HES 3026006.002, Pages 1 4 Rev B 9400 Series Installation Guide 9500 9600Installation Instructions

User Manual: HES HES 9400 Series Installation Guide Installation Guide

Open the PDF directly: View PDF PDF.
Page Count: 2

9400 / 9500 / 9600 Series Electric Strikes
Installation Instructions
HES, Inc.
Phoenix, AZ
800-626-7590
www.hesinnovations.com
1
Electrical Specifications
Minimum Wire Gauge Requirements
(Based on Round Trip)
Solenoid Voltage
12 VDC 24 VDC
200 feet or less
200 – 300 feet
300 – 400 feet
18 gauge
16 gauge
16 gauge
22 gauge
22 gauge
20 gauge
3
5
ASSA ABLOY, the global leader
in door opening solutions
Product Components
#10-32 & 10-24 Lockdown Screws (optional)
1
2
9400 / 9500 / 9600 Electric Strike Body
9400 / 9500 / 9600 Cover
4
Electrical Ratings for Solenoid
Continuous Duty 12 VDC
24
.50
24 VDC
96
.25
Resistance in Ohms
Amps
Solenoids are rated at +/- 10% indicated value.
4
4
Frame Preparation
9"
[228.6]
Centerline of Latchbolt
This edge toward door
2X Mounting Hole
Locations for
1/4-20 UNC Mounting Screws
7/8"
[22.5]
4-1/8"
[104.8]
1-3/4"
[44.5]
Clearance for
Power Wiring
Final Lockdown Feature
10-32 UNF or 10-24 UNC Screw (optional)
1-1/16"
[27.0]
4-1/8"
[104.8]
4X
[33.3]
1-5/16"
[33.3]
1-5/16"
1. LOOSEN the two 1/4”-20 x 1“ mounting screws.
2. ADJUST strike to appropriate horizontal position.
3. TIGHTEN the two 1/4”-20 x 1“ mounting screws.
4. LOCK DOWN adjustment by tightening the set screws.
Inches [mm]
3/4” [19]
Clearance for
LBM/LBSM Wiring
1/2” [12.7]
© 2014, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company.
3026006.002 rev B
12
7
Lockdown
Screw
(optional)
Set Screw
Location
Set Screw
Location
Mounting
Screw
Mounting
Screw
ATTACH the cover using the #6-32 x 1/4” Cover Screws.
5
6
#6-32 x 1/4” Cover Screws
5/64” Hex Key
7
12-Volt and 24-Volt Pigtails
6
1/4”-20 x 1” Mounting Screws
3
Deadlatch Vertical Alignment
Note: May not be to
scale. For easy installation,
the template should be
ordered.
Adjusting Horizontal and Lockdown
Installing the Cover
5. INSTALL the #10-32 UNF or 10-24 UNC lockdown
screw (optional).
7/8”
[22.5]
Diagram 1: Product Components
2
Installation
Note: For 12 VDC, the Plug In Connector (pigtail)
marked “12 VDC” should be used; for 24 VDC, the
pigtail marked “24 VDC should be used.
1. SELECT the appropriate pigtail that matches system
power and electrically CONNECT as illustrated in
Diagram 2.
2. If no connector is present, CONFIGURE the wires as
illustrated in Diagram 2.
3. If using the Latchbolt Monitor (LBM) or Latchbolt
Strike Monitor (LBSM), REFER to Diagrams 3 and 4 on
Page 3 to complete wiring.
Note: The 9400/9500/9600 ships in FAIL SECURE
OPERATION mode.
4. USE Diagrams 5 and 6 on Page 3 as a guide to
convert 9400/9500/9600 to FAIL SAFE OPERATION, if
needed.
CAUTION!
Before connecting any device at the installation site, verify input voltage using a multimeter.
Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding
10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
Note: When using a Corbin Russwin Series 5000 or
Yale 7000 series equipped with an offset deadlatch,
the deadlatch is located just above the Deadlatch
Vertical Alignment line as shown on the Installation
Template on Page 4.
5. PREPARE the door jamb using the Installation
Template located on Page 4 (with the exception of
the hole for final lockdown).
3
Installation (continued)
LBM Wiring
White
Orange Normally Open
Green Normally Closed
Common
Normally Open
Yellow Normally Closed
DIAGRAM 5: CYLINDRICAL LOCKSETS
LBSM Wiring
Brown
Blue Normally Open
Yellow Normally Closed
Common
Note 1: The 9400/9500/9600 series Electric
Strikes are pre-set for FAIL SECURE OPERATION
as shown in Diagram 5.
Note 2: There are Selector Stop Pins, one on
the left side and one on the right side. Both
Selector Stop Pins must be repositioned to
convert the strike to FAIL SAFE OPERATION.
1. To convert to FAIL SAFE OPERATION,
REMOVE the Selector Stop Pins on each side of
the strike body using the 5/64” hex key
provided.
2. MOVE the Selector Stop Pins to the FAIL
SAFE OPERATION position as pictured
(towards the center of the strike) in
Diagram 6.
3. TIGHTEN both Selector Stop Pins after they
have been moved to the FAIL SAFE OPERATION
position using the 5/64” hex key.
Note: Both keepers should be unlocked
without power, but lock when power is
applied.
4. VERIFY that both keepers are in FAIL SAFE
OPERATION.
Diagram 6: FAIL SAFE OPERATION
Diagram 5: FAIL SECURE OPERATION
Selector Stop
Pin Location
Selector Stop
Pin Location
Brown
Blue
Yellow
White
Orange
Green
RED
RED/GREEN
BLACK
VIOLET
RED
BLACK
VIOLET
RED/GREEN
IF CONNECTOR IS MISSING
(+ 12 VDC)
(-NEG)
(+ 24 VDC)
(-NEG)
or
Electric
Strike
Electric
Strike
CONNECT
TOGETHER
CONNECT
TOGETHER
CONNECT
TOGETHER
6. Electrically CONNECT the 9400/9500/9600 to the
Plug In Connector, and ATTACH the electric strike to
the jamb using the 1/4”-20 x 1“ mounting screws
provided.
7. CHECK latchbolt interaction to determine if hori-
zontal adjustment is needed, and ADJUST as needed.
LOCK DOWN the horizontal adjustment using the
#10-32 set screws as illustrated on Page 4.
8. OPTIONAL LOCKDOWN FEATURE: INSTALL the
#10-24 UNC or 10-32 UNF lockdown screw if
additional security is required. REMOVE the strike
before drilling hole.
9. INSTALL the cover plate, and FIX in place using the
#6-32 x 1/4” Cover Screws as illustrated on Page 4.
Preparing the Strike
Finishing the Installation
Preparing the Frame
Converting the Operation ModeConverting the Operation Mode