Greenheck Fan Smoke Dampers Smd 401M Users Manual

SMD-401M to the manual d678672a-9264-481a-9362-64544b284f60

2015-02-09

: Greenheck-Fan Greenheck-Fan-Smoke-Dampers-Smd-401M-Users-Manual-562490 greenheck-fan-smoke-dampers-smd-401m-users-manual-562490 greenheck-fan pdf

Open the PDF directly: View PDF PDF.
Page Count: 4

DownloadGreenheck-Fan Greenheck-Fan-Smoke-Dampers-Smd-401M-Users-Manual-  Greenheck-fan-smoke-dampers-smd-401m-users-manual
Open PDF In BrowserView PDF
SMD-401M
Smoke Dampers

Extruded Airfoil Blades
UL 555S Leakage Class I

APPLICATION

Model SMD-401M is a class I leakage rated modulating smoke
damper. The model SMD-401M serves the function of
both a control damper and smoke damper. High strength airfoil
blades ensure the lowest resistance to airflow in HVAC systems
with velocities to 2000 fpm (10.2 m/s ) and 4 wg (1 kPa). Model
SMD-401M may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and leakage in
either direction.

Ratings

	
Leakage Class:	
I
Operational Rating: Actual ratings are size dependent.
	
Max. Velocity:	
up to 2000 fpm (10.2 m/s)
	
Max. Pressure:	
4 in. wg (1 kPa)
	
Temperature:	
250°F (121ºC) with all actuators.

Standard Construction

	
Frame: 	
		
		
		
		
		
		
Blades: 	
	
		
		
		
Seals:	
	
		
		
Linkage:	
	
Axles:	
	
	
Bearings:	

Size Limitations:

5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes
less than 17 in. (432mm) high to
maximize free area and
performance.
Airfoil shape constructed of
heavy gauge extruded aluminum.
Structural reinforcement through
the entire length.
Extruded silicone rubber blade
seals. Flexible stainless steel
jamb seals.
Concealed in jamb.
1⁄2 in. (13mm) dia. plated steel.
Bronze sleeve type.

	
Minimum Size:	
		
Maximum Size:
	
	
Single Section:	
		

8 in. W x 8 in. H
(203mm W x 203mm H)

	
Multi Section:	
		

144 in. W x 36 in. H
(3658mm W x 914mm H)

36 in. W x 36 in. H
(914mm W x 914mm H)

Optional Features:
• Galvanized steel sleeves.
• Stainless steel bearings
• OCI (Open closed indication switches)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• POC Retaining angles
• Smoke detector
• Momentary switch
• Transitions (R, C, O)
• Sealed transitions and sleeves

Model SMD-401M meets the requirements for smoke
dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
ICBO Uniform Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:108)

“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
	
Standard 555S (Listing #R13317)

LH

H*
RH

W*

*W&H dimensions furnished approximately 1/4 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.

Installation instructions available at www.greenheck.com

SMD-401M	

Pressure Drop Data

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown.
All data has been corrected to represent standard air at a density of .075 lb/ft3 (1.201 kg/m3).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with
an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given
HVAC system.

AMCA Test Figures

5D

Figure 5.3 Illustrates a fully ducted damper. This
configuration has the lowest pressure drop of the
three test configurations because entrance and
exit losses are minimized by straight duct runs
upstream and downstream of the damper.

6D

Figure 5.3

Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has
a lower pressure drop than Figure 5.5 because
entrance losses are minimized by a straight duct
run upstream of the damper.

5D

4 (W) (H)
3.14

D

Figure 5.5 Illustrates a plenum mounted damper.
This configuration has the highest pressure drop
because of extremely high entrance and exit
losses due to the sudden changes of area in the
system.

Figure 5.2

Figure 5.5

10.0
9.0
8.0
7.0
6.0

5.5

5.0
4.0

10.0
9.0
8.0
7.0
6.0

10.0
9.0
8.0
7.0
6.0

5.0

5.0
4.0

4.0

5.2

3.0

5.5

3.0

5.3

2.0

Damper Size
36 in. x 36 in.
(914mm x 914mm)

Damper Size
24 in. x 24 in.
(610mm x 610mm)

Damper Size
12 in. x 12 in.
(305mm x 305mm)

3.0

5.5

2.0

2.0

Pressure Loss (in. wg)

Pressure Loss (in. wg
)

0.5
0.4
0.3
0.2

1.0
0.9
0.8
0.7
0.6

5.3

0.5
0.4
0.3
0.2

Pressure Loss (in. wg)

5.2
1.0
0.9
0.8
0.7
0.6

1.0
0.9
0.8
0.7
0.6

0.3
0.2

0.10
0.09
0.08
0.07
0.06

0.10
0.09
0.08
0.07
0.06

0.05

0.05

0.05

0.04

0.04

0.04

0.03

0.03

0.03

0.02

0.02

0.02

5 6 7 8 9 10
x 100

2

3

Velocity (fpm)

4
5 6 7 8 9 10
x 1000

5.3

0.4

0.10
0.09
0.08
0.07
0.06

4

5.2

0.5

4

5 6 7 8 9 10
x 100

2

3

Velocity (fpm)

4 5 6 7 8 9 10
x 1000

4

5 6 7 8 9 10
x 100

2

3

Velocity (fpm)

4 5 6 7 8 9 10
x 1000

Application Data
Damper Sideplate and Sleeve Dimensional Data

The drawings below illustrate the factory standard sideplate and sleeve mountings for the SMD-401M. The standard "A"
dimensions listed in the table provide adequate space for the mounting of actuators and controls.
If space constraints are a problem the "A" dimension can be varied
between 5 3⁄8 in. (136mm) and 12 in. (305mm).
1 1/2" max.
Sideplate

Sleeve

1 1/2" max.

11/2 in. max.

"A" Dimension
3 3/4"

in. (mm)
All Dampers*

Sleeve
Maximum

7 3/16 (183)

12 (305)

6 3/16 (157)

12
(305)

10 3/16
(259)

3 3/4 in.

6"

6 in.

LH

RH

Right hand drive is shown
Left hand drive available upon request

5 in.

A

Sideplate

Standard
When
height is
Varies
11 in. (279) or5 3/8"
less with OCI

11 3/16
(284)

*With the exception of dampers 11 in. (279mm) high or less (12 in. 6"
(305mm)high
or Aless if width5"is greater than 64 in. (1625mm)) with OCI
Varies
5 3/8 in.
option.
Sleeve Length
** On dampers 11 in. (279mm) high or less (12 in. (305mm)high or less if
LH
RH in.
width is greater than 64 in. (1625mm))
with OCI option, sideplate is 16
(406mm)
Right hand drive is shown
A
5 in. Left hand drive available upon request

12 in.**

3 3/4"

Varies

5 3/8"

A

5"
Sleeve Length

Sleeve Length

T*

Space Envelopes Required for
Actuators and Accessories

S

Externally mounted actuators always
require space
T*
outside of the damper sideplate or sleeve. The “S”
S
dimension illustrates
the clearance required for various
available actuators.
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below the
sideplate or sleeve. “B” and “T” dimensions are worst
case clearance requirements for some dampers less
than 18 in. (457mm) high. All damper sizes under 18
in. (457mm) high do not require these worst case
clearances. If space availability above or below the
damper sleeve is limited, each damper size should be
individually evaluated.
B*

Actuator Type/Model

B*

T*

With OCI

With OCI

B*

S

Pneumatic
331-2976

2 1/2 in. (64mm)

5 1/4 in. (133mm)

* For dampers 18 in.(457mm) or more in height these dimensions are 0 in.
1 Note: This actuator requires field calibration for the zero and span setting.

6 in. (152m)

Transitioned Damper Dimensions
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the SMD-401M can be supplied in a
factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct dimensions.
Drawings below show overall damper size.

D*+ 2 in. (51mm) +T

s

W*+ 2 in. (51mm)+T s

W* + 2 in. (51mm)+T s

D* + 2 in. (51mm)+T

s

H*+ 2 in. (51mm)+Ts
21/8 in.
(54mm)

21/8 in.

(54mm)

H*

H* + 2 in. (51mm)+T s

W*

16 in. (406mm)
Min.

D*

16 in. (406mm)
Min.

TYPE R

21/8 in. H*
(54mm)

W*

16 in. (406mm)
Min.

TYPE O

TYPE C

*	These dimensions are furnished approximately 1/4 in. (6mm) undersize, except round and oval dimensions which are
approximately 1/8 in. (3mm) undersize.
Ts = (2)(Sleeve Thickness)

Specifications
Smoke Dampers meeting the following specifications
shall be furnished and installed where shown on plans
and/or as described in schedules. Dampers shall meet
the requirements of NFPA 90A, 92A, 92B, 101 and 105 and
further shall be tested, rated and labeled in accordance with
the latest edition of UL Standard 555S. Smoke dampers
shall be of low leakage design qualified to UL 555S Leakage
Class I.
Each damper /actuator combination shall have a UL555S
elevated temperature rating of 250°F (121ºC) minimum and
shall be rated to operate at maximum design airflow at its
installed location. Each damper shall be supplied with an
appropriate actuator installed by the damper manufacturer
at the time of damper fabrication. Damper actuator shall be
(specifier select one of the following) electric type for 24 volt
operation.

Damper blades shall be hollow extruded aluminum airfoil
type with structural reinforcing tube running full length of
each blade. Damper frame shall be galvanized steel formed
into a structural hat channel shape with reinforced corners.
Bearings shall be sintered bronze sleeve type rotating in
extruded holes in the damper frame. Blade edge seals
shall be silicone rubber designed to inflate and provide a
tighter seal against leakage as pressure on either side of
the damper increases. Jamb seals shall be stainless steel
compression type. Damper must be rated for mounting
vertically (with blades running horizontal) or horizontally and
be UL 555S rated for leakage and airflow in either direction
through the damper.
The basis of design is Greenheck Model SMD-401M.

Copyright © 2007 Greenheck Fan Corporation
SMD-401M Rev. 5 April 2007



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-702
Create Date                     : 2008:10:29 14:27:03-05:00
Metadata Date                   : 2008:10:29 14:43:47-05:00
Modify Date                     : 2008:10:29 14:43:47-05:00
Creator Tool                    : Adobe InDesign CS3 (5.0.2)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 11211 bytes, use -b option to extract)
Instance ID                     : uuid:ffa3adc6-5b62-4c22-8481-8ca84cc6293e
Document ID                     : adobe:docid:indd:62add615-a81c-11dc-8eb9-9c76a2bb682f
Rendition Class                 : proof:pdf
Derived From Instance ID        : 62add614-a81c-11dc-8eb9-9c76a2bb682f
Derived From Document ID        : adobe:docid:indd:f6df44bf-129f-11dc-9e33-faaf856fcfcd
Manifest Link Form              : ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches
Manifest Reference Instance ID  : uuid:42930FBF0C06DB118093EC9FB2A064D0, uuid:109843B83F94DA11BAD1D23B39E671BC
Manifest Reference Document ID  : uuid:41930FBF0C06DB118093EC9FB2A064D0, uuid:0F9843B83F94DA11BAD1D23B39E671BC
Format                          : application/pdf
Producer                        : Adobe PDF Library 8.0
Trapped                         : False
Page Count                      : 4
Creator                         : Adobe InDesign CS3 (5.0.2)
EXIF Metadata provided by EXIF.tools

Navigation menu