertaining to the installation and use of
standby electric systems is available:
• Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85 John
Street, New York, N.Y. 10038.
• AGRICULTURAL WIRING HANDBOOK, obtainable
from the Food and Energy Council, 909 University
Avenue, Columbia, MO, 65201.
• ASAE EP-364.2, INSTALLATION AND MAINTENANCE OF FARM STANDBY ELECTRIC POWER,
available from the American Society of Agricultural
Engineers, 2950 Niles Road, St. Joseph, MI 49085.
• A52.1, AMERICAN NATIONAL STANDARD FOR
CHIMNEYS, FIREPLACES AND VENTING SYSTEMS, available from the American National
Standard Institute, 1430 Broadway, New York, N.Y.
10018.

2.2

GENERATOR LOCATION

Install the generator set, in its protective enclosure
outdoors, where adequate cooling and ventilating air
always is available. Consider these factors:
• Install the unit where air inlet and outlet openings
will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or drifting, consider using a windbreak to protect the unit.
• Install the generator on high ground where water
levels will not rise and endanger it.
• This genset must be installed on a level surface.
The base frame must be level within 1/2 inch all
around.
• Allow sufficient room on all sides of the generator
for maintenance and servicing. A good rule is to
allow five feet of space on all sides.
• Where strong prevailing winds blow from one
direction, face the generator air inlet openings into
the prevailing winds.
• Install the generator as close as possible to the
transfer switch. This reduces the length of wiring
and conduit.
• Install the generator as close as possible to the fuel
supply, to reduce the length of piping. HOWEVER,
REMEMBER THAT LAWS OR CODES MAY REGULATE THE DISTANCE.

2.3

GENERATOR MOUNTING AND
SUPPORT

Retain the generator compartment to a concrete slab
with 1/4-inch masonry type anchor bolts. Be sure the
bolts are long enough to retain the compartment. The
slab should be at least six inches thick and should
extend beyond the enclosure to a distance of at least
three inches on all sides. See Section 6 for generator
major dimensions.

2.4

BASIC STANDBY ELECTRIC
SYSTEM

Figure 2.1 shows a schematic diagram of a basic
standby electric system. Both the UTILITY power
supply and the STANDBY (GENERATOR) output are
connected to an approved transfer switch. The transfer switch is required by electrical code and serves
the following functions:
• Allows the LOAD circuits to be connected to only
one power supply at a time.
• Prevents electrical backfeed between the generator
and the UTILITY power circuits.
Notice that both the STANDBY and the UTILITY
power supplies to the transfer switch are protected
against overload by a main line circuit breaker.

Generac® Power Systems, Inc.

9

Section 2 — Installation
QUIETSOURCE™ 40kW Liquid-cooled Generators

Figure 2.1 – Basic Standby Electric System

2.7

GROUNDING THE GENERATOR

The National Electrical Code requires the frame and
external electrically conductive parts of this equipment to be properly connected to an approved earth
ground and/or grounding rods. For that purpose, a
GROUND LUG (Figure 2.2) is provided on the generator mounting base. Consult a qualified electrician
for grounding requirements in the area. Grounding
procedures must meet local regulations.

DANGER

2.5

EMERGENCY CIRCUIT ISOLATION
METHOD

This prevents overloading the generator by keeping
electrical loads below the wattage/amperage capacity
of the generator. If the generator is powering only critical loads, within the wattage/amperage capacity, during utility power outages, consider using the emergency circuit isolation method.

Do not connect the ground wire to any pipe
that carries a flammable or explosive substance
– FIRE or an EXPLOSION may result.
Proper grounding helps protect personnel against
electrical shock in the event of a ground fault condition in the generator or in connected electrical
devices. In addition, grounding helps dissipate static
electricity that often builds up in ungrounded
devices.

Figure 2.2 – Generator Grounding Lug (typical)

Critical electrical loads are grouped together and
wired into a separate “Emergency Distribution
Panel.” Load circuits powered by that panel are within the wattage/amperage capacity of the generator set.
When this method is used, it is difficult to overload
the generator. The transfer switch must meet the following requirements:
• It must have an ampere rating equal to the total
amperage rating of the emergency distribution
panel circuit.
• Have it installed between the building’s main distribution panel and the emergency distribution
panel.

2.6

TOTAL CIRCUIT ISOLATION
METHOD

When a generator capable of powering all electrical
loads in the circuit is to be installed, use the “Total
Circuit Isolation Method.” It is possible for the generator to be overloaded when this isolation method is
employed. The following apply to the transfer switch
in this type of system.
• Ampere rating of the transfer switch must equal
the ampere rating of the normal incoming utility
service.
• The transfer switch is installed between the utility
service entrance and the building distribution
panel.
• By code and approved means of service disconnect
must be located between the incoming utility service and the transfer switch.
10 Generac® Power Systems, Inc.

GROUNDING
LUG

2.8

GENERATOR AC NEUTRAL
CONNECTIONS

Generac uses an UNGROUNDED AC neutral.
Grounding is recommended only at the main service
entrance. If the neutral wire is grounded and one of
the phase loads becomes grounded, the excessive
current opens the load circuit breaker or collapses
the generator field. The actual result depends on the
electrical characteristics of the particular installed
generator.

2.9

TRANSFER SWITCH SIGNAL
CONNECTIONS

‹ 2.9.1

PRE-PACKAGED ATS

If the generator is to be installed with a pre-packaged
transfer switch, it is necessary to connect the control
wires to the generator and set position two of the
four-position dip switch to OFF.

Section 2 — Installation
QUIETSOURCE™ 40kW Liquid-cooled Generators

Setting switch two to OFF allows the control PCB to
perform the ATS control functions.

!

Control system interconnections consist of N1 and
N2, and leads 23 and 194. Control system interconnection leads must be run in a conduit that is separate from the AC power lead. Recommended wire
gauge sizes for this wiring depends on the length of
the wire, as recommended below:
MAXIMUM WIRE LENGTH
460 feet (140m)
461 to 730 feet (223m)
731 to 1,160 feet (354m)
1,161 to 1,850 feet (565m)

‹ 2.9.2

RECOMMENDED WIRE
SIZE
No. 18 AWG.
No. 16 AWG.
No. 14 AWG.
No. 12 AWG.

GTS-TYPE ENGINEERED TRANSFER
SWITCH

If the generator is to be installed with an engineered
transfer switch, such as a Generac GTS-type switch,
it is necessary to connect the two-wire start control
system.
Connect the two-wire start signal from the automatic
transfer switch to the automatic start connection,
which is located in the middle, on the bottom, inside
the control panel. Match wires 178 and 183 in the
transfer switch to 178 and 183 on the terminal strip
in the control panel. The conductors for the two-wire
start circuit must be in their own conduit. (See
Section 3.1 for further explanation.)

2.10 BATTERY INSTALLATION
DANGER

!

!

Standby generators installed with automatic
transfer switches will crank and start automatically when NORMAL (UTILITY) source voltage is
removed or is below an acceptable preset level.
To prevent such automatic start-up and possible
injury to personnel, do not connect battery
cables until certain that normal source voltage
at the transfer switch is correct and the system
is ready to be placed into operation.
Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after
charging. The slightest spark can ignite the gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or
other injury. Any area that houses a storage
battery must be properly ventilated. Do not
allow smoking, open flame, sparks or any spark
producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caustic
sulfuric acid solution that can cause severe
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If fluid is spilled, flush the
affected area immediately with clear water.

Do not dispose of the battery in a fire. The battery is capable of exploding.
Do not open or mutilate the battery. Released
electrolyte can be toxic and harmful to the skin
and eyes.
The battery represents a risk of high short circuit current. When working on the battery,
always remove watches, rings or other metal
objects, and only use tools that have insulated
handles.

‹ 2.10.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing,
• Where electrolyte contacts the skin, wash it off
immediately with water,
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention, and
• Spilled electrolyte is to be washed down with an
acid-neutralizing agent. A common practice is to
use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The
bicarbonate of soda solution is to be added until
the evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead acid batteries present a risk of fire
because they generate hydrogen gas. The following procedure are to be followed:
• DO NOT SMOKE when near batteries,
• DO NOT cause flame or spark in battery area, and
• Discharge static electricity from body before touching batteries by first touching a grounded metal
surface.
Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.

!

For recommended batteries, see Section 4.6.4. All
batteries must be at 100 percent state-of-charge
before they are installed on the generator.
Generac® Power Systems, Inc. 11

Section 3 — Operation
QUIETSOURCE™ 40kW Liquid-cooled Generators

When using maintenance-free batteries, it is not necessary to check the specific gravity or electrolyte level.
Have these procedures performed at the intervals
specified in Section 4, “Maintenance.” A negative
ground system is used. Battery connections are
shown on the wiring diagrams. Make sure all batteries are correctly connected and terminals are tight.
Observe battery polarity when connecting batteries to
the generator set.
NOTE:
Damage will result if the battery connections are
made in reverse.

2.11 PREPARATION BEFORE START-UP
The instructions in this section assume that the standby generator has been properly installed, serviced,
tested, adjusted and otherwise prepared for use by a
competent, qualified installation contractor. Be sure to
read the “Safety Rules” on pages 2 and 3, as well as all
other safety information in this manual, before
attempting to operate this (and related) equipment.

‹ 2.11.1 PRIOR TO INITIAL START-UP

Prior to initially starting the generator, it must
be properly prepared for use. Any attempt to
crank or start the engine before it has been
properly serviced with the recommended types
and quantities of engine fluids (oil, coolant,
fuel, etc.) may result in an engine failure.
Before starting the generator for the first time, the
installer must complete the following procedures. For
follow-up maintenance information and/or service
intervals, please refer to Section 4, “Maintenance.”

!

‹ 2.11.2 TRANSFER SWITCH
If this generator is used to supply power to any electrical system normally powered by an electric utility,
the National Electrical Code requires that a transfer
switch be installed. The transfer switch prevents electrical backfeed between two different electrical systems (for additional information, see the applicable
transfer switch manual for this unit). The transfer
switch, as well as the generator and other standby
components, must be properly located and mounted
in strict compliance with applicable codes, standards
and regulations.

‹ 2.11.3 FUEL SYSTEM
Make sure the fuel supply system to the generator (a)
delivers the correct fuel at the correct pressure and
(b) is properly purged and leak tested according to
code. No fuel leakage is permitted. See
“Specifications” (Section 1.10) for more information.
12 Generac® Power Systems, Inc.

‹ 2.11.4 GENERATOR SET LUBRICATION
Check the engine crankcase oil level before operating
and add oil to the proper level – the dipstick “FULL”
mark. Never operate the engine with the oil level
below the dipstick “ADD” mark. See “Specifications”
(Section 1.10) and “Engine Oil Recommendations”
(Section 1.14).
NOTE:
This engine is shipped from the manufacturer
with 15W-40 oil. This oil should be changed after
30 hours of operation.

‹ 2.11.5 ENGINE COOLANT
Have the engine cooling system properly filled with
the recommended coolant mixture. Check the system
for leaks and other problems. See “Specifications”
(Section 1.10) and “Coolant” (Section 1.15).

‹ 2.11.6 BELT TENSION
Check the engine fan belt tension and condition prior
to placing the unit into service and at recommended
intervals. Belt tension is correct when a force of
approximately 22 pounds (10 kg), applied midway
between pulleys, deflects the belt about 3/8- to 5/8 of
an inch (10 to 16 mm).

‹ 2.11.7 ELECTRICAL SYSTEM
Make sure the generator is properly connected to an
approved earth ground and/or ground rod.
Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.
Check to ensure that there are no loose electrical connections. Restrain any loose wires to keep them clear
of any moving generator set components.

3.1

USING AN ENGINEERED “GTS”
TRANSFER SWITCH

When required, the pre-packaged standby generator
can be installed with an engineered Generac “GTS”
type automatic transfer switch.
In this application, the GTS is responsible for utility
sensing, weekly exercising, and load transferring.
Position two of the four-position dip switch is used to
turn over this control to the GTS.

Pos2 ON — GTS Application
• The control board will NOT monitor utility.
• The control board will NOT perform a weekly exercise. (The five red LEDs will not flash in this
mode.)
• The control board will NOT activate the transfer
output.

Section 3 - Operation
QUIETSOURCE™ 40kW Liquid-cooled Generators

• The control board WILL monitor all engine conditions and shut down on all the faults listed in this
document.

Pos2 OFF — Prepackaged ATS Application
• The control board will perform all of the automatic features listed in this document.
• The two-wire start connections should NOT be
used.

GTS Mode Operation
When in GTS mode, the control board will respond
as follows based on the AUTO/OFF/MANUAL switch
position.
OFF — The generator will not start and run in this
position.
MANUAL — The control board will start and run the
generator whenever the switch is in the manual position.
AUTO — The control board will monitor the two-wire
start circuit. When a two-wire start is sent, the control board will immediately start and run the generator. When the two-wire start is removed, the control
board will immediately stop the generator.
NOTE:
If the generator is installed in conjunction with an
engineered GTS type transfer switch, refer to the
applicable transfer switch manual for exact operating parameters and timing sequences.

3.2

CONTROL CONSOLE
COMPONENTS

The components of a home standby generator control
console (Figure 3.1) are as follows:

Figure 3.1 - Home Standby Generator Panel
LED INDICATORS:
FLASHING GREEN LED = NO UTILITY SENSE
5 FLASHING RED LED'S = EXERCISER NOT SET
(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON
RED LED'S = INDIVIDUAL FAULT

‹ 3.2.1

AUTO/OFF/MANUAL SWITCH

Use this three-position switch as follows:
• Set the switch to AUTO for fully automatic operation. See “Automatic Operation” (Section 3.5).
• Set switch to MANUAL position to crank and start
the generator engine.
• Set switch to OFF position to shut down an operating engine. With OFF selected, operation will not
be possible.

DANGER

!

With switch set to AUTO, engine can crank and
start suddenly without warning. Such automatic start up normally occurs when utility source
voltage drops below a pre-set level. To prevent
possible injury that might be caused by such
sudden starts, set AUTO/OFF/MANUAL switch
to OFF before working on or around the unit.
Then, place a “DO NOT OPERATE” tag on control console.

‹ 3.2.2

FAULT INDICATOR LED

This LED goes ON when one or more of the following
engine faults occurs and when engine shuts down.
• Low Oil Pressure
• Overcrank
• Low Battery
• Overspeed/RPM Sensor Loss
• High Coolant Temperature/Low Coolant Level
See Section 1.7 for further explanation of engine protection functions.

‹ 3.2.3

15 AMP FUSE

This fuse protects the control console’s DC control
circuit against electrical overload. If the fuse has
melted open because of an overload, engine cranking
and startup cannot occur. If the fuse needs to be
replaced, use only an identical 15-amp replacement
fuse. (Type AGC)

(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)

OVER CRANK

RED LEDs

SYSTEM READY

AUTO
OFF
OFF

SET
EXECISER
TIME
SWITCH

4A FUSE
BATTERY
CHARGER

ON
SET
EXERCISE
TIME

‹ 3.2.4

4.0 AMP INLINE FUSE

This fuse protects the battery charger against electrical overload. If the fuse needs to be replaced, use only
an identical 4-amp replacement fuse (type AG).

LOW BATTERY

4A

MANUAL

NOTE:

GREEN LED

TO SET EXERCISER TIME
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

This fuse will not remove the + battery input
power from the PCB when it opens. This means
the exercise timer will not be reset.

0E7194

AUTO/OFF/MANUAL
SWITCH
15A FUSE
MAIN
POWER

‹ 3.2.5

SET EXERCISE TIME SWITCH

This switch allows programming the generator to
start and exercise automatically. “See Weekly
Exercise Cycle.”
Generac® Power Systems, Inc. 13

Section 3 — Operation
QUIETSOURCE™ 40kW Liquid-cooled Generators

‹ 3.2.6

SYSTEM READY LED

Figure 3.2 — Engine Governor Adjustment

The System Ready LED (green) has two main proposes. First, the LED will be ON when the
AUTO/OFF/MANUAL switch is in the AUTO position,
utility is present, and there are no system alarms.
This ON state indicates the system is fully ready for
automatic operation.

2

J2

U7
C4
D10

C21

C30
C2

RL1

3.4

ENGINE GOVERNOR
ADJUSTMENTS

Engine speed governing is also controlled by the
engine control board. Connector J2 on the engine
control board interfaces with a governor driver module and the Bosch throttle body. The engine governor
has been set by the factory during final testing of the
generator and, in most cases, should not be adjusted.
If, however, adjustments are necessary, or a new
engine control board is installed in the generator, the
following procedure should be followed (Figure 3.2):
1. Set all three potentiometers (pots) fully counterclockwise.
2. Under no load condition, increase the GAIN pot
as much as possible without causing instability.
3. Apply 1/4, 1/2, 3/4 and full load to the unit.
Decrease the GAIN pot if there is instability at any
load point.
4. Under full load condition, increase the STABILITY pot until the unit returns to 60 Hertz (or 50
Hertz in 50 Hertz applications).
5. Reduce load to 3/4, 1/2, 1/4 and no load.
Decrease the STABILITY pot if there is instability
at any load point.
6. Adjust differential pot to make the recovery to
load changes even faster and minimize load
change undershoot and overshoot. If it is set too
high, it may introduce oscillations at some load.
It can be set to zero (full CCW) if a small amount
causes oscillations at some load.
14 Generac® Power Systems, Inc.

RL2

R25

R1
R48
D17
R49

U1

J1
L3
D19

.VER 6094E0 #BCP

DIFFERENTIAL
STABILITY

This secondary function is only available with dip
switch two in the OFF position (standard ATS application).

To transfer electrical loads to the Standby (EMERGENCY) power source side and start the engine manually, refer to the Owner’s Manual of the particular
transfer switch.

Q2

C26

The system ready LED is also used to indicate the
presence of utility sensing at the PCB when the switch
is either in the AUTO or MANUAL modes. The LED
will flash at the rate of 1/2 second on, 1/2 second off
if the utility sensing level is below the transfer back
threshold.

MANUAL TRANSFER AND
START-UP

C27

C9

The system ready LED will be OFF when the switch
is in the MANUAL or OFF positions.

3.3

R44

LED1

DIP SWITCH
1
3
2
4

UNUSED
GTS/ATS
50/60 HZ

POSITION 1
50/60 HZ
ON = 50 HZ
OFF = 60 HZ

POSITION 2
GTS/ATS Select
ON = GTS
OFF = ATS (standard mode)

3.5

RETRANSFER AND SHUTDOWN

3.6

AUTOMATIC OPERATION

3.7

WEEKLY EXERCISE CYCLE

When utility power source voltage has been restored,
electrical loads may be transferred back to that
source and the generator can be shut down as follows:
• Verify that utility power supply voltage to the transfer switch has been positively turned OFF, using
whatever means provided (such as utility main line
circuit breaker).
• Set the generator’s main circuit breaker to its OFF
or OPEN position.
• Let the generator engine run at no-load for a few
minutes, to stabilize internal unit temperatures.
• On the generator console, set the AUTO/OFF/
MANUAL switch to OFF. Wait for engine to come to
a complete stop.
• For transfer to utility position, refer to the Owner’s
Manual of the particular transfer switch.
• Turn on the utility power supply to the transfer
switch, using whatever means provided (such as a
utility main line circuit breaker). The utility power
source now powers the loads.
To set the system for fully automatic operation, proceed as follows:
• Check that load circuits are connected to the
utility power supply.
• Set the AUTO/OFF/MANUAL switch to its AUTO
position.
• Set the generator main circuit breaker to its ON or
CLOSED position.
The engine control board will start and run the generator once every seven days for approximately 12
minutes. If utility should fail during this exercise
period, the engine control board will transfer the load
to the generator output and continue to run until utility returns.

Section 4 — Maintenance
QUIETSOURCE™ 40kW Liquid-cooled Generators

On the day, and at the time of day chosen for the generator to exercise, set the weekly exercise cycle as follows:
1. Place the AUTO/OFF/MANUAL switch in the
AUTO position.
2. Press and hold the “Set Exercise” switch for three
seconds, then release.
At this time all five red LEDs will flash for approximately 10 seconds, then the engine will start and run
for it’s 12 minute exercise period, then shut down.
The generator will now start and run each week at the
same time.
If DC power to the control board is lost, the weekly
exercise setting will be lost. This is indicated by all five
red LEDs continually flashing. In this state the generator will still start and run in manual mode, or automatically start and run if UTILITY is lost while in
AUTO mode, but it will not perform a weekly exercise
cycle.
If a failure occurs while running in this mode, the five
red LEDs will stop flashing, the individual fault LED
will turn on and the engine will shut down. Once the
AUTO/OFF/MANUAL switch has been switch to OFF,
the individual fault LED will turn OFF and the five
red LEDs will begin flashing to show exercise has still
not been set.

F

US

E

E

FUSE
15A
MAIN

F US

US

1. Test Engine Safety Devices (low oil pressure, low
coolant level, high coolant temperature).

C. ONCE ANNUALLY
1. Test engine governor. Adjust or repair, if needed.
2. Clean, inspect generator.
3. Flush cooling system.

D. FIRST 100 OPERATING HOURS
1. Change engine oil and oil filter. (After initial
change, service engine oil and filter at 150 operating hours or 6 months, whichever comes first.)
2. Retorque cylinder head. (See Torque Specs,
Section 1.13.)
3. Retorque intake and exhaust manifold. (See
Torque Specs, Section 1.13.)

E. EVERY 500 OPERATING HOURS
1. Service air cleaner.
2. Check starter.
3. Check engine DC alternator.

4.2

COOLING SYSTEM

Air intake and outlet openings in the generator compartment must be open and unobstructed for continued proper operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it
to shut down. (See Section 6 for installation drawings
and vent locations.)

F USE

FUSE
4A
BAT.
CHARGER

F SE

F

Figure 3.2 - “Set Exercise” Switch

B. ONCE EVERY SIX MONTHS

US

AUTO

The exhaust system parts from this product get
extremely hot and remain hot after shutdown.
High grass, weeds, brush, leaves, etc. must
remain clear of the exhaust. Such materials may
ignite and burn from the heat of the exhaust
system.

OFF
OFF
ON
SET
EXERCISE
TIME

4.1

MANUAL

MAINTENANCE PERFORMED BY
AUTHORIZED SERVICE FACILITIES

A. EVERY THREE MONTHS
1.
2.
3.
4.
5.
6.

Check battery state of charge and condition.
Inspect and test fuel system.
Check transfer switch.
Inspect exhaust system.
Check engine ignition system.
Check fan belts.

4.3

OVERLOAD PROTECTION FOR
ENGINE DC ELECTRICAL SYSTEM

Engine cranking, start up and running are controlled
by a solid state Engine Controller circuit board.
Battery voltage is delivered to that circuit board via a
15-amp fuse. These overcurrent protection devices
will open if the circuit is overloaded.

!

If a circuit breaker opens or a fuse element
melts, find the cause of the overload before
resetting the circuit breaker or replacing the
fuse.
Generac® Power Systems, Inc. 15

Section 4 — Maintenance
QUIETSOURCE™ 40kW Liquid-cooled Generators

4.4

CHECKING FLUID LEVELS

‹ 4.4.1

CHECK ENGINE OIL

Check engine crankcase oil level (Figure 4.1) at least
every 20 hours of operation, or prior to use.
• Remove oil dipstick and wipe dry with a clean,
lint-free cloth.
• Install oil dipstick, then remove again.
• Oil should be between FULL and ADD marks.
• If oil level is below the dipstick ADD mark, remove
oil fill cap. Add the recommended oil to bring oil
level up to the FULL mark. DO NOT FILL ABOVE
THE “FULL” MARK. See Section 1.14 for recommended oils.

Figure 4.1 - Oil Dipstick and Oil Fill Cap
Oil Dipstick

Oil Fill

4.5

MAINTENANCE OWNER/
OPERATOR CAN PERFORM

‹ 4.5.1

CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels” in Section 4.4.

‹ 4.5.2

CHECK BATTERY

• Check battery fluid level each week as outlined
under “Check Fluid Levels”.
• Check battery cables for condition, tightness, corrosion or damage. Clean, tighten or replace as
necessary.

‹ 4.5.3

EXERCISE SYSTEM

Start the generator engine at least once every seven
days and let it run at least 20 minutes. See Section
3.6, “Weekly Exercise Cycle”.

‹ 4.5.4

INSPECT COOLING SYSTEM

• Inspect engine cooling system at least once each
month.
• Check hoses for damage, deterioration, leaks, etc.
Correct any discrepancies found.
• Check hose clamps for tightness.

‹ 4.5.5

Oil Filter

CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels” in Section 4.4.

‹ 4.4.2

BATTERY FLUID

Check battery electrolyte fluid at least once weekly.
Fluid should cover separators in all battery cells. If
fluid level is low, add distilled water to cover tops of
separators. DO NOT USE TAP WATER IN BATTERY.

‹ 4.4.3

ENGINE COOLANT

Check coolant level in coolant recovery bottle. See
Specifications, Section 1.10.
• Add recommended coolant mixture as necessary.
• Periodically remove radiator pressure cap to make
sure the coolant recovery system is functioning
properly. Coolant should be at bottom of radiator
filler neck. If coolant level is low, inspect gasket in
radiator pressure cap. Replace cap, if necessary.
To have pressure cap tested, contact an authorized
Generac Service Dealer. Inspect cooling system
and coolant recovery system for leaks.

‹ 4.5.6

PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire
engine-generator monthly. Look for obvious damage,
loose, missing or corroded nuts, bolts and other fasteners. Look for fuel, oil or coolant leaks.

‹ 4.5.7

INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three
months. Check all exhaust system pipes, mufflers,
clamps, etc. for condition, tightness, leaks, security,
damage.

‹ 4.5.8

CHECK FAN BELT

• Inspect fan belts every three months. Replace any
damaged, deteriorated, worn or otherwise defective belt.
• Check fan belt tension. Thumb pressure, exerted
midway between pulleys, should deflect about 3/8
to 5/8 of an inch. Adjust belt tension as required.

‹ 4.5.9

INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

16 Generac® Power Systems, Inc.

Section 4 — Maintenance
QUIETSOURCE™ 40kW Liquid-cooled Generators

DANGER

!

Do not attempt to adjust the governor. Only
qualified service facilities should adjust the
governor. Excessively high operating speeds are
dangerous and increase the risk of personal
injury. Low speeds impose a heavy load on the
engine when adequate engine power is not
available and may shorten engine life. Correct
rated frequency and voltage are supplied only
at the proper governed speed. Some connected
electrical load devices may be damaged by
incorrect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

‹ 4.5.10 CHANGING ENGINE OIL
Refer to maintenance performed by authorized service dealers for engine oil and filter change frequencies.
Drain the oil while the engine is still warm from running. This means warm up the engine, shut it down
and drain immediately as follows:
1. Remove OIL DRAIN HOSE from its retaining clip.
2. Loosen and remove OIL DRAIN HOSE CAP. Drain
oil completely into suitable container.
3. When all oil has drained, install and tighten OIL
DRAIN HOSE CAP, and re-install into its retaining
clip.
4. Turn OIL FILTER (Figure 4.2) counterclockwise
and remove. Dispose of old filter.

Figure 4.2 - Oil Filter

After refilling the crankcase with oil, always
check oil level on dipstick. NEVER OPERATE
ENGINE WITH OIL BELOW THE DIPSTICK “ADD”
MARK.
7. Start engine and check for oil leaks.

!

‹ 4.5.11 CHANGING THE ENGINE AIR CLEANER
To replace the engine air cleaner, (part number
0A4637), remove the air cleaner cover and replace
the air filter making sure it is positioned properly
before reattaching the cover.
See the “Service Schedule,” Section 6, for air cleaner
maintenance.

‹ 4.5.12 SPARK PLUGS
Reset the spark plug gap or replace the spark plugs
as necessary. See Section 6.
1. Clean the area around the base of the spark plugs
to keep dirt and debris out of the engine. Clean by
scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to
clean.
2. Remove the spark plugs and check the condition.
Replace the spark plugs if worn or if reuse is
questionable. See the “Service Schedule,” Section
6, for recommended inspection.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 1.01 mm (0.040 inch) by
carefully bending the ground electrode (Figure
4.3).

Figure 4.3 – Setting the Spark Plug Gap
SET PLUG GAP AT 1.01 mm
(0.040 inch)

Oil Filter
‹ 4.5.13 COOLANT CHANGE
5. Apply light coating of new engine oil to seal of new
oil filter. Install FILTER and tighten by hand only.
DO NOT OVERTIGHTEN.
6. Remove OIL FILL CAP. Add recommended oil (see
SPECIFICATIONS). DO NOT FILL ABOVE THE
DIPSTICK “FULL” MARK. Crankcase oil capacity
is 4.0 U.S. quarts (3.8 liters).

Every year, have an authorized service dealer drain,
flush and refill the cooling system. See SPECIFICATIONS (Section 1.10) for cooling system recommendations.

Generac® Power Systems, Inc. 17

Section 4 — Maintenance
QUIETSOURCE™ 40kW Liquid-cooled Generators

4.6

MISCELLANEOUS MAINTENANCE

‹ 4.6.1

CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible.
Dirt and moisture that accumulates on internal generator windings have an adverse effect on insulation
resistance.

2. Check the battery fluid level of unsealed batteries
and, if necessary, fill with DISTILLED WATER
ONLY. DO NOT USE TAP WATER IN BATTERIES.
3. Have the state of charge and condition checked.
This should be done with an automotive-type battery hydrometer.

DANGER

Periodically clean generator exterior surfaces. A soft
brush may be used to loosen caked on dirt. Use a
vacuum system or dry, low pressure air to remove
any accumulations of dirt. The generator is housed
inside an all-weather enclosure, clean the enclosure
with a soft, damp cloth or sponge and water.
Once each year, have the generator cleaned and
inspected by a Generac Authorized Service Dealer.
That dealer will use dry, low pressure air to clean
internal windings. Parts inside the control console
should be cleaned and inspected at this time as well.
Finally, have the insulation resistance of stator and
rotor windings checked. If insulation resistances are
excessively low, the generator may require drying.

‹ 4.6.2

BATTERY

All lead-acid storage batteries discharge when not in
use. Refer to specific instructions and warnings that
accompany the battery. If such information is not
available, observe the following precautions when
handling a battery:
• DO NOT use jumper cables and a booster battery
to crank or start the generator engine.
• DO NOT recharge a weak battery while it is
installed in the generator. Remove battery from
generator and recharge in a well-ventilated area,
away from fuel vapors, sparks, heat or flames.
• Battery electrolyte fluid is an extremely caustic
sulfuric solution that can cause severe burns. DO
NOT permit fluid to contact eyes, skin, clothing,
painted surfaces, wiring insulation, etc. If any battery fluid is spilled, flush the affected area with
clear water immediately.
• Always wear safety glasses, rubber apron and
gloves when handling a battery.
• Batteries give off explosive hydrogen gas while
charging. The gas can form an explosive mixture
around the battery for several hours after charging.
Any spark, heat or flames can ignite the gas and
cause an explosion which can shatter the battery,
causing blindness or other serious injury.

‹ 4.6.3

!

!

!

Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after
charging. The slightest spark can ignite the gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or
other injury. Any area that houses a storage
battery must be properly ventilated. Do not
allow smoking, open flame, sparks or any spark
producing tools or equipment near the battery.
Battery electrolyte fluid is an extremely caustic
sulfuric acid solution that can cause severe
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If the fluid is spilled, flush
the affected area immediately with clear water.
Do not use any jumper cables or booster battery to crank and start the generator engine. If
the battery has completely discharged, remove
it from the generator for recharging.

Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.
Be sure the UTILITY power supply is turned off,
or sparking may occur at the battery posts as
the cables are attached and cause an explosion.

‹ 4.6.4

When replacing batteries, use the same number and
the type of battery that follows:
BCI Group No.
27F

1. Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
18 Generac® Power Systems, Inc.

CCA
700 @ 0 deg. F

NOTE:
The BCI number should be located directly
on the battery.

BATTERY MAINTENANCE

The battery should be inspected per the “Service
Schedule,” Section 6. The following procedure
should be followed for inspection:

BATTERY REPLACEMENT

PERIODIC REPLACEMENT PARTS
Part Name
Oil Filter
Radiator Cap
Air Cleaner
Spark Plug

Generac’s Part Number
# 0E7415
# 046627
# 0A4637
Champion # RC12LC4

Section 4 — Maintenance
QUIETSOURCE™ 40kW Liquid-cooled Generators

4.7

SCHEDULED MAINTENANCE

Following is a recommended maintenance schedule for QuietSource small standby and residential generator sets.
The established intervals in the schedule are the maximum recommended when the unit is used in an average
service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application. Use calendar time from the previous maintenance interval to determine the next required maintenance
interval.

Service Maintenance Interval Information:
The various service maintenance intervals are designated by interval numbers as follows:
1 An early inspection of the generator set to ensure it is ready to operate when required and to identify any potential problem areas.
Performed monthly, this procedure requires approximately .5 man-hours per unit to complete.
This inspection may be performed by the end user providing the following safety steps are taken to prevent
the engine from starting automatically without warning:
To prevent injury, perform the following steps in the order indicated before starting any maintenance:
•
Disable the generator set from starting and/or connecting to the load by setting the control panel
AUTO-OFF-MANUAL switch to the “OFF” position.
•
Remove the control panel fuse.
•
Turn off the battery charger.
•
Remove the negative battery cable.

The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition from burning out sensitive control panel components and circuits.
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal
operation when required.
2 A break-in service inspection of the generator set to ensure it is ready to operate and carry the load when
required, and to identify any potential problem areas.
Performed ONLY ONCE following the first three months after purchase of the unit and requires approximately 2.5 man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge
to accomplish and should be performed only by an authorized Generac Service Dealer.
3 An operational inspection of the generator set to ensure it is ready to operate and carry the load when required,
and to identify any potential problem areas.
Performed semi-annually, this procedure requires approximately 1.5 man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge
to accomplish and should be performed only by an authorized Generac Service Dealer.
4 A mid-level inspection of the generator set to ensure it is ready to operate and carry the load when required,
and to identify any potential problem areas.
Performed annually, this procedure requires approximately 4.0 man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge
to accomplish and should be performed only by an authorized Generac Service Dealer.
NOTE:
If the generator experiences heavy use, the maintenance intervals should be reduced so that procedures are
performed more frequently.

Generac® Power Systems, Inc. 19

Section 4 — Maintenance
QUIETSOURCE™ 40kW Liquid-cooled Generators

Maintenance
Tasks

Level 1
Recommended
to be done
monthly

1. Disable the unit from
operating per the first page
warning.
2. Check the engine oil level.
Adjust as necessary.
3. Check the engine coolant
level. Adjust as necessary.
4. Check the engine coolant
thermal protection level.
Correct as necessary.
5. Check the natural gas
delivery system on gas
engine driven units.
Tighten connections as
necessary.
6. Check the air inlets and
outlets for debris. Clean as
necessary.
7. Check the battery
electrolyte level if
accessible. Adjust as
necessary.
8. Check the battery posts,
cables, and charger for
loose connections,
corrosion, and proper
operation. Correct as
necessary.
9. Check the unit wiring for
loose connections,
corrosion, and damage.
Correct as necessary.
10. Check the engine
accessory drive belts for
wear, weather cracking,
and damage. Replace as
necessary.
11. Visually inspect the unit
looking for leaks, wear or
damage, loose connections
or components, and
corrosion. Correct as
necessary.
12. Test the engine and
transfer switch safety
devices. Correct and/or
adjust as necessary.

20 Generac® Power Systems, Inc.

Level 2
Task
Comp.
(DateInitials)

Required
to be done
3 months/
Break-in

Level 3
Task
Comp.
(DateInitials)

Required
to be done
Semiannually

Level 4
Task
Comp.
(DateInitials)

Required
to be done
Annually

Task
Comp.
(DateInitials)

Section 4 — Maintenance
QUIETSOURCE™ 40kW Liquid-cooled Generators

Maintenance
Tasks

Level 1
Recommended
to be done
monthly

Level 2
Task
Comp.
(DateInitials)

Required
to be done
3 months/
Break-in

Level 3
Task
Comp.
(DateInitials)

Required
to be done
Semiannually

Level 4
Task
Comp.
(DateInitials)

Required
to be done
Annually

Task
Comp.
(DateInitials)

13. Initiate an automatic start
and transfer of the unit to
site load and exercise it for
at least 1 hour looking for
leaks, loose connections
or components, and
abnormal operating
conditions. Correct as
necessary.
14. Start and exercise the unit
at full rated load (use a
load bank if the site load is
not enough) for at least 2
hours looking for leaks,
loose connections or
components, and abnormal
operating conditions.
Correct as necessary.
15. Change the engine oil.
16. Replace the engine oil
filter(s).
17. Replace the engine air
filter(s).
18. Replace the engine fuel
filter(s) on diesel engine
driven units and re-prime
the fuel system.
19. Check the engine spark
plugs on gas engine driven
units. Clean and re-gap or
replace as necessary.
20. Perform a 5 minute no-load
operational run of the unit
looking for any post service
problems.
21. Return the unit to standby
setup for operation when
required.

Generac® Power Systems, Inc. 21

Section 5 — Troubleshooting
QUIETSOURCE™ 40kW Liquid-cooled Generators

TROUBLESHOOTING POINTS
PROBLEM

CAUSE

CORRECTION

Engine won’t crank.

1. 15-amp fuse blown.
2. Loose or corroded or defective
battery cables.
3. Defective starter contactor.
4. Defective starter motor.
5. Dead or Defective Battery.
6. 4-amp fuse blown.

1. Replace fuse.
2. Tighten, clean or replace
battery cables as necessary.
3. Replace contactor.
4. Replace starter motor.
5. Remove, change or replace battery.
6. Replace fuse.

Engine cranks, but won't start

1. Out of fuel.
2. Fuel solenoid (FS) is defective
3. Open Wire #14 from Engine Control
circuit board.
4. Spark plugs defective.

1. Replenish fuel.
2. Replace solenoid.
3. Reconnect wire.

Engine starts hard, runs rough.

1. Air cleaner plugged or damaged.
2. Plugged fuel line.
3. Defective spark plugs.

1. Clean or replace as needed.
2. Unclog fuel line.
3. Clean, regap or replace plugs.

Engine starts, then shuts down.

1.
2.
3.
4.
5.
6.
7.

1.
2.
3.
4.
5.
6.
7.

AUTO/OFF/MANUAL Switch at
OFF, engine continues to run

1. Defective AUTO/OFF/MANUAL switch
2. Open/disconnected wire #15A between
AUTO/OFF/MANUAL switch and Control
Module circuit board.
3. Defective Control Module circuit board

1. Replace switch.
2. Reconnect/close wire.

1.
2.
3.
4.

1.
2.
3.
4.

No AC output from generator.

Engine oil level is low.
Engine is overheated.
Defective Low Oil Pressure Switch
Defective Coolant Temperature Switch
Defective Control Module circuit board.
Coolant Level is Low.
Defective Low Coolant Level Switch

Check main line circuit breaker.
Check circuit breaker & fuses.
Transfer switch set to NORMAL position
Generator internal failure.

5. Thermal circuit breaker open.

22 Generac® Power Systems, Inc.

4. Clean, regap or replace plugs.

Check oil and add oil as needed.
Check cooling system for leaks.
Replace switch.
Replace switch.
Replace board.
Repair leak - Add coolant.
Replace Switch.

3. Replace board.
Reset to ON or CLOSED.
Reset and replace, if necessary.
Set to GENERATOR position.
Contact an Authorized Generac
facility.
5. Auto-reset - Wait 5 min. and
attempt restart.

Section 6 — Installation Diagram
QUIETSOURCE™ 40kW Liquid-cooled Generators
Installation Diagram — Drawing No. 0E8797

Generac® Power Systems, Inc. 23

Section 7 - Electrical Data
QUIETSOURCE™ 40kW Liquid-cooled Generators
Wiring Diagram — Engine — Drawing No. 0E8115-A

24 Generac® Power Systems, Inc.

Section 7 - Electrical Data
QUIETSOURCE™ 40kW Liquid-cooled Generators
Wiring Diagram — Engine — Drawing No. 0E8115-A

Generac® Power Systems, Inc. 25

Section 7 - Electrical Data
QUIETSOURCE™ 40kW Liquid-cooled Generators
Electrical Schematic — Engine — Drawing No. 0E8116-A

26 Generac® Power Systems, Inc.

Section 7 - Electrical Data
QUIETSOURCE™ 40kW Liquid-cooled Generators
Electrical Schematic — Engine — Drawing No. 0E8116-A

Generac® Power Systems, Inc. 27

16

12

13

28 Generac® Power Systems, Inc.

9

34

35

18

8

42

43

7

6

5

TO
ENGINE
MOUNT

2

34

36

4

3
16

19

40

34

30

27

16

35

36

41

38

18

27

32

33

22

29

20

31

21

20

7

6

5

37

15

1

13

12
11

REAR BEARING
CARRIER

HARNESS
WIRE

TO
STARTER
CONTACTOR

TO
STARTER
BOLT

TO
ENGINE
18 BLOCK

14

16

10

4

3

2

Section 8 - Exploded Views and Parts

QUIETSOURCE™ 40kW Liquid-cooled Generators
Mounting Base — Drawing No. 0E8084-A

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Mounting Base — Drawing No. 0E8084-A

ITEM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
19
20
21
22
23*
24*
25*
26*
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43

PART NO.
0E7331
052860
052251
052257
052252
052259
052891
0536210214
074906
047411
055414
026850
022097
022473
049813
0A1694
025507
0E7359
027482
022129
045771
051756
046526
022131
055934M
049820
059473
061902
058665
038804D
038805J
021991
036833
022237
022131
075763
050331
050331A
0A4010
052858
065852
045764

QTY.
1
4
4
4
4
4
4
1
1
1
1
2
1
1
1
4
3
2
2
1
1
1
1
1
1
2
1
1
REF.
1
1
1
6
6
6
1
1
1
2
2
1
1

DESCRIPTION
WELDMENT MTG BASE 3.9L CRYSLR
NUT FLANGED HEX M12-1.75
DAMPENER VIBRATION 40 BLUE
SPACER .49 X .62 X 1.87 PWDR/ZNC
DAMPENER VIBRATION
WASHER FLAT M12
SCREW HHC M12-1.75 X 80 G8.8
ASSY WIRE 15.0"
SCREW HHTT M6-1.0 X 20 BP
SCREW HHC M6-1.0 X 16 BP
LUG SLDLSS #2-#8 X 17/64 CU
WASHER SHAKEPROOF EXT 1/4 STL
WASHER LOCK M6-1/4
WASHER FLAT M6-1/4 ZINC
NUT HEX M6 -1.0 G8 YEL CHR
1-1/2" BUTTON PLUG
WASHER SHAKEPROOF EXT 7/16 STL
ENGINE MOUNT (3.9L CHRYSLER)
WASHER SHAKEPROOF EXT 5/16 STL
WASHER LOCK M8-5/16
NUT HEX M8-1.25 G8 YEL CHR
SCREW HHC M10-1.5 X 20 G8.8
WASHER LOCK M10
WASHER FLAT 3/8-M10 ZINC
CLAMP VINYL .75 X .343 Z
NUT HEX LOCK M8-1.25 NY INS
HOLD DOWN BATTERY
HOLD DOWN BATTERY
BATT 12VDC 90-AH 27F
CABLE BATT RED #4 X 20.00
CABLE BATT BLK #1 X 30.00
EARTH STRAP
SCREW HHC 3/8-16 X 1 G8
WASHER LOCK 3/8
WASHER FLAT 3/8 ZINC
BOOT BATTERY CABLE
BATTERY POST COVWER (BLACK)
BATTERY POST COVWER (RED)
SCREW HHC M8-1.25 X 60 G8.8 FT
NUT TOP LOCK FL M8-1.25
SPRING CLIP HOLDER .37-.62
SCREW HHTT M4-0.7 X 8 BP

*NOT SHOWN-USED TO HOLD DOWN I/N 32.

Generac® Power Systems, Inc. 29

30 Generac® Power Systems, Inc.

3

30

31

LATCH DETAIL

38

1

32

34

18

17

45

27

2

41

4

37

4

35

53

25

RADIATOR

33

4

STATES FOAM IS ON FAR SIDE

STATES FOAM IS ON NEAR SIDE

46 4

55

53

4

4

13

9

11

SEE LATCH
DETAIL

26

TO "A"

TYPICAL OF ROOF PANEL THAT
REQUIRE INSULATION.
SECURE AS SHOWN.

36

"B"
52

4

58

4

4

6

53

8

9

12

"A"

22

15

54

16
17
18

5
57

5

"B"

20

52

10

14

7

53

21

51

28

19

43

4

5
57

40

23

17

16

18
17

41

1

39

26

TO "B"
(2-PLCS)

18

44

10

Section 8 - Exploded Views and Parts

QUIETSOURCE™ 40kW Liquid-cooled Generators
Enclosure — Drawing No. 0E8800-B

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Enclosure — Drawing No. 0E8800-B

ITEM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
50 *
51
52
53
54
55
56
57
58

PART NO.
0E8418
0E8414
0E8413
0C2454
0E7807
0E5902
0E5903
0E8387
0E5912
0E5911
089961
0A2115
0E8404
0D2538A
0D2538
043116
022097
022473
0E7570
0E7571
070015
0E7662
0D2537A
0D2537
0D2023
0E7869
0E8001
0E5913
0E8798
0D3037A
0C7781
0E5910
0E8052
0D3037
0E5900
0E5901
0E8799
0E8415
026850
0912970063
0912970064
049813
0E8416
0E8417
0E8665
0D2023
0E8442
0E7829A
0E7829B
0E7829P
0E7829R
0E7829S
0E7829T
0E7829N
078115

QTY.
1
1
1
62
1
1
1
1
2
1
2
4
1
1
1
8
12
12
2
4
4
4
1
1
2
2
1
1
1
1
2
1
1
1
1
1
1
1
4
2
2
2
1
1
1
1
1
1
2
4
2
1
1
2
8

DESCRIPTION
DUCT INTAKE MID AL
DUCT DISCHARGE RH AL
DUCT DISCHARGE LH AL
SCREW TH-FRM M6-1 X 16 N WA Z/JS
BAFFLE REAR BOTTOM
POST CORNER LH REAR HSB AL
POST CORNER RH REAR HSB AL
BAFFLE REAR TOP
DOOR SIDE HSB AL
SUPPORT RH SIDE HSB AL
FOAM STRIP 3/4" WIDE X 3/16" THK (40" LG)
WASHER NYLON .257
BRACKET STIFFENER RH FRONT
HINGE LIFT OFF TYPE B KNUCKLE
HINGE LIFT OFF TYPE B PIN
SCREW HHC M6-1.0 X 12 G8.8
WASHER LOCK M6-1/4
WASHER FLAT 1/4-M6 ZINC
GAS SPRING
BALL STUD GAS SPRING MOUNT
NUT HEX 5/16-18 LOCK
SCREW WING M6-1.00 X 25
HINGE LIFT OFF TYPE A KNUCKLE
HINGE LIFT OFF TYPE A PIN
TRIM VINYL SELF GRIPPING (91" LG)
BRACKET STIFFENING BACK
MUFFLER BOX
ROOF HSB AL
BRACE, FRONT TOP
LATCH 1/4 TURN NONLOCKING
PAWL DOOR HSB
SUPPORT LH SIDE HSB AL
MUFFLER BOX TOP
LATCH QUARTER TURN LOCKING
POST CORNER LH FRONT HSB AL
POST CORNER RH FRONT HSB AL
BRACE, FRONT BOTTOM
DUCT DISCHARGE MID AL
WASHER SHAKEPROOF EXT 1/4 STL
ASSY GRD WIRE 99HSB
ASSEMBLY,BASE-DOOR GROUND WIRE
NUT HEX M6 X 1.0 G8 YEL CHR
DUCT INTAKE LH AL
DUCT INTAKE RH AL
BRACKET STIFFENER LH FRONT
TRIM VINYL SELF GRIPPING (165.5"LG)
KIT INSULATION 3.9L HSB
AI ROOF PANEL 1
AI DOOR PANEL
AI CORNER POST PANEL 1
AI CORNER POST PANEL 2
AI SUPPORT LH PANEL
AI SUPPORT RH PANEL
AI ROOF PANEL 2
WASHER SELF LOCKING DOME

* ALL ITEMS NOTATED WITH "AI" ARE COMPONENTS OF 0E8442
Generac® Power Systems, Inc. 31

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Control Panel — Drawing No. 0E7118-H

32 Generac® Power Systems, Inc.

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Control Panel — Drawing No. 0E7118-H

ITEM

PART NO.

QTY.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

0E7195
0E7196
0E7197
0E7193
0E7194
0E4494
082573
032300
022676
067682B
060015
054199
0C2657
099076
040213
0E9668
0E4905

17
18
19
20
21

067680
0E6875A
0E6881 *
0C5139 *
0C5142 *

1
1
REF.
REF.
REF.

22
23
24

0E3161
054450
0D5070A

1
1
1

25
26
27

0E2514
0A9457
0E7539

1
1
1

28
29
30
31

046357 *
0D3719B
057073
0E7283
0E3628
0E3664
0E7539A
0D4698 *

32
33
34

1
1
1
1
1
1
1
2
1
1
1
1
1
1
2
1
1

REF.
1
1
1
1
1
1
REF.

DESCRIPTION
CONTROL BOX HSB
COVER FRONT PANEL HSB
COVER TOP PANEL HSB
DECAL WARNINGS HSB
DECAL CONTROLS HSB
SWITCH ROC DPDT ON-OFF-ON
SWITCH ROCKER DPST 125V SPD
HOLDER FUSE
FUSE 15A X AGC15
FUSE 4A SLO BLO GLASS
FITTING CONDUIT 90D 3/8"
DECAL DANGER HIGH VOLTAGE
TRANSFRMR 16V 6VA
TRANSFORMER 16V 56VA
PCB SUPPORT SNAP-IN 1/4"
ASSY PCB HSB CONTROLLER 3.9L
ASSY PCB HSB CONTRLR 3.0L
FORD
ASSY VOLTAGE REGULATOR 60HZ
RELAY 12VDC C FORM W/DIODE
SOCKET RELAY
CONN DEUTSCH RECEPT GY/FLN
CONN DEUTSCH RECEPT WDGE
BLKHD
ASSY BOSCH GOV DRIVER
CIRCT BRK 5.5 X 1 ETA 46-500-P
ASSY 2A 12V UL BATTERY
CHARGER
FITTING CONDUIT STR 1-1/2"
DECAL NEUTRAL
DECALCUSTOMER CNNCTN XFER
SW
BLOCK TERM 20A 6 X 6 X 1100V
DECAL CUSTOMER CNNCTN
JUNCTION BLOCK 3/8-16
CB 0150A2P240V S QN2 LL
CB 0200A2P240V S QN2 LL
BASE QN CIRCUIT BREAKER
DECAL TB1 HSB CONTROL PANEL
BLOCK TERM 20A 6 X 3 X 1100V

ITEM

PART NO.

QTY.

35
36

0E7252
0C1229

1
1

37
38
39

0C1127
0A1441B
0E7128

1
1
1

40
41
42

0E7358
074908
0C5141

8
6
1

43
44
45
46
47
49
50
51
52
53
54
55
56
57
58
59
60

0C2699
0C2323
022155
0C2265
022264
020911
066849
022152
023897
051716
090388
042568
022097
022473
0441140187
070370
023762

11
4
15
4
4
2
2
4
3
2
2
4
8
6
2
2
1

61
62
63
64
65
66
67
68

055444
030468
049939
022158
022985
038750
0A2115
0C2454

1
1
1
1
1
2
4
4

DESCRIPTION
BRACKET CB 221.5 X 102
DECAL WARNING ELECTRICAL
SHOCK
DECAL AVR COVER
COVER PLATE, AVR
HARNESS CNTRL PNL (NOT
SHOWN)
SCREW PPPH HI-LO #4-24 X 3/8
SCREW HHTT M5-0.8 X 10 BP
CONN DEUTSCH GASKET 8/12 POS
DT
SCREW PHTT #6-32 X 3/8 ZYC
SCREW PHTT #6-32 X 5/8 ZYC
WASHER LOCK #6
SCREW PHTT M4-0.7 X 12 ZYC
WASHER LOCK #8-M4
SCREW PPHM M5-0.8 X 30 ZINC
SCREW HHTT M5-0.8 X 16
WASHER LOCK #10
WASHER FLAT #10 ZINC
NUT HEX M5-0.8 G8 YEL CHR
SCREW HHTT M6-1.0 X 12 ZINC
SCREW HHC M6-1.0 X 20 G8.8
WASHER LOCK M6-1/4
WASHER FLAT 1/4-M6 ZINC
WIRE ASSY 3" X (2) 3/16" TABS
WASHER MICA .203
WASHER SHAKEPROOF EXT #10
STL
HEATSINK
WASHER STEP NYLON .20
RECTIFIER MSC 12A 600V 1N1206R
NUT HEX #10-32 STEEL
WASHER FLAT #6 ZINC
SCREW HHC M6-1.0 X 30 G8.8
WASHER NYLON .257
SCREW THF M6-1 X 16 N WA Z/JS

* ITEMS INCLUDED AS PART OF I/N 39

Generac® Power Systems, Inc. 33

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Engine — Drawing No. 0E8121-G

34 Generac® Power Systems, Inc.

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Engine — Drawing No. 0E8121-G

ITEM

PART NO.

QTY.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29

0E5048A
0E7477
0E6703
0E8336
0E7841
0E7254
0E7956
0E7953
047411
0E8591
0E7921
0E7749
022097
022473
049721
049813
036833
022131
022237
0E6729
022129
049821
057073
052677
066849
056739
0D2244M
087599
0E0992B

1
1
1
REF
2
1
1
1
4
6
1
1
7
10
2
3
11
21
14
1
11
3
1
1
2
1
1
1
REF

30

0E0992A

REF

31
32
33
34

0E7754
0E7854
0E7855
0E7952

1
1
1
1

35

0E0561

1

36
37
38

035606
061012
0A8584

1
1
1

39

050873A

1

DESCRIPTION
FLEXPLATE 3.9L HSB
MACHINING 3.9L ENGINE ADAPTOR
COVER FLYWHEEL ACCESS
REWORK 3.9L CHRYSLER ENGINE
GASKET THERMOSTAT ADAPTOR
MACH THERM ADAPTOR 3.9L CHRY
BRACKET IGNITION COIL
COIL IGNITION 3.9L CHRYSLER
SCREW HHC M6-1.0 X 16 G8.8
BOLT AUTO TRANS CRANKSHAFT
BRACKET ALTERNATOR
FAN SPACER ENGINE COOLING
WASHER LOCK M6-1/4
WASHER FLAT 1/4-M6 ZINC
SCREW HHC M6-1.0 X 35 G8.8 BLK
NUT HEX M6 X 1.0 G8 YEL CHR
SCREW HHC 3/8-16 X 1 G8
WASHER FLAT 3/8-M10 ZINC
WASHER LOCK 3/8
STARTER DELCO-REMY 12V
WASHER LOCK M8-5/16
SCREW SHC M8-1.25 X 30 G12.9
JUNCTION BLOCK 3/8-16
WASHER NYLON .50 X .87 X .06
SCREW HHTT M5-0.8 X 16
RELAY SOLENOID 12VDC PNL MNT
ASSY MAGPICKUP (3/8-24 MALE)
PLUG PLASTIC 3/8 NPT
PLUG EXPANSION 21/32" OD
(WATER PUMP) (QTY 1)
PLUG EXPANSION 14.1 OD
(INJCTOR HOLE) (QTY 6)
COOLING FAN 10-BLADE (KYSAIR)
CLUTCH COOLING FAN
TENSIONER W/BRACKET
PULLEY CRANKSHAFT 3.9L
CRYSLR
ASSY WATER LEVEL SENSOR C/E
PL
SENSOR HI COOLANT SHUTDOWN
PLUG STD PIPE 1/8 SOCKET HEAD
SWITCH OIL PRESSURE10 PSI
2POL
PLUG PIPE 1/4 CSK W/ VIBRA SL

ITEM

PART NO.

QTY.

40

031919

1

41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67

022145
030795
051756
046526
0A1232A
0A7801B
045772
022403
0E7950
0E7951
0E8445
0E7415
042568
061652
031578
082120
023645
0E9974
0D3488A
0E7954
0E8309
029187
032712
054455
0E8606
0E8642
0E8597

6
6
5
6
1
1
1
2
1
1
1
1
1
1
1
1
5
2
1
1
1
2
2
1
2
REF
1

68

0E8755

1

69
70
71
72
73
74
75
76
77
78
79

0E8731
026076
0E9975
0F1444A
0C2454
043790
069860C
048031J
0F1444
026925
026257

1
1
1
2
2
1
1
REF
1
1
1

DESCRIPTION
PLUG STD PIPE 3/8 COUNTERSUNK
WASHER FLAT 5/16-M8 ZINC
SCREW HHC 5/16-18 X 1 G5
SCREW HHC M10-1.5 X 20 G8.8
WASHER LOCK M10
ASSEMBLY, D.C. ALTERNATOR
PULLEY POLY-V 82 OD
NUT HEX M10-1.5 G8 YEL CHR
SCREW HHC 5/16-18 X 2 G5
TUBE DIPSTICK 3.9L CHRYSLER
DIPSTICK OIL LEVEL 3.9L CRYSLR
BRACKET DIPSTICK TUBE
OIL FILTER 3.9L CHRYSLER
SCREW HHC M6-1.0 X 20 G8.8
SCREW HHC M10-1.5 X 85 G8.8
SCREW HHC 3/8-16 X 1-1/2 G8
SPACER .41 X .75 X .39 ST/ZNC
SCREW SHC 3/8-16 X 1.25 G8.8 Z
CAP VINYL 3/8" ID X 1" DP BLK
BELT SERPENTINE 69.39"
CABLE IGN COIL 3.9L CHRYSLER
ASSY IGNITION MODULE 3.9L
SPACER .19 X .31 X .50 PL
SCREW HHTT #10-32 X 1.75 CZ
ADP OIL DRN 1/2-20
SCREW PPH TAPPING #4 X 3/8" LG
ASSEMBLY RESISTOR
HARNESS 3.9L CHRYSLER ENGINE
(NOT SHOWN)
HARNESS IGNITION 3.9L CHRY
(NOT SHOWN)
PLATE FLEX DISK SPACER
SCREW SHC 3/8-16 X 1.5 G8.8 NZ
CAP VINYL 1/4" ID X 1" DP BLK
HEAT SHEILD L/H SIDE
SCREW THF M6-1 X 16 N WA Z/JS
BARBED EL 90 3/8 NPT X 3/8
HOSE OIL DRAIN ASSY 21"
HOSE CLAMP BAND 5/8"
HEAT SHIELD R/H SIDE
PLUG STD PIPE 3/8 STEEL SQ HD
SCREW SHC 3/8-16 X 2 G8.8 NZ

Generac® Power Systems, Inc. 35

Section 8 - Exploded Views and Parts

13

WATER PUMP

26
25
24

3

21

"A"
36 Generac® Power Systems, Inc.

23

24

1

10

20

4

10

5

TO
THERMOSTAT
HOUSING

15

0

16

19

16

22

15

2

14

8

17

9

14

7

6

17

18

14

O "A"

QUIETSOURCE™ 40kW Liquid-cooled Generators
Radiator — Drawing No. 0E8102-E

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Radiator — Drawing No. 0E8102-E

ITEM
1
2
3
4
5
6
7
8
9
10
13
14
15
16
17
18
19
20
21
22
23
24
25
26

PART NO.
0D7825A
0D7174C
0E7640
0E7924
0F2853
0D8252
0D8251
0E0726
076749
035685
069860C
058443
0C2454
052250
048031C
029032
0A2111
0E7640A
035461
065852
051756
022131
046526
045772

QTY.
1
1
1
1
1
1
1
1
1
4
1
17
5
2
1
1
1
1
1
1
4
8
4
4

DESCRIPTION
RADIATOR COPPER BRASS
VENTURI,3.9L CRYSLR HSB 22"FAN
RADIATOR SUPPORT L/H SIDE
HOSE LOWER RADIATOR
HOSE, RADIATOR UPPER, 3.9L
FAN GUARD, TOP
FAN GUARD, BOTTOM
BRACKET, WATER BOTTLE 1.5L MIT
TANK COOLANT RECOVERY
CLAMP HOSE #28 1.32-2.25
HOSE OIL DRAIN ASSY 21"
SCREW CRIMPTITE 1/4-20 X 5/8
SCREW TH-FRM M6-1X16 N WA Z/JS
TAPE FOAM 1 X 1 (27"LG)
CLAMP HOSE BAND 1/4
HOSE 9/32 ID (30" LG)
SCREW SWAGE 10-32 X 5/16 Z/YC
RADIATOR SUPPORT R/H SIDE
BARBED STR 1/4NPT X 3/8
SPRING CLIP HOLDER .37-.62
SCREW HHC M10-1.5 X 20 G8.8
WASHER FLAT 3/8-M10 ZINC
WASHER LOCK M10
NUT HEX M10-1.5 G8 YEL CHR

Generac® Power Systems, Inc. 37

Section 8 - Exploded Views and Parts

TO
INTAKE
MANIFOLD

43

6

1

39

15

18

19

TO "B"

14

19

38 Generac® Power Systems, Inc.

TO ENGINE

45

42

16

2

4

41

40

5

11

17

6

9

13

12

6
8

3
27

2

31

30
29

32

13

37
38

36

"B"

35

34

20

21

46

23
24

22

25

44

33

QUIETSOURCE™ 40kW Liquid-cooled Generators
Fuel System — Drawing No. 0E8122-H

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Fuel System — Drawing No. 0E8122-H

ITEM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46

PART NO.
033212
075580
0E8365
039253
022145
022129
045771
042907
0C2454
026307
0E1056
0E6584
057822
059194
064945
0D1509
050279
0E7839
0E6586
0E4394
040105
0E6382B
0F2119
0E6376B
042561
0E7929
0A4637
0E6406
0E7702
0A4632A
037561
046580
0E8286
044118
049815
049226
051713
022097
057796
057795A
052223
061012
0E9295
0F3994
0E7121

QTY.
4
1
1
2
2
8
2
2
2
1
1
1
2
1
1
1
1
1
2
1
1
1
1
1
2
1
1
1
1
1
1
4
1
1
4
4
4
4
1
1
1
1
1
1
1

DESCRIPTION
SCREW HHC 5/16-18 X 1-1/4 G5
FLANGE FUEL INLET
ASSY REG. 3.9L N/G-LPV 1800RPM
SCREW HHC M8-1.25 X 20 G8.8
WASHER FLAT 5/16 ZINC
WASHER LOCK M8-5/16
NUT HEX M8-1.25 G8 YEL CHR
SCREW HHC M8-1.25 X 16 G8.8
SCREW TH-FRM M6-1 X 16 N WA Z/JS
ELBOW 90D STREET 3/4
FUEL HOSE ASSY NAT.GAS/L.P.V.
BRACKET REGULATOR 3.0L FORD HSB
CLAMP HOSE #8 .53-1.00
HOSE 5/8 ID LPG & NG (36" LG)
GASKET CARB ADAPTOR
DECAL INLET PRESSURE
DECAL FUEL INLET NG
MACHINING, CARBURETOR ADAPTOR
GASKET BOSCH 32 & 40
ACTUATOR BOSCH 40 GOVERNOR
HOSE COOL 2IN ID 20R4 (2" LG)
VENTURI HOLDER W/40MM ACTUATOR
O-RING 45.63 ID X 2.62 WIDTH
VENTURI 28 ID THROTTLE W/CHOK
CLAMP HOSE #36 1.88-2.75
BASE AIR CLEANER PLATE
FILTER AIR 11.5" CA326
HOLDER VENTURI
HOLD DOWN AIR CLEANER
PLATE AIR CLEANER TOP
NUT WING 1/4-20 NYLK
SCREW SHC M6-1.0 X 45 G12.9
STREET EL 45DEG 1/2" NPT BRASS
BARBED STR 1/2NPT X 5/8
SCREW HHC M5-0.8 X 16 G8.8
WASHER LOCK M5
WASHER FLAT M5
WASHER LOCK M6-1/4
GROMMET
BARBED EL 90 3/4 PLASTIC
HOSE 1/2 ID SAE-30R2 FUEL/OIL
PLUG STD PIPE 1/8 SOCKET HEAD
ASSY THROTTLE 28MM
PCV VALVE 2.5L FORD
O-RING 47.625 ID X 2.38 WIDTH

Generac® Power Systems, Inc. 39

Section 8 - Exploded Views and Parts

15

7

17

4

1

18

31

30

20

5

21

19

6

LEADS

7

2

8

14

9

24

12

*

3

13*

10

23

11

13

22

QUIETSOURCE™ 40kW Liquid-cooled Generators
Alternator — Drawing No. 0E5146-B

40 Generac® Power Systems, Inc.

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Alternator — Drawing No. 0E5146-B

ITEM

PART NO.

QTY.

1

0E5093A
0E7413A
0E5094A
0E7412A
0E5706
0E5048
0E5048A
0E6668
0E6076
046526
051755
04576100BK
04576100BF
043123
051779
0E7587
023365
092980
052625
0A2602
042558
0A2601
0E7226
045757
052857
051715
038150
077043F

1
1
1
1
1
REF
REF
1
1
8
4
4
4
4
4
1
5
4
4
1
1
1
1
2
2
4
4
1

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

ROTOR REPLACEMENT PARTS
30
047248
31
070892

1
1

DESCRIPTION
ROTOR 390 30KW 1P DIRECT HSB
ROTOR 390 40KW 1P DIRECT HSB
STR-390--35AD1 HSB (382MM LONG)(3.0LFORD)
STR-390--40AD HSB (433MM LONG)(3.9L CHRYSLER)
REAR BEARING CARRIER 390/DRCT
FLEXPLATE 3.0L FORD
FLEXPLATE 3.9L HSB
FLYWHEEL ASSY 3.0L HSB LG GEAR
REVCOR FAN 10.75 X 2 W/PRESS DIS
WASHER LOCK M10
SCREW HHC M10-1.5 X 16 G8.8
STUD M14-2.0 X 490 G5 ZINC (3.0L FORD)
STUD M14-2.0 X 540 G5 ZINC (3.9L CHRYSLER)
WASHER LOCK M14
NUT HEX M14-2.0 G8 YEL CHR
ASSY BRUSH HOLDER 390/HSB
WASHER SHAKEPROOF INT #8
SCREW PPHM M4-0.7 X 25
SCREW SHC M10-1.5 X 35 G12.9
WASHER FLAT .688 ID X 3.25 OD
KEY SQ 3/8 X 1 STEEL
SCREW HHC M16-2.0 X 45 G8.8
GUARD STATOR 390
SCREW HHC M6-1.0 X 25 G8.8
NUT TOP LOCK FL M6-1.0
NUT HEX M4-0.7 G8 YEL CHR
WASHER FLAT #8 ZINC
CONDUIT FLEX 1-1/4" (30" LG)

BALL BEARING-45 MM
SLIP RING -MACHINED-

Generac® Power Systems, Inc. 41

Section 8 - Exploded Views and Parts
QUIETSOURCE™ 40kW Liquid-cooled Generators
Muffler — Drawing No. 0E8068-F

7

21

13
12
10

1

11
5

22

10
11

10

12

23
13

14

22
TO
COMPARTMENT

9

17
19

21

10

TO EXHAUST
MANIFOLD
16

19

6

20

14
17

24
11
2

20
11

19

3

20

8

TO EXHAUST
MANIFOLD

19

8

8

15
4

ITEM

15

11

PART NO.

18

QTY.

1

0E8616

1

2
3
4
5
6
7
8
9
10
11
12

0F1081
0F1087
0E8026
0E5914
0E8702
0E8727
036797
039253
022145
022129
045771

1
1
1
1
1
1
3
2
6
9
3

DESCRIPTION
MUFFLER 7" X 9" X 21" 2.5" IN &
OUT
WYE, PIPE 3.9L CHRYSLER
PIPE R/H SIDE 3.9L CHRYSLER
PIPE L/H EXHAUST MANIFOLD
BRACKET MUFFLER 30" LG
PIPE MUFFLER INLET
PIPE MUFFLER OUT
BOLT U 5/16-18 X 2.25
SCREW HHC M8-1.25 X 20 G8.8
WASHER FLAT 5/16-M8 ZINC
WASHER LOCK M8-5/16
NUT HEX M8-1.25 G8 YEL CHR

42 Generac® Power Systems, Inc.

ITEM

PART NO.

QTY.

13

0C2454

4

14
15
16
17
18
19
20
21
22
23
24

052860
052891
0E8816
051769
0E0170
049808
024114
080762
0E8726
039288
0E0170A

4
4
2
4
1
8
6
2
2
1
1

DESCRIPTION
SCREW TH-FRM M6-1 X 16 N WA
Z/JS
NUT TOP LOCK FL M12-1.75
SCREW HHC M12-1.75 X 80 G8.8
FLANGE EXHAUST 2" PIPE
WASHER LOCK M12
BLANKET EXHAUST 800MM
WASHER FLAT M12
NUT HEX 5/16-24 STEEL
BOLT U 3/8-16 X 2.62
STRAP MUFFLER
SCREW HHC M8-1.25 X 55 G8.8
EXHAUST BLANKET 988MM

Section 9 - Notes
QUIETSOURCE™ 40kW Liquid-cooled Generators

Generac® Power Systems, Inc. 43

Section 9 - Notes
QUIETSOURCE™ 40kW Liquid-cooled Generators

44 Generac® Power Systems, Inc.

Section 9 - Notes
QUIETSOURCE™ 40kW Liquid-cooled Generators

Generac® Power Systems, Inc. 45

Section 10 – Warranty
QUIETSOURCE™ 40kW Liquid-cooled Generators

GENERAC POWER SYSTEMS "TWO YEAR" LIMITED WARRANTY FOR QUIETSOURCE™
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants that its Quietsource
generator will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its
option, repair or replace any part which, upon examination, inspection and testing by Generac or an Authorized Warranty
Service Dealer, is found to be defective. Any equipment that the purchaser/owner claims to be defective must be examined by
the nearest Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are
to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac Quietsource prepackaged emergency
automatic standby generators sold and rated for use in "Standby" applications.

WARRANTY SCHEDULE
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase
and maintenance is required):
Engine - All Components
Alternator - All Components
Transfer System - All Components
All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat
Rate Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Quietsource generators that utilize non-Generac replacement parts.
• Quietsource generators utilizing non-Generac automatic transfer switches.
• Repairs or diagnostics performed by individuals other than Guardian/Generac authorized dealers not authorized in writing by
Generac Power Systems.
• Any Quietsource generators used as rental or trailer mounted applications.
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where
utility power service does not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with
all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty
will not cover repair when normal use has exhausted the life of a part(s) or engine.
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire,
freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent and/or insect infestation.
• Products that are modified or altered in a manner not authorized by Generac in writing.
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or
replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit
warranty period.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
• Rental equipment used while warranty repairs are being performed.
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)
• Overnight freight costs for replacement part(s).
• Overtime labor.
• Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some
states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO
EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH
DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC® POWER SYSTEMS, INC.
P.O. BOX 297 • WHITEWATER, WI 53190
Part No. 0E9042

Revision E (03/15/05)

Revision (2.05)
Printed in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Count                      : 48
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:a42588ca-71b4-44b9-aa86-1b11cced27d5
Producer                        : Acrobat Distiller 6.0 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2005:03:15 09:56:34-06:00
Create Date                     : 2005:03:15 09:56:34-06:00
Document ID                     : uuid:1392370c-b984-4c88-9082-31e9236923a1
Format                          : application/pdf
Title                           : 0E9042RevE.qxd
Creator                         : bpeterso
Author                          : bpeterso
EXIF Metadata provided by EXIF.tools

Navigation menu