Model SP
Model CSP
Ceiling Exhaust and Inline Fans

®

Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!

Model SP

Model CSP

Model SP is a direct drive ceiling exhaust fan designed
for clean air applications where low sound levels are
required. Many options and accessories are available
such as lights, motion detectors, ceiling radiation
dampers and speed controls. Capacities range from 25
to 1,600 cfm (42 to 2,718 m3/hr) and 1 in. wg (248 Pa).
AMCA Licensed for Sound and Air Performance.

Model CSP is a direct drive inline exhaust fan designed
for clean air applications where low sound levels are
required. Capacities range from 70 to 3,800 cfm (119 to
6,456 m3/hr) and 1 in. wg (248 Pa). AMCA Licensed for
Air Performance.

ENERGY STAR® Certified models include:
SP-A, 50, 70, 90, 200, 250, 290 and 410;
SP-B, 50, 70, 80 and 90.

WARNING!
To reduce the risk of fire, electric shock, or injury to
persons, observe the following:
• Suitable for use with solid state speed controls.
• Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer.
• Before servicing or cleaning unit, switch power off at service
panel and lock service disconnecting means to prevent
power from being switched on accidentally. When the service
disconnecting means cannot be locked, securely fasten a
prominent warning device, such as a tag, to the service panel.
• Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
• Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as
those published by the National Fire Protection Association
(NFPA), and the American Society for Heating, Refrigeration
and Air Conditioning Engineers (ASHRAE) and the local code
authorities.
• When cutting or drilling into wall or ceiling, do not damage
electrical wiring or other hidden utilities.
• Acceptable for use over a bathtub or shower when installed
in a GFCI protected branch circuit. (Up through size SP-A390)
• Never place a switch where it can be reached from a tub or
shower.
• Ducted fans must always be vented to the outdoors.
• These fans are not recommended for cooking exhaust
applications. They are designed primarily for low temperature,
clean air applications only. The diagram shows the minimum
distance these fans should be placed in relation to cooking
equipment.
• Fan/Light combination not to be installed in a ceiling thermally
insulated to a value greater than R40.

CAUTION!
• For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.

®

Ceiling Exhaust and Inline Fans

1

Prepare the fan
Power Assembly

Remove Wiring Knockout

If power assembly (motor, wheel, and scroll) is not
installed in housing, insert the electrical plug into fan
socket, then slide scroll end of power assembly into
fan housing. Attach by using two sheet metal screws
provided.

Remove either top or side wiring knockout,
depending on wiring
direction, by
Electrical
Access
bending it back
Panel
and forth to
break tabs.

B Model

A Model

Knockouts

Ductwork

Airflow

Check ductwork to see if the fan’s discharge requires
rotation from horizontal to vertical discharge.

Airflow

Fan Rotation
To rotate from horizontal to vertical discharge
A-Models Only
A-50-500, 710, 780 Models
Remove the two screws holding the power assembly
in and pull power assembly out. Rotate power
assembly 180 degrees and put back into fan. Use
the same screws to reattach power assembly to fan
housing. Flip fan over and remove the four screws
holding the discharge duct and damper assembly.
Exchange the assembly with plate mounted on top of
fan, as shown in these illustrations.

A-700, 900-1500 Models
Remove the eight screws
holding the access panel or
collar as shown in picture.
Rotate the fan housing so
the discharge is facing up.
Replace access panel or
collar and screws.

2

Ceiling Exhaust and Inline Fans

Access
Panel

Access
Panel

®

Ceiling Radiation Damper (CRD)
If fan is to be used in a fire resistive membrane
ceiling, a ceiling radiation damper must be used.
If the ceiling radiation damper is already mounted to
the fan from the factory, proceed to Install the Fan.

To mount the ceiling radiation damper to fan, make sure
grille attachment tabs are facing down. Then place the inlet
part of the fan into the ceiling radiation damper collar, and
use self-tapping sheet metal screws (by others) to screw
through the damper collar and into the fan housing. If the
fan/light combination is being used, make sure ceiling
radiation damper has
an electrical plug in it.
The electrical plug must
be inserted into the fan.
Make sure the electrical
wire will not interfere with
damper operation as
shown in figure below.

Wires to ceiling fan

Attachment Tabs

A-50-510, 710, 780 Models

B-Models

Do not allow
interference
in this area

A-700, 900-1550 Models

Wires from lighted grille

Discharge Installation SP-A 50-90 Models
1

2

Insert plastic duct tab into SP-A box slots.

Rotate plastic SP-A duct adapter (PN 473322)
until the screw tabs meets SP-A box.

Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)

SP-A Box

Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
SP-A Box

SP-A Box Slot

Plastic SP-A
Duct Adapter Tabs

Plastic SP-A
Duct Adapter (PN 473322)

Plastic SP-A
Duct Adapter (PN 473322)

3

Screw Tabs

Install screws provided to secure discharge.

Screw holes
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)

®

Ceiling Exhaust and Inline Fans

3

Discharge Installation SP/CSP-B 50-200 Models

1

2

Insert SP-B box scroll tab into SP-B box
scroll slots.

Rotate plastic SP-B duct adapter (PN 474433)
until the two SP-B mounting tabs fully engage
into the two SP-B box mounting slots.

SP-B
Box Scroll Tabs
SP-B
Box Mounting Slots

SP-B
Box Scroll Slots

SP-B
Box Mounting Tabs

3

OPTIONAL
Align the pins on the TR 6x4 adaptor to the
duct pin hole on the SP-B 6-inch duct. Push
until the adaptor snaps into place.

TR 6x4 Pin

SP-B
Plastic Duct Pin Hole

TR 6x4
(PN 473324)

4

Ceiling Exhaust and Inline Fans

SP-B
6-inch
Plastic Duct
(PN 474433)

®

Install the Fan
1. For best
performance,
choose a location
with the shortest
possible duct run
and minimum
number of elbows.
Do not mount near
cooking equipment, as
shown in Fig. 1.

Do not install
fan in this area
45°

Fig. 1

Bottom Mount

2. Attach adjustable
mounting brackets
to fan, but leave the
screws loose until
proper height is
determined, shown
in Fig. 2. Cut hole to
dimensions shown
in table below:

45°

Brackets can be
used in either
position to adapt to
most mounting
situations

Bottom Mount

Top Mount

Fig. 2

Ceiling Openings
Sizes
SP-A50, A70, A90
SP-A110, A125, A190
SP-A200, A250, A290, A390

Fan/CRD

107⁄8 x 133⁄8

111⁄8 x 137⁄16

121⁄8 x 141⁄4

121⁄4 x 143⁄8

SP-A700

233⁄4 x 113⁄4

241⁄8 x 121⁄4

SP-A410, A510, A710, A780
SP-A900, A1050, A1410,
A1550
SP-B 50 - 200

3

14 ⁄4 x 18 ⁄8

147⁄8 x 187⁄16

143⁄4 x 24

147⁄8 x 241⁄8

141⁄8 x 113⁄4

143⁄8 x 121⁄4

3

For Hanging
Installations:
Use Greenheck’s
optional vibration
isolator kit Part Number
VI Kit. Using the fan’s
standard adjustable
mounting brackets and
10 by 32 threaded rod
(by others), hang unit as
shown in Fig. 4.

Slots in the
brackets
allow fine
adjustment
for flush
fit with
wall/ceiling
opening

Fig. 3

Fig. 4

3. Installation of ductwork
is critical to the performance
of the fan, shown in Fig. 5.
Straight ductwork (1) or
ductwork that turns in
the same direction as the
wheel (2) is recommended.
Ductwork turning opposite
the wheel direction (3) will
cause turbulence and back
pressure resulting in poor
performance.

Fig. 5
1
(GOOD)

3
(POOR)

2
(GOOD)

AIRFLOW

Fan or Fan/Light

For Frame Construction:
Position unit between
joists. Position brackets
such that bottom
edge of housing will
be flush with finished
ceiling, and tighten the
adjustable mounting
brackets, shown in
Fig. 3.

NOTE
Model SP-A 50-90 are standard with a round duct.
Should Model SP-A 110-190 require a round duct,
Model RDC (Round Duct Connector) may be ordered
from Greenheck for field installation.

4. Slide ductwork over the fan’s discharge collar and
securely attach it with sheet metal screws.
Make sure the screws do not interfere with damper
operation. Check damper to make sure it opens freely.

Wire the Fan
1. Remove wiring cover.
If fan/light combination
is being used, make
sure the fan plug is
connected to the fan
receptacle and the light
Fan Outlet (top)
plug is connected to
the light receptacle,
Light Outlet (bottom)
Fig. 6
shown in Fig. 6.
Using proper wire
connectors, wire the fan as shown in Fig. 7a.
For wiring of light proceed to Fig. 7b.
Fan

Light

Fig. 7a

Fig. 7b

115 & 277 Volt

220 - 240 Volt

Black wire is “Hot”
White wire is “Neutral”
Green wire is “Ground”

Black wire is “Hot”
White wire is “Hot”
Green wire is “Neutral/Ground”

2. Push all wiring into the unit’s cover and replace
wiring cover.

®

Ceiling Exhaust and Inline Fans

5

Attach the Grille

Fig. 8

1. If lighted grille is being used, plug wire into fan
socket.
If lighted grille and ceiling radiation damper are
being used, plug wire from lighted grille into ceiling
radiation damper socket. Do not plug wire directly
into the fan socket. Make sure the wire does not
interfere with the ceiling radiation damper operation.

Fig. 9

2. Attach grille with two screws provided. Make sure
not to over tighten; over tightening will damage
grille.
3. Slide attachment screw covers over the attachment
screws, shown in Figure 8 and 9.
4. If lighted grille is being used, install light bulb(s) into
light socket(s). For incandescent lights, use maximum
100 watt bulb (by others). For fluorescent lights, use
27W GU24 bulbs. Greenheck has replacement 27W
GU24 bulbs call 1-800-355-5354 to order.

Squeeze
tabs to
insert/remove lens

5. If lighted grille is being used, snap lens into place, by
pushing on the outside edges of lens, shown in Fig. 9.
To remove lens, use small screw driver and pry on
one side of lens.
6. Turn on power and check fan and light operation.

Converting from ceiling to cabinet design for Model SP fans
All SP convertible sizes will be shipped with grille and duct collar cover.
Conversion Kit Parts List
• Qty. of 1 Blower Box Cover

B
A

Tools Required
• Phillips Head Screwdriver
Step 1: Remove grille (A) by removing the two
grille screws (B).
Step 2: Remove duct collar cover (C) by
removing the four duct collar screws (D).
Step 3: Discard grille (A), two grille screws (B),
and duct collar cover (C).
Step 4: Remove the six (6) tinnerman clips (E)
by twisting them to one side and pulling
straight out. Discard two of the six
tinnerman clips.

C
D

D

F

E

Step 5: Insert the remaining four tinnerman clips
(E) on grille opening side.
Step 6: Place blower box cover (F) over
tinnerman clips (E), which were inserted
in step 5.
Step 7: Screw the blower box cover (F) into place
with four blower box cover screws (D).
E
SP/CSP models shown are
UL and cUL listed E 33599

6

Ceiling Exhaust and Inline Fans

®

Other Installation Considerations

Flex Duct
Connections

Ductwork and Noise
Fiberglass ductboard is a better choice than metal
ductwork for reducing fan noise and is highly
recommended for low sound applications. Where metal
duct is used, sound transmission can be reduced with
flexible duct connections between the fan and the duct.

Sound and Location
The location of these fans must be taken into
consideration before installation. In critical sound
installations, insulated ductwork, flexible duct
connections or placing the fan in a remote section of
ductwork are solutions to meeting the required fan sound
levels.

Filters
The addition of an intake filter is highly recommended
for these fans, even in clean air environments excess
dirt can accumulate on wheels and motors causing
reduced performance and imbalance.

Remote
Mounted
CSP and SP-C
Converted
to Inline

Fiberglass
Ductboard
SP and SP-C
Mounted Directly
Overhead

Filters, once installed, should be checked and cleaned
periodically to maintain performance.
Greenheck offers washable aluminum mesh filters
specifically designed for these fans. Please consult our
SP/CSP catalog for more information.

Correct Low
Sound Installation
Incorrect
SP/CSP models shown are
UL and cUL listed E 33599

General Maintenance Suggestions
Model SP/CSP ceiling exhaust fans require very little maintenance. But since small problems over time left
unchecked could lead to loss of performance or early motor failure, we do recommend that the unit be inspected
periodically (once or twice a year).
The fan motor and wheel should be checked for dust and dirt accumulations. Dirt buildup can lead to loss of
performance and motor overheating. Cleaning can be accomplished by brushing off any dust that may have
accumulated. Even filtered units can accumulate build-up and should be checked when cleaning filters.
The motor should be checked for lubrication at this time. Lubricate only those motors which have an oil hole
provided. A few drops of all purpose oil (SAE 20) will be sufficient.

®

Ceiling Exhaust and Inline Fans

7

Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck SP and CSP catalog provides additional
information describing the equipment, fan performance,
available accessories, and specification data.

AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at www.amca.org.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com

8

474680 • SP/CSP, Rev. 1, March 2011

Copyright 2011 © Greenheck Fan Corporation



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Instance ID                     : uuid:bd0d864d-417c-44f6-8b89-c501d12ef643
Original Document ID            : adobe:docid:indd:1da76088-9453-11dc-b82e-d4748b937e81
Document ID                     : xmp.id:9531DA86A114E2118E3EB325156878A0
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:9131DA86A114E2118E3EB325156878A0
Derived From Document ID        : xmp.did:1E990376DFFDE11188BA92278353BA19
Derived From Original Document ID: adobe:docid:indd:1da76088-9453-11dc-b82e-d4748b937e81
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2012:10:12 14:39:11-05:00
Create Date                     : 2012:10:15 16:47:11-05:00
Modify Date                     : 2012:10:24 10:23:32-05:00
Metadata Date                   : 2012:10:24 10:23:32-05:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Format                          : application/pdf
Title                           : untitled
Producer                        : Acrobat Distiller 10.1.4 (Windows)
Trapped                         : False
Page Count                      : 8
Creator                         : Adobe InDesign CS6 (Windows)
EXIF Metadata provided by EXIF.tools

Navigation menu