TECHNICAL MANU
AL
MANUAL
AVPTC Air Handlers
• Refer to Service Manual RS6200006 for installation, operation & troubleshooting information.
• All safety information must be followed as provided in the Service Manual.
• Refer to the appropriate Parts Catalog for part number information.
• Models listed on page 3.

This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury due to improper
service procedures or services performed by an unqualified person.
Copyright © 2010 - 2011 Goodman Manufacturing Company, L.P.

RT6121001r2
January 2011

PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.

A

V

P

T

C

1830

1

4

EXPANSION
DEVICE:
F: Flowrater
T: TXV
(Expansion
Device)

PRODUCT
TYPE:
A: Air Handler

A
MINOR
REVISION*

MAJOR
REVISION*

CABINET FINISH:
U: Unpainted
P: Painted
N: Uncased
APPLICATION
C: Ceiling Mount PSC Motor
D: Downflow PSC Motor
E: Multi-Position Varible Speed Motor
R: Multi-Position PSC Motor
S: Energy-Efficient Motor:
Multi-Position PSC Motor
T: Coated Coils
V: Variable Speed ECM Motor

A

REFRIGERANT CHARGE:
4:
R-410A
EXPANSION
DEVICE:
C: 4-Wire
Communicating
Ready

ELECTRICAL:
1: 208-230V/1ph/60Hz

NOMINAL CAPACITY RANGE:
Multi-Position & Downflow Applications
1830: 1 1/2 - 2 1/2 Tons
3137: 2 1/2 - 3 Tons
4260: 3 1/2 - 5 Tons

All Airhandlers use DIRECT DRIVE MOTORS. Power supply is AC 208-230v, 60 hz, 1 phase.

WARNING

HIGH VOLTAGE!
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.

Goodman will not be responsible
for any injury or property damage
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.

WARNING

2

Installation and repair of this unit
should be performed ONLY by individuals meeting (at a minimum)
the requirements of an "entry level technician", as specified by the Air-Conditioning, Heating, and Refrigeration
Institute (AHRI). Attempting to install or repair this unit
without such background may result in product damage,
personal injury or death.

WARNING

PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
AVPTC183014**
AVPTC313714**
AVPTC426014**

WARNING

The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.

Do not connect or use any device
that is not design certified by
Goodman for use with this unit.
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.

WARNING

To prevent the risk of property
damage, personal injury, or death,
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.

WARNING

3

PRODUCT DESIGN
WARNING
When installing or servicing this equipment, safety
clothing, including hand and eye protection, is
strongly advised. If installing this equipment in an
area that has special safety requirements (hard hats
etc.), observe these requirements. To protect the
unit when brazing close to the painted surfaces,
the use of a quenching cloth is strongly advised to
prevent scorching or marring of the equipment finish.

AIR HANDLERS
*See Air Handler Specification Sheet for Proper Combinations.

ALL AIR HANDLERS USE DIRECT DRIVE MOTORS. POWER SUPPLY IS 220-240 V, 60 HZ, 1
PHASE
Installation
Before installing this appliance insure that it is properly sized
and adequate power is available.
This appliance can be installed in the vertical position without modification.
The horizontal left and downflow positions require product
modification and instructions for these field conversions can
be found in the AVPTC installation instruction manual.
This product is designed for zero inches (0 inches) clearance; however, adequate access for service or replacement
must be considered without removing permanent structure.
This unit can be installed on a platform when deemed necessary.

WARNING
The unit MUST have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal injury if an electrical fault should occur. The
electrical ground circuit may consist of an appropriately sized electrical wire connecting the
ground lug in the unit control box to the building
electrical service panel. Other methods of grounding are permitted if performed in accordance with
the “National Electric Code” (NEC)/“American National Standards Institute” (ANSI)/“National Fire
Protection Association” (NFPA) 70 and local/state
codes. In Canada, electrical grounding is to be in
accordance with the Canadian Electric Code CSA
C22.1. Failure to observe this warning can result
in electrical shock that can cause personal injury
or death.

WARNING
If this appliance is installed in an enclosed area
such as a garage or utility room with any carbon
monoxide (CO) producing appliance (i.e. automobile, furnace, water-heaters, etc.), ensure the area
is properly ventilated.

4

In an attic installation a secondary drain pan must be provided by the installer and placed under the entire unit with a
separate drain line properly sloped and terminated in an area
visible to the owner. This secondary drain pan is required in
the event that there is a leak or main drain blockage. Closed
cell insulation should be applied to the drain lines in unconditioned spaces where sweating may occur.
Appliances installed in garages, warehouses or other areas
where they may be subjected to mechanical damage must
be suitably guarded against such damage by installing behind protective barriers, being elevated or located out of the
normal path of vehicles. When installed on a base, the base
must also be protected by similar means.
Heating and cooling equipment located in garages, which
may generate a glow, spark or flame capable of igniting flammable vapors, must be installed with the ignition source at
least 18"[46cm] above the floor level.
When more than one appliance is installed in a building it
shall be permanently identified as to the area or space serviced by the equipment.

PRODUCT DESIGN
When this product is installed in the downflow installation in
an unconditioned space, remove the horizontal drain pan and
install the following insulation kit

AVPTC Model

Insulation Kit

1830

DPI36-42/20

3137
4260

See following chart for the correct DPIH kit.

AVPTC Model

Insulation Kit

1830

DPIH36-42

3137
4260

DPIH48-61

DPI48-61/-20

This kit is used to prevent sweating on the vertical drain pan.
To prevent the horizontal drain pan from sweating in high
humidity applications, it is recommended that a DPIH
insulation accessory kit be used. NOTE: The DPIH insulation kit is not supplied with this product and must be
purchased separately.

*AVPTC is a multi-position, variable-speed air handler and is
used with R-410A. The unit's blower design includes a variable-speed ECM motor and is compatible with heat pumps
and variable-capacity cooling applications. (See note below.)
*NOTE: Factory-sealed to achieve a 2% or less leakage rate
at 1.0" water gauge external duct static pressure.
Complies with the Factory-sealed Air Handling Credit as
listed in the 2001 Florida Building Code, Chapter 13, Section
610.2.A.2.1.

5

AVPTC

PRODUCT DIMENSIONS
D

B

C

E

A

SUCTION
LINE
LIQUID
LINE
INLET
TUBE
F

G

I
INLET
(RIGHT SIDE VIEW)

H
INLET
(FRONT VIEW)

Model

A

B

C

D

E

F

G

H

I

J

AVPTC183014

46 3/4"

22"

17 1/2"

19 1/2"

10'

14 1/2"

11 15/16"

17 1/8"

17 15/16"

2"

AVPTC313714

53 1/4"

24"

20"

22"

12"

19 5/8"

11 15/16"

19 5/8"

19 15/16"

1 13/16"

AVPTC426014

53 1/4"

24"

20"

22"

12"

19 5/8"

11 15/16"

19 5/8"

19 15/16"

1 13/16"

6

PRODUCT SPECIFICATIONS

AVPTC

AVPTC183016*

AVPTC313716*

AVPTC426016*

9 1/2"

10 5/8"

10 5/8"

Width
Lineset Connection Size

8"

10 5/8"

10 5/8"

Coil Drain Connection FPT

3/4"

3/4"

3/4"

Liquid

3/8"

3/8"

3/8"

Suction
Electrical Data
Voltage

3/4"

7/8"

7/8"

208/240

208/240

208/240

Min. Circuit Ampacity

4.9/4.9

6.5/6.5

8.6/8.6

15/15

15/15

15/15

197
253

197
253

197
253

FLA

3.90

5.20

6.90

HP
Ship Weight (lbs)

1/2

3/4

1

127

178

197

Blower Wheel
Diameter

Max. Overcurrent Device (amps)
Minimum VAC
Maximum VAC
Blower Motor

7

BLOWER PERFORMANCE DATA
Speed Selection Dip Switches
Cool
Selection
Switches

Adjust
Selection
Switches

2

3

4

Electric Heat Airflow and Temperature Rise Table
Htr Kw

10

11

ON

ON

ON

600

600

600

6

5

ON

ON

OFF

700

700

700

TAP

1

A

OFF

OFF OFF

OFF

OFF OFF

6

ON

OFF

ON

800

800

800

B

ON

OFF

ON

OFF

ON

OFF

8

ON

OFF

OFF

1000

1000

1000

C

OFF

ON OFF

ON

OFF

ON

10

OFF

ON

ON

1200

1200

1200

D

ON

ON

ON

ON

ON

15

OFF

ON

OFF

NR

1400

1400

ON

5

AVPTC 183014* AVPTC 313714* AVPTC 426014*

9

3

Profile
Selection
Switches

Pre-Run

Short-Run

OFF Delay

20

OFF

OFF

ON

NR

NR

1600

A

-------

--------

60 sec/100%

21

OFF

OFF

OFF

NR

NR

1600

B

-------

30 sec/50%

60 sec/100%

Profiles

C

-------

7.5 min/82%

60 sec/100%

D

30 sec/50%

7.5 min/82%

30 sec/50%

NOTE: Airflow data shown applies to the emergency heat mode (electric heat only)
in either legacy mode operation or fully communicating mode operation.

Cooling/Heat Pump Airflow Table

To set airflow: (1) Select model and desired
high stage cooling airflow. Determine the cooresponding tap
( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate
ON / OFF positions. (2) Select model and installed electric
heater size. Set switches 9, 10, and 11 to the appropriate
ON/OFF positions. (3) Select the airflow adjustment factor tap
A and D are 0%; Tap B is +10%; Tap C -10%. Set dip switches 3
and 4 to the appropriate ON / OFF positions.

To set Comfort Mode: Select desired Comfort Mode profile
(see profiles above). Set switches 5 and 6 to the approriate
ON / OFF positions.

Model

Tap

AVPTC 183014 *

A
B
C
D

422
563
694
825

630
840
1036
1232

AVPTC 313714*

A
B
C
D

409
553
696
829

610
825
1040
1237

A

810

1210

C
D

1047
1209

1562
1804

AVPTC 426014*

Low Stage
Cool

High Stage
Cool

0140A00048 REV A

Heat Kit Selection

MODELS

AVPTC183014A*

AVPTC313714*

AVPTC426014A*

HKR-03*

X

X

X

HKR-05*/-05C*

X

X

X

HKR-06*

X

X

X

HKR-08*/-08C*

X

X

X

HKR-10*/-10C*

X1

X

X

2

X

HKR-15C

*

X

HKR-20C

X3

HKR-21C

X3

Revision level that may or may not be designated.

C Circuit breaker option.
1

For units operating in Legacy mode, use dip switches 9-ON, 10-OFF, 11-OFF, to obtain 1000 CFM, or 9-OFF, 10-ON, 11-ON to obtain 1200 CFM.
For units operating in Communicating mode, use dip switch 8 kW Htr to obtain 1000 CFM or 10 kW Htr to obtain 1200 CFM.

2

This heater kit can only be used for ‘1000 CFM or higher’ applications.

3

This heater kit can only be used for ‘1200 CFM or higher’ applications.

8

BLOWER PERFORMANCE DATA
Outdoor
Control

Indoor Control
BIAS Dipswitches
Switch 1 Switch 2

TERM
Dipswitch

TERM
Dipswitches

Switch 3

Switch 1 Switch 2

Data Line
Voltages, Vdc
1-C

2-C

1-2

ON

ON

ON

ON

ON

>2.5

<2.5

>0.2

ON
ON

ON
ON

OFF
ON

ON
OFF

ON
ON

>2.8
>2.8

<2.2
<2.2

>0.6
>0.6

ON

ON

ON

ON

OFF

>2.8

<2.2

>0.6

ON

ON

OFF

OFF

OFF

5

0

5

OFF

ON

ON

ON

ON

0

0

0

ON

OFF

ON

ON
ON
5
5
0
ON or
ON or
OFF
OFF
ON or OFF
0
0
0
OFF
OFF
TERM1 / TERM2 = Termination dipswitches at outdoor unit. See installation
TM
instructions with CT compatiable outdoor unit.

OFF

ON

1

BIAS

2

BIAS

3

TERM

Indoor Unit BIAS and TERMINATION Dipswitches

9

WIRING DIAGRAMS

AVPTC
FL

FL
FL

FL
HTR 2 TL

FL

HTR1 TL

BK

BK
FL

RD
BK

HTR 1 TL

BK

HTR 2 TL

RD

FL
HTR 1 TL

FL
HTR 1 TL

HTR2 TL

FL

RD

HTR 3 TL

FL

1
BK

2

BK

HTR3 TL

1

BK

YL

HTR 4 TL

1

BL
BK

RD
PU
BK

2

3
4

M1

BK

R

RD
5

M2

YL

PU
BL
M3

4

M4

5

WH

R2

RD

4

BR

5

WH

3

BL

BL
M2

RD

M1

YL
RD

M3

M2

M4

M5

M7

M6

M8

R1

6

RD

R2

BL

4

BR

5

BK

BK

RD

6

WH

7

BK

7

BK

8

B K RD

RD

M1

M4

6

7

YL

8
RD

YL

BK

8

9

RD

BL
BK

9

8

RD

9

9

L1 L2
L1

ONE (1) ELEMENT ROWS

L2

L1

TWO (2) ELEMENT ROWS

L2

L1

L2

THREE (3) ELEMENT ROWS

L1

L2

L1

L2

FOUR (4) ELEMENT ROWS

NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPEC IFIED FOR THE AIRHANDLER/HEAT ER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE
PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROW S INSTALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.

L1
2

2

RD

3

3

1

1

GND

RD

RD

L2

GND

PL1 PL2

GN
DISCONNECT

BL

RD

1

3

7
8
9

BR
BL
2

7
8
9

WH

TR

TH

SEE
NOTE
7

FUSE

CFM LED

ELEC
HEAT
AF

DELAY

DEHUM
UNUSED

O
Y2

2
DIP SWITCHES

LEARN

STATUS
LED

W2
W1

BIAS
TERM

BIAS

4

G
C
RX LED
R

SEE NOTE 6

2
1

BL
GY
BK
RD

CIRCULATOR BLOWER
4

4

2

2

3

1
ECM MOTOR
HARNESS

GND

1
2
3
4
5

FUSE 3 A

24 VAC

W1 (1)

W1

W2 (2)

W2
Y1
Y2

L2
40 VA
TRANSFORMER

TH

R

24V THERMOSTAT CONNECTIONS

Y1

3

208/230 VAC

L1

DEHUM
24 V THERMOSTAT CONNECTIONS

1

GND

24 V
3A

SEE
NOTE 5

DIAGNOSTIC
LED
ADJUST

R
D

INDOOR
AIR
CIRCULATOR
BLWR

COM

COOL

B
K

6
5
4

BL

BK

4

6
5
4

BK

-

HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

M3

BL

BK

BK

WH

7
RD

M2

R1

6

BK

RD

2

PU

3

BL
M1

M1
M2

R

BK

PU

BK

3

1

2

YL

RD

RD

BL

HEAT SEQUENCER R1
HEAT SEQUENCER R2

+VDC (1)
TO
MICRO

G

RX (2)
INDOOR
AIR
CIRCULATOR
BLWR

TX (3)

O

DEHUM
GND (4)

GN

C
TR

BK

COM

RD

INTEGRATED CONTROL MODULE

NOTES:
1. PLACE RED WIRE ON TRANSFORMER TERMINAL 2 FOR 208 VAC
OPERATION.
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED
WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT
MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING
MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C.
USE COPPER CONDUCTORS ONLY
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND
LOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT,
DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY (N
THERMOSTAT INPUTS)
6. BIAS AND TERM DIP SWITCHES MUST BE IN "ON" POSITION. RED
STATUS LED PROVIDES NETWORK STATUS. GREEN RX LED INDICATES
NETWORK TRAFFIC. USE LEARN BUTTON TO RESET NETWORK.
7. DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT

0140A00039

REV.C

COLOR CODES:
PK PINK
BR BROWN
W H WHITE
BL BLUE
GY GRAY
RD RED
YL YELLOW
OR ORANGE
VT VIOLET
GN GREEN
BK BLACK

GND

LOW VOLTAGE (24V)
LOW VOLTAGE FIELD
HI VOLTAGE (230V)
HI VOLTAGE FIELD
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
EQUIPMENT GND
FIELD GND
FIELD SPLICE
RESISTER
OVERCURRENT
PROT. DEVICE
PLUG CONNECTION

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
10



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Create Date                     : 2011:01:25 16:32:35-06:00
Modify Date                     : 2011:02:01 09:05:37-06:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:56:37
Metadata Date                   : 2011:02:01 09:05:37-06:00
Format                          : application/pdf
Title                           : untitled
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Document ID                     : uuid:e7778021-ef33-4bf1-abb9-c928a86c010f
Instance ID                     : uuid:fe974ae1-5273-3f4b-8e86-34c5c3465bd2
Page Count                      : 10
EXIF Metadata provided by EXIF.tools

Navigation menu