Guardian Technologies Quietpact 40Lp 004701 0 Users Manual

004701-0 to the manual 60103ba3-ce65-46b3-a4d3-94664771f762

2015-02-09

: Guardian-Technologies Guardian-Technologies-Quietpact-40Lp-004701-0-Users-Manual-563104 guardian-technologies-quietpact-40lp-004701-0-users-manual-563104 guardian-technologies pdf

Open the PDF directly: View PDF PDF.
Page Count: 52

DownloadGuardian-Technologies Guardian-Technologies-Quietpact-40Lp-004701-0-Users-Manual-  Guardian-technologies-quietpact-40lp-004701-0-users-manual
Open PDF In BrowserView PDF
Owner’s Manual and
Installation Instructions
Air-cooled Recreational
Vehicle Generators

						

This manual should remain with the unit.

•M
 odel: 004701-0
QUIETPACT 40LP

Introduction

Thank you for purchasing this model of the
QUIETPACT product line. This model is designed
and manufactured to supply electrical power for recreational vehicles.

 Read This Manual Thoroughly
If any portion of this manual is not understood, contact
an Authorized Service Dealer for starting, operating
and servicing procedures.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their definitions are as follows:

danger
 fter this heading, read instructions that, if not
A
strictly complied with, will result in personal injury, including death, or severe property damage.

 fter this heading, read instructions that, if not
A
strictly complied with, may result in personal injury
or property damage.

The operator (driver) is responsible for proper and
safe use of the vehicle and its equipment, and the
safety of all vehicle occupants. We strongly recommend that the operator read this manual and thoroughly understand all instructions before using this
equipment. We also strongly recommend instructing
other occupants in the vehicle to properly start and
operate the generator. This prepares them if they need
to operate the equipment in an emergency.

 Contents
This manual contains pertinent owner’s information,
including warranty, electrical diagrams, exploded
views and lists of repair parts for generator model
numbers 004701-0. In addition, the latter portion of
this manual contains information necessary for the
proper installation of these generators.

 Operation and Maintenance
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by an Authorized
Service Dealer. Normal maintenance service and
replacement of parts are the responsibility of the
owner/operator and, as such, are not considered
defects in materials or workmanship within the
terms of the warranty. Individual operating habits
and usage contribute to the need for maintenance
service.

 fter this heading, read instructions that, if not
A
strictly complied with, could result in damage to
equipment and/or property.
NOTE:

Proper maintenance and care of the generator ensures
a minimum number of problems and keep operating
expenses at a minimum. See an Authorized Service
Dealer for service aids and accessories.

After this heading, read explanatory statements
that require special emphasis.

 How to Obtain Service

These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compliance with the special instructions while performing
the service are essential to preventing accidents.

When the generator requires servicing or repairs,
simply contact an Authorized Service Dealer for
assistance. Service technicians are factory-trained
and are capable of handling all service needs.

Four commonly used safety symbols accompany the
Danger, Warning and Caution blocks. The type
of information each indicates follows:

When contacting an Authorized Service Dealer or
factory about parts and service, always supply
complete model number and serial number of
unit as given on its data label, which is located on
generator.

This symbol points out important safety informa tion
that, if not followed, could endanger personal
safety and/or property of others.



Model No._ ____________

Serial No._______________

This symbol points out potential explosion hazard.	
			
This symbol points out potential fire hazard.

		
This symbol points out potential electrical shock
 hazard.			

Authorized SERVICE
DEALER LOCATION
To locate the nearest AUTHORIZED SERVICE
DEALER, please call this number:

1-800-333-1322
or access the web at
www.generac.com
		

the
the
the
the

Table of Contents
Recreational Vehicle Generator

Part I – Owner’s Manual

Part II – Installation Instructions

Introduction.........................................Inside Front Cover

Safety Rules...................................................................... 16

Read This Manual Thoroughly........................................ IFC
Contents......................................................................... IFC
Operation and Maintenance............................................ IFC
How to Obtain Service.................................................... IFC
Authorized Service Dealer Locator Number.................... IFC

Safety Rules.........................................................................2
Section 1 – General Information....................................4
1.1	

Generator Identification..............................................4

1.2	

Generator Applicability...............................................5

1.3	

Safety..........................................................................5

1.4	

Generator AC Connection System...............................5

1.5	

Specifications..............................................................5

Section 1 – General Information................................. 18
1.1	

Purpose and Scope of the Manual.............................18

1.2	

Safety........................................................................18

1.3	

Standards Booklets...................................................18

1.4	

Equipment Description.............................................18

1.5	

Generator Engine Operating Speed...........................18

1.6	

Generator AC Connection System.............................18

Section 2 – Installation.................................................. 20
2.1	

Location and Support...............................................20

2.2	

Generator Compartments.........................................21

2.3	

Cooling and Ventilating Air.......................................23

2.4	

LP Gasoline Fuel System..........................................24

2.5	

Exhaust System........................................................26

2.6	

Electrical Connections..............................................27

Generator Control Panel.............................................6

2.7	

Battery Installation....................................................28

2.2	

Optional Remote Start/Stop Panel...............................7

2.8	

Optional Accessories.................................................30

2.3	

Before Starting the Engine..........................................7

2.4	

Starting the Generator................................................7

2.5	

Stopping the Generator...............................................8

Section 3 – Post-installation Start-up
Adjustments................................................ 31

2.6	

Applying Loads to Generator......................................8

3.1	

Post Installation Tests...............................................31

2.7	

Do Not Overload the Generator...................................8

3.2	

Before Initial Start-up...............................................31

2.8	

Protection Systems.....................................................8

3.3	

Initial Start................................................................31

2.9	

Additional Information................................................9

3.4	

Testing Under Load..................................................31

3.5	

Installation Checklist................................................32

Section 2 – Operation.......................................................6
2.1	

Section 3 – Maintenance............................................... 10
3.1	

Checking the Engine Oil Level...................................10

3.2	

Changing the Engine Oil and/or Oil Filter.................10

3.3	

Maintaining the Engine Air Cleaner..........................11

3.4	

Clean Air Intake........................................................11

3.5	

Checking the Engine Spark Plug...............................12

3.6	

Clean Spark Arrestor................................................12

3.7	

Cleaning the Generator.............................................12

3.8	

Battery Maintenance.................................................13

3.9	

Major Service Manual...............................................13

Appendix
Appendix
Appendix
Appendix

1
2
3
4

–
–
–
–

Troubleshooting..................................... 33
Electrical Data........................................ 34
Exploded Views and Parts Lists......... 36
Warranty.................................................. 48

3.10	 Exercising the Generator..........................................13
3.11	 Out of Service Procedure..........................................13
3.12	 Adjusting Valve Clearance.........................................14
3.13	 RV Generator Service Interval...................................14

	

	



Safety Rules
Recreational Vehicle Generator



S
 ave These Instructions – The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas of the recreational vehicle.
Safety should be stressed to all operators and potential operators of this equipment.



WARNING!



This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.



WARNING!



The engine exhaust from this product contains
chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become
familiar with this manual and with the unit. The generator can operate safely, efficiently and reliably only
if it is properly installed, operated and maintained.
Many accidents are caused by failing to follow simple
and fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed
to the unit, are, therefore, not all inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique utilized does not render the generator unsafe.

danger
Despite the safe design of this generator,
 operating
this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to operate or maintain this
equipment.

Potentially lethal voltages are generated by
 these
machines. Ensure all steps are taken to

render the machine safe before attempting to
work on the generator.

Parts of the generator are rotating and/or hot
 during
operation. Exercise care near running
generators.

 General Hazards 
•	 For safety reasons, the manufacturer recommends
that the installation, initial start-up and maintenance of this equipment is carried out by an
Authorized Service Dealer.
	 	



•	 The generator engine releases DEADLY carbon
monoxide gas through its exhaust system. This
dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death.
Never operate the generator set with the vehicle
inside any garage or other enclosed area. DO NOT
OPERATE THE GENERATOR IF THE EXHAUST
SYSTEM IS LEAKING OR HAS BEEN DAMAGED.
SYMPTOMS OF CARBON MONOXIDE POISONING
ARE (a) inability to think coherently, (b) nausea,
(c) vomiting, (d) twitching muscles, (e) throbbing
temples, (f) dizziness, (g) headaches, (h) weakness, and (i) sleepiness. IF EXPERIENCING ANY
OF THESE SYMPTOMS, MOVE INTO FRESH AIR
IMMEDIATELY. IF SYMPTOMS PERSIST, GET
MEDICAL HELP. Shut down the generator and
do not operate it until it has been inspected and
repaired.
•	 Never sleep in the vehicle while the genset is running unless the vehicle has a working carbon
monoxide detector. The exhaust system must be
installed in accordance with the genset installation
manual. Make sure there is ample fresh air when
operating the genset in a confined area.
•	 The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. This exhaust
system must be installed properly, in strict compliance with applicable codes and standards.
Following installation, do nothing that might render the system unsafe or in noncompliance with
such codes and standards. The generator compartment must be completely vapor sealed from
the vehicle interior. There must be no possibility of
exhaust fumes entering the vehicle interior. Never
operate this equipment with a leaking or defective
exhaust system.
•	 Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
is operating.
•	 Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation and is required to expel toxic fumes and fuel
vapors from the generator compartment. Without
sufficient cooling airflow, the engine/generator
quickly overheats, which causes serious damage
to the generator. Do not alter the installation or
permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of
the generator.

Safety Rules
Recreational Vehicle Generator

•	 When working on this equipment, remain alert
at all times. Never work on the equipment when
physically or mentally fatigued.
•	 Inspect the generator regularly, and contact the
nearest Authorized Service Dealer immediately for
parts needing repair or replacement.
•	 Before performing any maintenance on the generator, disconnect its battery cables to prevent
accidental start up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or (–)
first. Reconnect that cable last.
•	 Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.

 Electrical Hazards 
•	 The generator covered by this manual produces
dangerous electrical voltages and can cause fatal
electrical shock. Avoid contact with bare wires, terminals, connections, etc., while the unit is running.
Ensure all appropriate covers, guards and barriers
are in place before operating the generator. If work
must be done around an operating unit, stand on
an insulated, dry surface to reduce shock hazard.
•	 Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
•	 During installation onto the vehicle, have the
generator properly grounded (bonded) either by
solid mounting to the vehicle frame or chassis,
or by means of an approved bonding conductor.
DO NOT disconnect the bonding conductor, if so
equipped. DO NOT reconnect the bonding conductor to any generator part that might be removed or
disassembled during routine maintenance. If the
grounding conductor must be replaced, use only a
flexible conductor that is of No. 8 American Wire
Gauge (AWG) copper wire minimum.
•	 In case of accident caused by electric shock, immediately shut down the source of electrical power.
If this is not possible, attempt to free the victim
from the live conductor. AVOID DIRECT CONTACT
WITH THE VICTIM. Use a nonconducting implement, such as a rope or board, to free the victim
from the live conductor. If the victim is unconscious, apply first aid and get immediate medical
help.
•	 Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving components causing injury.

 Fire Hazards 
•	 For fire safety, the generator must be installed
and maintained properly. Installation always must
comply with applicable codes, standards, laws
and regulations. Adhere strictly to local, state and
national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions
and recommendations. Following proper installation, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regulations.
•	 Keep a fire extinguisher in the vehicle at all times.
Extinguishers rated “ABC” by the National Fire
Protection Association are appropriate for use on
the recreational vehicle generator electrical system. Keep the extinguisher properly charged and
be familiar with its use. If there are any questions
pertaining to fire extinguishers, consult the local fire
department.

 Explosion Hazards 
•	 Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
•	 Gasoline is extremely FLAMMABLE and its vapors
are EXPLOSIVE. Do not permit smoking, open
flame, sparks or any source of heat in the vicinity
while handling gasoline. Comply with all laws governing the storage and handling of gasoline.

	

	



Section 1 – General Information
Recreational Vehicle Generator

1.1 	Generator Identification
Please record the following information from the generator DATA DECAL or information decal.
	

1.	 Model Number______________________ 	

2.	 Serial Number___________________

	

3.	 kW Rating_ _________________________ 	

4.	 Rated Voltage___________________

Model: 004701-0
	
	
	
	
	
	
	
	
	

1.	 Generator Air Intake
2.	 Engine Start/Stop Switch
3.	 Fuse
4.	Optional Remote Panel Receptacle (Side View)
5.	Generator AC Output Leads (Side View)
6.	 Fuel Primer Switch
7.	 Circuit Breaker
8.	 Starter Contactor
9.	 Fuel Inlet

	10.	
	11.	
	12.	
	13.	
	14.	
	15.	
	16.	
	17.	

Battery Hookup
LP Regulator/Solenoid
Oil Filter
Oil Drain Cap
Oil Dipstick
Air Filter (Behind Access Panel)
Oil Fill
Spark Plug

11
9
FUEL
INLET

BATTERY

BATTERY

NEG.

POS.

8 17

10

3 2 6 7

4

CONTROL CENTER
C .B .
3 0 A

FUEL

S T A RT

S T OP

P R IM E

FUS E
15 A

REMOTE

S E R V IC E A C C E S S P A N E L

14/16

AIR FILTER LOCATED BEHIND PANEL.

MAINTENANCE SCHEDULE
OIL LEVEL:

CHECK DAILY

AIR FILTER:

CLEAN PREFILTER
EVERY 100 HOURS.
REPLACE ELEMENT
EVERY 250 HOURS.

OIL & OIL FILTER:

CHANGE EVERY 100
HOURS. (OR ANNUALLY)

SPARK PLUGS:

INSPECT & CLEAN
PLUGS EVERY 100
HOURS. REPLACE PLUGS
EVERY 500 HOURS.
(IF NECESSARY)

FUEL FILTER:

CHANGE EVERY 400
HOURS. (OR ANNUALLY)

*

*
*
*

PERFORM MORE OFTEN IN DUSTY CONDITIONS

REPLACEMENT INFORMATION
PREFILTER P/N:
AIR FILTER P/N:
OIL FILTER P/N:
SPARK PLUG P/N:

0D4511
0D3262
070185
072347

FUEL FILTER P/N:

087769

OIL CAPACITY WITH FILTER:

TEMPERATURE

0.8L/0.84QT

SAE VISCOSITY

32°F AND HIGHER
10°F TO 100°F
0°F TO 80°F
-20°F TO 50°F

30
15W-40
10W-30
5W-30

WHEN SERVICE OR PARTS ARE NEEDED IN
THE USA OR CANADA, CONTACT THE GENERAC
SERVICE LOCATOR AT 1-800-333-1322.

13
	 	

12

1

15

5

Section 1 – General Information
Recreational Vehicle Generator

1.2	GENERATOR APPLICABILITY

These generators have been designed and manufactured for supplying electrical power for recreational
vehicles. Do not modify the generator or use it for
any application other than for what it was designed.
If there are any questions pertaining to its application, write or call the factory. Do not use the unit until
advised by a competent authority.

danger
For fire safety, the generator must have been
 properly
installed in compliance with ANSI

1.4 	Generator ac
connection system

This generator set is equipped with dual stator AC
power windings. These two-stator windings supply electrical power to customer electrical loads by
means of a two-wire connection system. Note, however, that the neutral is bonded to the frame of the
engine-generator.
The generator may have been installed so that it powers 120-volt AC loads (Figure 1.1).

Figure 1.1 – Connections for 120 Volts Only

119.2-1975/NFPA 501C-1974, “Standard for
Recreational Vehicles, Part III – Installation of
Electrical Systems.” The generator also must
have been installed in strict compliance with the
manufacturer’s detailed installation instructions.
After installation, do nothing that might render the unit in noncompliance with such codes,
standards and instructions.
Use this generator to supply electrical power for
operating 120-volt, single-phase, 60 Hertz, AC electrical loads. These loads can require up to 3,400
watts (3.4 kW) of power, but cannot exceed 28.3 AC
amperes of current at 120 volts.



 o not overload the generator. Some installaD
tions may require that electrical loads be alternated to avoid overloading. Applying excessively high electrical loads may damage the generator and may shorten its life. Add up the rated
watts of all electrical lighting, appliance, tool
and motor loads the generator will power at
one time. This total should not be greater than
the wattage capacity of the generator. If an
electrical device nameplate gives only volts and
amps, multiply volts times amps to obtain watts
(volts x amps = watts). Some electric motors
require more watts of power (or amps of current) for starting than for continuous operation.

1.3 	SAFETY

Before attempting to use the generator set, carefully read the “Safety Rules” section of this manual.
Comply strictly with these rules to prevent accidents
and damage to equipment and/or property. We suggest copying and posting the “Safety Rules” in potential hazard areas of the vehicle. Stress safety to all
operators and potential operators of this equipment.

28.3 AMP

1.5 	Specifications
 1.5.1	 Fuel Requirements
These generators are equipped with a liquefied petroleum (LP) gas fuel system. LP gas is usually aupplied
as a liquid in pressure tanks.
These generators require a “vapor withdrawal” type
fuel system. This type of gaseous fuel system uses the
vapors forming above the liquid fuel in the storage
tank. Air temperature around the storage tank must
be high enough to sustain adequate fuel vaporization.
In colder climates, use of an independent heat source
may be needed to be sure the fuel sufficiently vaporizes in the storage tank.
LP gas may consist of propane, butane, or a mixture
of the two gases. Propane vaporizes at tempertures as
low as -20°F (-29°C), but butane returns to its liquid
state when the temperature drops below about 32°F
(0°C). For that reason, a higher ratio of propane is
desired in the gas mixure when temperatures drop
below freezing.

 1.5.2	 Fuel Consumption
	

	

Model	
004701-0	

1/2 Load	
0.55	

Full Load
0.73

Fuel consumption is in gal/hr.
	

	



Section 1 – General Information
Recreational Vehicle Generator

 1.5.3	 engine oil requirements
Use only high quality detergent oil rated with American
Petroleum Institute (API) Service Classification SF,
SG or SH. The recommended oil weights include the
following:
•	 During summer months: SAE 30. An acceptable
substitute is SAE 10W-30.
•	 During winter months: SAE 5W-30. DO NOT USE
SAE 10-W40.
Crankcase and oil filter capacity is approximately
800 mL or .84 U.S. quarts. Do NOT use special additives. See Sections 3.1 and 3.2 (Page 12) for oil level
check and fill procedures.

 1.5.4	Engine
Type of Engine.................................... GN-220, Single-cylinder
Cooling Method.........................................................Air-cooled
Rated Horsepower........................................7.8 @ 4,200 rpm
Displacement................................................................... 220cc
Cylinder Block..........................Aluminum w/Cast Iron Sleeve
Type of Governor..............................Mechanical, Fixed Speed
Air Cleaner.........................Paper Element w/Foam Precleaner
Starter........................................................ 12-volt DC Electric
Ignition System...................... Solid-state w/Flywheel Magneto
Recommended Spark Plug............................Part No. 0E7585
Spark Plug Gap..........................................0.030 inch (76 mm)
Recommended Minimum Battery...............400 Cold-cranking
Amperes

 1.5.5	Generator
Rated Maximum Continuous
AC Output (Gasoline)............................3,400 Watts (3.4 kW)
Rated Voltage........................................................ 120 Volts AC
Rated Maximum Continuous
AC Current (Gasoline)..................................... 28.3 Amperes
Phase............................................................................... Single
Rotor RPM........................................................................3,600
Number of Rotor Poles...........................................................2
Engine RPM......................................................................3,600
Rated AC Frequency........................................................ 60 Hz
Battery Charge Voltage...........................................14 Volts DC
Battery Charge Current................................. 2 Amperes (max)
Gasoline weight......................................................170 Pounds
Length.....................................................749.8 mm (29.52 in.)
Width......................................................483.1 mm (19.02 in.)
Height.....................................................342.2 mm (13.47 in.)

 1.5.6	 emissions compliance period
For non-handheld engines the Emissions Compliance
Period referred to on the Emissions Compliance
Label indicates the number of operating hours for
which the engine has been shown to meet Federal
emission requirements.
	 	

•	 For engines less than 225 cc displacement, Category
C=125 hours, B=250 hours, and A=500 hours.
•	 For engines of 225 cc or more, Category C=250
hours, B=500 hours, and A=1000 hours.

2.1 	 generator control panel

The following features are mounted on the generator
control panel (Figure 2.1):

Figure 2.1 – Generator Control Panel

CONTROL CENTER
S T A R T

F U E L

S T O P

P R IM E

C .B .
3 0 A

FUS E
7. 5 A

 2.1.1	 start/stop switch
To crank and start the engine, hold this switch in the
START position. Release the switch when the engine
starts. To stop an operating engine, press and hold
the switch in the STOP position until the engine shuts
off. The switch center position is the RUN position.

 2.1.2	fuse
The fuse protects the engine’s DC control circuit
against electrical overload. If the fuse element has
melted open due to overloading, the engine cannot
be cranked. If the fuse must be replaced, use only an
identical replacement.

 2.1.3	main breaker
The main breaker protects the generator’s AC output circuit against overload and provides a method
of turning OFF the generator’s 120-volt AC output
to the vehicle circuits. The generator has a 30-amp
breaker.

Section 2 – Operation
Recreational Vehicle Generator

2.2 	optional remote
start/stop panel

A remote mounted Start/Stop Panel is available that
permits starting and stopping the generator engine
conveniently from inside the vehicle.
Contact an Authorized Service Dealer to order, a
remote panel that includes a Start/Stop switch, a
generator run lamp, a fuel prime switch, and an
hourmeter. The hourmeter provides a continuous
indication of engine/generator operating time. Use
the hourmeter for checking off periodic maintenance
requirements on the unit.

2.3	Before starting the engine
NOTE:

Instructions and information in this manual
assume the generator has been properly installed,
connected, serviced, tested and adjusted by a
qualified installation technician or installation
contractor.

 2.3.1	 Installation
Generator installation must have been properly completed so it complies with all applicable codes, standards and regulations and with the manufacturer's
recommendations.

 2.3.2	 engine lubrication
Have the engine crankcase properly serviced with the
recommended oil before starting. Refer to Section
1.5.4 and Sections 3.1 and 3.2 for oil servicing procedures and recommendations.

attempt to crank or start the engine before
 itAny
has been properly serviced with the recommended oil may result in an engine failure.

 2.3.3	 Fuel Supply
The engine must have an adequate supply of proper
fuel to operate. Before starting it, check that sufficient fuel is available.

 2.3.4	Cooling and Ventilating Air
Air inlet and outlet openings in the generator compartment must be open and unobstructed for continued proper operation. Without sufficient cooling
and ventilating airflow, the engine/generator quickly
overheats, which causes it to shut down and may
damage the generator.

 2.3.5	 engine exhaust gas
Before starting the generator engine, be sure there is
no way for exhaust gases to enter the vehicle interior
and endanger people or animals. Close windows,
doors and other openings in the vehicle that, if open,
might permit exhaust gases to enter the vehicle.

danger
The generator engine releases DEADLY carbon
 monoxide
gas through its exhaust system. This

dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even
death. Never operate the generator set with
the vehicle inside any garage or other enclosed
area. DO NOT OPERATE THE GENERATOR IF THE
EXHAUST SYSTEM IS LEAKING OR HAS BEEN
DAMAGED. SYMPTOMS OF CARBON MONOXIDE
POISONING ARE (a) inability to think coherently, (b) nausea, (c) vomiting, (d) twitching
muscles, (e) throbbing temples, (f) dizziness,
(g) headaches, (h) weakness, and (i) sleepiness.
IF EXPERIENCING ANY OF THESE SYMPTOMS,
MOVE INTO FRESH AIR IMMEDIATELY. IF
SYMPTOMS PERSIST, GET MEDICAL HELP. Shut
down the generator and do not operate it until
it has been inspected and repaired.

danger
Never sleep in the vehicle while the genset is
 running
unless the vehicle has a working carbon
monoxide detector. The exhaust system must be
installed in accordance with the genset installation manual. Make sure there is ample fresh air
throughout the RV when operating the genset
at all times.

2.4 	 starting the generator
NOTE:

Read the vehicle manufacturer’s instructions.
The owner/operator should become familiar with
the vehicle in which this generator is installed.
Differences exist between vehicles. For example,
some vehicles may use a transfer switch to isolate
dockside power from the generator, while other
vehicles may use an isolating receptacle. Some
vehicles may be equipped with a DC converter,
which allows the generator to power certain DC
lighting and other DC loads.
To start the generator from either the generator control panel or from the optional remote panel, proceed
as follows:
1.	 Turn OFF electrical loads using the means provided in the vehicle (such as a main line circuit
breaker or transfer switch).
	

	



Section 2 – Operation
Recreational Vehicle Generator

NOTE:
If starting from the generator control panel, turn
OFF loads by setting the generator’s main circuit
breaker to the OFF (or open) position. If starting
from a remote panel, turn OFF loads using the
means provided in the vehicle (such as a main
circuit breaker). Electrical load circuits will be
turned ON after the generator has started, stabilized and warmed up.
2.	 If the engine has not been started in more than
two weeks, press the Fuel Pump Primer switch
and hold it for about 10 to 15 seconds to prime
the fuel system. However, if the engine is warm,
skip Step 2.
3.	 Hold the engine Start/Stop switch in the START
position to crank the engine. Release the switch
when the engine starts.



If the engine does not start after it has been
cranking for 15 seconds, release the Start/Stop
switch, wait one minute and try again. Holding
the switch for longer than 15 seconds can damage the starter motor.
4.	 Let the engine run at no-load for a few minutes to
stabilize and warm up.
5.	 Turn ON electrical loads using the means
provided (such as a main circuit breaker or
transfer switch).

2.5 	 stopping the generator

1.	 Turn OFF all electrical loads using the means
provided (such as a main circuit breaker or
transfer switch).
2.	 Let generator run at no-load for a few minutes, to
stabilize internal engine generator temperatures.
3.	 Place the Start/Stop switch in its STOP position.

2.6 	APPLYING LOADS TO GENERATOR

When applying electrical loads to the generator,
observe these guidelines:
•	 Before applying electrical loads, let the generator
stabilize and warm up for a minute or two.
•	 DO NOT overload the generator.

 2.6.1	 letting the engine stabilize
The generator supplies correct rated voltage only at
the proper governed speed. Some electrical appliances may be extremely sensitive to voltage. Incorrect
voltages can damage such appliances.

	 	

If electrical loads are applied at reduced operating
speeds, such loads imposed on the engine when sufficient power is not available may shorten engine life.
Never turn ON electrical loads until after the generator engine has started and stabilized at no-load.

2.7	do not overload the
generator

Read the rated wattage/amperage capacity of the generator on the generator data label (see Section 1.1).
Applying electrical loads in excess of the unit’s rated
capacity will cause the engine/generator to automatically shut down.
To avoid overloading, add up the wattage of all connected electrical lighting, appliance, tool and motor
loads. This total should not be greater than the
generator’s rated wattage capacity.
•	 Most lighting, appliance, tool and motor loads
indicate their required watts on their nameplate or
data plate. For light bulbs, simply note the wattage
rating of the bulb.
•	 If a load does not show its rated wattage, multiply
that load’s rated VOLTS times AMPS to obtain
WATTS.
•	 Induction type motors (such as those that run the
vehicle’s furnace fan, refrigerator, air conditioner,
etc.) need about 2-1/2 time more watts of power for
starting than for running (for a few seconds during
motor starting). Be sure to allow for this when connecting electrical loads to the generator. First, figure the watts needed to start electric motors in the
system. To that figure, add the running wattages of
other items that will be operated by the generator.
•	 Do not apply heavy electrical loads for the first two
or three hours of operation.

2.8 	Protection Systems
 2.8.1	Low Oil Pressure Switch
This switch (Figure 2.2) has normally closed (N.C.)
contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop
below a preset level, switch contacts close, and the
engine automatically shuts down. The unit should not
be restarted until oil is added.

 2.8.2	High Temperature Switch
This switch (Figure 2.2), which has normally open
(N.O.) contacts, is mounted near the oil filter. The
contacts close if the temperature should exceed
approximately 284º F (140º C), initiating an engine
shutdown.

Section 2 – Operation
Recreational Vehicle Generator

Figure 2.2 – Low Oil Pressure and
High Temperature Switches

Figure 2.4 – Solid State Voltage Regulator

High Temperature Switch
Low Oil Pressure
Switch

The voltage regulator also incorporates a “voltage
surge protection circuit.” This circuit prevents troublesome surges in the generator AC output voltage.
Voltage surge is a common cause of damage to electronic equipment.

 2.8.3	field boost
The Controller Circuit Board houses a field boost
diode and resistor that are not part of the automatic
choke circuit. These two components are part of
a “field boost” circuit (Figure 2.3). During engine
cranking only, a positive DC (battery) voltage is
delivered through the diode, resistor, brushes and
slip rings, to the generator rotor. Application of this
voltage to the rotor “flashes the field” whenever it is
started. Flashing of the field each time the generator
starts makes sure that a sufficiently strong magnetic
field is available to produce “pickup” voltage in the
stator windings.

Figure 2.3 – Field Boost Circuit

2.9 	Additional Information
 2.9.1	 25-HOUR BREAK-IN PERIOD
The first 25 hours of operation is the break-in period
for the generator. Properly breaking in the generator is essential to minimize fuel consumption and
provide maximum engine performance. During this
25-hour break-in period, follow this procedure:
•	 Run the unit at varying electrical loads to help seat
the engine piston rings properly.
•	 Check the engine oil level frequently. Add oil if
needed. It is normal for the generator engine to
consume more oil than is normal until the piston
rings have properly seated.
•	 For the 75-hour operation following the break-in
period, avoid light electrical loads. Load the generator at 50 percent (or more) of its rated wattage capacity. Repeated light loads during these 75
hours can cause improper seating of engine piston
rings, resulting in blowby and high oil consumption.
•	 After operating the unit for 25 hours, complete the
tasks recommended under Section 2.10.2.

 2.9.2	 25-HOUR CHECK-UP
 2.8.4	 overvoltage protection
A solid-state voltage regulator (Figure 2.4) controls
the generator’s AC output voltage. This regulator supplies an excitation current to the rotor. By regulating
the rotor’s excitation current, the strength of its magnetic field is regulated and, in turn, the voltage delivered to connected electrical loads is controlled. When
the AC frequency is 60 Hertz, voltage is regulated at
120 volts (voltage-to-frequency ratio is 2-to-1).

After the 25-hour break-in period, contact an
Authorized Service Dealer for the following maintenance. The vehicle owner is responsible for any
charges:
•	 Change the engine crankcase oil and oil filter.
•	 Check the oil level.
•	 Inspect the cooling and ventilation openings.
•	 Check the engine carburetor adjustments.
•	 Check the engine ignition system.
•	 Inspect the entire electrical system.
•	 Inspect the engine exhaust system.
	

	



Section 3 – Maintenance
Recreational Vehicle Generator

 2.9.3	attention required after
submersion
If the recreational vehicle generator has been submerged in water, it must not be started and operated. Following any submersion in water, have an
Authorized Service Dealer thoroughly clean and dry
the generator.

 2.9.4	OPERATion in high grass orbrush
Never operate the generator while the vehicle is
parked over high grass, weeds, brush, leaves or any
other combustible substance. Such materials can
ignite and burn from the heat of the exhaust system.
The generator exhaust system becomes extremely
hot during operation and remains hot for a long time
after it has shut down.

3.1	CHECKING the ENGINE OIL
LEVEL

For oil capacities and requirements, see “Engine
Oil Requirements,” Section 1.5.4. Check the engine
crankcase oil level at least every eight hours of operation, or before using it. To check the engine oil level,
proceed as follows (see Figure 3.1):
1.	 Be sure the generator is as level as possible.
2.	 Remove the dipstick and wipe it dry with a clean,
lint-free cloth.
3.	 Install and tighten the dipstick cap; then, remove
it again. The oil level should be at the dipstick
“Full” mark.
4.	 If necessary, remove the oil fill cap on the rocker
cover and slowly add oil until it reaches the dipstick “Full” mark. DO NOT FILL ABOVE THE
“FULL” MARK.

 2.9.5	 effects of moisture and dirt
Keep the generator set as clean and dry as possible.
Protect the unit against excessive dust, dirt, corrosive vapors, road splash, etc. Permitting dirt and
moisture to accumulate on generator windings will
have an adverse effect on the insulation resistance of
those windings.
When moisture is allowed to remain in contact with
windings, some of the moisture will be retained in
voids and cracks in the insulation. This causes a
reduced insulation resistance and will eventually
cause problems. Dirt will make the problem worse,
since dirt tends to hold moisture in contact with
windings. Salt (as from sea air) also will worsen the
problem since it tends to absorb moisture from the
air. Salt and moisture, when combined, form a good
electrical conductor.

Never operate the engine with the oil level
 below
the “Add” mark on the dipstick. Doing

this could damage the engine.
5.	 Install and tighten the oil fill cap and the dipstick
before operating the engine.

3.2 	CHANGing the ENGINE OIL
and/or Oil Filter

•	 Change the engine oil after the first 25 hours
of operation (after the 25-hour break-in period, see Section 2.10.1). Thereafter, change the
oil every 100 operating hours. Change the oil more
frequently if operating consistently under heavy
load or at high ambient temperatures.

Figure 3.1 – Oil Maintenance Features
CONTROL CENTER
C .B .
3 0 A

F U E L

S T A R T

S T O P

P R IM E

FUS E
7.5 A

S E R V IC E

A C C E S S

P A N E L

AIR FILTER LOCATED BEHIND PANEL.

MAINTENANCE SCHEDULE
OIL LEVEL:

CHECK DAILY

AIR FILTER:

CLEAN PREFILTER
EVERY 100 HOURS. *
REPLACE ELEMENT
EVERY 250 HOURS. *

OIL & OIL FILTER:

CHANGE EVERY 100
HOURS. (OR ANNUALLY) *
*

GENERAC
											POWERED
OHVI

GEN
ER A
C

To Re

I

INSPECT & CLEAN
PLUGS EVERY 100
HOURS. REPLACE PLUGS
EVERY 500 HOURS.
(IF NECESSARY)

FUEL FILTER:

CHANGE EVERY 400
HOURS. (OR ANNUALLY)

REPLACEMENT INFORMATION
PREFILTER P/N:
AIR FILTER P/N:
OIL FILTER P/N:
SPARK PLUG P/N:

ve
mo

, W
ter
P owe
ew a
r S y s t e m s , I n c . - W h it

PERFORM MORE OFTEN IN DUSTY CONDITIONS

SPARK PLUGS:

FUEL FILTER P/N:
OIL CAPACITY WITH FILTER:

TEMPERATURE
32˚F AND HIGHER
10˚F TO 100˚F
0˚F TO 80˚F
-20˚F TO 50˚F

GENERAC	OHVI	INDUSTRIAL	ENGINE

QUIETPACT	0G
TM

RV	SERVICE	LOCATOR:

Oil Dipstick/Oil Fill
	 10	

WHEN SERVICE OR PARTS ARE NEEDED IN
THE USA OR CANADA, CONTACT THE GENERAC
SERVICE LOCATOR AT 1-800-333-1322.

.00..

Oil Drain

Oil Filter

0D4511
0D3262
070185
072347
0D7515
0.8L/0.84QT

SAE VISCOSITY
30
15W-40
10W-30
5W-30

Section 3 – Maintenance
Recreational Vehicle Generator

•	 Change the engine oil filter after the first 25 hours
of operation, and every 100 operating hours thereafter.
To change the oil and/or oil filter, proceed as
follows (see Figure 3.1):
1.	 Run the engine until it is thoroughly warmed up
(at least five minutes) then shut OFF the engine.
2.	 Immediately after the engine shuts OFF, pull the
oil drain cover free of the base. Remove the plug
from the tube with a 5/16” allen wrench and drain
the oil into a suitable container. Loosening the oil
fill cap will allow the crankcase to drain faster.
3.	 After the oil has drained, replace the plug onto
the end of the oil drain tube. Retain the cover in
the base.
4.	 With the oil drained, remove the old oil filter by
turning it counterclockwise. Place a towel underneath to catch excess oil.
5.	 Apply a light coating of clean engine oil to the gasket of the new filter. Fill the filter until saturated
with clean oil.
6.	 Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tighten
the filter an additional 3/4 to one turn.
7.	 Remove the dipstick and wipe it dry with a clean,
lint-free cloth. This will be used later to check the
oil level.
8.	 Remove the oil fill cap on the oil fill tube and
slowly add the proper type and amount of recommended oil (see Section 1.5.4). Periodically use
the dipstick to check the oil level and continue to
fill the crankcase until the oil reaches the dipstick
“Full” mark. DO NOT FILL ABOVE THE “FULL”
MARK.
9.	 Install and tighten the oil fill cap and the dipstick
before operating the engine.
10.	Start the engine and check for leaks.
NOTE:
Check the oil level and fill to the “FULL” mark
after checking for leaks. The filter will retain some
oil.

3.3 	Maintaining The ENGINE
AIR CLEANER
 3.3.1	 cleaning the Foam Precleaner
Clean and re-oil the foam precleaner every three
months or every 25 hours of operation, whichever
occurs first. Service the foam precleaner more frequently if operating the generator in extremely dusty
or dirty conditions. Use the following procedure
(Figure 3.2):

3.	 Remove the foam precleaner from the cover.
4.	 Wash the foam precleaner in liquid detergent and
water.
5.	 Wrap the foam precleaner in a clean cloth and
gently squeeze it dry.
6.	 Saturate the foam precleaner in clean engine
oil. Gently squeeze it in a clean cloth to remove
excess oil and to distribute oil (DO NOT TWIST).
7.	 Install the foam precleaner into the cover, followed by the paper filter.
8.	 Install the cover, foam precleaner and paper filter.
9.	 Tighten the two screws to retain the filter in place.

Figure 3.2 – Engine Air Cleaner

 3.3.2	cleaning or replacing the paper
filter
Once each year or every 100 hours of operation
(whichever comes first), clean or replace the paper
filter. The new replacement filter must be flame
retardant. Service the paper filter more frequently if
operating the generator in extremely dusty or dirty
conditions. Use the following procedure (Figure 3.2):
1.	 Follow steps 1-3 in Section 3.3.1; service the
foam precleaner if necessary.
2.	 Remove the paper filter.
3.	 Clean the air filter by tapping it gently on a solid
surface. If the filter is too dirty, replace it with a
new one. Dispose of the old filter properly.
4.	 Clean the air cleaner cover then reassemble
following steps 7-9 in Section 3.3.1.

3.4 	Clean air intake

Clean all foreign material from the air intake (Figure
3.3) at least once every 100 hours of operation. Clean
more often if necessary.
Inspect the area around the generator exhaust muffler periodically and remove all grass, leaves, dirt,
etc., from this area.

1.	 Turn the two screws counterclockwise to loosen.
2.	 Remove the cover, foam precleaner and paper filter.
	

	 11

Section 3 – Maintenance
Recreational Vehicle Generator

Figure 3.3 – Cleaning Air Intake

3.6 	 clean spark arrestor

The engine exhaust muffler has a spark arrestor
screen. Inspect and clean the screen every 50 hours
of operation or once each year, whichever comes first
(Figure 3.5).
NOTE:
If using the generator on any forest-covered,
brush-covered or grass-covered unimproved land,
it must equipped with a spark arrestor. The spark
arrestor must be maintained in good condition by
the owner/operator.
Clean and inspect the spark arrestor as follows:
USTC

3.5 	Checking the Engine Spark
Plug

Clean the spark plug and reset the spark plug gap
every 100 hours of operation.
1.	 Clean the area around the base of the spark plug
to keep dirt and debris out of the engine. Remove
the spark plug and check the condition. Replace
the spark plug if worn or if reuse is questionable.
2.	 Clean spark plug by scraping or washing using a
wire brush and commercial solvent. Do not blast
the spark plug to clean.
3.	 Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.030 inch (0.76 mm)
by carefully bending the ground electrode
(Figure 3.4).

Figure 3.4 – Setting the Spark Plug Gap

•	Remove the screen retaining bracket by removing
the screw.
•	Slide the spark arrestor screen out from the tail
pipe.
•	Inspect screen and replace if torn, perforated or
otherwise damaged. DO NOT USE a defective
screen. If screen is not damaged, clean it with commercial solvent.
•	 Replace the screen and the retaining bracket.

Figure 3.5 - Spark Arrestor

TAILPIPE
P/N 0E0683

SPARK ARRRESTOR
SCREEN P/N 089680
RETAINING
SCREW P/N 056892

3.7	CLEANING THE GENERATOR

Keep the generator set as clean and dry as possible.
Protect the unit against excessive dust, dirt, corrosive
vapors, road splash, etc. Permitting dirt and moisture to accumulate on generator windings will have
an adverse effect on the insulation resistance of those
windings.


	 12	

Sparking can occur if the wire terminal does
not fit firmly on the spark plug terminal end. If
necessary, re-form the wire terminal to obtain
a tight fit.

When moisture is allowed to remain in contact with
windings, some of the moisture will be retained in
voids and cracks in the insulation. This causes a
reduced insulation resistance and will eventually
cause problems. Dirt will make the problem worse,
since dirt tends to hold moisture in contact with
windings. Salt (as from sea air) also will worsen the
problem since it tends to absorb moisture from the
air. Salt and moisture, when combined, form a good
electrical conductor which can be damaging to the
generator windings.

Section 3 – Maintenance
Recreational Vehicle Generator

Do NOT use a forceful spray of water to clean
 the
generator. Water will enter the generator

interior and cause problems, and may also contaminate the generator fuel system.

3.8 	Battery Maintenance

All lead-acid batteries will discharge when not in
use. The generator battery should be inspected as
follows:

 3.8.1	Weekly
•	 Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
•	 Check the battery fluid level of unsealed batteries
and, if necessary, fill with Distilled Water Only. Do
not use tap water in batteries.

• Disconnect any charging source prior to connecting
or disconnecting battery terminals; and
• Do not use any jumper cables or booster battery to
crank and start the generator engine. If any battery
has discharged, remove it for recharging.

Do not open or mutilate the battery. Released
 electrolyte
has been known to be harmful to
the skin and eyes, and to be toxic.

The electrolyte is a dilute sulfuric acid that is
 harmful
to the skin and eyes. It is electrically
•
•
•

 3.8.2	Every Six Months
•	 Have the state of charge and condition checked.
This should be done with an automotive-type battery hydrometer.
Note:
Servicing of the battery is to be performed or
supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
Damage will result if the battery connections are
made in reverse.

danger
Do not dispose of the battery in a fire. The
 battery
is capable of exploding. Storage bat-

teries give off explosive hydrogen gas. This gas
can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery
and cause blindness or other injury. Any area
that houses a storage battery must be properly
ventilated. Do not allow smoking, open flame,
sparks, or any spark producing tools or equipment near the battery. Discharge static electricity from body before touching the battery by
first touching a grounded metal surface.

A battery presents a risk of electrical shock
 and
high short circuit current. The following
•
•
•
•

precautions are to be observed when working
on batteries:
Remove watches, rings or other metal objects;
Use tools with insulated handles;
Wear rubber gloves and boots;
Do not lay tools or metal parts on top of the
battery;

•

conductive and corrosive. The following
procedures are to be observed:
Wear full eye protection and protective clothing;
Where electrolyte contacts the skin, wash it off
immediately with water;
Where electrolyte contacts the eyes, flush
thoroughly and immediately with water and seek
medical attention; and
Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.

3.9 	 Major Service Manual

To obtain a service manual for the generator, contact
the nearest Authorized Service Dealer or. Make sure
to identify the MODEL NUMBER and SERIES.

3.10 	Exercising the Generator

The manufacturer recommends that the generator be
started and operated at least once every seven days.
Let the unit run for at least 30 minutes to “exercise”
the engine.

3.11 	Out of Service Procedure
 3.11.1	Removal From Service
If the generator cannot be exercised every seven days,
and it is to be out of service longer than 30 days, prepare the generator for storage as follows:
1.	 Start the engine and let it warm up.
2.	 Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
NOTE:
Using a fuel additive such as STA-BIL fuel stabilizer, or an equivalent, will prevent gum deposits
from forming in the engine’s fuel system.
	

	 13

Section 3 – Maintenance
Recreational Vehicle Generator

3.	 While the engine is still warm from running, drain
the oil completely. Refill the crankcase with SAE
10W-30 oil having API classification “For Service
SF.”
4.	 Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
5.	 Remove the spark plug and pour two or three
tablespoons of clean, fresh engine oil into the
spark plug threaded openings. Reinstall and
tighten the spark plug.
6.	 Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery
on any concrete or earthen floor.
7.	 Clean and wipe the entire generator.

Figure 3.6 — Adjusting Valve Clearance

 3.11.2	Return To Service
To return the unit to service after storage, proceed
as follows:
1.	 Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommended oil is used in the engine (see Section 1.5.4,
Page 6). If necessary, drain and refill with the
proper oil.
2.	 Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with distilled water. DO NOT USE TAP WATER IN THE
BATTERY. Recharge the battery to 100 percent
state of charge, or, if defective, replace the battery.
3.	 Clean and wipe the entire generator.
4.	 Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected
incorrectly.
5.	 Turn OFF all electrical loads. Add fuel if necessary and then start the engine.
6.	 Allow the unit to run for several minutes to warm
up.
7.	 Apply electrical loads to at least 50 percent of the
unit’s rated wattage capacity.
8.	 When the engine is thoroughly warmed up, shut
it down.
9.	 The generator is now ready for service.

3.12	ADJUSTING VALVE CLEARANCE

After the first 50 hours of operation, adjust the valve
clearance in the engine.
When adjusting valve clearance, the engine should be
at room temperature and the piston should be at Top
Dead Center (TDC) of its compression stroke (both
valves closed). Correct clearance is 0.001-0.003 inch
(0.03-0.07mm). Adjust valve clearance as follows:
1.	 Loosen the rocker arm jam nut. Use an allen
wrench to turn the pivot ball stud while checking
clearance between the rocker arm and the valve
stem with a feeler gauge (Figure 3.6).
	 14	

2.	 When valve clearance is correct, hold the pivot
ball stud with the allen wrench and tighten the
rocker arm jam nut with a crows foot. Tighten
the jam nut to 65-85 inch-pounds torque. After
tightening the jam nut, recheck valve clearance to
make sure it did not change (Figure 3.7).

Figure 3.7 — Tightening Jam Nut

3.13	rv generator service
interval

50 Hours................................. Clean Spark Arrestor
100 Hours............................Change Engine Oil/filter
100 Hours................................... Clean Air Pre-filter
100 Hours................................. Inspect Spark Plugs
250 Hours............. Replace Paper Air Filter Element
500 Hours.................................Replace Spark Plugs
1st 50 Hours-then
every 500 Hrs............................ Adjust Valve Lash

Part II –
Installation
Instructions

danger

Only qualified electricians or contractors

Safety Rules
Recreational Vehicle Generator

DANGER: For fire safety, installation of a generator into a recreational vehicle must comply
strictly with article 551, NFPA 70; ANSI C1-1975; AND, ANSI A119.2-1975/NFPA 501C “Standard
for Recreational Vehicles” (Part 3, “Installation of Electrical Systems”). In addition, installation
must comply with the manufacturer’s instructions and recommendations.



Notice to Installer

These Installation Instructions have been published
by the manufacturer to aid in the installation of the
products described in this manual. The manufacturer assumes that installation personnel are familiar
with the procedures for installing such products, or
similar products. The manufacturer also assumes
that personnel have been trained in the recommended installation procedures for these products and
that such training includes (a) use of common hand
tools, (b) use of special tools, and (c) use of any tools
and/or equipment from other suppliers.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed
to the unit, are, therefore, not all inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique utilized does not render the generator unsafe.
Information, illustrations, specifications, etc., contained in these Installation Instructions are based on
the latest information available at the time of publication. Every effort has been expended to be sure that
such data is both accurate and current. However, the
manufacturer reserves the right to change, alter or
otherwise improve this product at any time without
prior notice.

danger
Despite the safe design of this generator,
 operating
this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to operate or maintain this
equipment.

Potentially lethal voltages are generated by
 these
machines. Ensure all steps are taken to

render the machine safe before attempting to
work on the generator.

Parts of the generator are rotating and/or hot
 during
operation. Exercise care near running
generators.

	 16	



 General Hazards 
•	 For safety reasons, the manufacturer recommends
that the installation, initial start-up and maintenance of this equipment is carried out by an
Authorized Service Dealer.
•	 The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. This exhaust
system must be installed properly, in strict compliance with applicable codes and standards.
Following installation, do nothing that might render the system unsafe or in noncompliance with
such codes and standards. The generator compartment must be completely vapor sealed from
the vehicle interior. There must be no possibility of
exhaust fumes entering the vehicle interior. Never
operate this equipment with a leaking or defective
exhaust system.
•	 Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
is operating.
•	 Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation and is required to expel toxic fumes and fuel
vapors from the generator compartment. Without
sufficient cooling airflow, the engine/generator
quickly overheats, which causes serious damage
to the generator. Do not alter the installation or
permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of
the generator.
•	 When working on this equipment, remain alert
at all times. Never work on the equipment when
physically or mentally fatigued.
•	 Before performing any maintenance on the generator, disconnect its battery cables to prevent
accidental start up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or (–)
first. Reconnect that cable last.
•	 Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
•	 Never insert any tool or other object through openings in the generator interior, even if the unit is not
running. Serious injury or damage to the equipment may occur.

Safety Rules
Recreational Vehicle Generator

 Electrical Hazards 

 Fire Hazards 

•	 The generator covered by this manual produces
dangerous electrical voltages and can cause fatal
electrical shock. Avoid contact with bare wires, terminals, connections, etc., while the unit is running.
Ensure all appropriate covers, guards and barriers
are in place before operating the generator. If work
must be done around an operating unit, stand on
an insulated, dry surface to reduce shock hazard.
•	 Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
•	 During installation onto the vehicle, properly
ground (bond) the generator either by solid mounting to the vehicle frame or chassis, or by means of
an approved bonding conductor. DO NOT connect
the bonding conductor to any generator part that
might be removed or disassembled during routine
maintenance. If the grounding conductor must be
replaced, use only a flexible conductor that is of
No. 8 American Wire Gauge (AWG) copper wire
minimum.
•	 If the vehicle electrical circuits can be powered by
any other source of electricity (such as a “dockside”
power receptacle), there must be no possibility of
connecting the different power sources to the vehicle circuits at the same time. The dockside (utility)
power source must be positively isolated from the
vehicle circuits whenever the generator is operating. Failure to isolate the vehicle circuits from
the dockside power supply when the generator is
running may result in damage to the generator or
serious injury or death to dockside (utility) power
workers due to backfeed of electrical energy.
•	 In case of accident caused by electric shock, immediately shut down the source of electrical power.
If this is not possible, attempt to free the victim
from the live conductor. AVOID DIRECT CONTACT
WITH THE VICTIM. Use a nonconducting implement, such as a rope or board, to free the victim
from the live conductor. If the victim is unconscious, apply first aid and get immediate medical
help.
•	 Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving components causing injury.

•	 For fire safety, the generator must be installed
and maintained properly. Installation always must
comply with applicable codes, standards, laws
and regulations. Adhere strictly to local, state and
national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions
and recommendations. Following proper installation, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regulations.
•	 Keep a fire extinguisher in the vehicle at all times.
Extinguishers rated “ABC” by the National Fire
Protection Association are appropriate for use on
the recreational vehicle generator electrical system.
Keep the extinguisher properly charged and be
familiar with its use. If there are any question pertaining to fire extinguishers, consult the local fire
department.

 Explosion Hazards 
•	 Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
•	 Gasoline is extremely FLAMMABLE and its vapors
are EXPLOSIVE. Do not permit smoking, open
flame, sparks or any source of heat in the vicinity
while handling gasoline. Comply with all laws governing the storage and handling of gasoline.
•	 Fuel lines must be properly installed and
fastened, and free of leaks. There must be
no possibility of gasoline vapors entering the
vehicle interior.
•	 You are required to install an approved, flexible,
nonconductive fuel line between the generator fuel
connection point and rigid fuel lines.

	

	 17

Section 1 – General Information
Recreational Vehicle Generator

1.1 	PURPOSE AND SCOPE
OF the MANUAL

These Installation Instructions have been prepared
especially for the purpose of familiarizing installers
and owners of the applicable equipment with the
product's installation requirements. Give serious
consideration to all information and instructions in
the manual, both for safety and for continued reliable
operation of the equipment.
Because of the different recreational vehicle models and the variations between the models, it would
be extremely difficult, if not impractical, to provide
detailed instructions for every possible installation.
For that reason, instructions and illustrations in this
manual are general in nature. Illustrations are not
intended to serve as detailed installation blueprints.
The installation should comply strictly with all applicable codes, standards and regulations pertaining
to the installation and use of this product. If any
portion of this manual appears to be in conflict with
such codes, standards or regulations, the applicable
codes, standards or regulations must take precedence over the manual.

1.2 	SAFETY

Before handling, installing, operating or servicing this
equipment, carefully read the “Notice to Installer”
and “Safety Rules” on Pages 18 and 19. Comply with
all safety rules to prevent death, personal injury or
damage to equipment and/or property. Stress safety
to all installers, operators and service technicians
who work on this equipment.

6.	 CSA Electrical Bulletin 946, available from the
Canadian Standards Association, Housing and
Constructions Materials Section, 178 Rexdale
Boulevard, Rexdale, Ontario, Canada, M9W 1R3.

1.4 	EQUIPMENT DESCRIPTION

Instructions and information in this section pertain
to air-cooled generators. This generator is designed
specifically for installing in recreational vehicles. This
generator operates 120-volts, single-phase, 60-Hertz,
AC electrical loads that require 28.3 amps.

1.5 	GENERATOR ENGINE
OPERATING SPEED

The generator’s revolving field (rotor) is driven by a
single-cylinder, four-cycle engine. The generator supplies 120 volts AC at 60 Hertz when the rotor is operating at 3,600 rpm.

1.6 	GENERATOR AC
CONNECTION SYSTEM

The generator is equipped with dual stator power
windings as shown in Figure 1.1.

Figure 1.1 – 120-volt Single Voltage Connection

28.3 AMP

1.3 	STANDARDS BOOKLETS

Installation, use and servicing of this equipment
should comply strictly with published standards, as
well as the manufacturer's recommendations. The
following standards booklets (latest revision) are
available from the sources indicated:
1.	 NFPA Standard 501C, “Standard for Recreational
Vehicles,” available from the National Fire
Protection Association, Batterymarch Park,
Quincy, MA 02269.
2.	 NFPA 70, “NFPA Handbook of the National
Electric Code,” available same as Item 1.
3.	 ANSI C1-1975 and ANSI 119.2-1975, available
from the American National Standards Institute,
1430 Broadway, New York, NY 10018.
4.	 ANSI A119.2/NFPA 501C, available from the
Recreational Vehicle Association, 1896 Preston
White Drive, Reston, VA 22090.
5.	 California Administrative Code, Title 25, available from the State of California, Documents
Section, P.O. Box 1015, North Highlands,
CA 95660.
	 18	

•	 The AC connection system on all air-cooled generators uses a GROUNDED neutral.
•	 A separate green ground wire is connected to the
recreational vehicle’s junction box.
NOTE:
Do NOT connect loads in excess of circuit
breaker ratings.

55.5
[2 3/16"]

37 6. 5
[14 13/16"]

429.5
[16 15/16"]

476.4
[18 3/4"]

342.2
[13 1/2"]

29
[1 1/8"]

48.1
[1 7/8"]

TAIL PIPE
EXIT

416
[16 3/8"]

HOT AIR
EXHAUST

TYP.
6.7
[1/4"]

50.8
[2"]

222.7
[8 3/4"]

210
[8 1/4"]

369.7
[14 9/16"]

34 3.4
[13 1/2"]

300.7
[11 13/16"]

101
[4"]

82.5
[3 1/4"]

423.2
[16 11/16"]

	

736.4
[29"]

OIL DRAIN

36.5
[1 7/16
7/16"]

83.5
[3 5/16"]
176.6
[6 15/16"]

170
[6 11/16"]

FRONT DOOR ACCESS FOR
ALL REQUIRED MAINTENANCE

778.9
[30 11/16"]
REF.

688.3
[27 1/8"]

79
[3 1/8"]

AIR
INTAKE

60
[2 3/8"]

717.7
[28 1/4"]

VIEW FROM TOP

118
[4 5/8"]

63.5
[2 1/2"]

223.5
[8 13/16"]

360.5
[14 3/16"]

414.5
[16 5/16"]

5/16"-18 WELDNUTS
(6 PLACES)

211.3
[8 5/16"]

500.2
[19 11/16"]
REF.

39.6
[1 9/16"]

34.3
[1 3/8"]

71.2
[2 13/16"]

69.6
[2 3/4"]

AC OUTPUT
HARNESS

REMOTE PANEL
CONNECTOR

NEG. BAT.
CONNECTION

POS. BAT.
CONNECTION

LP FUEL INLET

CONNECTIONS IN
BACK OF GENERATOR

NOTE: ALL AIR INTAKES AND EXHAUST OUTLETS MUST BE
KEPT CLEAR OF ANY OBSTRUCTIONS. ALL OPEN AREA
IS REQUIRED FOR COOLING.

Section 1 – General Information
Recreational Vehicle Generator

Figure 1.2 – Major Features and Dimensions (Drawing No. 0F4610)

	 19

Section 2 – Installation
Recreational Vehicle Generator

2.1 	Location and Support
 2.1.1	GENERATOR LOCATION
The most desirable location for the generator set is
between the vehicle's main frame members. However,
this is seldom possible. Most units must be installed
on the side of the vehicle and are difficult to reinforce.
Many recreational vehicles have been factory equipped
with an area for the generator set. Some vehicles may
even have a generator compartment provided by the
vehicle manufacturer.
Plan the generator location based on the following:
•	 The generator set must be installed on a framework that is part of the recreational vehicle, as
outlined in Section 2.1.2.
•	 The location must provide an access opening
that is large enough to permit generator removal
(unless the generator is to be removed from underneath the supporting framework).
•	 The location must provide easy access to frequently serviced components, such as filters, oil drains,
spark plugs and other common maintenance
parts.
•	 The location must provide sufficient room to allow
minimum clearances as outlined in Section 2.2. If
sound insulation is to be used on the compartment
walls and ceiling, the minimum recommended
applies to the space between the generator and
such insulation.
•	 The location must provide adequate cooling and
ventilating airflow for the generator without a great
deal of work and expense.
•	 If mounting the generator in an enclosed compartment, the base of the generator must rest flat on
the floor without any gaps.
•	 When using a suspended mounting system, ensure
the base of the generator is flush with the surrounding bodywork. If the unit is mounted higher
in the structure, heated air may recirculate into the
generator causing it to overheat.

 2.1.2	GENERATOR SUPPORT
The generator must be securely attached to a metal
framework that has been made part of the vehicle
frame structure by bolting or welding. The metal
framework on which the generator will rest and
which will restrain the generator set should consist
of at least two horizontal beams. These beams should
consist of (a) 1-1/2-inch square, 11-gauge steel tubing OR (b) 1-1/2-inch, 11-gauge angle iron. A typical
supporting frame with horizontal support tubing, is
shown in Figure 2.1.
The generator can be installed so that it sits on top
of the horizontal support tubing if the vehicle design
permits. Another method is to suspend the genera	 20	

tor below the horizontal support tubing by means of
suitable, structurally sound metal framework. The
following general rules apply:
•	 Vehicle construction MUST be capable of supporting the weight of the generator.
•	 Whether the generator is mounted above the horizontal support tubing or suspended below the tubing, the supporting frame used must be structurally sound.
•	 If the generator cannot be bolted directly to
the supporting frame or support tubing, consider using additional tubing, angle brackets
or other supports to give the supporting frame sufficient strength.

Figure 2.1 – Typical Horizontal Support Frame

 2.1.4	GENERATOR RESTRAINT
Use four 5/16"-18 hardened steel bolts (Grade 5) to
fasten the generator to the supporting frame or the
support tubing. These bolts must pass through (a)
the generator mounting base, (b) the compartment
floor (if a compartment is used) and (c) the supporting framework (Figure 2.2). All bolts must be long
enough so that when tight, at least three threads are
visible past the retaining lock nuts. Refer to Section
2.2 for the location of the generator mounting holes.

Figure 2.2 – Typical Generator Restraint

Section 2 – Installation
Recreational Vehicle Generator

2.2 	Generator Compartments

Figure 2.4 – Typical Compartment Construction

Whether the generator set is being installed inside a
compartment specifically manufactured to house a
generator or inside a compartment that the installer
constructs, the compartment must meet certain specifications as outlined in the following sections:

 2.2.1	COMPARTMENT SIZE
Plan the compartment size carefully. Provide a minimum clearance of 1/2 inch (13 mm) on the front and
top, 1/2 inch (25 mm) on the left side, two (2) inches
on the right side, and 2-1/2 inch (63.5 mm) from the
back for air circulation AFTER the compartment has
been lined with metal and sound insulation (Figure
2.3).

Figure 2.3 – Clearances
Plywood
Compartment

1/2" Clearance on Top
2-1/2" Clearance
in Back

2" Right Side
Insulation

1/2"
in Front

1/2" Left Side

ed
nd
me
com 12")
e
R
m
nce inimu
ara
Cle low (M
"
8
1
Be

NOTE:
Refer to “Figure 1.2 – Major Features and
Dimensions”.

 2.2.2	COMPARTMENT Construction
•	 The generator compartment should be either constructed of, or lined with, 26-gauge galvanized
steel.
NOTE:
Aluminum is NOT an acceptable alternative
to galvanized steel due to aluminum’s low
melting point.
•	 If the compartment is lined with galvanized steel,
it may be constructed of any material. The manufacturer recommends that the compartment be
constructed of 1/2-inch thick plywood (not strandboard), with the floor made of a double thickness
of 1/2-inch plywood with the grain of the wood at
cross section for added strength (Figure 2.4).
•	 If constructing a compartment, line the exterior
(underside) of the compartment floor with 26gauge galvanized steel.

•	 All seams, splices and joints of the compartment walls (unless vapor tight by design) should
be caulked to prevent poisonous, flammable or
explosive vapors from entering the vehicle interior.
NOTE:
Caulking must be done so that the caulking material will stay in place permanently. Pressing such
materials as putty tape onto joints and seams is
not acceptable. A high quality silicone rubber base
sealant is recommended.
•	 Holes and openings made in the compartment
walls to allow for the passage of electrical conduit,
conductors, hoses, cables, etc., into the vehicle living area must be sealed vapor tight with silicone
rubber base sealant.
•	 If flexible metal conduit is used, it must be sealed
internally at the end where it terminates inside the
compartment’s electrical junction box.
NOTE:
Flexible metal conduit, due to its unique construction, is NOT vapor tight along its entire length.
•	 Seams and joints of the galvanized steel (whether
used as a liner or for the compartment itself) must
be lapped and mechanically secured. Such seams
may be manufactured, welded, bolted, riveted or
screwed. Manufactured lock seams are shown in
Figure 2.5. Installer constructed compartments
typically utilize a standard lap joint.
•	 After the compartment has been metal lined and
vapor sealed, line the compartment interior walls
and ceiling with an approved, nonflammable sound
insulating material. See Section 2.2.3.
	

	 21

Section 2 – Installation
Recreational Vehicle Generator

Figure 2.5 – Types of Lock Seams

 2.2.4	ACOUSTICS
For additional noise abatement, the installer may
wish to consider the following:
•	 Using special sound insulating materials.
•	 Construction of a special noise abatement
compartment.
NOTE:
Any method used to reduce noise must not
adversely affect the flow of cooling and ventilating
air into or out of the compartment.

danger



 o not install any flammable material directly
D
above or around the compartment. Heat,
transferred through the compartment structure,
may be sufficient to ignite, char or discolor
seat cushions, fiberboard and other flammable
materials. Use approved nonflammable insulating materials in high temperature areas.

 2.2.3	Sound Insulating Materials
Once installers have determined that a compartment
is properly constructed and metal lined, they can add
acoustical material. This may include additional sealant or insulating material, to reflect noise away from
the vehicle interior.
Sound insulating materials should be of a nonflammable type. One excellent insulating material is a 1inch (25 mm) thick fiberglass having a 2-pound density. When fiberglass is used, its coated side should
face toward the compartment interior.

danger
Do not install sound insulation or any absorbent
 material
on the compartment floor interior. Such
materials will become soaked with combustible
or explosive vapors and liquids and will become
a fire hazard.
Using a combination of sound insulating materials
can often reduce noise more effectively than a single
material. For example, a sheet of lead or visco-elastic
material, along with a layer of other acoustical material, is more effective than when a single material is
used.

	 22	

In addition to the effective use of sound insulating
materials, construction of a special noise abatement
compartment might be considered to reduce noise
levels. Such a compartment might be constructed as
follows (Figure 2.6):
•	 Use 5/8-inch thick or 3/4-inch thick plywood in the
compartment.
•	 Construct the compartment floor of a double thickness of 5/8-inch or 3/4-inch plywood.
•	 Line the compartment interior walls and floor, as
well as the underside of the floor, with 26-gauge
galvanized steel.
•	 Vapor seal all compartment seams and joints.
•	 Over the galvanized steel lining, install a combination of acoustical materials as mentioned in
Section 2.2.3.

danger
To prevent fire or explosion, do not install any
 insulation
or other absorbent materials on the

interior or underside of the compartment floor.
•	 Seal all compartment door edges to prevent noise
leakage around the door perimeter.
•	 Line the compartment door interior (except for air
openings) with suitable, fireproof sound insulation
(such as 1-inch (25 mm) thick fiberglass with a 2pound density).

Figure 2.6 – Typical Noise Abatement

Section 2 – Installation
Recreational Vehicle Generator

Figure 2.7 – Compartment Floor Cutout (Drawing 0F4610)
VIEW FROM TOP
423.2
[16 11/16"]

TYP.
6.7
[1/4"]

82.5
[3 1/4"]

717.7
[28 1/4"]
343.4
[13 1/2"]

CONNECTIONS IN
BACK OF GENERATOR

50.8
[2"]

476.4
[18 3/4"]

60
[2 3/8"]

376.5
[14 13/16"]

170
[6 11/16"]

210
[8 1/4"]

HOT AIR
EXHAUST
429.5
[16 15/16"]

NOTE: ALL AIR INTAKES AND EXHAUST OUTLETS MUST BE
KEPT CLEAR OF ANY OBSTRUCTIONS. ALL OPEN AREA
IS REQUIRED FOR COOLING.

5/16"-18 WELDNUTS
(6 PLACES)

416
[16 3/8"]

118
[4 5/8"]

LP FUEL INLET
414.5
[16 5/16"]

AIR
INTAKE

TAIL PIPE
EXIT

360.5
[14 3/16"]

79
[3 1/8"]

101
[4"]

83.5
[3 5/16"]
176.6
[6 15/16"]

223.5
[8 13/16"]

211.3
[8 5/16"]

71.2
[2 13/16"]
POS. BAT.
CONNECTION

34.3
[1 3/8"]

36.5
[1 7/16
7/16"]
55.5
[2 3/16"]

48.1
[1 7/8"]
29
[1 1/8"]

222.7
[8 3/4"]

NEG. BAT.
CONNECTION
63.5
[2 1/2"]

300.7
[11 13/16"]

39.6
[1 9/16"]

69.6
[2 3/4"]

OIL DRAIN
369.7
[14 9/16"]

688.3
[27 1/8"]
736.4
[29"]

All measurements are in millimeters, 25.4 mm = 1”.
REMOTE PANEL
CONNECTOR
500.2
[19 11/16"]
REF.

778.9
[30 11/16"]
REF.

 2.2.5	COMPARTMENT FLOOR CUTOUTS
Provide openings in the generator compartment for
the following items (Figure 2.7):
•	 Engine exhaust
and cooling air outlets
342.2
[13 1/2"]
•	 Generator cooling
air inlet
•	 Four holes for passage of generator mounting
bolts. See Section 2.1.4.

danger

FRONT DOOR ACCESS FOR
ALL REQUIRED MAINTENANCE

Fuel lines and exhaust piping must not pen etrate
into the vehicle living area.

2.3 	Cooling and Ventilating Air

It is absolutely essential that an adequate flow of
air for cooling, ventilating and engine combustion
be supplied to the generator set. Without sufficient
airflow, the engine/generator quickly overheats. Such
overheating can cause serious operating difficulties
and also may cause fire and personal injury. The
installer must make sure that sufficient air is available to the generator for cooling, ventilating and
combustion. The installer also must provide for a
path for exhausting the cooling air to the exterior of a
compartment, if so equipped.

danger

AC OUTPUT
HARNESS

Never use discharged cooling air for heating or
 permit
such air to enter the vehicle interior. This
air contains deadly carbon monoxide gas and
other poisonous, flammable or explosive gases.

 2.3.1	GENERATOR airflow
Engine operation drives cooling fans for the two-stage
cooling air system. A pressure fan draws cooling air
into the bottom right side of the generator (Figure
2.8). This airflow cools the engine/generator and electronic components. The second part of the cooling
system, a suction fan, draws air that is heated from
a hot engine into a collector compartment at the left
side of the unit. This heated air (although cooler than
exhaust muffler) is then deflected out the bottom
toward the ground.

	

	 23

Section 2 – Installation
Recreational Vehicle Generator

Figure 2.8 – Airflow Through Engine/Generator

danger
Use only approved components in the fuel sup ply
system. All components must be properly

installed in accordance with applicable codes.
Improper installation or use of unauthorized
components may result in fire or an explosion.
Follow approved methods to test the system
for leaks. No leakage is permitted. Do not allow
fuel vapors to enter the vehicle interior.

Figure 2.9 – Typical Propane Gas Fuel System

 2.3.2	TESTING THE INSTALLATION
The manufacturer recommends testing the installation to be sure adequate cooling airflow is available to
the unit before placing the unit into service. If the unit
shows signs of overheating, enlarge the air openings.
Never place a unit into service until absolutely certain
that cooling and ventilation is adequate.
NOTE:
Test the installation, especially if bringing in air
from below the generator set.

2.4 	LP Gas Fuel System
danger
LP gas is highly explosive. The gas is heavier
 than
air and tends to settle in low areas. Even

the slightest spark can ignite it and cause and
explosion. Only competent, qualified people
should be allowed to install, test, adjust or service an LP gas fuel system. Install the optional
fuel system in compliance with applicable codes,
standards and regulations. After the installation, do not do anything that might render the
system in noncompliance with applicable codes
and standards.
The LP powered range of generators are fitted with a
nonadjustable, factory set system. These systems are
tamper-proof to meet 1997 California Air Resources
Board requirements for engine emission.

 2.4.1	Parts not Included in Fuel
System
The propane fuel system does NOT include such
items as (a) gas tank, (b) gas piping, (c) fittings, (d)
valves, and (e) primary regulator, used to store the
gaseous fuel and deliver it to the gaseous fuel solenoid (Figure 2.9).
	 24	

 2.4.2	SOME IMPORTANT CONSIDERATIONS
When installing an LP gas system, consider seriously
the following items:
•	 All fittings, lines, hoses and clamps must be
tight and free of leaks. Apply a pipe sealant to
threads when assembling threaded connections.
This reduces the possibility of leakage.
•	 Test the entire fuel system for leaks using approved
test methods.
•	 Optimum gas pressure at the inlet to the gaseous
fuel solenoid valve and secondary regulator is 11
inches water column.
•	 The installer’s fuel supply connection point is at
the gaseous fuel solenoid valve. This is a 3/4-inch
(female) connection. Provide a suitable 3/4-inch
NPT (male) connector to attach to the fuel supply
line.

Section 2 – Installation
Recreational Vehicle Generator

•	 Use a length of approved flexible fuel hose between
the gaseous fuel solenoid valve and rigid gas piping. The flexible line should be at least 6 inches
longer than necessary.

Figure 2.10 – LP Gas Carburetion Diagram

 2.4.3	 vapor withdrawal
LP gas is stored in pressure tanks as a liquid. The
gas systems used with these generators were designed
only for vapor withdrawal type systems. Vapor withdrawal systems use the gas vapors that form above
the liquid fuel in the tank. Do NOT attempt to use the
generator with any liquid withdrawal type system.

 2.4.4	 primary regulator
Gas pressure delivered to the solenoid valve must be
properly regulated by means of a primary gas regulator. Mount the primary regulator at the gas tank
outlet or in the supply line from the gas tank. The
following rules apply:
•	 For best results, the primary regulator supplies
gaseous fuel to the secondary regulator at 11 inches water column. Do NOT exceed 14 inches water
column.
•	 The installer must be sure the primary regulator is
rated at sufficient gas flow to operate the generator
plus all other gas appliances in the circuit.
NOTE:
Recommended MINIMUM gas flow rate for all aircooled generators is 40 cubic feet per hour.
If an existing primary gas regulator does not have
a sufficient flow capacity for the generator and
other gas appliances in the circuit, (a) install a
primary regulator with adequate flow rate, or (b)
install a separate regulator only and rated at least
40 cubic feet per hour. The inlet side of any primary regulator that supplies the generator must
connect directly to a gas pressure tank. Do NOT
tee the generator line into a gas circuit feeding
other areas.

 2.4.5	GASEOUS CARBURETION
LP gas vapors should be supplied to the secondary
regulator inlet at about 11 inches water column (positive pressure). The engine pistons draw air in during the intake stroke (Figure 2.10). This air passes
through a carburetor venturi, which creates a low
pressure that is proportional to the quantity of air
being pumped. The low pressure from the carburetor
venturi acts on the regulator diaphragm to pull the
diaphragm toward the source of low pressure. A lever
attached to the diaphragm opens a valve to permit
gas glow through the carburetor.

The greater the airflow through the carburetor venturi, the lower the pressure at the venturi throat. The
lower the pressure at the venturi throat, the greater
the diaphragm movement, and the greater the movement of the regulator valve. The more the regulator
valve opens, the greater the gas flow that is proportional to airflow through the generator.
The following facts about the secondary regulator
must be emphasized:
•	 The regulator must be sensitive to venturi throat
pressure changes throughout the operating range.
•	 The regulator must be properly adjusted so it will
stop the flow of gas when the engine is not running
(no air flow through the carburetor).
•	 The slightest airflow (and vacuum in the venturi
throat) should move the regulator valve off its seat
and permit gas to flow.

 2.4.6	fuel supply lines
•	 LP gas lines must be accessible, but protected
against possible damage.
•	 Do NOT connect electrical wiring to any LP gas fuel
line or run wiring alongside the lines.
•	 Route gas lines away from hot engine exhausts.
•	 Retain gas lines with metal clamps that do not have
sharp edges.
•	 Install an approved length of flexible hose between
the gaseous fuel solenoid valve and rigid fuel
supply lines. The flexible line must be nonmetallic, nonorganic and nonconductive. It must be
approved for use with LP gas.

 2.4.7	 excess flow valve
LP gas tanks should have an excess flow valve,
according to NFPA 501C, Paragraph 3-4.4. This
valve and the gas lines must be carefully sized so the
valve will close when a fuel line is severed or broken.
Consult the Natural-LP Gas Association for information and limitations of excess flow valves.
Manual shutoff valves on the supply tank and elsewhere in the system must be fully open when operating the generator. The excess flow valve functions
properly only if all valves are fully open.
	

	 25

Section 2 – Installation
Recreational Vehicle Generator

 2.4.8	 leakage tests
Do not place the generator into service until the gas
system has been properly tested for leaks. To test the
system, a separate source of 12 volts DC is needed to
open the gaseous fuel solenoid valve.
The leak test must comply fully with NFPA, Paragraph
318. All connections, hoses, valve regulators, fittings,
and other fuel system parts must be tested under
gas or air pressure of not less than 90 psi (620 kPa),
while using soap and water or an equivalent solution
to check for leaks. Other approved methods of testing
for leaks may be used, if appropriate. DO NOT USE
ANY FLAME TO TEST FOR LEAKS.

danger
Gaseous fuel lines between the tank and the
 secondary
regulator are under a positive pres-

sure (about 11 inches water column). Gas pressure at the outlet side of the secondary regulator, however, is a negative pressure and can
draw flame inside a line or fitting and cause an
explosion.

2.5 	Exhaust System

The generator exhaust system must be safely and
properly installed. Only approved mufflers and other
exhaust system parts must be used. A properly
installed exhaust system must be vapor tight, quiet
and completely safe.

danger
The generator engine gives off DEADLY carbon
 monoxide
gas through its exhaust system. This
dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even
death. Never operate the generator set with
the vehicle inside any garage or other enclosed
area. DO NOT OPERATE THE GENERATOR IF THE
EXHAUST SYSTEM IS LEAKING OR HAS BEEN
DAMAGED. SYMPTOMS OF CARBON MONOXIDE
POISONING ARE (a) inability to think coherently; (b) vomiting; (c) twitching muscles; (d)
throbbing temples; (e) dizziness; (f) headaches;
(g) weakness; and (h) sleepiness. IF FEELING
ANY OF THESE SYMPTOMS, MOVE INTO FRESH
AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET
MEDICAL HELP. Do not operate the generator
until its exhaust system has been inspected and
properly repaired.

	 26	

Never tee the generator engine exhaust pipe
 into
the vehicle engine exhaust piping. This

causes excessive back pressure on the generator
engine. Also, water from one engine can damage the other engine.

 2.5.1	SPARK ARRESTOR
This spark arrestor assembly meets code and standard requirements of the U.S. Forest Service. Use
only mufflers and parts approved by the manufacturer. Any person(s) installing an unapproved muffler, or
an unapproved exhaust system part, or modifying an
exhaust system in any way that might cause a hazard,
is liable for any damage, injury or warranty expense
that might be caused by such unapproved installation
or modification.
Failure to provide and maintain a spark arrestor may
be in violation of the law. If this generator is used on
any forest covered, brush covered or grass covered
unimproved land, provide a spark arrestor. The vehicle owner or operator must maintain this device in
good condition. In the state of California, the preceding is required by law (Section 4442 of the California
Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.
When installing/replacing the tailpipe or spark arrestor components, verify that the tailpipe has a hole
to securely fasten the spark arrestor components
(see Figures 2.11 and 2.12). Use only manufacturer
supplied hardware. Substitution of parts may cause
damage to the screen or a loose fit to the tailpipe.

Figure 2.11 - Spark Arrestor

TAILPIPE
P/N 0E0683

SPARK ARRRESTOR
SCREEN P/N 089680
RETAINING
SCREW P/N 056892

Section 2 – Installation
Recreational Vehicle Generator

Figure 2.12 — Spark Arrestor Installation

2.6 	Electrical Connections
Be sure to read Section 1.6.

The following general rules apply to electrical connections in a recreational vehicle:

27.4 [1.08"] I.D.

40 [1.58"]

5.5 [7/32"] DRILL
BOTTOM SIDE ONLY

 2.5.2	EXHAUST SYSTEM SAFETY
•	 Maintain a clearance of at least 3 inches (76 mm)
between exhaust system parts and any combustible material (such as wood, felt, cotton, organic
fibers or other like material). If the 3-inch (76 mm)
clearance cannot be maintained, locate, insulate or
shield the exhaust part(s) so that the temperature
of any combustible material is not raised more
than 117° F (65° C) above the ambient air temperature.
•	 Extend the exhaust system at least 1 inch (25 mm)
past the outer edge of the vehicle. Do not terminate
the exhaust system under the vehicle.
•	 Terminate the exhaust tailpipe such that exhaust
gases will not be drawn back into the generator
compartment and recirculated.
•	 If there is any possibility of the tailpipe or muffler
being damaged, protect these damage-prone areas
by means of a protective device (such as a skid
bar).
•	 Install the generator exhaust system according to
safe automotive practices.
•	 Use enough exhaust system hangers to prevent any
part of the system from being dislocated.
•	 Use exhaust system parts recommended by the
manufacturer. Using unapproved exhaust mufflers
and exhaust system parts is the responsibility of
the person(s) installing such unauthorized parts.
•	 Do not terminate the exhaust system under any
opening, window or vent that can be opened or is
not permanently sealed from the vehicle interior.
•	 Exhaust piping must be large enough to prevent
excessive back pressure on the generator engine.
•	 Never tee the generator engine exhaust pipe into
the vehicle engine exhaust piping. This causes
excessive back pressure on the generator engine.
Also, water from one engine can damage the other
engine.
•	 Plan exhaust system installation carefully. Comply
with all applicable codes, standards and regulations.

•	 Qualified electricians who are familiar with applicable codes, standards and regulations should
install electrical wiring.
•	 The wiring should comply with codes, standards
and regulations. The National Electrical Code
(NFPA 70), and state and local codes apply.
•	 Switches and circuit breakers should be of a type
approved for use in recreational vehicles and must
be mounted and installed to prevent damage from
road shock.
•	 Wiring must be of adequate size, have approved
insulative qualities and be properly supported.
•	 Conduit and wire openings into the generator compartment (if used) must be vapor-sealed to prevent
entry of flammable, explosive or poisonous gases
into the vehicle.

 2.6.1	ELECTRICAL JUNCTION BOX
Install an approved, square electrical junction box
with a blank cover on the interior or exterior wall of
the area planed for installation of the generator (NOT
on the generator). Route the generator's AC output
leads into this junction box through approved flexible conduit. This is the point of first termination for
generator AC output leads.

 2.6.2	WIRING
•	 Wiring should be of stranded copper to reduce the
chance that vibration may cause breakage.
•	 Wire gauge size should be large enough to handle at
least 115 percent of the installed generator's rated
maximum current.
•	 Neutral conductors must be the same size as other
leg wires.
•	 Route power supply conductors from generator AC
output leads (white), (black) and the green ground
wire through approved flexible conduit to the electrical junction box on the compartment wall.
	 If flexible metal conduit is used between the generator and the compartment junction box, the conduit end that terminates the compartment junction
box must be vapor-sealed. Flexible metal conduit
is NOT vapor tight along its entire length.
•	 From the junction box, route power supply wires
through approved conduit to either (a) double-pole,
double-throw transfer switch, or (b) approved isolation receptacle. Connecting to a transfer switch
or isolation receptacle must prevent vehicle electrical circuits from being connected to two different
power supplies at the same time (such as generator and dockside power).
	

	 27

LP FUEL INLET
414.5
[16 5/16"]

Section 2 – Installation

360.5
[14 3/16"]

Recreational Vehicle Generator
211.3
[8 5/16"]

6"]

]

71.2
[2 13/16"]
POS. BAT.
CONNECTION

34.3
[1 3/8"]

•	 Conductors must be rated 221° F (105°
C) or must
NEG. BAT.
be of a larger conductor
size. 69.6 CONNECTION
39.6
[1 9/16"]

[2 3/4"]

 2.6.3	GENERATOR AC CONNECTIONS
Generator AC output leads (BLACK) “hot” and
(WHITE) grounded neutral come out of the generator
as shown in Figure 2.13. There is also a green lead
that connects to ground in the junction box of the
recreational vehicle.

Figure 2.13 – Generator AC Output Leads
REMOTE PANEL
CONNECTOR
500.2
[19 11/16"]
REF.

AC OUTPUT
HARNESS

•	 If using metallic conduit, vapor seal the end of the
conduit where it enters the junction box. Do this
because flexible metallic conduit is not vaporproof
along its entire length.

 2.6.5	ISOLATING DIFFERENT POWER
SOURCES
Connections from the junction box must terminate in
a double-pole, double-throw transfer switch (Figure
2.14). An alternate method for isolating different
power sources is by using an isolating receptacle
(Figure 2.15). Whichever method is used, be certain
that both power sources are NOT connected at the
same time.

 2.6.6	POWER SUPPLY CORD
The power supply cord must comply with all applicable codes, standards and regulations. It must be
large enough to handle the full amperage to which it
will be subjected.

 2.6.7	GROUND FAULT CIRCUIT
INTERRUPTERS

Leads BLACK to WHITE are protected against overload by a 30-amp circuit breaker (CB1). Use this
line-to-neutral connection separately to operate 120volt, single-phase, 60 Hertz, AC loads requiring up to
3,400 watts (3.4 kW) of power.



 o NOT connect electrical loads in excess of any
D
circuit breaker rating or probems will develop
with circuit breaker tripping, which causes a loss
of AC output. Also, do NOT exceed the generator's rated wattage capacity. Add the watts
or amperes of all lighting, appliance, tool and
motor loads the generator will operate at one
time. This total should be less than the unit's
rated wattage/amperage capacity.

 2.6.4	CONDUIT
Route the connections between the generator and the
junction box through approved, flexible conduit. The
following general rules apply:
•	 Cut wiring to the required length and allow extra
wire for junction box connections.
•	 Carefully prepare conduit ends to prevent sharp
edges from cutting through wiring insulation.
•	 Route conduit so it does not interfere with generator movement.
	 28	

The National Electrical Code (NFPA 70, 551-7)
requires that ground fault circuit interrupters (GFCIs)
be installed on all external and some internal electrical receptacles. Contact the dealer for recommendations.

2.7 	Battery Installation
 2.7.1	RECOMMENDED BATTERY
Install a battery
requirements:

that

meets

the

following

•	 The battery must be a 12-volt, automotive type
storage battery.
•	 For prevailing ambient temperatures above 32°
F (0° C), use a battery rated 70 amp-hours and
capable of delivering 400 cold-cranking amperes.
•	 For prevailing ambient temperatures below 32°
F (0° C), use a battery rated 95 amp-hours and
capable of delivering 400 cold-cranking amperes.
NOTE:
If the battery is to be used to power other vehicle
accessories, as well as start the generator, a battery with a larger capacity may be needed.

 2.7.2	BATTERY CABLES
Using battery cables that are too long or too small in
diameter may cause a drop in voltage, which causes
starting problems. For the best cold weather starting,
the voltage drop between battery terminals and the
generator connection point should not exceed 0.12
volts per 100 amperes of cranking current.

Section 2 – Installation
Recreational Vehicle Generator

Figure 2.14 – Transfer Switch Isolation Method

Figure 2.15 – Installation With Isolation Receptacle

These generators are rated at about 100 DC amperes
of cranking current.

	
	

CABLE LENGTH
in Feet (Meters)	

CABLE SIZE

Select battery cables based on (a) cable length and
(b) prevailing ambient temperatures. Generally, the
longer the cable and the colder the weather, the larger
the cable size must be, as shown in the following
chart.

	
	
	

0 to 10 (0 to 3)	
11 to 15 (3.4 to 4.5)	
16 to 20 (4.5 to 6)	

2*
0
000

* For warm weather, use No. 2 cable up to 20 feet.
	

	 29

Section 2 – Installation
Recreational Vehicle Generator

 2.7.3	BATTERY CABLE CONNECTIONS

Figure 2.17 – Remote Panel Plug-in Receptacle

1.	 Connect the battery cable from the battery post or
to

NOTE: ALL AIR INTAKES AND EXHAUST OUTLETS MUST BE
terminal indicated by a POSITIVE, POS or (+)
KEPT CLEAR OF ANY OBSTRUCTIONS. ALL OPEN AREA
the lug on the starter contactor (Figure 2.16).
IS REQUIRED FOR COOLING.

NOTE:

Check to be sure the battery cable boot for the
starter cable has been installed.

CONNECTIONS
IN the battery post
2.	 Connect
the battery cable from
indicated by a NEGATIVE, NEG or (-) to the
BACK
OF
GENERATOR
frame
ground
connection
(Figure 2.16).
3.	 Connect cables so the connectors are clean
and tight.

6

14A

14A

18

18

17

17

15

5
4

15

14

3
2

14

0

1

0

LP FUEL INLET
Figure 2.16 – Connecting Battery
Cables

12.00"

71.2
[2 13/16"]

11.3
5/16"]

POS. BAT.
CONNECTION

34.3
[1 3/8"]

NEG. BAT.
CONNECTION
39.6
[1 9/16"]

69.6
[2 3/4"]

WIRE
COLOR

0
14
15
17
18
14A

WHITE
RED
ORANGE
YELLOW
BROWN
BLUE

LENGTH (mm)
12.0 (305)
12.0 (305)
12.0 (305)
12.0 (305)
12.0 (305)
12.0 (305)

FUNCTION
GROUND
ENGINE RUN SIGNAL

12 VDC
START
STOP
PRIME

P/N: 0D9099-B

 2.8.1	 remote start/stop panel

 2.7.4	BATTERY COMPARTMENT
Install the generator battery in its own, vented compartment. Place the battery compartment away from
any source of heat, sparks or flame.
Provide ventilation openings in the battery compartment. The minimum size of openings should be 2
square inches at the top of the compartment. Mount
the battery on a strong, rigid supporting structure,
where leaks and spills of battery fluid will not cause
damage.

2.8 	Optional Accessories

A plug-in receptacle (Figure 2.17) is provided
on
REMOTE PANEL
the generator set. Use this receptacle toCONNECTOR
connect an
optional500.2
remote-mounted start/stop panel to the
[19 11/16"]
generator.
Installation of such a panel will permit
starting REF.
and stopping the generator engine from any
AC OUTPUT
convenient location inside the vehicle.
HARNESS

	 30	

WIRE
No.

A remote mounted Start/Stop panel (Figure 2.18) is
available that allows the user to start and stop the
generator engine conveniently from inside the vehicle.
The remote panel includes a Start/Stop switch, hourmeter, generator run lamp, a fuel prime switch, and
a wire harness. The hourmeter should be used in
conjunction with the maintenance operations found
in Part I of this manual.

Figure 2.18 – Optional Remote Panel

FUEL

PRIME

RUN

STOP

Section 3 – Post-installation Start-up Adjustments
Recreational Vehicle Generator

3.1 	Post Installation Tests

The air-cooled generator set was factory tested and
adjusted. It should not be necessary to adjust the unit
any further except under special circumstances.

Do not make any unnecessary adjustments.
 Factory
settings are correct for most applica-

tions. When making adjustments, however, be
careful to avoid overspeeding the engine.

3.2 	BEFORE INITIAL START-UP
Before starting, complete the following:

1.	 Check the engine crankcase oil level and, if necessary, fill to the dipstick “FULL” mark (crosshatched area) with the recommended oil. Do not
fill above the FULL mark.
2.	 Check the fuel supply. Gas fuel lines must have
been properly purged and leak tested in accordance with applicable fuel codes. All fuel shutoff
valves in the fuel supply lines must be open.

danger
If a liquid propane (LP) gas fuel system has been
 installed,
it must be properly tested for leaks
before operating the system in compliance with
ANSI A119.2/NFPA 501C. No leakage is permitted. Be sure no gasoline fuel vapors enter the
vehicle interior.

3.3 	 INITIAL START

When absolutely certain that the unit has been properly installed and prepared for use, start the engine
as follows:
1.	 Turn off all electrical loads. Do this by setting the
generator’s main circuit breakers to their “OFF”
(or open) position.
2.	 Refer to Part I, Section 2.5, “Starting the
Generator”, for cranking and starting instructions. The engine may require more cranking
for initial starting since the fuel lines have to be
primed (use of the primer switch will shorten this
time).

3.	 Let the engine warm up for about five minutes to
allow internal temperatures to stabilize.
4.	 Carefully inspect the engine/generator for fuel, oil
and exhaust system leaks. Before proceeding to
the next step, correct any leakage immediately.
5.	 When all tests and adjustments at no-load are
completed, apply electrical loads and check for
proper operation under load. See Section 3.4.
Run the unit at least 30 minutes with loads
applied.
6.	 Turn off all electrical loads by setting the generator’s main circuit breakers to their “OFF” (or
open) position.
7.	 Let the unit run at no-load for a few minutes to
stabilize internal engine/generator temperatures.
Then, shut down the engine.
NOTE:
The generator set was thoroughly tested and
adjusted at the factory before shipping. No additional adjustment should be necessary. Only qualified service technicians who have been trained
should perform adjustments outlined in this
manual.

3.4 	TESTING UNDER LOAD

Apply electrical loads equal to about 75 to 100 percent of the unit's rated wattage/amperage capacity.
Let the unit run at least 30 minutes with load applied.
During this part of the test, check that the unit is not
running excessively hot and that adequate cooling
airflow is available. Do not allow the unit to overheat
during prolonged operation.
NOTE:
The generator engine is equipped with a high temperature switch. The switch has normally closed
(N.C.) contacts. When the engine temperature is
too high, switch contacts close, and the engine
shuts down automatically.
THE MANUFACTURER recommends testING
the generator for adequate cooling.

	

	 31

Section 3 – Post-Installation Start-up Adjustments
Recreational Vehicle Generator

3.5 	 Installation Checklist

 Electrical Connections

 Location and support

❑	Connections comply with local code requirements
and all National Electrical Codes.

❑	 Generator is properly located.

❑	 Junction box is properly installed.

❑	 Generator is properly supported.

❑	 Wiring meets all standards.

❑	 Generator is properly restrained.

❑	All connections are correct.

 Generator Compartment
❑	 Compartment construction is proper.
❑	 Holes/Openings are vapor-sealed.
❑	 Compartment size is correct.

❑	Conduit is properly installed and sealed.
❑	 Generator is properly bonded to the vehicle.

 Battery Installation
❑	 Recommended battery is installed.

❑	 Compartment is vapor-sealed.

❑	 Recommended cables are installed.

❑	 Sound insulation is correct.

❑	 Cables are clean and tight.

❑	 Floor cutouts are properly completed.

❑	 Cables are connected properly.

 Cooling and Ventilating Air
❑	Airflow is adequate.
❑	Air inlet opening is correct.

❑	 Proper ventilation is provided.
❑	Terminals are coated with anti-corrosion grease,
and terminal covers are positioned.

❑	Compensate for restrictions.

 Optional Accessories

❑	Check that installation has been tested.

❑	Check that remote start/stop panels (if used) are
installed properly.

 LP Gas Fuel System

❑	Check that hourmeter kit (if used) is installed
properly.

❑	Fuel system is properly installed and checked
for leaks.
❑	Pressure at regulator inlet is correct.
❑	Rated flow of primary regulator is correct.
❑	All parts are properly installed.
❑	Fuel system is properly tested/adjusted.

❑	Check that any other options and accessories (if
used) are installed properly.

 Post Installation Tests
❑	 Check that all tests are completed properly.

 Exhaust System
❑	Exhaust system complies with all applicable
codes.
❑	Exhaust system is properly and safely installed.

	

Date of Installation_____________________________________________________

	

Name of Installer________________________________________________________

	

Signature of Installer__________________________________________________

	 32	

Appendix 1 – Troubleshooting
Recreational Vehicle Generator

Troubleshooting Guide
Problem	Cause	Correction
The engine will not crank.	
1.	
	
2.	
		
	
3.	
		
	
4.	
	
5.	
	
6.	

Fuse blown	
1.	
Loose, corroded or defective	
2.	
battery cables		
Defective engine Start/Stop 	
3.	
switch	
Defective starter contactor	
4.	
Defective starter motor	
5.	
Low or defective battery	
6.	

Replace fuse.
Tighten, clean or replace
as necessary.
Replace Start/Stop switch.

The engine cranks but 	
1.	
will not start.	
2.	
	
3.	
		
	
4.	
	
5.	
	
6.	

Out of fuel	
1.	
Defective fuel solenoid	
2.	
Open #14 wire from 	
3.	
engine control board		
Flooded engine	
4.	
Defective spark plug(s)	
5.	
Fuel line shut-off closed	
6.	

Replenish fuel.
Replace fuel solenoid.
Check connections and.
insulation of #14 wires.
Wait 5-10 minutes before trying.
Clean, re-gap or replace plug(s).
Open fuel line shut-off.

Replace contactor.
Replace starter motor.
Charge or replace battery.

The engine starts hard	
1.	 Air cleaner 	
1.	 Check, clean or replace air cleaner.
and runs rough.		 plugged or damaged		
	
2.	 Defective spark plug(s)	
2.	 Clean, re-gap or replace plug(s).
The engine starts, but shuts 	
1.	 Engine oil level low	
1.	
down when the Start/Stop 	
2.	 Defective low oil 	
2.	
switch is released.		 pressure switch
	
3.	 Defective high temperature	
3.	
		 switch
	
4.	 Defective engine control board	 4.	
	
5.	 Overheated engine	
5.	
				
The Start/Stop switch is 	
1.	
set to Stop, but the engine	
2.	
continues to run.		
		
	
3.	
		
		
	
4.	

Defective Start/Stop switch	
Open/Disconnected #18 wire	
between Start/Stop switch
and engine control board
Open/Disconnected #0 wire	
between Start/Stop switch
and engine control board
Defective engine control board 	

Check oil and add oil as needed.
Replace pressure switch.
Replace temperature switch.
Replace control board.
Check that the airflow
openings are adequate.

1.	 Replace switch.
2.	 Reconnect or close wire.
3.	 Reconnect or close wire.
4.	 Replace control board.

There is no AC output from 	
1.	 Main line circuit breaker open	 1.	 Reset circuit breaker
the generator.				 to ON (or closed).
	
2.	 Fault with vehicle circuit 	
2.	 Reset and replace if necessary.
		 breaker and/or fuses	
	
3.	 Transfer switch set to NORMAL	 3.	 Set switch to GENERATOR.
	
4.	 Start switch not held long	
4.	 Stop, then restart the engine
		 enough to flash the field		 (Hold Start switch for at least
				 2 seconds).
	
5.	 Generator internal failure	
5.	Contact an Authorized Service
Dealer.
	

	 33

Appendix 2 — Electrical Data
Recreational Vehicle Generator
Electrical Schematic and Wiring Diagram – Drawing No. 0D8063-D

BATTERY
RED

BLK
SC

RED

13

16

SM

F1
15
14A

FP

14

CH

SW2

14

16
PCB

15

0

FS

0

SC

J3

J1-1

56

J2

J1-2

90

CS

0

J1-3
14

15

J1-4

SP

IM

18A

J1-5
J1-6

17

J1-7

17

(START)

0B

SW1
(STOP)

J1-8

0

J1-13
J1-14

18

J1-15

18

LOP
0

REMOTE
PANEL
CONNECTOR

66
4
17

0I
17
14
18

14

15
14 A

BCR
66
15

1
2
3
4

5
6
7
8

5
6
7
8

14 A 1 5 18 14 17 0

66

77

1
2
3
4

WHITE

J1-12

85

RED

85

YELLOW

66

J1-11

HTO
0

BROWN

J1-10

85

BLUE

4

ORANGE

J1-9

BATTERY CHARGE WINDING
STOP

55
R1

START

0N
4

L1
POWER WINDING

HM

33
0N

44

22S

11S

FUEL
PRIME

11P

22P
ELECTRONIC
VOLTAGE

REMOTE PANEL
(OPTIONAL)

CB1

REGULATOR

0K
2A

4
CB3

0N

2

4

6

T1

DPE WINDING
0F
WHITE

4
FIELD

GREEN

T2
120V 30A
NEUTRAL CONNECTION
BY CUSTOMER

	 34	

BLACK

LEGEND

BCR - BATTERY CHARGE RECTIFIER
CB1 - CIRCUIT BREAKER, 30A
CB3 - CIRCUIT BREAKER, 2.5A
CH - CHOKE HEATER (GASOLINE ONLY)
CS - CHOKE SOLENOID
F1 - FUSE, 7.5A
FP - FUEL PUMP-OR-LPG SHUT OFF VALVE
FS - FUEL SOLENOID (GASOLINE ONLY)
GT - TERMINAL, GROUND 4-TAB
HM - METER, HOUR (OPTIONAL)
HTO - SWITCH, HIGH TEMP. OIL (CLOSES ON HIGH TEMP.)
IM - IGNITION MAGNETO
L1 - LIGHT, RUN (OPTIONAL)
LOP - SWITCH, LOW OIL PRESSURE (CLOSES ON LOW PRESSURE)
PCB - ENGINE CONTROLLER
R1 - RESISTOR, 1 OHM 25W
SC - STARTER CONTACTOR
SM - STARTER MOTOR
SW1 - SWITCH, START/STOP
SW2 - SWITCH FUEL PRIMER
SP - SPARK PLUG
TC - TERMINAL, CONN. 4-TAB

Appendix 2 — Electrical Data
Recreationl Vehicle Generator
Electrical Schematic and Wiring Diagram – Drawing No. 0D8063-D

SUPPLIED BY
CUSTOMER
SUPPLIED BY
CUSTOMER

12V
BATTERY

16

SM

SC

4 0K

11S

6 2A

4

13

ELECTRONIC
VOLTAGE
REGULATOR

22S

16

56

STATOR

2A

0
0

15

J3

15
14

J2

56

J1-1
J1-2
J1-3
J1-4
J1-5
J1-6
PCB J1-7
J1-8
J1-9
J1-10
J1-11
J1-12
J1-13
J1-14
J1-15

0

90

22S

2A

18A

6

11S

17

17

4

17

0

77

4

66

18

2

17

66

33 11P
22P
44
55

90
16

14

2A

15

CLOSEST TO BEARING

RED

4

4

2
13

CB3

18

77

2

11P

BCR

33

2A

R1

18

1

0

0

2

90

3

14

0F
0

0I

CONN. 2
PIN#

FS

TC

14

15

0B

FP

18

RED

13
15

14A

5

11P

18

14A
15

GT

15
14A

11P
WHITE

BLACK

18
14

6

REMOTE
PANEL
CONNECTOR

33

F1

0
90

4

18

SW1

SW2

15

3 7

14

17
14A

2

0

17
14

14

1

14

1
2 8

0I

GT

14
14

0N

0N

0

0

44

0

0K

0
CONN. 1
PIN#

18

0F

17

15

66

85

55

22P

66

2

18A

FIELD

0F

0

85

CB1

18

14A

18A
85

14A

15

15

85
LOP

0

HTO

FILTER MTG
SCREW

T2
T1

GREEN

18A

CUSTOMER
AC CONNECTION
0
90

CS

14

CH

BLACK

SP1

WHITE

GREEN

NEUTRAL CONNECTION
BY CUSTOMER

IM1

	

	 35

	 36	

41

5

16

38

21

45

4

15

2

46

37

42

52

3

17

19

34 33
52

50

9

30

32
31

52

21

40

51

52

21

43 21

36

28

41

21

21

39

54

1
21
53

18

22
23

11

10

24

20

6

42

8

47

7

24

13

23

14

22

25

49

21

12

26

44

Appendix 3 — Exploded Views and Parts Lists

Recreational Vehicle Generator
Enclosure – Drawing No. 0F4589

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
Enclosure – Drawing No. 0F4589

ITEM	

PART NO.	

	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	

0F3916	
0D6942	
0D6939	
0F3920	
0F3917	
0F3918	
0F3919	
0D6944	
0D8254	
0C5644	
0A1495	
0E1742A	
047290	
048031E	
0D8628B	
047411	
022473	
023484S	
022097	
086729	
0D3700	
022129	
022259	
075763A	
0D7293	
064113	
0C7561	
0A4456	
049813	
022237	
022131	
0C5443	
0C7423	
029451	
074908	
0D8717	
0D9020	
0742600144	
0E0724	
0A7215	
0742600143	
029451A	
0D8627	
0D8628	
0D8628A	
0D8691	
0D7176	
0A2115	
0D9282	
0E0393	
0C7968	
0E0014	
0E0017	

1	
2	
3	
4	
5	
6	
7	
8	
9	
10	
11	
12	
13	
14	
15	
16	
17	
18	
19	
20	
21	
22	
23	
24	
25	
26	
27	
28	
30	
31	
32	
33	
34	
35	
36	
37	
38	
39	
40	
41	
42	
43	
44	
45	
46	
47	
48	
49	
50	
51	
52	
53	
54	

QTY.	
1	
1	
1	
1	
1	
1	
1	
1	
1	
2	
4	
1	
1	
1	
1	
2	
2	
1	
2	
1	
22	
2	
2	
2	
1	
1	
1	
1	
2	
1	
2	
1	
1	
2.1'	
4	
1	
1	
1	
1	
20	
1	
8.75'	
2	
1	
1	
1	
4	
1	
1	
1	
4	
1	
1	

DESCRIPTION
TRAY, ENCLOSURE
PANEL, ENCLOSURE SIDE
PANEL, REAR DIVIDER
PANEL, ENCLOSURE ROOF
PANEL, ENCLOSURE BACK
PANEL, FRONT DIVIDER
COMPARTMENT, AIR INTAKE
PANEL, ENCLOSURE DOOR
SHIELD, MUFFLER
SLIDE LATCH, FLUSH
SCREW HHTT M4-0.7 X 10mm
LP REGULAT0R
HOSE 3/8" I.D. SINGLE BRAID 33" LONG
HOSE CLAMP BAND 3/8"
FOAM, FRONT AIR OUT COMPARTMENT
SCREW HHC M6-1.0 X 16
WASHER FLAT ¼"
BUSHING, 1.09" SNAP
WASHER LOCK M6-1/4"
CONTACTOR, STARTER
NUT FLANGE M6-1.0 NYLOK
WASHER LOCK M8-5/16"
NUT HEX 5/16"-18
BOOT BATTERY CABLE
PANEL AIR BOX COVER
SCREW, M6-1.00 x 20mm WING
BOLT CARR 3/8"-16 X 1" BRASS
3/8" SPECIAL L/WASHER
NUT HEX M6 X 1.0
WASHER LOCK 3/8"
WASHER FLAT 3/8-M10"
BLOCK, TERMINAL BATTERY POST
STUD 3/8"-16 X 2"-1/4" BRASS
TAPE FOAM 1/8" x ½"
SCREW HHTT M5-0.8 X 10
CUSTOMER CONNECTION HARNESS
FOAM, AIR OUT COMPARTMENT SIDE
CABLE, STARTER
ASSEMBLY OIL DRAIN
SCREW SW ¼"-20 x 5/8" WITH NYLON WASHER
CABLE, BATTERY CONNECTION
FOAM TAPE 1/16" X ½"
FOAM, AIR INTAKE COMPARTMENT
FOAM, ROOF AIR OUT COMPARTMENT
FOAM, BACK COMPARTMENT
FOAM, DOOR PANEL
WASHER SELF LOCKING 1"
WASHER NYLON .250"
HARDWARE CLOTH COMPARTMENT AIR OUT
ASSEMBLY, CAP & DIPSTICK
NUT HEX JAM 3/8"-16 BRASS
BOX, MUFFLER TAIL PIPE
GASKET, MUFFLER TAIL PIPE BOX

	

	 37

Appendix 3 — Exploded Views and Parts Lists

18
18

37

18

21
28
38

23

21
2
18

27

26
10

25
2
18
1

4

3

5

2

7

24

8

24

9

22

2

35

11

12

39

2

15

18
2

23

36

13

2

2

8

2

14

17

18
43

16

2

0
1

21

29

32

30

42

34

31

29

33

Recreational Vehicle Generator
Generator – Drawing No. 0F4590

	 38	

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
Generator – Drawing No. 0F4590

ITEM	

PART NO.	

	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	

050322	
022129	
049451	
0C8096A	
0D8120	
066849	
066386	
0D4217	
073159	
0D4484H	
0D4430H	
0D4216	
048614	
0D2588A	
022131	
027028	
0D6832	
022145	
030231	
0C3168	
022259	
0C8565	
0D8048	
083512	
0D6831	
029451	
0D6918	
0D2558	
087680	
0D7530	
0D9723	
0D4511	
0D8451	
022097	
0D7440	
090388	
0D7441	
081105	
089476	
022531	
0D8981	
048031E	

1	
2	
3	
4	
5	
6	
7	
8	
9	
10	
11	
12	
13	
14	
15	
16	
17	
18	
19	
20	
21	
22	
23	
24	
25	
26	
27	
28	
29	
30	
31	
32	
33	
34	
35	
36	
37	
38	
39	
41	
42	
43	

QTY.	
1	
22	
1	
1	
4	
2	
1	
1	
1	
1	
1	
1	
4	
1	
4	
4	
1	
18	
3	
1	
10	
2	
4	
6	
1	
2.14'	
1	
1	
2	
1	
1	
1	
1	
1	
1	
2	
2	
2	
1	
1	
1	
1	

DESCRIPTION
SCREW IHHC 5/16"-24 x 9-3/4"
WASHER LOCK M8-5/16"
WASHER FLAT .406" I.D. x 1.62" O.D.
FAN, 8" CURVE BLADE, 16.5mm I.D.
SCREW IHHC M8-1.25 X 260mm
SCREW HHTT M5-0.8 X 16
ASSEMBLY, BRUSH HOLDER
CARRIER, REAR BEARING
BEARING
ROTOR
STATOR
ADAPTOR, ENGINE
SCREW HHC 5/16"-24 X 3/4"
GASKET, FRONT DIVIDER
WASHER FLAT 3/8"-M10
NUT LOCK HEX 5/16"-18 NYLON INSERT
BRACKET, ENGINE MOUNTING
WASHER FLAT 5/16"
SCREW HHC 5/16"-18 X 1-1/2"
5/16" SPECIAL LOCK WASHER
NUT HEX 5/16"-18
SCREW SHC M8-1.25 x 18mm
VIBRATION MOUNT
SCREW HHTT M8-1.2 x 16mm
BRACKET, ALTERNATOR MOUNTING
TAPE ELEC. UL FOAM 1/8" x 1/2"
DUCT, ALTERNATOR AIR
GASKET, ALTERNATOR DUCT
NUT WING M6-1.0
STUD, M6-1.0 OFFSET
ELEMENT, AIR FILTER
PRECLEANER, AIR
WASHER FLAT .281" I.D. x 1.50" O.D.
WASHER LOCK M6-1/4"
MUFFLER
SCREW HHTT M6-1.0 x 12mm
BOLT CARR 5/16"-18 x 2"
NUT FLANG 5/16"-18 LOCK
GASKET, EXHAUST
SCREW HHC 5/16"-18 X 1-3/4"
FILTER GASKET RV
HOSE CLAMP 3/8"

	

	 39

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
Control Panel – Drawing No. 0F4591

26

9

13
12
31

24
23
7

17

23

30

27

8

4
18

37

36

17
5
6
25
24
25
23
14

29

19

35

28
22
	 40	

25

21
20

15
1

11

17

2

16

10

3

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
Control Panel – Drawing No. 0F4591

ITEM	

PART NO.	

	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	

0830490	
075210A	
092234	
065795	
023484F	
023484R	
075234	
057159	
054502	
087798	
092113	
032300	
0A9611	
090145	
0E2314	
0A1658	
075235	
047411	
049226	
051716	
075476	
022264	
051715	
0A2053	
022473	
022097	
049813	
055440	
049815	
038750	
051714	
0D8794	
025105	
028739	
0D8308	
0F5025	
023484S	
043182	
031879	

1	
2	
3	
4	
5	
6	
7	
8	
	
9	
10	
11	
12	
13	
	
14	
15	
16	
17	
18	
19	
20	
21	
22	
23	
24	
25	
26	
27	
28	
29	
30	
31	
32	
33	
34	
35	
36	
37	

QTY.	
1	
1	
1	
1	
2	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
2	
2	
2	
5	
1	
2	
2	
4	
1	
5	
4	
4	
2	
1	
2	
2	
1	
2	
2	
1	
1	
1	
2	
2	

DESCRIPTION
REGULATOR VOLTAGE
TERMINAL BLOCK
CONTROLLER P.C.B.
BATTERY CHARGER RECTIFIER
BUSHING SNAP 1"
BUSHING SNAP 1-1/4"
RESISTOR, 1 OHM 25W
CIRCUIT BREAKER 2.0 Amp (60Hz)
CIRCUIT BREAKER 3.0 Amp (50Hz)
SWITCH S.P.D.T.
SWITCH S.P.D.T. ON-MOM-ON
HOLDER FUSE
FUSE 7.5A
CIRCUIT BREAKER, 30 X 1 (60HZ)
CIRCUIT BREAKER, 15A 2 POLE (50HZ)
LOCK WASHER SPECIAL
SCREW HHC M5-0.8 x 30mm
SCREW HHC M6-1.0 X 16mm
WASHER LOCK M5
NUT HEX M5-0.8
SCREW PPHM M4-0.7 x 16mm
WASHER LOCK #8-M4
NUT HEX M4-0.7
SCREW HHC M6-1.0 x 65mm
WASHER FLAT 1/4"
WASHER LOCK M6-1/4"
NUT HEX M6-1.0
SCREW HHC M5-0.8 X 25mm
SCREW HHC M5-0.8 X 16mm
SCREW HHC M6-1.0 X 30mm
NUT, HEX M3-0.5
PANEL CONTROL
SCREW RHM #6-32 X 1/4" SIMS
TIE WRAP UL 4" (NOT SHOWN)
DECAL (NOT SHOWN)
HARNESS (NOT SHOWN)
BUSHING, SNAP 1.09"
WASHER LOCK M3
WASHER FLAT M3

	

	 41

Appendix 3 — Exploded Views and Parts Lists

51

50
48

6

49

31
37

52

30

28

53
32

29

23 24 25

22
21
34

44

38

9

9

41
42

43

46

47

9

18

45

20
40

14

19

13

26 27

8

9

10

11

12

35

36

7

15

16

16
15

33

3

9

9

1

2

Recreational Vehicle Generator
GN-220 H/SH Engine – Drawing No. 0F5791 Part 1

	 42	

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
GN-220 H/SH Engine – Drawing No. 0F5791 Part 1

ITEM	

PART NO.	

	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	

0D8433	
0C1069	
090695F	
081810	
083312	
0D8400	
0C8917D	
0C8798A	
045756	
082774	
022129	
081990	
0D9004A	
072347	
022097	
082981	
081675	
0C1085	
0D7666A	
090051	
080316	
090948	
078631	
0F5759	
091846	
0D7558	
078643	
0D8372	
0C2756	
0D7458	
0C3979	
085953	
0D8739A	
036277	
0E7019	
083512	
082025	
092984	
094820	
089739	
091848	
0D8778	
0D8803	
0A8584	
070185B	
075281	
043182	
0D8397	
0D8591	
077091	
0A7095	
077075	
0C2824	

1	
2	
3	
4	
5	
6	
7	
8	
9	
10	
11	
12	
13	
14	
15	
16	
17	
18	
19	
20	
21	
22	
23	
24	
25	
26	
27	
28	
29	
30	
31	
32	
33	
34	
35	
36	
37	
38	
39	
40	
41	
42	
43	
44	
45	
46	
47	
48	
49	
50	
51	
52	
53	

QTY.	
1	
10	
1	
1	
1	
1	
1	
1	
10	
1	
2	
2	
1	
1	
2	
2	
1	
2	
1	
1	
2	
1	
1	
1	
1	
1	
2	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
2	
1	
1	
1	
2	
1	
1	
1	
2	
1	
2	

DESCRIPTION
GUARD, FAN
SCREW, HHTT M6-1.0 X 8mm
BLOWER HOUSING
NUT, HEX M16-1.5
WASHER, M16 CONICAL
ASSEMBLY, CHOKE SOLENOID BRACKET
FLYWHEEL, WITH RING GEAR
BACKPLATE, ELECTRIC START
SCREW HHTT M6-1.0 X 10mm
KEY, WOODRUFF 4 x 19D
5/16"-M8 LOCK WASHER
SCREW SHC M8-1.25 X 40mm
STARTER ASSEMBLY
SPARKPLUG
LOCKWASHER, ¼"- M6
TAPTITE, M6-1.0 x 30mm
ASSEMBLY, IGNITION COIL
SCREW PPHM M3-0.5 X 8mm
BREATHER TUBE
GASKET, MANIFOLD/ HEAD
SCREW HHFC M6-1.0 X 30mm
INTAKE MANIFOLD
GASKET CARBURETOR/MANIFOLD
CARBURETOR LP WITH CHOKE
GASKET, CARB/ ADAPTOR
ADAPTOR, CARB
BOLT, CARB MOUNT M6-1.0 x 75mm
GASKET, CARB TO AIRBOX
ASSEMBLY, GOVERNOR LEVER
ROD, GOVERNOR
SPRING, ANTI LASH
WASHER, CARB WEAR
ASSEMBLY BRACKET GOVERNOR ADJUST
ELBOW 90D STREET 1/8NPT
SPRING, GOVERNOR
SCREW HHTT M8-1.2 x 16mm
NUT HEX LOCK M5-0.8 NYLOCK
TOP WRAPPER
PLUG, EXPANSION
LOWER WRAPPER
GASKET, OIL PSI PAD
ADAPTER, OIL FILTER
SCREW SHC M6-1.0 X 22mm
SWITCH, OIL- 10 PSI
FILTER, OIL
SWITCH, THERMAL 284F
WASHER LOCK M3
ROD, CHOKE CONTROL
SOLENOID, CHOKE
PIN, COTTER
SCREW PRHMS #4-40 x 1-1/8" LONG
COVER, CHOKE COIL
SCREW TAP-R #10-32 X 9/16"

	

	 43

Appendix 3 — Exploded Views and Parts Lists

13
47

11

12

7

21

18

39

40

1

36
46

31
26

25
48

23
22

24
	 44	

43

42

50

28

13

44

45

30

17

4

32

20

34

37

5

49

38

41

35

16

15

19

1

29

52

8

10

7

51

2

3

6

9

10

Recreational Vehicle Generator
GN-220 H/SH Engine – Drawing No. 0F5791 Part 2

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
GN-220 H/SH Engine – Drawing No. 0F5791 Part 2

ITEM	

PART NO.	

	N/A	
	 1	
	 2	
	 3	
	 4	
	 5	
	 6	
	 7	
	 8	
	 9	
	 10	
	 11	
	 12	
	 13	
	 14	
	 15	
	 16	
	 17	
	 18	
	 19	
	 20	
	 21	
	 22	
	 23	
	 24	
	 25	
	 26	
	 27	
	 28	
	 29	
	 30	
	 31	
	 32	
	 33 	
	 34	
	 35	
	 36	
	 37	
	 38	
	 39	
	 40	
	 41	
	 42	
	 43	
	 44	
	 45	
	 46	
	 47	
	 48	
	 49	
	 50	
	 51	
	 52	

0F5800	
078621	
076389	
088411	
0A8897B	
077168	
088057	
076390	
083337A	
078658	
0F0967	
089213E	
0A7637	
0E3811	
0D1303	
078645	
0A7811	
072683A	
0F0687	
089096	
088156	
0A8822	
078691	
0A5772	
0A5776	
074908	
078606	
076361	
0D2414	
099922	
0C3733	
0C4390	
084186	
083192	
0E0057	
078699B	
021705B	
0C3590	
0C3591	
0D9853A	
083235	
080336	
0C8754	
077161	
077160	
076307	
088403	
026073A	
088412A	
076329	
0C3592	
049340	
045761A	

QTY.	
1	
1	
1	
1	
1	
5	
1	
2	
1	
1	
2	
1	
1	
2	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
4	
1	
6	
1	
2	
2	
2	
1	
1	
4	
1	
1	
1	
2	
2	
1	
1	
2	
2	
2	
1	
1	
1	
1	
4	
1	
1	

DESCRIPTION
LONG BLOCK ASSEMBLY 220 RV LP
CONNECTING ROD ASSEMBLY
PISTON PIN
PISTON RING SET
GEAR COVER ASSEMBLY
M8 x 56mm HEAD BOLT
PISTON
PIN RETAINER RING
TAPERED CRANKSHAFT ASSEMBLY
GOVERNOR "R" PIN
WASHER FLAT 1/4, .015 THK
CRANKCASE ASSEMBLY
GOVERNOR ARM
OIL SEAL
GOVERNOR GEAR ASSEMBLY
GOVERNOR GEAR C-RING
GOVERNOR SPOOL
1/8" NPT PIPE PLUG
CAMSHAFT ASSEMBLY
CRANKCASE GASKET
VALVE STEM SEAL
CYLINDER HEAD GASKET
OIL PRESSURE RELIEF COVER
OIL PRESSURE SPRING
11/32" BALL
M5 FORM SCREW
M6-1.0 x 12mm SCREW
GOVERNOR GEAR THRUST WASHER
SCREW, HHFC M8-1.25 X 35mm
SPRING WASHER
VALVE RETAINER
VALVE SPRING
VALVE SPRING WEAR WASHER
GEROTER SET
"O" RING
SLEEVE, SEAM DWL
CYLINDER HEAD ASSEMBLY
EXHAUST VALVE
INTAKE VALVE
PUSH ROD
TAPPET
OIL PICK-UP ASSEMBLY
ROCKER COVER GASKET
PIVOT BALL STUD
GN- 191/220 ROCKER ARM
ROCKER ARM JAM NUT
PUSH ROD GUIDE PLATE
1/4" NPT PIPE PLUG
ROCKER COVER ASSEMBLY
PLASTIC OIL FILL PLUG
VALVE SPRING KEEPER
BARBED ELBOW 90 1/4" NPT X 3/8"
STUD M8-1.25 / 10mm X 30mm

	

	 45

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
Regulator – Drawing No. 0F5819

2
3

4
5
6
1

9

8
7

26

10

14

11
15

12

16
17

13

19
20

18

21

22
23

24

25

	 46	

Appendix 3 — Exploded Views and Parts Lists
Recreational Vehicle Generator
Regulator – Drawing No. 0F5819

ITEM	

PART NO.	

	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	

0D5694	
0F4795	
0F5022	
0C6070	
0C4680	
0C4647	
0C4643	
0D3973	
0D7020A	
026073	
0D3308	
070728	
0C5764	
0C4643A	
0C5764	
0C5968	
0C5759	
0C5761	
0C6069	
0C6731	
0C6067	
0C4706	
0C6068	
0C5762	
045764	
0C5760K	

1	
2	
3	
4	
5	
6	
7	
8	
9	
10	
11	
12	
13	
14	
15	
16	
17	
18	
19	
20	
21	
22	
23	
24	
25	
26	

QTY.	
1	
4	
1	
1	
1	
1	
1	
1	
1	
2	
2	
2	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
1	
8	
1	

DESCRIPTION
CASTING, TWIN REGULATOR HOUSING
SCREW PPHM SEMS M4-0.7 X 10
SOLENOID COIL, 12VDC
SPRING-SOLENOID PLUNGER
PLUNGER LP REG. ASSY
GASKET, SOLENOID
INLET, TWIN REGULATOR NO HOLE
PLUG, EXPANSION 16MM TWINREG
BARBED STR 1/2NPT X 3/8" W/VS
PLUG STD PIPE 1/8 STEEL SQ HD
WASHER FLAT 3.2MM ID X 10MM OD
SCREW PFILHM M3-0.5 X 5
SPRING, REGULATOR
INLET, TWIN REG 11.11 DIA.
SEAL, INLET REGULATOR
SUPPORT, INLET SEAL
PIN, PIVOT ARM
LEVER, REGULATOR
GASKET, DIAPHRAGM
RIVET .118 X .125 ALUMINUM
SUPPORT, DIAPHRAGM
DIAPHRAGM, TWIN REGULATOR
CAP, DIAPHRAGM SUPPORT
COVER,TWIN REGULATOR
SCREW HHTT M4-0.7 X 8 BP
JET LP

	

	 47

Appendix 4 – Warranty
Recreational Vehicle Generator

CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and the United States Environmental Protection Agency (EPA), together with
Generac Power Systems, Inc. (Generac), are pleased to explain the Emission Control System Warranty on your new engine.*
New utility, and lawn and garden equipment engines must be designed, built and equipped to meet stringent anti-smog
standards for the state of California and the federal government. Generac will warrant the emission control system on your
engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper
maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition and exhaust systems. Generac will repair
your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.

MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1997 and later model year engines are warranted for two years as hereinafter noted. If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.

PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance
on your engine. However, Generac cannot deny warranty solely because of the lack of receipts or for your failure to ensure
the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect, improper maintenance or unapproved modifications, or the use of counterfeit and/or ‘grey market’ parts not made, supplied or approved by Generac.
You are responsible for presenting your engine to a Generac Authorized Warranty Service Facility as soon as a problem
occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:

1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California and federal law. See also the “Generac
Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you
by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in
terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where
the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe
important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner. The purchaser/owner shall
be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the
inspection or repair facilities. The purchaser/owner also shall be responsible for any and/or all damages or losses incurred
while the engine is being transported/shipped for inspection or warranty repairs.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the following address:

Attention Warranty Department
Generac Power Systems, Inc.
P.O. Box 297
Whitewater, WI 53190
Part 1

	 48	

Appendix 4 – Warranty
Recreational Vehicle Generator

EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1997 and later model year engines:
(a) Applicability: This warranty shall apply to 1997 and later model year engines. The ECS Warranty Period shall begin on
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue
for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment, and to each subsequent purchaser/owner, that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the EPA and CARB pursuant
to their respective authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a
warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine
manufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace
as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty
shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the purchaser/owner. Such use shall not reduce
Generac’s ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or ‘grey market’ parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of
such an unapproved, add-on, modified, counterfeit and/or ‘grey market’ part.

EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.1) Gasoline carburetor assembly and its
internal components (if so equipped).
a) Fuel filter (if so equipped)
b) Carburetor gaskets
c) Fuel pump (if so equipped)
1.2) LPG carburetion assembly and its
internal components (if so equipped).
a) Fuel controller (if so equipped)
b) Mixer and its gaskets (if so equipped)
c) Carburetor and its gaskets (if so equipped)
d) Primary gas regulator (if so equipped)
e) LP liquid vaporizer (if so equipped)

2) Air Induction System including:
a) Intake pipe/manifold
b) Air cleaner
3) Ignition System including:
a) Spark plug
b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including:
a) Muffler gasket
b) Exhaust manifold
5) Crankcase Breather Assembly including:
a) Breather connection tube

*Generac engine types covered by this warranty statement include the following:
1) Utility
2) Lawn and Garden Equipment
3) Recreational Vehicle (RV) Generator
4) Industrial Mobile (IM) Generator
Part 2

	

	 49

Appendix 4 – Warranty
Recreational Vehicle Generator

GENERAC POWER SYSTEMS’ Three-YEAR LIMITED WARRANTY
FOR Guardian Recreational Vehicle Generators
NOTE: All units must be installed by Generac Power Systems Authorized Service Facilities. For a period
of 3 (three) years of operation from the date of original sale, Generac Power Systems, Inc. (Generac) will, at its option, repair or
replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Facility, is
found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that
the purchaser/owner claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service
Facility. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner.
This warranty applies only to Generac generators sold and rated for “Recreational Vehicle” (RV) applications, as Generac has defined
Recreational Vehicle generator applications. The factory recommends exercising the unit one half-hour every month.

WARRANTY SCHEDULE – Commercial Applications

	 YEAR ONE – 100% (one hundred percent) coverage on part(s), labor, removal and reinstallation listed:
• 	 Engine – All components
• 	 Alternator – All components

WARRANTY SCHEDULE – Consumer/Personal Applications

	 YEARS ONE AND TWO – 100% (one hundred percent) coverage on part(s), labor, removal and reinstallation listed:
• 	 Engine – All components
• 	 Alternator – All components
	 YEAR Three – 100% (one hundred percent) only on selected part(s) and labor listed [Any labor and part(s) not listed, and removal
and reinstallation are the owner’s responsibility]:
• 	 Rotor, Stator, Computer Control Board (part numbers 0A6060 and 0A3369) and inverter, (if applicable with regard to the generator)
Cylinder Block, Cylinder Head, Crankshaft, Piston(s), Valve, Valve Lifter(s), Intake and Exhaust Manifolds
Generac RV generators manufactured prior to December 31, 1997, DO NOT have a transferable warranty. Generac RV generators
manufactured after January 1, 1998, have a transferable warranty to the second owner only for the remainder of the three-year
limited warranty. Proof-of-purchase is required and must be presented to a Generac Authorized Warranty Service Facility prior to the
performance of any warranty service.
All warranty expense allowances are subject to the conditions defined in Guardian’s Warranty Policies and Procedures Guide.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
•	 Generac Guardian generators that utilize non-Generac replacement parts.
•	 Costs of normal maintenance, adjustments, installation and start-up.
•	 Repairs or diagnostics performed by individuals other than Guardian/Generac authorized dealers not authorized in writing by
Generac Power Systems.
•	 Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
•	 Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all
mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not
cover repair when normal use has exhausted the life of a part(s) or engine.
•	 Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire,
freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
•	 Damage related to rodent and/or insect infestation.
•	 Products that are modified or altered in a manner not authorized by Generac in writing.
•	 Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or
replacement of the defective part(s).
•	 Failure due to misapplication.
•	 Telephone, cellular phone, facsimile, internet access or other communication expenses.
•	 Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty
period.
•	 Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
•	 Rental equipment used while warranty repairs are being performed.
•	 Overnight freight costs for replacement part(s).
•	 Overtime labor.
•	 Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO
OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow
limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL
GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT
RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages,
so the above limitation may not apply to you.
This warranty gives you specific legal rights. You also have other rights from state to state.
P.O. BOX 297 • WHITEWATER, WI 53190
Part No. 0F4594

Revision 0 (06/29/05)

Revision 02.05

Printed in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Tagged PDF                      : Yes
XMP Toolkit                     : 3.1.1-111
Instance ID                     : uuid:42ac09d6-c245-4920-adf6-fad05cf8ffb2
Document ID                     : adobe:docid:indd:5b283d66-e70e-11d9-8537-9245cb9abbc5
Rendition Class                 : proof:pdf
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:FABD599540E7D911BCE3F87DDD7EA275, uuid:146D4D060FE8D911A593AE9E6BB75254, uuid:186D4D060FE8D911A593AE9E6BB75254, uuid:D2317A5A39E7D9118644C4F84F49435F, uuid:D4317A5A39E7D9118644C4F84F49435F, uuid:D4317A5A39E7D9118644C4F84F49435F, uuid:C264EB8B50E7D911BC86914CADF946F8, uuid:F4BD599540E7D911BCE3F87DDD7EA275, uuid:F6BD599540E7D911BCE3F87DDD7EA275
Manifest Reference Document ID  : uuid:F9BD599540E7D911BCE3F87DDD7EA275, uuid:126D4D060FE8D911A593AE9E6BB75254, uuid:176D4D060FE8D911A593AE9E6BB75254, uuid:D1317A5A39E7D9118644C4F84F49435F, uuid:D3317A5A39E7D9118644C4F84F49435F, uuid:D3317A5A39E7D9118644C4F84F49435F, uuid:C164EB8B50E7D911BC86914CADF946F8, uuid:F3BD599540E7D911BCE3F87DDD7EA275, uuid:F5BD599540E7D911BCE3F87DDD7EA275
Create Date                     : 2005:06:29 10:58:46-05:00
Modify Date                     : 2005:06:29 10:59:18-05:00
Metadata Date                   : 2005:06:29 10:59:18-05:00
Creator Tool                    : Adobe InDesign CS2 (4.0)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 10681 bytes, use -b option to extract)
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 52
Creator                         : Adobe InDesign CS2 (4.0)
EXIF Metadata provided by EXIF.tools

Navigation menu