Installation manual
for room air conditioner

HSU-26HEK03/R2(DB)/I
HSU-35HEK03/R2(DB)/I
HSU-53HEK03/R2(DB)/I
HSU-71HEK03/R2(DB)/I
HSU-26HEK03/R2(DB)/O
HSU-35HEK03/R2(DB)/O
HSU-53HEK03/R2(DB)/O
HSU-71HEK03/R2(DB)/O
Read this manual before installation and keep it for future reference.
Please explain to the user how the product works and refer them to the operation manual.
NO.0010553937

Content

2

Preparation

p3

Accessory parts

p3

Selection pipe

p3

Drawing for the installation of indoor and outdoor units

p3

Indoor unit

p5

Outdoor unit

p6

Refrigerant charge label

p8

Check for installation and test run

p8

Preparation

Accessory parts
Remote controller (1)

Drain hose (1)

Driver

AAA dry battery (2)

Cushion (4)

Nibbler

Mounting plate (1)

Drain-elbow (1)

Plastic cap (4)
Ø4X25 Screw (4)

Pipe supporting plate (1)

Necessary tools for installation

Hacksaw
Hole core drill
Spanner (17,19 and 26mm)
Gas leakage detector or soap-and-water solution
Vacuum pump
Torque wrench (17mm, 22mm, 26mm)
Pipe cutter
Flaring tool

Selection of pipe

Knife

Model

Measuring tape

HSU-26HEK03/R2(DB)/O

")

9.52mm (3/8")

Reamer

HSU-35HEK03/R2(DB)/O

")

9.52mm (3/8")

Refrigeration gauges

HSU-53HEK03/R2(DB)/O

")

12.7mm (1/2")

HSU-71HEK03/R2(DB)/O

")

15.88mm (5/8")

Power source

Liquid pipe (Ø)

Gas pipe (Ø)

NOTE: The thickness of the pipe must be at least 0.8mm.

Install an exclusive circuit for the power.
Check the power source voltage is the same as the rating plate.

Selection of installation place
Indoor Unit
The place chosen to install the indoor unit should be:
Not affected by heat or steam generated in the vicinity, where inlet and outlet
of the unit are not blocked or restricted.
Where it is possible to drain easily, and where piping can be connected
with the outdoor unit.

Power requirements
Model

Max rated current

HSU-26HEK03/R2(DB)/O

6.1

HSU-35HEK03/R2(DB)/O

6.0

HSU-53HEK03/R2(DB)/O

10.5

HSU-71HEK03/R2(DB)/O

13.8

Where conditioned air can be evenly distributed through the whole room.
Where there is more than 1m distance from televisions, radios, wireless

are on.

Outdoor Unit
The place chosen to install the outdoor unit should be:
Strong enough to bear the unit, where vibration and noise are not increased.
Where discharged air and noise do not cause a nuisance to the neighbours.
Where a distance marked

3

Drawing for the installation of indoor and outdoor units

Attention must be
paid to the rising up
of drain hose

More than 5cm (26/35/53)
More than 10cm (71)

Optional parts for piping
A Non-adhesive tape
B Adhesive tape
C Saddle (L.S.) with screws
D Connecting electric cable
for indoor and outdoor

G

More than 10cm

E Drain hose
F Heating insulating material
G Piping hole cover

Arrangement of
piping directions

More than 10cm

Rear
right

Left

the outdoor unit (Unit:mm)

F

Rear left

A

Z

Right
Below

C

X

More than 10cm (26/35/53)

Y

X

More than 15cm (71)
More than 10cm (26/35/53)

Model

More than 20cm (71)

y

z

140

500

256

HSU-35HEK03/R2(DB)/O

140

500

256

HSU-53HEK03/R2(DB)/O

113.5

583

319.5

HSU-71HEK03/R2(DB)/O

113.5

633

340

HSU-26HEK03/R2(DB)/O

A and G are supplied parts

D

pipe length is 2m.

Dimensions
x

Fixing of outdoor unit
E

Fix the unit to concrete or block with
horizontally.

More than 60cm

earthquake or strong wind.
More than 15cm (9/12/18)
More than 25cm (24)

unit by attaching
a vibration-proof mat.

The picture above is just for your reference. Please refer to the actual product purchased.

4

Indoor Unit
1 Fitting of the Mounting Plate and Positioning of the Wall Hole

2 Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of ‘B’mm in diameter, slightly descending to outside the wall.

1. Find a suitable mounting location, ensuring there is adequate support to hold
the weight of the unit, check it is level, then temporarily fasten the plate.

Install piping hole cover and seal it off with putty after installation.
Wall hole

2. Check the plate is level, by hanging a thread with a weight from
the central top of the plate or using a spirit level, then fasten securely.

ØBmm

3. Determine the wall hole location ‘A’ using a measuring tape.

Indoor side

(Section of wall hole)

Thickness of wall

Outdoor side

G Piping hole pipe

3 Installation of the Indoor Unit

Drawing of pipe
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with adhesive tape

[ Left Left-rear piping ]

HSU-26HEK03/R2(DB)/I

In case of left side piping, cut away, with a nibbler, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the
mark of hole for left-rear piping which is marked on heat insulation materials.

938

245

245

20

20

60

100

2. Insert the indoor/outdoor electric cable from the back of the indoor unit, and
pull it out on the front side, then connect them.
3. Coat the
seal face with refrigerant oil and connect pipes. Cover the
connection part with heat insulation materials, and
it with adhesive tape.

60
480

229

Indoor/outdoor electric cable

110

Heat insulation
material

HSU-35HEK03/R2(DB)/I

Lid for right
piping
Lid for under piping pipe

Lid for left piping

Drain hose

Piping
Pipe supporting
plate

1046

268
13

13

268

299

Fix with adhesive tape

70

85

191

70
667

135

Indoor/outdoor electric cable and drain hose must be bound with refrigerant
piping by protecting tape.

[ Other direction piping ]
Cut away, with a nibbler, the lid for piping (according to the piping direction)
and then bend the pipe according to the position of wall hole. When
bending, be careful not to crush the pipes.
Connect the indoor/outdoor electric cable.

HSU-53HEK03/R2(DB)/I

Fixing the indoor unit body
Hang the unit body onto the upper notches of the
mounting plate. Move the body from side to side to
it is
securely.

12

12

260

260

1156

320

265

1. Insert the drain hose into the cavity of heat insulation materials of indoor unit.

70

40
138

70
860

105

HSU-71HEK03/R2(DB)/I

In order to
the body onto the mounting plate,hold
up the body on an angle from the underside and
then pull it down perpendicularly.

mounting plate

Unloading of indoor unit body
When you remove the indoor unit,
use your hand to raise the
body from the hooks, then lift the
bottom of the body outward
slightly and lift the unit on an angle
until it separates from the mounting plate.

Hooks mounting plate

Fix a mounting bar to the side bar and lintel (sold separately), and then fasten
mounting bar.
the plate to the
Refer to note 1, “ When the mounting plate is

“, for the position of wall hole.

5

Indoor unit cont.

DRED Function
6.Please consult your reseller and/or installer to determine if you have a DRED appliance.
Connect output from your home's electricity power meter (where available) to the RJ45
connector on the outdoor unit, as shown.

4 Connecting the indoor/outdoor Electric Cable

Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit,
then take off wiring cover by removing its screws.

(This function is unavailable on some models.)

When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall
hole, in which the pipe is fitted or installed.
2. Pull out the cable on the front side, and connect the cable
making a loop.

When connecting the cable before installing
the indoor unit
Loosen the screws and insert the cable ends fully into terminal block,
then tighten the screws.
Pull the cable slightly to make sure the cables have been properly
inserted and tightened.
After the cable connection, always fasten the connected cable
with the wiring cover.

1 Installation of Outdoor Unit
Install according to ‘Drawing for the installation of indoor and outdoor units’
(see page 4)

2 Connection of pipes
To bend a pipe, use the correct bending tool, so as not to crush the
pipe, and the bending radius should be 30 to 40 mm or longer.
Connect the pipe gas side

Note

the terminal number of indoor
When connecting the cable,
and outdoor units carefully. If wiring is not correct, the system will
not operate correctly. Damage to the PCB due to incorrect
wiring is not covered by warranty.

The connection pipe is specialized for R410A.

Half union

Flare nut

Forcedfastening
fasteningwithout
without careful
careful centering
Forced
centeringmay
may
damagethe
thethreads
threadsand
and cause
cause a leakage of
damage
of gas.
gas.

Pipe Diameter( )

Pipe diameter (Ø)

Electrical connection
Outdoor unit

Indoor unit

Spanner

Fastening torque

Fastening torque

Liquid side6.35mm(1/4")
Liquid side 6.35mm (1/4")
18 N.m
Liquid/Gas side9.52mm(3/8")
Liquid/Gas side 9.52mm (3/8") 42 N.m
Gas side 12.7mm(1/2")
Gas side 12.7mm (1/2")
55 N.m
Gas side 15.88mm(5/8")
Torque wrench
Gas side 15.88mm (5/8")
60 N.m

18N.m

42 N.m
55N.m
60 N.m

Be careful that foreign materials such as sand, etc. do not enter the pipe. The
charge of refrigerant must be conducted by professional air conditioner engineer.
Before adding additional refrigerant, perform air evacuation from the refrigerant
pipes and indoor unit using a vacuum pump, then charge additional refrigerant.

4G0.75mm2

CAUTION
Power cable:

3G1.5mm

POWER

2

Outdoor unit

HSU-26HEK03/R2(DB)/O
HSU-35HEK03/R2(DB)/O

B

A

1

Indoor unit

Indoor unit

B

Outdoor unit

2

A

3(C)

3G2.5mm

Outdoor unit

B

1. If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similar qualified person. The type of connecting wire
and power cable is H05RN-F or H07RN-F.

Oil trap

A

HSU-53HEK03/R2(DB)/O
HSU-71HEK03/R2(DB)/O

Indoor unit

In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7m
Max. Length: Bmax
= 15m (HSU – 26/35)
= 25m (HSU – 53/71)

Pre charge
Base charge pipe length

Additional
charge amount

2. If the PC board fuse is broken replace with a T.3.15A/250VAC (Indoor)
or T.25A/250VAC (Outdoor).

Model

3. The wiring method should be in line with the local and national wiring
standards.

HSU-26HEK03/R2(DB)/O

1000g

7m

20g/m

HSU-35HEK03/R2(DB)/O

1080g

7m

20g/m

4. After installation, the power isolator should be easily reached.

6

Max.Elevation: Amax
= 10m (HSU – 26/35)
= 15m (HSU – 53/71)

Outdoor unit

2N

Power cable:

{

1L

POWER
2

( )

2

( )

4G0.75mm

Indoor unit

wiring. The breaker should be
5. A breaker should be incorporated into
all-pole switch and the distance between its two contacts should be not less
than 3mm.

HSU-53HEK03/R2(DB)/O

1550g

10m

20g/m

HSU-71HEK03/R2(DB)/O

2100g

10m

50g/m

Outdoor unit cont.
33 Connection of Electrical Cable
Use the same method on indoor unit. Loosen the screws on terminal block
and insert the plugs fully into terminal block, then tighten the screws.

Step 4
Open the 2-way valve to an angle of anticlockwise 90 degrees.
After 6 seconds, close the 2-way valve and test for refrigerant gas leakage.

If wiring is not correct, proper operation can not be carried out and the
controller may be damaged.

2-way valve

Fix the cable with a clamp.

3-way valve
O

4 Attaching Drain-Elbow

Open 90

If the drain-elbow is used,
please attach it as
(Note: Only for heat pump unit.)

Step 5
No gas leakage? If ok, proceed to Step 6.

455 Evacuation Method: Use vacuum pump

Step 1
Remove the service port cap from the 3 way valve, the valve caps for the
2 way & 3 way valves. Connect hose to the service port (low) side of the
manifold gauge.
Then connect the centre hose from the manifold gauge to the vacuum pump.

In case of refrigerant leakage, tighten parts of pipe connections. If leakage
stops, then proceed to Step 6.

If this does not stop gas leakage, reclaim all refrigerant from the service
and repeating vacuuming on the system, with the
port. After
prescribed refrigerant level. Check again for leaks.

2-way valve Liquid Side
3-way valve Gas Side
Gauge manifold (for R410A)

Step 6
Detach the charge hose from the service port, open 2-way valve and 3-way valve.
Turn the valve anticlockwise until closed.

2-way valve
3-way valve
Tube (for R410A)

Vacuum pump (for R410A)

Step 2
Open the tap on the low side of the manifold and operate the vacuum pump.
If the gauge (low) reaches a vacuum immediately repeat step 1 above again.

Step 7
To prevent refrigerant leakage, tighten the service port’s taps and caps to ensure
sealed.
they are

2-way valve
3-way valve

Open

Valve rod cap

Step 3
Vacuum for over 15min. Check the (low) gauge which should read
-0.1 MPa (-76 cm Hg) at Iow pressure side. After completion of vacuuming
the system, close the low tap on the manifold and turn off the vacuum pump.
Check the low side gauge to see if it holds for 1-2 min. If the gauge does not
and return to the beginning of Step 3.
hold pressure, check all the

Close

Service port cap

Valve rod cap

Step 8
After

the caps, check for refrigerant gas leakage around the caps.

CAUTION
If the refrigerant of the air conditioner leaks, it is necessary to reclaim all
the refrigerant, then pull a vacuum BEFORE recharging the refrigerant into
the air conditioner according to the amount marked on the name plate.
Please do not charge with refrigerant, except as
(R410A), or
allow air to enter into the cooling circulation system. Otherwise, this may
cause abnormal high pressure in the system which may lead to personal
injuries or damage to piping.

7

Outdoor unit cont.

Refrigerant charge label
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol

1 Power Source Installation
The air conditioner must be wired with a dedicated circuit to the distribution
board. The protection device should be sized to meet the current
requirements of the unit as shown on page 3 and comply with local and
national wiring standards.

R410A

1=

kg

2

2=

kg

1+2=

kg

1

If installing the air conditioner in a moist place, please install an earth
leakage breaker.

F

A
B
C
D

E

For installation in other places, use a circuit breaker.
Protocol. Do not vent into the atmosphere.

2 Cutting and Flaring Work of Piping

Refrigerant type: R410A
GWP* value:1975

Pipe cutting is carried out with a pipe cutter and burrs must be removed.

A

Flare tool for R410A

Conventional flare tool

Clutch-type

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

0~0.5mm

1.0~1.5mm

1.5~2.0mm

1.Cut pipe

Flare tooling die

GWP=global warming potential

2.Remove burs

be adhered in the proximity of the product charging port (e.g. onto the inside of the
stop value cover).
A
B factory refrigerant charge of the product: see unit name plate
C
D total refrigerant charge

3.Insert the flare nut

4.Flare pipe

E outdoor unit
F refrigerant cylinder and manifold for charging

Check for installation and test run
Correct

Incorrect

Lean

Damage of flare

Crack

Please kindly explain to our customers how to operate the unit through
the instruction manual.
Partial

Too
T outside

Check items for test run

Put check mark

in boxes

Gas leak from connecting pipe?

3 On Drainage

Insulation of pipe connecting
Pp ?

Please install the drain hose to be always sloping downhill.
Examples of incorrect

Are the indoor and outdoor interconnecting cables
interconnecting cables

Less than
5cm
It becomes The end is imm- It waves. The gap with the
There is the bad
high midway. ersed in water.
ground is too small. smell from a ditch

Is drainage securely carried out?
Is the earth line securely connected?

Is power source voltage correct?
Is there any noise?

condensate is carried to outdoor.
In case that the attached drain hose is in a room, please apply
insulation to drain
.

Is the indicator lamp lit?
Are cooling and heating (when in heat pump) performing normally?
Is the operation of room temperature adjustment normal?

8



Source Exif Data:
File Type                       : AI
File Type Extension             : ai
MIME Type                       : application/vnd.adobe.illustrator
PDF Version                     : 1.6
Linearized                      : No
Author                          : 01339437
Modify Date                     : 2015:06:12 11:50:37+10:00
Create Date                     : 2015:03:03 11:17:59+08:00
For                             : ,
Bounding Box                    : 0 0 638 884
Creator Version                 : 14
Container Version               : 11
Page Count                      : 8
Has XFA                         : No
XMP Toolkit                     : XMP Core 4.1.1
Metadata Date                   : 2015:05:07 16:46:46+08:00
Creator Tool                    : PScript5.dll Version 5.2
Page Image Page Number          : 1, 2
Page Image Format               : JPEG, JPEG
Page Image Width                : 256, 256
Page Image Height               : 256, 256
Page Image                      : (Binary data 6433 bytes, use -b option to extract), (Binary data 4878 bytes, use -b option to extract)
Thumbnail Width                 : 188
Thumbnail Height                : 256
Thumbnail Format                : JPEG
Thumbnail Image                 : (Binary data 15871 bytes, use -b option to extract)
Document ID                     : uuid:970C09E253C1E4119132E1BA2C1AFAC7
Instance ID                     : uuid:edb07fab-a8e1-4d65-b198-930da8307cf0
Derived From Instance ID        : uuid:53171bd9-39f5-4dc4-85b7-3dd923a0f6af
Derived From Document ID        : xmp.did:70A23B51225AE211BCF793A4E6DBECDF
Derived From Rendition Class    : proof:pdf
N Pages                         : 1
Has Visible Transparency        : False
Has Visible Overprint           : True
Max Page Size W                 : 224.816941
Max Page Size H                 : 311.816626
Max Page Size Unit              : Millimeters
Font Name                       : ArialNarrow, Arial-BoldMT, ArialMT, TradeGothicLTStd, AdobeSerifMM, Arial
Font Family                     : Arial, Arial, Arial, TradeGothicLTStd, AdobeSerifMM, Arial
Font Face                       : Narrow, Bold, Regular
Font Type                       : Open Type, Open Type, Open Type, Unknown, Unknown, Unknown
Font Version                    : Version 2.37, Version 3.00, Version 3.00, Version 3.12, Version 3.12, Version 3.12
Font Composite                  : False, False, False, False, False, False
Font File Name                  : ARIALN.TTF, ARIALBD.TTF, ARIAL.TTF, simsun.ttc, simsun.ttc, simsun.ttc
Plate Names                     : Cyan, Magenta, Yellow, Black
Swatch Group Name               : 默认色板组
Swatch Group Type               : 0
Doc Change Count                : 5100
Format                          : application/pdf
Title                           : <303031303533383431325FB0B2D7B0CBB5C3F7CAE92E706466>
Creator                         : 01339437
Producer                        : PDF-XChange Viewer [Version: 2.0 (Build 47.0) (Feb 17 2010; 18:30:51)]
Image Height                    : 884
Image Width                     : 638
Image Size                      : 638x884
Megapixels                      : 0.564
EXIF Metadata provided by EXIF.tools

Navigation menu