Goodman GMPN040 3 User Manual GAS FURNACE Manuals And Guides 1303135L
User Manual: Goodman GMPN040-3 GMPN040-3 GOODMAN GAS FURNACE - Manuals and Guides View the owners manual for your GOODMAN GAS FURNACE #GMPN0403. Home:Heating & Cooling Parts:Goodman Parts:Goodman GAS FURNACE Manual
Open the PDF directly: View PDF .
Page Count: 25
INSTALLATION & OPERATING
INSTRUCTIONS
for GMPN
CONDENSING GAS FURNACE
(CATEGORY IV)
(U.S. PAT. # 5,437,263)
EPA POLLUTION PREVENTER
E FF|CII_NCY
RATING
CERT_FIEO
ama
IF THIS FURNACE IS INSTALLED IN AN ENCLOSED AREA, SUCH AS A GARAGE OR
UTILITY ROOM, EITHER ALONE OR WITH ANY OTHER CARBON MONOXIDE PRODUCING
DEVICE (i.e. ATUOMOBLIE, SPACE HEATER, WATER HEATER, ETC.) INSURE THAT THE
ENCLOSED AREA IS PROPERLY VENTILATED.
WARNING
CARBON MONOXIDE (REFERRED TO AS CO) CAN CAUSE SERIOUS PERSONAL INJURY I
OR DEATH. I
WARN ING I
THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED I
ON SITE ONLY. I
Goodman Manufacturing Company, L.P.
IO-151D 1501 Seamist, Houston, Texas 77008 12/01
REPLACEMENT PARTS
Replacement parts for this appliance are available through your contractor or local distributor. For
the location of your nearest distributor consult the white business pages, the yellow page section
of the local telephone book or contact;
SERVICE PARTS DEPARTMENT
GOODMAN MANUFACTURING CO., L.P.
1501 SEAMIST
HOUSTON, TEXAS 77008
(713) 861 - 2500
The major parts groups are as follows;
BLOWER ASSEMBLY
Motor
Blower Housing
Blower wheel
Misc. sheetmetal items
Capacitor
HEAT EXCHANGER
Heat exchanger sections
Innerfront
Secondary coil
ELECTRICAL CONTROLS
Control board
Auxiliary /main limit switch
Roll-out switch
Transformer
Door interlock switch
Air pressure switch
Induced draft blower
BURNER ASSEMBLY
Burners
Manifold
Orifices
Gas Valve
Ignitor
Flame sensor
MISCELLANEOUS
Wrapper
Access doors
Chimney
Gaskets and seals
Wiring assemblies
In order to effectively process the parts requirement the distributor /contractor will need the entire
model number and serial number found on the series and rating plate located inside the blower
compartment.
IO-151 2
INDEX
WARNINGS & GENERAL INFORMATION
LOCATION, CLEARANCES
VENTING
GAS PIPING TABLE
CIRCULATING & RETURN AIR
ELECTRICAL SUPPLY
CONTROL VOLTAGE
RATING THE FURNACE
TIMING THE GAS METER
SAFETY CONTROLS
CIRCULATING AIR FILTERS
TEMPERATURE RISE, MAINTENANCE
SERVICE INSTRUCTIONS, SEQUENCE OF OPERATION
REMOVING AN EXISTING APPLIANCE
INSPECTING AND CLEANING THE HEAT EXCHANGER
COMBUSTION AIR, BLOWER OFF DELAY, EAC CONTROL
HUMIDIFIER CONTROL
DRAIN CONNECTIONS
LIGHTING INSTRUCTIONS
WIRING DIAGRAM
4,5
5,6
6-9
9-11
11,12
12, 13
13
14, 15
16, 17
17, 18
18
19, 20
20, 21
21
22
23
23, 24
25
26
15, 16
THIS FURNACE CONTAINS ELECTRONIC COMPONENTS WHICH REQUIRE A DEFINITE GROUND.
PROVISIONS ARE MADE FOR CONNECTION OF THE GROUND. IF THIS PRODUCT IS NOT PERMANENTLY
AND POSITIVELY GROUNDED NUMEROUS SERVICE CALLS MAY RESULT. A DEDICATED GROUND FROM
THE MAIN POWER SUPPLY OR AN EARTH GROUND MUST BE PROVIDED.
IO-1151C 3
WARNING I
WHILE CARBON MONOXIDE DETECTORS DO PROVIDE ADDITIONAL PROTECTION,
CURRENT LIMITATIONS TO THEIR EFFECTIVENESS REQUIRES THAT YOU OTHERWISE
CONTINUE TO FOLLOW APPROPRIATE INSTRUCTIONS LOCATED IN THE "INSTALLATION
& OPERATING INSTRUCTIONS" AND "USERS INFORMATION" MANUALS RELATING TO
PROTECTING PERSONS FROM THE RISKS OF CARBON MONOXIDE. REVIEW EACH CO
DETECTORS MANUFACTURERS' EXPLANATION OF THEIR UNIT'S CAPABILITIES AND
FOLLOW THOSE INSTALLATION AND OPERATING MANUAL WHEN INSTALLING AND
OPERATING THESE UNITS.
WARNING I
THE CIRCULATING AIR DUCTS MUST BE COMPLETELY AND POSITIVALLY SEALED TO I
PREVENT THE COMBUSTION PRODUCTS, INCLUDING CARBON MONOXIDE, FROM I
ENTERING THE LIVING SPACE. I
TO ENSURE PROPER INSTALLATION AND OPERATION OF THIS PRODUCT, COMPLETELY
READ AND UNDERSTAND THESE INSTRUCTIONS PRIOR TO ATTEMPTING TO ASSEMBLE,
INSTALL, MAINTAIN, OR REPAIR. IF THESE INSTRUCTIONS ARE NOT FOLLOWED
PRECISELY THERE IS A POTENTIAL OF CARBON MONOXIDE POISONING, WHICH CAN
RESULT IN SERIOUS ILLNESS OR DEATH.
THIS FURNACE WAS EQUIPPED AT THE FACTORY FOR USE WITH NATURAL GAS ONLY.
LIQUID PETROLEUM (LP) CONVERSION, IF REQUIRED, MUST BE PERFORMED BY A
QUALIFIED TECHNICIAN FAMILIAR WITH PERFORMING THIS TYPE OF CONVERSION. IF
LP CONVERSION IS REQUIRED, ALL INSTRUCTIONS INCLUDED WITH THE FACTORY
AUTHORIZED KIT MUST BE FOLLOWED. THE ONLY KIT THAT MUST BE USED FOR THIS
CONVERSION IS THE FACTORY AUTHORIZED LPM-01. FAILURE TO FOLLOW THOSE
INSTRUCTIONS EXPLICITLY MAY CAUSE FIRE, EXPLOSION, OR PERSONAL AND
PROPERTY DAMAGE.
UNLESS ALLOWED BY LOCAL CODE, DO NOT INSTALL A LIQUID PETROLEUM GAS
BURNING APPLIANCE IN A PIT, BASEMENT, OR SIMILAR LOCATION. LP, A HEAVIER THAN
AIR GAS, CAN COLLECT IN LOW AREAS AND MAY NOT DISPERSE NATURALLY.
APPLIANCES SO FUELED SHALL NOT BE INSTALLED IN AN ABOVE GRADE UNDER
FLOOR SPACE OR BASEMENT UNLESS SUCH LOCATION IS PROVIDED WITH APPROVED
MEANS FOR REMOVAL OF UNBURNED GAS.
IGENERAL INFORMATION I
These Installation and Operating Instructions are intended for use by fully qualified installation
technicians. Some localities require the installer/sevicer to be licensed. If in doubt, check with
local authorities.
INSTALLATION: In the USA this furnace MUST be installed in accordance with the latest edition
of the ANSI Z223.1 booklet entitled "National Fuel Gas Code" (NFPA 54), and the requirements
or codes of the local utility or other authority having jurisdiction. In Canada this furnace must be
IO-151 4
installed in accordance with the current CAN/CGA-B149.1 & 2 Gas Installation Codes, local
plumbing or waste water codes and other applicable codes.
Additional helpful publications are available from the NFPA are, NFPA 90A - Installation of Air
Conditioning and Ventilating System and NFPA 90B - Warm Air Heating and Air Conditioning
System.
ANNUAL inspections of the furnace and it's vent system is strongly recommended. It is the
installer's responsibility to inform the user of this importance.
All venting shall be in accordance with PART 7, Venting of Equipment, of the National Fuel Gas
Code, ANSI Z223.1, or applicable local building and/or air conditioning codes.
These publications are available from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
The GMPN series of furnaces meet the California NOx emmission standards and California
seasonal efficiency standards.
ILOCATION I
DO NOT install this furnace in a mobile home. This furnace is designed only for installation in
buildings constructed on site and connected to ductwork. When installed in a utility room or closet,
the door should be wide enough to allow the largest part of the furnace to enter, or to permit the
replacement of another appliance, such as a water heater. This furnace is designed to be
installed indoors only. DO NOT install outdoors. This furnace should be installed in such a
manner so that it is protected from water. If any components should become wetted or
submerged under water, replace those parts before returning the furnace to operation. DO NOT
use as a construction heater. DO NOT use in an area where freezing may occur without properly
protecting the vent and drain system. The drain may crack and leak if subjected to freezing
temperatures. DO NOT install in a room used or designed to be used as a bedroom, bathroom or
storage closet, or in any enclosed space with access only through such a room or space.
A return air filter grille or means of inserting a filter into the return air duct is recommended.
The furnace and it's individual shut-off must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa)
The furnace must be isolated from the gas supply piping system by closing it's individual manual
shut-off valve during any pressure testing of the gas supply piping system at pressures equal to or
less than 1/2 psig (3.5 kPa).
MINIMUM CLEARANCES TO COMBUSTIBLE SURFACES
Unobstructed front clearance of 24" for servicing is recommended.
VENT-0" FRONT-3" RIGHT SIDE - 1"
LEFT SIDE - 1" REAR - 0" TOP OF PLENUM - 1"
ACCESSIBILITY CLEARANCE, WHERE GREATER, SHOULD TAKE PRECEDENCE OVER
MINIMUM FIRE PROTECTION CLEARANCE.
A gas fired furnace for installation in a residential garage must be installed so that the ignition
source and burners are located not less than eighteen inches (18") above the floor and is
protected or located to prevent physical damage by vehicles.
IO-151 5
A gas furnace must not be installed directly on carpeting, tile, or other combustible materials
other than wood flooring.
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE
CABINET. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIAL INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND
LIQUIDS. THE USER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE
USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSE.
A SOLID BASE PLATE IS SUPPLIED WITH THIS FURNACE. IT MUST BE LEFT IN PLACE
WHEN THE FURNACE IS INSTALLED WITH SIDE RETURN DUCTS. FAILURE TO LEAVE
THIS BASE PLATE INSTALLED COULD CAUSE PRODUCTS OF COMBUSTION, INCLUDING
CARBON MONOXIDE, TO BE CIRCULATED INTO THE LIVING SPACE AND CREATE A
POTENTIALLY HAZARDOUS CONDITION, INCLUDING CARBON MONOXIDE POISONING.
REFER TO THE SECTION ON "CIRCULATING AIR SUPPLY" FOR RETURN DUCT
INSTRUCTIONS.
Before proceeding with this installation check the following;
• Correct clearance from combustible materials
• Adequate accessibility for servicing
• Flooring is not carpet or any other combustible material, except wood
• Adequate combustion /ventilation air is supplied
• Metal base plate is in place when using side(s) for return air
• In a garage, the furnace has been adequately elevated and protected from vehicle damage
• Furnace area is free of flammable materials and vapors such as gasoline
I VENTING ]
PROPER INSTALLATION OF THE VENTING SYSTEM IS CRITICAL TO SAFE OPERATION OF
THIS PRODUCT. CAREFULLY READ AND UNDERSTAND THE INSTRUCTIONS IN THIS
SECTION. DO NOT CONNECT TO AN EXISTING VENT OR CHIMNEY.
THE FOLLOWING TABLE SHOWS THE MAXIMUM VENT LENGTH WITH VARIOUS
QUANTITY OF ELBOWS. ELBOWS MUST BE LONG RADIUS TYPE (QUARTER BENDS OR
DWV).
MODEL VENT 0 ELL 1 ELL 2 ELL 3 ELL 4 ELL
DIA,
GM P N040 2" 100' 100' 100' 100' 100'
GM P N060 3" 100' 100' 100' 100' 100'
GMPN060 2" 75' 67.5' 60' 52.5' 45'
GM P N080 3" 100' 100' 100' 100' 100'
IO-151 6
GMPN080 2" 75' 67.5' 60' 52.5' 45'
GMPN100 3" 100' 100' 100' 100' 100'
GMPN120 3" 100' 100' 100' 100' 100'
Should more elbows be required, subtract 7.5' from the vent length for each elbow used (over 4
as noted above). A maximum of 6 elbows is acceptable. The use of two 45 ° over one 90 ° is
preferred. Do not count the termination as an elbow.
Minimum vent lengths are 5 ft. for vertical runs and 3ft. for horizontal runs.
A pitch of 1/4" per foot toward the drain assembly is necessary for proper drainage.
The GMPN series of gas furnace is a condensing type appliance. The products of combustion are
recirculated through a secondary coil. During this process the flue products are brought to a
temperature below dew point. Thus the moisture present in the flue products condense, leaving a
liquid by-product. This by-product must be removed from the furnace and it's collection system.
In addition, the vent temperatures are also considerably lower than conventional furnaces. This
allows the use of low temperature plastic as the vent system. The recommended material is
schedule 40 PVC, DWV, ABS (or equivalent if allowed by local code). See previous chart for
proper sizing. The drain trap and related parts must be installed as shown in the illustrations
located elsewhere in these instructions. Failure to follow these instructions can cause products of
combustion including Carbon Monoxide to enter the building. This appliance may be horizontally
vented through an exterior wall. See the illustrations located elsewhere in this manual.
IF THIS FURNACE IS INSTALLED IN AN ATTIC OR SIMILAR AREA WHERE CONDENSATE
OVERFLOW MAY BE A PROBLEM AN AUXILIARY DRAIN PAN MUST BE INSTALLED
UNDER THE FURNACE WITH THE AUXILIARY DRAIN LINES ROUTED TO THE OUTDOORS
TO PREVENT WATER DAMAGE CAUSED BY LEAKS.
The vent pipes must be inspected annually.
Visually check the vent terminal screen and clean if necessary.
Visually check for blockage of the condensate disposal system. Hoses may be disconnected to
determine that proper flow is maintained. Should an obstruction be observed, it can be dislodged
by forcing a stream of water through it using a device such as a garden hose.
This appliance may be vertically or horizontally vented. Horizontal venting requires a 90 ° long
sweep elbow be installed as the vent terminal. This elbow is to be installed discharging
downward and the factory supplied termination screen is to be attached. To prevent damage to
the vent pipe and its terminal the distance from the terminal to the exiting wall is to be the
minimum practical distance (within 12" would be acceptable). Vertical venting does not require
any terminal. If desired, the vent may be faced downward to prevent water or other foreign objects
from entering the vent pipe. In that case two long radius elbows may be employed, facing
downward and terminating no less than one foot (1') from the roof surface.
PROTECTION FROM FREEZING
The vent pipe and drain assembly must be properly protected from freezing particularly if it is
installed in an UNHEATED SPACE. Low wattage tape heaters should be employed on the drain
system. The vent pipe should be insulated using a one (1) inch thick closed foam insulation if
exposed to the outdoors. For pipes located indoors or protected from the elements such as a
garage, basement, etc. fiberglass with an R value of 7 or greater is acceptable.
IO-151 7
DO NOT install the vent pipe in the same chase with the vent from another fuel burning appliance,
except with a GMN, GMPN, GSUS, or GSU furnace manufactured by GOODMAN.
DO NOT install the vent pipe within six (6) inches of another fuel burning appliance.
The drain trap must be easily accessible for checking and /or cleaning. It must be mounted as
shown elsewhere in this I&O.
DO NOT install the trap higher than the venter blower outlet.
DO NOT install this appliance in any area where freezing may occur without properly protecting
the drain assembly.
DO NOT terminate the vent under a deck or overhang or where a positive pressure or the
recirculation of vent products may occur.
CONSULT LOCAL CODES FOR SPECIAL ADDITIONAL REQUIREMENTS.
THE COMBUSTION PRODUCTS AND MOISTURE IN THE FLUE GASES WILL CONDENSE.
THE CONDENSATE MAY FREEZE ON THE EXTERIOR WALL AND SURROUNDING
SURFACES. SOME DISCOLORATION OR ETCHING IS TO BE EXPECTED.
When selecting which exterior wall to penetrate the following items should be taken into
consideration:
Layout the vent system to avoid the possibility of interference with beams, poles, posts, electrical
wiring, plumbing, etc.
When possible the vent termination should not be subjected to prevailing winds.
The vent termination must be located at least twelve (12) inches above grade or expected snow
depth. Consideration should be given to past unusual snow falls.
• DO NOT locate the terminal less than seven (7) feet above public walkways or where it could
cause a nuisance or hazard. This also applies to steps and stairwells.
• DO NOT locate the termination where condensate may present a problem such as flower
beds, patios, etc.
• DO NOT locate within four (4) feet of a gas or electric meter or gas regulator.
• DO NOT locate the vent terminal within four (4) feet between buildings.
• DO NOT locate the vent terminal less than twelve (12) inches above a door or an operable
window.
• DO NOT locate the vent terminal less than four (4) feet below OR four (4) feet horizontally
from, any door, window, or gravity air inlet into any building.
• DO NOT locate the vent terminal within three (3) feet of an inside corner of a building or
structure. A minor inside corner formed by a masonry chimney is an exception to this
requirement.
To protect the exterior surface from staining due to the condensate an aluminum plate or similar
material may be installed surrounding the termination. This plate should extend approximately two
(2) feet from the penetration.
CAUTION
The area surrounding the vent pipe must be kept free of snow, trash, bushes or any other
obstacle which may cause a blockage. A blockage can cause CARBON MONOXIDE to enter the
building.
SUPPORTING AND PITCHING THE VENT
All horizontal runs must be supported at least every five (5) feet and at joints with straps or
hangers. No sags or dips are permitted. The pipe must be saddle supported only. Do not secure
the hangers or straps tightly to the pipes, allow for expansion and contraction of the vent pipe
material. Maintain a 1/4 " per foot minimum pitch upward on the horizontal vent pipe from the
IO-151 8
drain to the terminal. This will allow the condensate to flow backwards into the drain system and
not out the terminal. When penetrating the structure to the outdoors install a sleeve to allow for
expansion and contraction. Vertical runs must be supported a minimum of every six (6) feet.
DO NOT rigidly support the vent pipe, always allow for expansion and contraction.
IJOINING PIPE AND FITTINGS ]
Observe all cautions stated on the cement label.
DO NOT CEMENT THE PIPE OR FITTINGS DIRECTLY TO THE VENTER. A RUBBER BOOT
AND HOSE CLAMPS ARE PROVIDED FOR THIS PURPOSE.
I CONDENSATE DRAIN ]
This furnace is designed to remove both sensible and latent heat from the combustion flue gas.
As a result water vapor is condensed in the secondary heat exchanger. This condensate must be
drained either to the outdoors or, where local code permits, to a sewage system.
In areas where floor level drains are not available a condensate pump may be employed. This
condensate pump must be constructed of corrosion resistant materials. It must also have an
auxiliary switch which will shut down the furnace in the event of pump failure or drain tube
blockage.
DO NOT run the condensate drain to an outdoor drain or to an unheated area where the
possibility of freezing may occur. If installed above a ceiling or other areas where condensate
overflow may cause damage, due to drain freezing or blockage, an auxiliary drain pan draining to
the outdoors is required.
Note: Some local codes require this condensate to be neutralized prior to disposal.
See illustrations elsewhere in this I&O for proper drain connections.
I GAS PIPING & GAS PIPE CAPACITY TABLE ]
Check the rating plate to make certain that the gas supplied is compatable with the unit
requirements. Care should be taken after the installation of this appliance that the gas control
valve is not subjected to high gas supply line pressure.
In making connections, avoid strains as they may cause noise and damage the controls. Always
use a back-up wrench when tightening the gas supply pipe to the gas control valve. Check for
leaks in the gas supply using soap bubbles or other approved methods.
NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS. THIS PRACTICE MAY CAUSE A
FIRE, EXPLOSION, BODILY HARM OR PROPERTY DAMAGE.
Pipe joint compound must be resistant to the action of LP gas. When connecting the gas service
to the furnace, a ground joint union and manual shutoff must be installed exterior to the furnace
cabinet so the control assembly may be easily removed.
A 1/8" NPT plug on the supply pipe near the manual valve for the purpose of making pressure
measurement must also be installed. The valve should be readily accessible for turning on or off.
A capped sediment trap, sometimes called a drip leg, must be installed in the gas supply pipe as
close to the furnace as possible. The sediment trap must incorporate a change of gas flow
direction.
Refer to local codes or the above mentioned publications for proper location and size of the
manual shutoff and sediment trap lengths.
The gas pipe must be sized to eliminate undue pressure drop. See pipe capacity table or consult
your local utility.
IO-151 9
Both the supply and manifold pressure must be measured with the furnace running using the field
supplied pressure tap near the manual shut-off valve and the pressure adjusted if necessary.
All gas piping must conform to local codes, or in the absence of local codes, to the National Fuel
Gas Code ANSI Z223.1 and /or CAN/CGA B149 Installation Codes.
NOTE: COPPER TUBING MUST NOT BE USED FOR NATURAL GAS INSTALLATIONS
WHERE MORE THAN .3 GRAINS OF HYDROGEN SULFIDE PER 100 STANDARD CUBIC
FEET OF GAS IS PRESENT.
FOR INSTALLATIONS IN THE COMMONWEALTH OF MASSACHUSETTS SEE FUEL GAS
AND PLUMBING CODE 248 CMR: APPENDIX C.
Capacity of gas pipe of different diameters and length in ft3/hr, with a pressure drop of 0.3" W.C.
and a specific gravity of 0.60 (natural gas).
PIPE
SIZE*
LENGTH OF PIPE IN FEET
10 20 30 40 50 60 70 80
1/2 132 92 73 63 56 50 46 43
3/4 278 190 152 130 115 105 96 90
1 520 350 285 245 215 195 180 170
1 1/4 1050 730 590 500 440 400 370 350
1 1/2 1600 1100 890 760 670 610 560 530
Nominal size of Iron Pipe in inches.
After the length of pipe has been determined, select the pipe size which will provide the minimum
cubic feet per hour of gas flow for the required input of the appliance. In the case where more
than one appliance utilizes the same supply pipe be sure to consider the sum of all appliances.
The cubic feet of gas required for the appliances should be determined using the following
formula;
Cubic feet of gas required = Gas input of appliance (Btu/hr) /heating value of gas(Btu/hr)
The gas input of the appliance is marked on the specification plate. The heating value of the gas
may be determined by contacting the gas utility or gas supplier.
If the local utility permits the use of a flexible gas connector ALWAYS USE A NEW FLEXIBLE
CONNECTOR. DO NOT USE FLEXIBLE GAS LINES WHICH HA VE SERVICED ANOTHER
APPLIANCE. AFTER A PERIOD OF TIME THESE LINES MAY BECOME BRITTLE AND WITH
THE DISCONNECTION AND RECONNECTION CAN DEVELOP LEAKS.
ICIRCULATING AIR SUPPLY AND RETURN AIR 1
NEVER LAY THIS FURNACE ON IT'S FRONT OR REAR
IO-151 10
The circulating air supply may be taken from; 1) Outside the building, 2) return ducts from several
rooms, 3) central return, 4) any combination of the above.
When a cooling coil is not installed it is recommended that the supply duct have an access panel
so the heat exchanger can be viewed. This panel shall be of sufficient size to permit the entrance
of a light or probe to assist in the observation of the heat exchanger integrity or sampling the air
stream. It should be sealed to prevent air leakage during normal operation.
DO NOT take return air from bathrooms, kitchens, furnace rooms, garages, utility/laundry rooms
or cold areas. If outside air is utilized it should not be taken from within 10 feet of an appliance
vent outlet, a vent opening or a plumbing drainage system, or the discharge from an exhaust
system unless the outlet is three (3) feet above the outside air inlet. DO NOT take return air from
areas where it can pick-up objectionable odors, fumes or flammable vapors.
Note: When a combination of outdoor and indoor air is utilized the system should be designed
and adjusted such that the temperature reaching the appliance will not drop below 50 ° F during
heating operation. This will minimize the possibility of condensate forming inside the heat
exchanger. When this type of system is utilized the volume of air must not be reduced.
Plenum chambers and air ducts must be installed in accordance with the Standard for the
Installation of Air Conditioning and Ventilating Systems, NFPA #90A, or the Standard for the
Installation of Warm Air Heating and Air Conditioning Systems, NFPA # 90B.
If installed in parallel with a cooling unit the damper or other means used to control the flow of air
must be adequate to prevent chilled air from entering the furnace, and if manually operated must
be equipped with means to prevent operation of the other unit unless the damper is in the full heat
or cool position.
NOTE: UPON INITIAL START-UP SOME SMOKE OR AN ODOR MAY BE PRESENT. THIS IS
NORMAL AND SHOULD DISAPPEAR IN A SHORT AMOUNT OF TIME. ITIS RECOMMENDED
THAT WINDOWS AND DOORS BE OPENED UPON INITIAL START-UP TO VENT THIS NON-
TOXIC SMOKE.
One of the most common causes of problems, including premature heat exchanger failure, in a
forced air heating system is insufficient return air. The return air connections to the furnace should
be approximatly equal to the area of warm air discharge. Consult local codes for specific
requirements. The blower speed should be adjusted to maintain the temperature rise range
shown on the rating plate.
The total static pressure should not exceed 0.50" W.C.
NEVER ALLOW THE PRODUCTS OF COMBUSTION TO ENTER THE RETURN DUCTWORK
OR CIRCULATING AIR SUPPLY. ALL RETURN DUCTS MUST BE ADEQUATELY SECURED
TO THE FURNACE AND COMPLETELY SEALED. ALL OTHER DUCTWORK MUST BE
SECURED WITH APPROVED CONNECTIONS AND SEALED AIRTIGHT. THE VENT AND
COMBUSTION AIR SUPPLY PIPES MUST BE PROPERLY INSTALLED AND SUPPORTED TO
PREVENT LEAKAGE AS NOTED ELSEWHERE IN THESE INSTRUCTIONS. WHEN A
FURNACE IS MOUNTED ON A PLATFORM IT MUST BE SEALED AIRTIGHT BETWEEN THE
IO-151 11
FURNACE AND RETURN DUCTWORK. THE FLOOR OR PLATFORM MUST PROVIDE
SOUND PHYSICAL SUPPORT FOR THE FURNACE WITHOUT CRACKING, GAPS, SAGGING
ETC. AROUND THE BASE AS TO PROVIDE A SEAL BETWEEN THE SUPPORT AND THE
BASE.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM ENTERING THE RETURN AIR
SUPPLY MAY CAUSE SEVERE ILLNESS OR DEATH FROM CARBON MONOXIDE
POISONING.
Install the return air to terminate through the base under the furnace. For installations where
return air ducts cannot be run under the floor, the return air supply may be taken from the side(s).
WHERE THE MAXIMUM REQUIRED AIR FLOW IS 1800 CFM OR GREATER THE BOTTOM
OR BOTH SIDES MUST BE UTILIZED FOR RETURN AIR SUPPLY. NEVER USE THE REAR
OF THE FURNACE FOR THE RETURN CONNECTION.
A SOLID METAL BASEPLATE IS SUPPLIED WITH THIS FURNACE. THIS BASEPLATE MUST
BE IN PLACE WHEN THE FURNACE IS INSTALLED WITH SIDE(S) RETURN AIR DUCTS.
FAILURE TO DO SO MAY PERMIT COMBUSTION PRODUCTS TO ENTER THE LIVING
SPACE. THIS MAY CREATE POTENTIALLY HAZARDOUS CONDITIONS SUCH AS CARBON
MONOXIDE POISONING OR DEATH. FULL SIZE RETURN AIR DUCT OPENINGS MUST BE
UTILIZED. EMBOSSES ARE PROVIDED FOR THIS PURPOSE.
IELECTRICAL SUPPLY CONNECTIONS ]
The electrical requirements are listed on the series and rating plate on the furnace. A separate
supply line with a current overload device and a manual switch, where required, must be installed.
Type "T" wire or equivalent with a minimum rating of 95°F ( 35°C ) temperature rise must be run
directly from the main power supply to the junction box in the furnace. Copper conductors are
required.
Installation of the electrical supply must be in accordance with local codes. In the absence of
local codes refer to the National Electrical Code ANSI/NFPA No. 70 (latest edition), which can be
obtained from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. In
Canada refer to the latest edition of the Canadian Electrical Code C22.1 Part I.
ICONTROL VOLTAGE CONNECTIONS 1
THERMOSTAT INSTALLATION:
Install the thermostat in accordance with the instructions accompanying the thermostat. Run the
thermostat wires into the control compartment of the furnace. Connect the thermostat wiring as
shown on the wiring diagram. The thermostat wiring should be a minimum of 18 gauge. Adhere to
recommended color code to facilitate future troubleshooting.
The thermostat should be located near the return air grille or opening. It should be approximately
5 feet from the floor level. Never locate the thermostat where it will be influenced by heat
generated by hot water pipes, lamps, televisions, direct sunlight, supply air registers, etc.
IO-151 12
Interconnecting wiring must be secured and protected from damage or disconnection. The use of
solderless connectors or equivalent is recommended. The low voltage control wiring exiting the
furnace is labeled "thermostat wiring".
SETTING THE HEAT ANTICIPATOR
The following method should be used in measuring the amp draw of the control circuit to assure
proper adjustment of the thermostat heat anticipator
,1
YELLOW PURPLE PURPLE
CONDENSER FURNACE
\,
W
BLUE
I RATING THE FURN CE WHITE
This furnace is ship!c G
__ n the factory equipped for u ._!ith nat;,ra! r RED uctions are
for use with natura THERMOSTAT es up to 2,000 feet, using a heating va GREEN 3tu/hr. Should
this appliance be converted to LP, refer to the instructions included in ne tactory a_ithorized LP
Conversion Kit (LPM-01). If for use at altitudes in excess of 2,000 feet refer to the instructions
included in the factory authorized High Altitude Kit (HA-02).
It is imwrap the'"R" leg around'a ciip-on'he input rate of the furnace to prevent an overfiring situation.
Overfilamp meter 10 times. It exchanger failure. The input is controlled bytLhe supply
pressLEnergize the furnace in the ;sure and heating (calorific) valu_"X
The SLheat mode. Record the reading, ured with _o _ o,,,4 - u,__urnina aDI31_ \\in\_,
st be adju_dt th_"se o e pressur_ /_eries and
.Divide this reading by
°perat 10. Set the heat anticipator ,_Sin exc _ _ J" Ure an fice_ on //" /t"
rating on the thermostat to match table belo_rate is 4%° for e_,\ /)ooThefeet
above°rifice_thisEXAMPLE:reading Jupon a heat_o proximately 1 ,C"\\ /z'ft3
If the reading on the amp meter is
"4", divide this by 10. __
The anticipator setting will be .4 NAT. GAS ORIFICE SI;
amps. #45
#47
#47
I 5,000 #47
IO-151 13
1
6,000 I #48
7,000 #48
The input to the furnace must be checked AFTER reorificing.
For altitudes above 7,000 feet refer to appropriate section of the National Fuel Gas Code, ANSI
Z223.1. To calculate the input of the furnace for installations in altitudes over 2,000 feet, use the
following formula;
CORRECTED INPUT = SERIES & RATING PLATE INPUT - (ALTITUDE X .04) X SERIES &
RATING PLATE INPUT /1000
EXAMPLE:
Corrected input for a 100,000 Btu/hr. appliance installed at an altitude of 6.000 ft. utilizing natural
3
gas with a heating value of 1,000 But/ft is determined by-
Corrected Input = 100,000 - (6,000 X .04) X (100,000 /1,000)
Corrected Input = 100,000 - (240 X 100)
Corrected Input = 100,000 - 24,000
Corrected Input = 76,000
Using the orifices sized as shown in the table for 6,000 feet (#48), a meter time of 48.0 seconds is
measured. The actual firing rate of the furnace is
Input = 1,000 (heating value of the gas) X 3600 (constant) /48.0 (meter time for 1 ft3of gas)
Input = 3,600,000 /48.0
Input = 76,000 Btu/hr
In Canada, the series and rating plate input for the furnace apply to installations up to 2,000 feet
(610m) above sea level. Kit HA-02 for natural and LP gases is required to convert furnaces from
elevations of 2,000 to 4,500 feet (610m to 1,370m). Canadian certification applies to the
installations of up to 4,500 feet above sea level. Installations above 4,500 feet is subject to
acceptance by the local authorities having jurisdiction.
WARNING I
BEFORE ATTEMPTING ANY SERVICE OR ADJUSTMENTS - INSURE THAT THE GAS AND I
ELECTRICAL SUPPLIES ARE "OFF". I
ITIMING THE GAS METER ]
Use the following method to determine the firing rate of the furnace. The supply pressure tap
should be located on the field installed piping or gas shut-off valve. The manifold pressure tap is
located on the combination gas valve in the furnace and labeled "OUTLET PRESSURE TAP".
• Install a manometer graduated in tenths of an inch of water column on the supply pressure tap
of the gas supply pipe.
• Remove plug at the "Manifold" pressure tap on the gas valve and install a second manometer.
• Determine the size of gas meter used.
• Shut off all other gas fired appliances with the exception of the pilots.
• Place furnace in operation.
• Check the supply pressure as shown the on series and rating plate.
• After 15 minutes of operation, time the meter with a stop watch for 2 revolutions & divide by 2.
• Use the appropriate column to determine the furnace input.
IO-151 14
• If necessary, adjust the manifold pressure at the gas valve by removing the regulator cap and
turning the adjustment screw clockwise to raise the pressure and counterclockwise to reduce
the pressure. The manifold pressure must be between 3.2" W.C. and 3.8" W.C. for natural gas
and 9.5"W.C. and 10.5" W.C. for LP ( a field conversion is necessary for LP). The inability to
maintain the proper pressure range will require reorificing. After replacing the orifices, repeat
the above steps to insure that the furnace input is adjusted properly.
• Turn off gas and electrical supply, remove manometers and replace any plugs which were
removed. Use a pipe joint compound which is suitable for use with LP gas.
• Restore any other appliances affected to their normal operating mode.
METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES EQUIPPED FOR USE
WITH NATURAL GAS AT 0 - 2,000 FEET ALTITUDE.
INPUT
Btu/hr
METER
SIZE
FT 3
HEAT
VAL UE
1,100
MIN. SEC.
HEAT
VALUE
900
MIN.
SEC.
1 21
13 30
0 54
9 00
0 41
6 45
0 32
5 24
0 27
4 30
HEAT
VAL U E
1,000
MIN.
SEC.
1 30
15 00
1 00
10 10
0 45
7 30
0 36
6 00
0 30
5 00
HEAT
VALUE
1040
MIN.
SEC.
1 33
15 36
1 O3
10 24
0 47
7 48
0 37
6 14
0 31
5 12
40,000 1 1 39
10 16 30
60,000 1 1 06
10 11 00
80,000 1 0 50
10 8 15
100,000 1 0 40
10 6 36
120,000 1 0 33
10 5 30
IMAIN BURNER ADJUSTMENT
The main burners should not need adjustment in most instances. However, air shutters are
provided should adjustment be necessary.
After the furnace has been in operation for at least five (5) minutes loosen the shutter locking
screw and close the shutter until yellow tipped flames appear. Now slowly open the shutters until
the yellow disappears. Retighten the locking screw.
1
ISAFETY CONTROL FUNCTIONS AND CHECK-OUT PROCEDURE ]
GENERAL
In most cases the safety controls are wired is series with the "W" leg. It is imperative that these
switches remain in the circuit. Never jumper, relocate (unless as noted on the furnace) or bypass
any control. The safety controls must be checked for proper operation at the time of start-up of
the furnace.
WARNING I
SHOULD ANY SAFETY CONTROL BE ALTERED, JUMPERED OR BYPASSED, A I
HAZARDOUS CONDITION SUCH AS FIRE OR THE POSSIBILITY OF CARBON MONOXIDE I
ENTERING THE BUILDING MAY OCCUR. I
IO-151 15
MAIN LIMIT SWITCH
The main limit switch is a 1/2" disc designed to shut off the burner gas should the outlet (bonnet)
temperature exceed the maximum design outlet air temperature. This switch is not adjustable. To
check the operation, block the return air flow through the unit temporarily. The limit switch should
function and shut the burner gas off within a few minutes. Remove the blockage and allow the
switch to cool sufficiently before reestablishing burner flames.
VENT PRESSURE SWITCH
This furnace utilizes a vent pressure switch which prevents the furnace from operating should any
portion of the vent system become restricted or a venter failure occur. To check this switch, place
the furnace in operation and remove the hose from the switch. The gas burners will extinguish.
Replacing the hose will allow the furnace to operate normally.
FLAME ROLL-OUT SWITCH
This furnace is equipped with four (4) flame roll-out switches. These manually resetable switches
are 1/2" disc type and are non-adjustable. They are designed to shut down the burner gas in the
event that flames are detected outside the heat exchanger. Should a switch function, contact a
qualified service person to determine the cause of function before resetting. To reset this
switch press the button on top of the switch after the furnace has cooled. To test the operation of
the switch with the furnace in operation, place an open flame on the disc portion of the switch.
The switch should function to shut down the burner gas. Wait until the furnace has cooled
sufficiently before resetting the switch.
FLAME SENSOR
The ignition is provided by electronic means. The burner flames should be extinguished if the
flame sensor fails to detect the presence of burner flame. To test, disconnect the flame sensor
wire before placing the furnace in operation. The electronic ignition should ignite the burners.
However the burners should shut off after a few seconds of operation. Disconnect the electrical
supply to the furnace, reinstall the disconnected sensor wire and reset the power supply to restore
the furnace to it's normal operation.
BLOWER DOOR INTERLOCK SWITCH
The purpose of the switch is to disconnect electrical power to the furnace should the blower door
become dislodged, removed, or not properly reinstalled such as performing a filter change.
ALLOWING THE FURNACE TO OPERATE WITHOUT THE BLOWER DOOR BEING
SECURELY IN PLACE CAN CAUSE COMBUSTION PRODUCTS TO BECOME CIRCULATED
THROUGHOUT THE LIVING AREA WHICH CAN CAUSE SERIOUS ILLNESS OR CARBON
MONOXIDE POISONING. To test the operation of this switch, place the furnace in operation and
remove the blower access door. The burner flames will extinguish and the venter and circulating
air blowers should both stop. To restore the unit to normal operation, shut off the electrical power
to the unit, replace the blower access door and restore the electrical power.
STACK OVER-TEMPERATURE SWITCH
Located on the venter blower housing, this switch is designed to shut down the burners should the
circulating air blower fail or the secondary coil become blocked. To test this switch, bypass the
main limit switch, disconnect the circulating air blower, and place the furnace in operation. After a
short period of time this switch should function shutting down the burners. IT IS VERY
IMPORTANT TO REMOVE THE BYPASS FROM THE MAIN LIMIT SWITCH AND REPLACE
THE WIRES WHICH WERE DISCONNECTED FOR THIS TEST PRIOR TO RETURNING THE
FURNACE IN NORMAL OPERATION.
IO-151 16
INTEGRATED FAN /IGNITION CONTROL
This furnace is equipped with a combination ignition module and fan control. An electronic device
ignites the burners upon a call for heat. It also controls the venter blower and the various speed
selections of the circulating air blower. This control is located in the circulating air blower
compartment. Upon a demand for heat the venter is energized. After a short purge, the electronic
ignition device is energized. The burners are ignited after a short delay and the burner flame is
proven. The circulating air blower is energized approximately thirty (30) seconds after the burners
are ignited. The circulating air blower off time is field selectable. THIS CONTROL IS NOT FIELD
SERVICEABLE.
ICIRCULATING AIR FILTERS 1
One of the most common causes of problems in a forced air heating system is blocked or dirty
filters. Circulating air filters must be inspected monthly for dirt accumulation and replaced if
necessary. Failure to maintain clean filters can cause premature heat exchanger failure. A new
home may require more frequent replacement until all construction dust and dirt is removed.
Circulating air filters are to be installed external to the furnace cabinet.
Before performing any service on this furnace, including checking or replacing circulating air filters
- disconnect main power.
DO NOT operate the furnace for extended periods of time without filters in place. Dust and dirt in
the air will restrict the air movement over the secondary coil causing nuisance cycling of safety
controls which may result in a "no heat condition."
INPUT BTUH
40,000
60,000
80,000
100,000
120,000
MINIMUM FILTER SIZES
FILTER SIZE
320 /160 IN. z
480 /240 IN. z
640 /320 IN. z
727 /363 IN. z
960 /480 IN. z
TYPE
DISPOS./PERMAN.
DISPOS./PERMAN.
DISPOS./PERMAN.
DISPOS./PERMAN.
DISPOS./PERMAN.
I TEMPERATURE RISE 1
The temperature difference between the outlet air and the inlet air of the furnace is known as the
temperature rise. This furnace is designed to operate within the temperature rise displayed on the
furnace series and rating plate. To ensure satisfactory performance, the temperature rise of the
furnace must be measured and adjusted if necessary. Use the following procedure to measure
and adjust the temperature rise;
• Prior to starting the furnace visually inspect all joints and seams in the supply and return air
ducts for leaks. Repair them if necessary.
• Adjust the room thermostat to obtain constant operation.
• Allow the furnace to operate for at least fifteen (15) minutes.
• With an accurate thermometer measure the temperature at the return air grille. If a
combination indoor /outdoor system is used, the temperature must be measured downstream
of the connection.
IO-151 17
• Measure the outlet air temperature at a point approximately twelve to eighteen (12 -18) inches
from the supply air duct opening of the furnace. It may be necessary to measure the outlet air
at several places to obtain an accurate average. NOTE: IF AN AIR CONDITIONING COIL IS
INSTALLED TAKE CARE SO AS NOT TO DAMAGE THAT COIL.
• Adjust the temperature by changing circulating air blower speed tap.
I MOTOR LUBRICATION AND MAINTENANCE ]
The circulating air blower is equipped with sleeve bearings which are permanently lubricated by
the motor manufacturer and require no lubrication. At the time of the monthly filter inspection
clean the exterior of the circulating air motor, especially around the perimeter air holes to prevent
the possibility of overheating due to an accumulation of dust or dirt on the windings and motor
casing. As suggested elsewhere in these instructions, the air filters are to be kept clean. Dirty
filters will restrict the air flow over the motor windings and possibly cause an overheating
condition. The venter motor has bearings which are prelubricated by the motor manufacturer and
require no attention.
I SERVICE INSTRUCTIONS ]
• DO keep the circulating air filters clean. The heating system will operate more efficiently and
economically.
• DO arrange drapes and furniture so that the supply air registers and return air grilles are
unobstructed.
• DO close doors and windows. This will reduce the heat load on the system.
• DO avoid excessive use of bathroom and kitchen exhaust fans.
• DO NOT let heat generated by televisions, lamps, direct sunlight, etc. influence the thermostat
operation.
• Exclusive of the mounting platform, keep all combustible materials at least three (3) feet from
the furnace.
• DO NOT use the furnace room as a storage area.
• DO NOT store gasoline or other flammable liquids or vapors in the vicinity of the furnace.
I SEQUENCE OF OPERATION ]
This appliance is controlled by the thermostat. Within this section, the term lockout is referenced.
This lockout is a "soft" lockout which will reset after one hour. It is the obligation of the installer to
educate the user on the proper use of the thermostat and the sequence of operation in both the
heating and cooling modes. It is also important that any repair or service be performed by a
QUALIFIED service person, not by the user.
HEATING MODE
• The furnace control checks for an open main limit (this limit is in the normally closed ). If the
limit is open, the furnace will remain inoperable until the limit is closed. During an open limit
the circulating air blower will be energized. The status light will blink four (4) times.
• The room thermostat reacts to a demand for heat.
• The control will then check to insure that the vent pressure switch is open. If, at this point, the
vent pressure switch is closed the control will blink two (2) times and will remain inoperable
until this situation is corrected.
• The venter blower is energized.
IO-151 18
• The vent pressure switch will close when it detects a pressure in excess of it's setting. If the
pressure switch fails to close the status light will flash three (3) times. The sequence cannot
continue until the pressure switch closes.
• The flame rollout switches are then checked to assure that they are in the closed position.
• After a pre-purge of about fifteen (15) seconds the electronic ignition device will be energized.
• After a slight delay the gas valve will open if the flame rollout swithches are closed.
• The burners will ignite and the flame sensor will detect the presence of flame. The ignition
device will deenergize. If the sensor does not detect the burner flame, the gas valve will close
and the ignition cycle will be repeated for a total of three attempts. If, after the third attempt,
the presence of flame is not detected, the furnace will go into a lockout condition for one (1)
hour. It will then repeat the ignition cycle. This one (1) hour lockout and retry will occur
indefinitely.
• Thirty (30) seconds after the main valve is energized the circulating air blower will be activated.
• The furnace will remain in operation until the demand for heat is satisfied.
• Once the demand is satisfied the venter will shut off, and the circulating air blower will shut off
after the field selectable time off is attained.
• The furnace will remain dormant until the next demand for heat.
COOLING MODE
• A demand for cooling is initiated.
• The control checks for an open limit. If an open limit is detected the furnace will remain
inoperable until the condition is corrected. During an open limit condition the circulating air
blower will be energized. The status light will blink four (4) times.
• The condenser contactor will close.
• After approximately five (5) seconds the circulating air blower will start on the cooling speed.
• After the room thermostat is satisfied the condenser contactor will open.
• The circulating air blower will remain in operation for approximately sixty (60) seconds.
I REMOVING AN EXISTING APPLIANCE ]
When replacing an existing appliance, the resulting installation must comply with all local codes,
or in the absence of local codes, to the National Fuel Gas Codes ANSI Z223.1 and/or CAN/CGA
B149 Installation Codes as well as these installation instructions.
If the installation of this GMPN furnace requires that an existing appliance be removed from a
venting system which still serves another gas fired appliance this may require that the existing
vent be re-sized. The following steps shall be performed with each appliance connected to the
venting system placed in operation while any other appliance connected to the venting system are
not in operation;
a) Seal any unused openings in the venting system;
b) Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel
Gas Code, ANSI Z223.1 or the CAN/CGA B149 Installation Codes and these instructions.
Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition;
c) In so far as practical close all building doors and windows and all doors between the space in
which the appliance(s) connected to the venting system are located and other spaces in the
IO-151 19
building. Turn on clothes dryers and any other appliance not connected to the venting system.
Turn on any exhaust fans such as range hoods and bathroom exhausts, so they shall operate at
their maximum speed. DO NOT operate a summer exhaust fan (whole house fan). Close fireplace
dampers;
d) Follow lighting instructions. Place the appliance being inspected in operation. Adjust the
thermostat so the appliance shall operate continuously;
e) Test for draft hood equipped appliance spillage at the relief opening after five (5) minutes of
burner operation. Use the flame of a match or candle;
f) After it has been determined that each appliance connected to the venting system properly
vents when tested as outlined above, return all doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance back to their previous condition of use;
g) If improper venting is observed during any of the above tests, the venting system must be
corrected.
If resizing of the existing vent is required this shall be sized in accordance with Appendix G of the
National Fuel Gas Code, ANSI Z223.1 or CAN/CGA B149 Installation Codes.
I INSPECTING & CLEANING THE HEAT EXCHANGER ]
CAUTION I
Label all wires prior to disconnection when servicing controls. Wiring errors can cause dangerous I
and improper operation. Verify proper operation after servicing. I
It is the obligation of the installer to advise the user to have the furnace inspected and cleaned
annually. To clean the heat exchanger perform the following:
•Adjust the room thermostat to its lowest setting.
• Turn off the gas and electric supply to the furnace.
• Remove the control access door.
• Open the gas supply union.
• Disconnect the gas supply line attached to the gas valve.
• Remove the wires connected to the gas valve.
• Remove the burner box assembly. Care must be exercised to avoid damage to the igniter.
• Inshot burners should not require cleaning. However, if they exhibit signs of corrosion they can
be cleaned by brushing with a stiff wire brush.
• Remove the vent from the furnace venter blower.
• Remove the venter blower and collector box.
• With a stiff wire brush on a flexible handle, remove any loose scale from the heat exchanger at
both the flue and burner openings.
• Use a 1/2" diameter brush to remove any deposits in the secondary heat exchanger.
• With a vacuum remove any loose scale dislodged and any additional debris found in the heat
exchanger.
• Visually inspect the heat exchanger cells for any cracks or openings using a bright light.
•If any failures are discovered it is important to disable the furnace and notify the user to
ensure that it remains inoperable until repairs are implemented.
IO-151 20
• Reassemble the furnace in the reverse order. Note: No additional screws or wires are supplied
with this product. All components must be reassembled to avoid an unsafe condition.
• Reconnect gas supply and check for leaks using a soap solution. If a flexible gas line is used
examine it for cracks or weakness. Replace if necessary.
• Restore electrical power.
• Follow the lighting instructions to place the furnace into operation.
Note - It is important to use a pipe joint compound that is resistant to the effects of LP gas.
I SOURCE OF COMBUSTION AIR ]
The recommended source of combustion air is to use the outdoor air supply. However, the use of
indoor air in most applications is acceptable except as follows;
1. If the furnace is installed in a confined space it is recommended that the necessary
combustion come from outdoors by way of the attic, crawl space, or direct openingto the outside.
2. If indoor combustion is used, there must be no exposure to the substances listed in #3 below.
3. The following installations may require OUTDOOR AIR for combustion, due to chemical
exposures;
• Commercial buildings • Furnaces installed in hobby or craft rooms
• Buildings with indoor pools • Furnaces installed near chemical storage
• Furnaces installed in laundry rooms areas
Exposures to the following substances in the combustion air supply may also require OUTDOOR
AIR for combustion;
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
perchloroethylene)
• Printing inks, paint removers, varnishes,
etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes
dryers
• Masonry acid washing materials
IBLOWER OFF DELAY ]
In the heating mode, the time period between the extinguishing of the burners and the circulating
blower turning off, is known as the "Blower Off Delay." This time is factory preset at 150 seconds.
The 150 second delay can be changed to 120 or 90 seconds by changing the position of a jumper
on the Ignition Control.
FACT[3RY SETTIN8 [3PTI[3NAL SETTINGS
SEC, SEC, SEC,
_ L [3",,,,,,,"E :£ [3FF \
TEi<IVlNAL \_ \\
/
/
90 _
120 %
_5o \
/
9O
i20
©
i50 \
kS \'_
/
/
IO-151 21
IELECTRONIC AIR CLEANER CONTROL ]
The red-capped terminal on the ignition control marked "EAC" is to supply 115 VAC to an
Electronic Air Cleaner. This terminal is powered in both the heating and air conditioning modes
when the circulating blower is operating.
IHUMIDIFIER CONTROL ]
The screw terminal on the ignition control called "HUM" is designed to give a 24 VAC signal to a
humidistat in the heating mode. DO NOT USE ON HUMIDIFIERS WHICH USE 115 VAC.
FZEL I} b F PL I E13
HUHII3IFZER _ ....... '_
/\
/H H
""k x /
FIEL1} S >I>LIE13
HU/_I]}ZSTAT
H Iv
IGNITI[3N C[3NTR[3L
IDRAIN CONNECTIONS ]
UPFLOW LEFT SIDE DOWNFLOW LEFT SIDE
ii i
ii i
ii i
iIi
ii i
iii
iii
iii
ii i
iii
ii i
ii i
iii
iii
ii i
Ii I
ii i
ii i
ii i
iii
iii
i1 i
iii
li i
i1 i
I
I
,I
!!
ii
ii
ii
¢-Pt
tlb
"14.
ii
II
II
II
II
II
ii
ii
!!
ii
ii
ii
II
II
II
II
',I
II
ii
IO-151 22
DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE
III
III
I II
in
in
III
HORIZONTAL LEFT HORIZONTAL RIGHT
IO-151 23
LIGHTING INSTRUCTIONS
These instructions are also on the furnace
AiI-mg If you do not follow these instructions exactly,
a fire or explosion may result causing property
damage, personal injury or loss of life.
A. This appliance does not have a pilot. It
is equipped with an ignition device which
automatically lights the burners. Do not
try to light the burners by hand.
B. BEFORE OPERATING smell around
the appliance area for gas. Be sure to
smell next to the floor because some gas
is heavier than air and witl settle on the
floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch;
do not use any telephone in your
building.
• Immediately call your supplier
from a neighbor's phone. Follow
the gas suppliers instructions.
• If you cannot reach your gas supplier,
call the fire department.
C. Use only your hand to move the gas
control switch or knob. Never use
tools. If the gas control switch or knob
wilt not operate, don't try to repair it,
calt a qualified service technician.
Force or attempted repair may result in
a fire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately calt
a qualified service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
WARNING: Improper
installation, adjustm-
ent, alteration, service
or maintenance can
cause injury or prop-
erty damage. Refer to
the user's information
manual provided with
this furnace. For ass-
istance or additional
information consult a
qualified installer, ser-
vice agency or the
gas supplier.
This furnace must be
installed in accordan-
ce with the manufac-
turers instructions
and local codes. In
the absence of local
codes follow the
National Fuel Gas
OPERATING INSTRUCTIONS
1. STOP! Read the safety information
above on this label.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appl-
iance.
4. This appliance is equipped with an
automatic ignition system which autom-
atically lights the burners. Do not try to
tinhf fh_ hi irn_r_ hv h_ncl
7. Wait five (5) minutes to clear out any
gas. If you then smell gas, STOP!
Follow "B" in the safety information
_hnv_ nn fhi_ I_h_l If vnJl clnn'f _m_ll
gas, go to the next step.
8. Move the gas control switch or knob
to "ON".
9. Replace control access panel.
10. Turn on all electric Dower to the
Code, ANSI Z223.1.
For indoor installation.
PGB & PGJ
For outdoor install-
ation only.
m
9
0"1
r,o
o'1
FROM FURNACE
CHS,qSIS (ROUND
,v
CONDENSING <, O
UNIT ',, R
T' STAT ' ....... -....
DS
1
TWIN
ROS ROS
NOTE:
THE LEADS FROM THE MOTOR
MAY iE CHANGE[) TO THE
REQUIRED SPEED.
, SO
FS
P
RSS ROS
MED HI YELLO t,/
MED LOW OAS,NOE
HIGH
//5 /60 /I
POv',ER SUPPL
I[}BRI
IDBR2
HEaT
SOOL
HSIR
HSI
LS
FUSE
"k P,J'_'
IDBR2
i. ¢/
.%/
P',,R HSIR
,f--\
IDBR/
SO ROS ROS ROS ROS G V
DS [}}(}('f SWITBH
FS FLAHE SENSOR
OV OAS VALVE
HSI HOT SURFACE IGNITOR
HSIR HOT SURFACE IONITION RELAY
IDB INDOOR BLOWER
IDBR INDOOR BLOWER RE/:_Y
LS LIHIT SWITCH
PS PRESSURE SWITCH
fV POWER VENTOR
PVf POWEf VENT fEL,_Y
ROB I{OLLO( T SWITCH
SO STACK OVERTEk,IP SWITCH
WIRING CODE NOTES:
FACTORY WIRING 1 REPLACEMENT WIRE MUST
HIGH VOLTAGE _ BE THE SAME SIZE AND TYPE
LOW VOLTAGE OF INSLB,_TION AS Of IGINAL
(/OoC}
2 WARNING CABINET MUST BE
fSERMANENTLY Of OJNDE[} AN[}
CONFORM TO NEC & LOCAL
WIRE COLOR CODE CODES.
B BLACK (/) PK PINK (9)
BL BLJE (4) p PUf fLE (B)
BI( BROWN (7) W WHITE (0)
G GREEN (8) ELLOW (5)
0 ORANGE (6) R RE[} (2)
]_28578 04