Heat Controller Hag Series For R 410A Quick Start Guide IOM 04 12 09

Heat-Controller-Iom-Hag-06-15-09-Quick-Start-Guide heat-controller-iom-hag-06-15-09-quick-start-guide

2014-07-19

: Heat-Controller Heat-Controller-Hag-Series-For-R-410A-Quick-Start-Guide heat-controller-hag-series-for-r-410a-quick-start-guide heat-controller pdf

Open the PDF directly: View PDF PDF.
Page Count: 7

DownloadHeat-Controller Heat-Controller-Hag-Series-For-R-410A-Quick-Start-Guide IOM HAG 04-12-09
Open PDF In BrowserView PDF
A. Introduction

C. Unpacking the Unit

Heat Controller, Inc., Air Handlers come in a variety of models and
sizes for upflow or horizontal use and when combined with cooling coils, are ready for air conditioning and heat pump applications.
These instructions are primarily to assist qualified individuals trained
and experienced in the proper installation of this type of equipment.

The unit should be unpacked on receipt and if damage is found,
a claim should be made immediately to the shipping carrier. This
is the responsibility of the entity receiving the equipment. The air
handler is completely assembled, as received. Electric power, thermostat wiring, refrigerant piping and duct connections are needed
to complete an installation. Additionally, a drain connection will
be needed.
Check the rating plate for unit size, voltage, phase etc. to make
sure unit meets your requirements.

B. Rules for Safe Installation and Operation
1. Read these rules and the instructions carefully. Failure
to follow the rules and the instructions could cause a
malfunction of the unit, and a possible safety hazard.
Keep these instructions nearby the unit for future
reference.
2. This unit has been designed and manufactured to comply
with National Codes; however, it is the installer’s
responsibility to install this unit to comply with
prevailing codes and regulations. Heat Controller, Inc.,
assumes no responsibility for units installed in violation
of any code or regulation.
3. Before servicing, ALWAYS SHUT OFF
ELECTRICITY TO THE UNIT. This will prevent any
electrical shocks.
4. Ground the unit to prevent electric shock. All electrical
wiring should be in accordance with the National
Electrical Code.
5. Duct work must be installed in accordance with the
standards of the National Fire Protection Association
(NFPA) for the installation of Air Conditioning, Warm
Air Heating and Ventilating Systems (NFPA 90A and
90B). The air distribution duct system should be sized for
0.2 inches of static pressure. See National Environmental
Systems Contractors Association Manual K for duct
sizing recommendations. Ductwork in non-conditioned
spaces must be insulated to prevent formation of
condensate and for maximum operating efficiency.
6. The safety testing agency label appearing on the unit
covers the unit and factory installed coil(s) only. It does
not cover any other equipment.
7. Exterior surface of cabinet may sweat when unit is installed
in non-conditioned space such as attic or garage. Installer
must provide protection such as full size auxiliary drain
pan on all units installed in non-conditioned space such as
attic or garage type installations to prevent damage from
condensation. It is recommended that units installed in
non-conditioned space be insulated on the outside with 1”
thick fiberglass with the vapor barrier on the outside.
8. While designed to operate quietly when properly installed,
several steps should be taken to insure this. Use of
isolation pads when mounting unit, flexible duct collars
for discharge, and use of acoustical duct liners are all
good installation practices that promote quiet operation.
9. Cabinet insulation is rated for R=4.2 (standard). Some
jurisdictions require R=6.0 on installations in nonconditioned space. Add insulation 1” thick to exterior of
air handler to comply in these jurisdictions, putting the
vapor barrier on the outside.

D. Physical Installation
MINIMUM CLEARANCES
These units have a 0” minimum clearance to combustible materials rating from all cabinet surfaces. The unit should be installed
with serviceability clearance of 30” from the front of the unit. The
unit can be serviced entirely from the front, including replacing the
filter. Be sure and route primary and secondary drain connections
so as not to obstruct filter replacement.

ARRANGEMENT
Unit is shipped from the factory arranged to be installed in a vertical upflow or horizontal right to left airflow position (standard) or
field convertible to a horizontal left to right airflow position.

Upflow Application

In an upflow installation the discharge outlet is at the top. Care
should be taken to ensure unit is level to permit proper condensate
drainage. Normal upflow installation will be in a basement or closet. If installed in a closet, the closet should have a platform framed
in, with an opening on top of the platform centered in the closet.
Connect the supply air outlet to a discharge air plenum. Install return air grilles from outside the closet to space below the platform.
Platform must be at least 10” above the floor. Run all supply and
return ductwork in accordance with local codes.

Horizontal application
Horizontal application will normally be used in an attic or crawl
space. This type installation requires a return air duct be attached
to the air handler inlet. The opposite end of the return air duct
is attached to a return air filter grille through the ceiling or wall.
Remove filter from unit if filter grill is used. The unit is shipped in
right to left configuration.

Caution
A “P” trap must be installed in the coil
drain line! Cap unused drain fittings.
WARNING
To ensure unit will not interfere with drains and
refrigerant lines, modification must be made
prior to installing these lines..
For left to right applications.
1. Remove and set aside front panels.
2. Remove the coil support bracket (4-screws).
1

3. Remove horizontal drain pan retaining clip (1-screw).
4. Carefully remove coil assembly and bottom drain pan.
5. Move horizontal drain pan from left hand side of coil to
right side.
6. Install modified coil assembly back into unit.
7. Reinstall coil support bracket and horizontal drain pan
retaining clip.
8. Determine drain holes being used and reposition knockout
caps.
9. Reinstall doors.

Terminal number 4 on the (FR) fan relay is the cooling blower
speed and terminal number 6 on the (FR) is the heating blower
speed.

I. Refrigerant Piping
All air handlers have DX refrigerant cooling coils installed, liquid
and suction piping should be sized in accordance with condensing
unit manufacturer’s recommendations. An adapter (by others) may
be required to make the transition between the line set and the
coil connector. The evaporator coil has sweat copper connections.
The suction line is a swaged solder cup connection. The liquid line
connection is made to a tail piece portion of the TXV. Remove the
nut on the inlet to the expansion valve and place it on the tail piece
prior to brazing the liquid line. DO NOT connect the tail piece
to the TXV until the liquid line has been brazed to the tail piece.
Refrigerant lines should be soldered with silver solder or other
high temperature brazing alloy. Dry nitrogen must flow through the
refrigerant lines during the brazing operation to prevent oxidation.

Caution
IT IS MANDATORY TO USE AN
EMERGENCY AUXILIARY DRAIN PAN
WITH ANY COIL OR AIR HANDLER
INSTALLED IN AN ATTIC OR ABOVE A
FINISHED CEIING!

E. Electric Furnace

J. Refrigerant Flow Control

Optional electric heating packages are available, see the unit label
for various sizes.
* See Electric Heater Kit Specifications Table

As shipped, the TXV installed on the A-coil is for the nominal
capacity of a 13 SEER matched with Heat Controller, Inc.,
condensing units. The TXV is for use on an R-410A system. For
other refrigerants, contact the factory. TXV has a built-in check
valve for reverse flow and is suitable for heat pump operation. All
are externally equalized with non-adjustable superheat and have
15% bleed. Hard start capability for outdoor units is not normally
required when a 15% bleed valve is used. The external equalizer
line attached to the TXV has a female flare nut and is attached to
the suction line at the coil. Install the TXV bulb to the suction line
using the bulb clamp furnished with the kit. The bulb should be
installed on a horizontal run of the suction line if possible. On a
line less than 7/8” OD, the bulb may be installed on top of the line.
With 7/8” OD or over, the bulb should be installed in a position of
about 4 or 8 o’clock. If the bulb installation is made on a vertical
run, the bulb should be located at least 6 inches from any bend
and on the tubing side opposite the plane of the bend. On vertical
bulb installations, the bulbs should be positioned with the bulb
capillary tube at the top. The bulb must be insulated using thermal
insulation to protect it from the effects of the surrounding ambient
temperature.

F. Power Wiring

Refer to the unit’s nameplate for specific electrical data.

Caution
DISCONNECT POWER AT MAIN FUSE OR CIRCUIT
BREAKER DISTRIBUTION PANEL BEFORE WIRING
UNIT TO PREVENT SHOCK OR FIRE HAZARD.
Use copper conductors only. Tighten all wire connectors.
Refer to unit nameplate for minimum circuit ampacity. For correct
wire size, refer to the National Electrical Code. Use 75˚C minimum
wire in unit wiring compartment.

NOTE: SEE UNIT FOR COMPLETE WIRING DIAGRAM
LOCATED ON BLOWER HOUSING.

G. Control Wiring
Field connections are made to the low voltage terminal strip.
Consult installation instructions provided with accessory items
for specific information on control wiring. Use 18 AWG minimum
copper control conductors for control wiring up to 50 feet between
units. 16 AWG control conductors are recommended for lengths up
to 100 feet. Class 2 wiring is acceptable. Do not short control leads.
Transformer burn-out will result. Set thermostat heat anticipator at
0.15 amps for air handler.

H. Blower Motor

Units are equipped with a three-speed blower motor. Two factoryselected motor speed leads are connected to the fan relay (FR) to
provide automatic speed change for heating and cooling airflow
volumes. The pre-selected motor speeds would normally not have
to be changed in the field. All HAH models contain a post purge
timer (TDR) that delays the blower turning off at the end of the
cooling cycle, this improves energy efficiency.
2

K. CONDENSATE DRAIN

M. CHECK TEST AND START UP
TURN OFF POWER AT BREAKER PANEL
Electric heaters are high current devices. Verify that
all electrical connectors, whether push-on or
compression-type are tight. Loose connections will
cause the wire and/or terminal to fail.
The unit should be tested after the system has been
completely installed to determine proper operation.
Energize the unit by switching on the line voltage
source and the thermostat.

The air handler drain pan has ¾” FPT primary and
secondary connections whether used in an upflow or
horizontal configuration. Piping from each stub is to
have a 1½” minimum trap and each run pitched so as
to provide for adequate drainage and secondary
fittings together into a common drain. When an air
handler is installed above a finished ceiling, an
auxiliary drain pan must be provided under the unit
as required by most local building codes. The
secondary drain must be piped to a location that
would provide the occupant a warning if the primary
drain is blocked.

N. PERIODIC MAINTENANCE
Inspect and clean or replace filters at least every three
months to ensure good airflow and optimum system
capacity, efficiency and life. This equipment should
NEVER BE OPERATED WITHOUT AN AIR FILTER
in place (see Section AIR FILTER). The blower motor
is permanently lubricated. ALWAYS disconnect
power before removing access doors!

L. AIR FILTER
Air handlers are factory equipped with an air filter.
If the return grille has its own filter, the filter
installed in the air handler should be removed. Air
filter should be inspected and cleaned or replaced as
often as is necessary to prevent restriction of air flow
(minimum every three months for normal
installations). Always replace the filter with the
same type originally furnished.
Dimensions
AHB Dimensions
24-60
AHB HAG
24, 30,
36 1336
1324,

AHBHAG
42, 48,
601360
1348,

3

ELECTRIC HEATER KIT SPECIFICATIONS
MODEL
USED WITH
N/A

Without heat

kW@
240V
208V

MINIMUM CIRCUIT
AMPACITY
240V
208V

MAX. FUSE OR
BREAKER (HACR)
240V
208V

0

0

2.1

1.9

15

15

5.0

3.8

29

25

30

25

8.0

6.0

44

39

45

40

10

7.5

55

48

60

50

0

0

3.5

3.4

15

15

5.0

3.8

30

27

30

30

8.0

6.0

46

40

50

40

10

7.5

56

49

60

50

15

11.3

56/26

49/23

60/30

50/30

0

0

4.0

3.9

15

15

7800-313B

5.0

3.8

30

27

30

25

7800-314B

8.0

6.0

46

41

50

45

10

7.5

57

50

60

50

7800-316B

15

11.3

53/30

46/27

60/30

50/30

7800-317B

20

15

57/63

50/46

60/60

50/50

0

0

6.0

5.9

15

15

7800-313B

5.0

3.8

32

29

35

30

7800-314B

8.0

6.0

48

42

50

45

10

7.5

59

52

60

60

7800-316B

15

11.3

60/35

50/30

7800-317B

20

15

60/60

60/50

7800-305B
7800-306B

HAG24-00-1A

7800-308B
N/A

Without heat

7800-305B
7800-306B
7800-308B

HAG36-00-1A

7800-312B
N/A

7800-315B

N/A

7800-315B

7800-400

Without heat

HAG48-00-1A

Without heat

HAG60-00-1A
HAG61-00-1A

5 3/32
59/53

46/29
52/46

4-Pole Jumper BarAssembly 15 and 20kWonly

4

CB 2

T1 T2

CB 1

T1 T2

H EAT SEQ U EN C ER

HS

18 G A TYPE 1015 600V TEW 105 C
18 G A T Y P E 1015 600V T E W 105 C 24V

FIELD WIRING PER LO CAL CO DE
12 G A TYPE 1015 600V TEW 105 C

HAG - T O 20 KW W IT H T D R

XF M R T R AN SF O R M ER

L S LI M I T SWI T C H
T D R T IM E D EL AY R EL AY

C I R C U IT BR EAKER
F AN R EL AY

CB
FR

LS- 1

BLOWER
MOTOR

BRN

BRN

BLU

WH T/YEL

5 KW RESISTIVE HEAT STR IP

LS- 2

5 KW RESISTIVE HEAT STR IP

LS- 3

RED
BLK

WHT

MALE P3

FEMALE P2

BLU

BLU

H

3

5

FR

1

O U T D O O R U N IT C O N TAC T O R

RED
BLK
BLK
BLK
BLK

RED

RED

RED

RED

4, 5 KW RESISTIVE HEAT STR IP

3

5

H
TD R

H S-2

WHT
WHT

H S-1

1

4

1

4

6

C

L EGEND

L1 L2

L1 L2

RED

RED

LS- 4

BLU

RED

BLK

XF MR

BLK

WHT

24VAC

4, 5 KW RESISTIVE HEAT STR IP

GRN

RED

BLU
YEL
208/240240VAC

RED

YEL
YEL

W1 T-STAT
W2 AN D

CO N D

GRN
RED
YEL
RED

BLU

5

RED

5

4

BLK

GROUND LUG
2

3

ORG

W1
W2
Y

R
G

HI

FR

2

1

2 2
P2 P3

H S-1

H S- 1

H S- 2

H S- 2

CB

L1
CB

4 P2
4 P3

LO

C

H S- 1

T DR

H S-2

TD R

XF MR

L S-1

L S-2

1

FR

2 0 8 VAC

6 6
P3 P2

3 3
P3 P2

H E A T S T R IP - 1

BL OWER
MOT OR

FR

L S-3

L S-4

H E A T S T R IP - 2

H E A T S T R IP - 3

H E A T S T R IP - 4

2

CB

L2
CB

06/2009



Source Exif Data:
File Type                       : AI
File Type Extension             : ai
MIME Type                       : application/vnd.adobe.illustrator
PDF Version                     : 1.5
Linearized                      : Yes
Create Date                     : 2009:04:13 11:30:03-05:00
Creator                         : Adobe Illustrator CS3
Modify Date                     : 2009:06:16 09:56:58-04:00
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Metadata Date                   : 2009:06:16 09:56:58-04:00
Creator Tool                    : Adobe Illustrator CS3
Thumbnail Width                 : 200
Thumbnail Height                : 256
Thumbnail Format                : JPEG
Thumbnail Image                 : (Binary data 6417 bytes, use -b option to extract)
Format                          : application/pdf
Title                           : IOM HAG 04-12-09
Document ID                     : uuid:3620a5f5-a1fb-48f1-b362-cb918a950fb9
Instance ID                     : uuid:ec28bd32-f15c-4f70-83b5-1cf54cc9c7c6
Rendition Class                 : proof:pdf
Producer                        : Adobe Acrobat 8.0
N Pages                         : 1
Has Visible Transparency        : False
Has Visible Overprint           : False
Max Page Size W                 : 612.000000
Max Page Size H                 : 792.000000
Max Page Size Unit              : Points
Font Name                       : MyriadPro-Regular
Font Family                     : Myriad Pro
Font Face                       : Regular
Font Type                       : Open Type
Font Version                    : Version 2.037;PS 2.000;hotconv 1.0.51;makeotf.lib2.0.18671
Font Composite                  : False
Font File Name                  : MyriadPro-Regular.otf
Plate Names                     : Cyan, Magenta, Yellow, Black
Swatch Group Name               : Default Swatch Group
Swatch Group Type               : 0
Page Count                      : 7
Profile CMM Type                : Lino
Profile Version                 : 2.1.0
Profile Class                   : Display Device Profile
Color Space Data                : RGB
Profile Connection Space        : XYZ
Profile Date Time               : 1998:02:09 06:49:00
Profile File Signature          : acsp
Primary Platform                : Microsoft Corporation
CMM Flags                       : Not Embedded, Independent
Device Manufacturer             : IEC
Device Model                    : sRGB
Device Attributes               : Reflective, Glossy, Positive, Color
Rendering Intent                : Media-Relative Colorimetric
Connection Space Illuminant     : 0.9642 1 0.82491
Profile Creator                 : HP
Profile ID                      : 0
Profile Copyright               : Copyright (c) 1998 Hewlett-Packard Company
Profile Description             : sRGB IEC61966-2.1
Media White Point               : 0.95045 1 1.08905
Media Black Point               : 0 0 0
Red Matrix Column               : 0.43607 0.22249 0.01392
Green Matrix Column             : 0.38515 0.71687 0.09708
Blue Matrix Column              : 0.14307 0.06061 0.7141
Device Mfg Desc                 : IEC http://www.iec.ch
Device Model Desc               : IEC 61966-2.1 Default RGB colour space - sRGB
Viewing Cond Desc               : Reference Viewing Condition in IEC61966-2.1
Viewing Cond Illuminant         : 19.6445 20.3718 16.8089
Viewing Cond Surround           : 3.92889 4.07439 3.36179
Viewing Cond Illuminant Type    : D50
Luminance                       : 76.03647 80 87.12462
Measurement Observer            : CIE 1931
Measurement Backing             : 0 0 0
Measurement Geometry            : Unknown
Measurement Flare               : 0.999%
Measurement Illuminant          : D65
Technology                      : Cathode Ray Tube Display
Red Tone Reproduction Curve     : (Binary data 2060 bytes, use -b option to extract)
Green Tone Reproduction Curve   : (Binary data 2060 bytes, use -b option to extract)
Blue Tone Reproduction Curve    : (Binary data 2060 bytes, use -b option to extract)
For                             : Zachery Loeprich,
Bounding Box                    : 0 0 612 792
Container Version               : 11
Creator Version                 : 14
Image Height                    : 792
Image Width                     : 612
Image Size                      : 612x792
Megapixels                      : 0.485
EXIF Metadata provided by EXIF.tools

Navigation menu