Honeywell Analytics Asia Pacific OELD Smart Junction Box for Gas Detectors User Manual OELD Instruction Manual

Honeywell Analytics Asia Pacific Co., Ltd. Smart Junction Box for Gas Detectors OELD Instruction Manual

Manual

Download: Honeywell Analytics Asia Pacific OELD Smart Junction Box for Gas Detectors User Manual OELD Instruction Manual
Mirror Download [FCC.gov]Honeywell Analytics Asia Pacific OELD Smart Junction Box for Gas Detectors User Manual OELD Instruction Manual
Document ID3066098
Application IDUo6KqEFffv3Dh4ZiXQSrhA==
Document DescriptionManual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize101.27kB (1265856 bits)
Date Submitted2016-07-17 00:00:00
Date Available2017-01-13 00:00:00
Creation Date2016-07-06 14:22:20
Producing SoftwareAdobe PDF Library 10.0
Document Lastmod2016-07-06 14:22:26
Document TitleOELD Instruction Manual
Document CreatorAcrobat PDFMaker 10.1 for Word
Document Author: Kim, Jesse

Operating Instructions
OELD
Smart Junction Box
(3018M5000_1-3)
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
Content
1 Safety....................................................................................................................................................... 2
1.1 Safety Warnings and Information ..................................................................................................... 2
1.2 Disposal............................................................................................................................................ 2
1.3 Waste Electrical and Electronic Equipment (WEEE) Directive ........................................................ 3
1.4 Important Information ....................................................................................................................... 3
2 Overview .................................................................................................................................................. 5
2.1 Introduction ...................................................................................................................................... 5
2.2 Optional Accessories ....................................................................................................................... 7
2.2.1 Pipe Mount Kit (1226A0358)..................................................................................................... 7
2.2.2 Ceiling Mount Bracket Kit (1226A0355) ................................................................................... 7
2.2.3 Sunshade (94000-C-1018) ....................................................................................................... 7
3 Installation ............................................................................................................................................... 8
3.1 Siting ................................................................................................................................................ 8
3.2 Mechanical Installation ..................................................................................................................... 8
3.2.1 Installation to a Flat Surface ..................................................................................................... 8
3.2.2 Optional pipe and celling mount installation ............................................................................. 9
3.2.3 Using Excel Mounting Plate ...................................................................................................... 9
3.3 Electrical Installation ...................................................................................................................... 10
4 Electrical Connections ........................................................................................................................... 11
4.1 Power Supply ................................................................................................................................. 12
4.1.1 Example Cable Length Calculation ........................................................................................ 12
4.2 Cabling Recommendation .............................................................................................................. 12
4.3 Earth Regimes ............................................................................................................................... 13
4.4 Fix the 4-20mA Input ...................................................................................................................... 13
5 Configuration ......................................................................................................................................... 14
5.1 General........................................................................................................................................... 14
5.2 Configuration Process .................................................................................................................... 15
6. Operation .............................................................................................................................................. 16
6.1 LCD ................................................................................................................................................ 16
6.1.1 Start-up ................................................................................................................................... 16
6.1.2 Normal Operation ................................................................................................................... 17
6.1.3 Display Screen ........................................................................................................................ 17
6.2 BLE Communication (Optional)...................................................................................................... 18
6.3 Alternative communications (SHC-1) ............................................................................................. 18
7. OELD Mobile App ................................................................................................................................. 20
7.1 Install mobile App ........................................................................................................................... 20
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
7.2 Run OELD Mobile App ................................................................................................................... 20
8. Maintenance ......................................................................................................................................... 24
8.1 General........................................................................................................................................... 24
8.2 Display Module Replacement ........................................................................................................ 24
9. Faults and Warning .............................................................................................................................. 25
10 Specifications ...................................................................................................................................... 26
11. Ordering Information........................................................................................................................... 28
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
1 Safety
1.1 Safety Warnings and Information
WARNING
1. Installation must be in accordance with the recognized standards of the appropriate authority
in the country concerned. For Europe see EN 60079-14 and EN 60079-29-2.
2. Do not open the enclosure when energized or when an explosive atmosphere may be present.
3. Operators should be fully aware of the action to be taken if the gas concentration exceeds
the alarm level.
4. Do not modify or alter the construction of the product as essential safety and certification
requirements may be invalidated.
5. Assessed under ATEX only for ignition hazards.
6. Access to the interior of the product, when carrying out any work, must be conducted only by
trained personnel.
7. Do not use the OELD LCD backlit status indication for safety-related purposes.
8. In order to maintain electrical safety, the unit must not be operated in atmospheres of more
than 21% oxygen.
9. To minimize the risk of electrostatic charge, provisions shall be made for an adequate
grounding, equipment shall be installed in a manner so that accidental discharge shall not
occur
Special Conditions for Safe Use – Terminals
In order to comply with the ATEX Certification, the following special conditions of use must be adhered to: 1. Not more than one single or multiple strand lead shall be connected into either side of any terminal,
unless multiple conductors have been joined in a suitable manner, e.g. two conductors into a single insulated crimped boot lace ferrule.
2. Leads connected to the terminals shall be insulated for the appropriate voltage and this insulation
shall extend to within 1 mm of the terminal throat.
3. All terminal screws, used and unused, shall be tightened down to between 0.5 N m and 0.7 N m.
4. The terminals shall only be installed and wired with cable in an ambient temperature of -10 °C to
+80 °C.
1.2 Disposal
Dispose of the product in accordance with local regulations. The materials used are: Enclosure
Lid
Continuity plate
Aluminum or SS316
Aluminum or SS316
Zinc plated steel
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
1.3 Waste Electrical and Electronic Equipment (WEEE) Directive
This symbol indicates that this product and/or parts of the product may not be treated as
household or municipal waste. Waste electrical products (end of life) should be recovered/recycled where suitable specialist WEEE disposal facilities exist. For more information about recycling of this product, contact your local authority, our agent/distributor or
the manufacturer.
1.4 Important Information
This manual is for use with the OELD junction box only.
Honeywell Analytics can take no responsibility for installation and/or use of its equipment if not done
so in accordance with the appropriate issue and/or amendment of the Operating Instructions.
The reader of these Operating Instructions should ensure that it is appropriate in all details for the
exact equipment to be installed and/or operated. If in doubt, contact Honeywell Analytics for advice.
The following types of notices are used throughout these Operating Instructions:
WARNING
Identifies a hazardous or unsafe practice which could result in severe injury or death to personnel.
Caution: Identifies a hazardous or unsafe practice which could result in minor injury to personnel, or product or property damage.
Note: Identifies useful/additional information.
Every effort has been made to ensure the accuracy of this document, however, Honeywell Analytics
can assume no responsibility for any errors or omissions in this document or their consequences.
Honeywell Analytics would greatly appreciate being informed of any errors or omissions that may be
found in the content of this document.
For information not covered in this document, or if there is a requirement to send comments/corrections about this document, please contact Honeywell Analytics using the contact details
given on the back page.
Honeywell Analytics reserve the right to change or revise the information supplied in this document without notice and without obligation to notify any person or organization of such revision or change. If information is required that does not appear in this document, contact the
local distributor/agent or Honeywell Analytics.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
1.5 FCC Information
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions.
1) This device may not cause harmful interference, and
2) This device must accept any interference received, including interference that may cause undesir
ed operation.
This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter. This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. End users must follow the specific operating instructions for satisfying RF exposure compliance.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to pro-vide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
CAUTION : Changes or modifications not expressly approved by the manufacturer responsible for
compliance could void the user’s authority to operate the equipment.
1.6 IC Information
This device complies with Industry Canada’s lisence-exempt RSSs. Operation is subject to the following two conditions:
1) This device may not cause interference; and
2) This device must accept any interference, including interference that may cause undesired operation of the device
WARNING
OELD has been tested and meets applicable limits for radio frequency (RF) exposure. According to the RF Exposure report, minimum 20 cm separate distance is required.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
2 Overview
2.1 Introduction
OELD is an ATEX certified Ex d junction box for use with sensors that feature a 4-20mA output. The
sensor is Searchpoint Optima Plus or Searchline Excel. It provides a local visual status indication, and
a Bluetooth low energy interface for remote monitoring and configuration using mobile device. OELD
is ATEX approved for use in either Zone 1 (gas) or Zone 21 (dust) hazardous areas as well as cULus
approved for use in Class I Division 1 or Class II Division 1.
OELD has five entries – either M25 or NPT3/4. It is supplied with three Ex d certified blanking plugs.
Transport plugs are fitted to the other two entries, which must be replaced with a sensor, suitable
cable glands or blanking plugs before use.
Internally, the box has a continuity plate with two earth connection points, and a 12-way terminal
block. The OELD features a three-color backlit (green, yellow and red), and customized 7-segment
liquid crystal display. In operation, the LCD backlit provides a status indication as follows:
•
•
•
•
Green – Normal operation or Warning
Yellow – Fault or Inhibit
Red – Alarm (level is configurable)
Blue – BLE pairing / connection
WARNING
Do not use the OELD LCD backlit status indication for safety-related purposes.
The OELD is configured using mobile device over Bluetooth Low Energy. The following parameters
can be configured:
•
•
•
Threshold for local alarm indicator (red lights)
4-20mA input level for local display
Gas name and measurement units for local display
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
2.2 Optional Accessories
2.2.1 Pipe Mount Kit (1226A0358)
The Pipe Mount kit (1226A0358) allows the OELD
to be mounted to pipe from 2”-6” (50-150mm) in
diameter. The kit includes the pipe mount bracket,
two carriage bolts, nuts, and lock washers.
2.2.2 Ceiling Mount Bracket Kit (1226A0355)
The optional Ceiling Mount Bracket Kit
(1226A0355) allows the OELD Transmitter to be
mounted to the ceiling. The kit includes two stainless steel ceiling mount brackets, bolts, and nuts.
2.2.3 Sunshade (94000-C-1018)
An optional sunshade is available which covers
the OELD and can extend over either side to also
protect a Searchpoint Optima or Searchline Excel
The sunshade slots over the OELD mounting bolts so
no additional fixings are required. The sunshade is
stainless steel 316.
Use the sunshade to reduce the effects of direct solar
heating.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
3 Installation
3.1 Siting
The placement of gas detectors should be determined following the advice of:
• experts having specialist knowledge of gas dispersion
• experts having knowledge of the process plant system and equipment involved
• safety personnel
• engineering personnel
The agreement reached on the location of detectors should be recorded.
Guidance on the positioning of gas detectors to provide the best detection coverage is contained in
IEC/EN 60079-29-2 and other national Codes of Practice. It is recommended that the installation designer consults these Codes of Practice when determining where detectors are to be located.
3.2 Mechanical Installation
The OELD can be mounted in a number of ways using the integral mounting tabs. The OELD can be
attached to flat wall surfaces or to Unistrut®. With the optional Pipe Mount kit, the unit can be mounted to pipe of diameter 2” to 6” (50 to 150mm). A ceiling mount bracket kit (1226A0358) is also available.
3.2.1 Installation to a Flat Surface
OELD may be fixed directly to a suitable flat surface, using the integral mounting points (dimensions
shown below).
Note: When installing OELD ensure that the correct sensor orientation is considered. Refer to the
sensor manufacturer’s instructions.
Ensure that mounting bolts are fully tightened and suitable locking washers are used.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
3.2.2 Optional pipe and celling mount installation
OELD may be fixed to a vertical pipe of 50 to 150 mm (2 to 6 inches) in diameter using the optional
Pipe Mounting Bracket. The pipe mounting bracket kit (1226A0358) consists of one bracket, two sets
of carriage bolts, nuts and lock washers.
The optional Ceiling Mount Bracket Kit (1226A0355) allows the OELD to be mounted to the ceiling. Kit
includes: (2) Stainless Steel Ceiling Mount Brackets, bolts and nuts.
3.2.3 Using Excel Mounting Plate
OELD may be fixed to the Excel mounting plate (2104D0237) which is available to be ordered with
Excel. Two of M10 tapped holes, ‘K’, is for OELD. Refer Excel technical manual for other details. The
mounting plate fixings are not supplied.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
3.3 Electrical Installation
1. Remove the lid.
2. Lift the handle and take out the internal display module.
3. Fit a suitable approved Ex d cable gland to the required cable entry for the field cable.
4. Fit a sensor (the Optima Plus or Excel) to a suitable entry. (Refer to sensor manual for specific
information). Use sealing washers where necessary to maintain the ingress protection rating
(IP66/67). Use one of the supplied locking rings to connect to the earth continuity plate.
5. Fit approved Ex d blanking plugs to all unused cable entries. Use sealing washers where necessary to maintain the ingress protection rating (IP66/67).
Caution: Ensure that all red transport plugs have been replaced with the correct blanking
plugs, sensor or cable glands.
6. Make electrical connections (see Chapter 4).
7. Carefully replace the display module and fully tighten the lid
Caution: Take care to avoid trapping cables when replacing the display module.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
4 Electrical Connections
Terminal Block 1
Number
Marking
Color
Description
V+
Red
V+ Field Power
V-
Black
V- Field Power
mA
White
mA Signal to Field Wiring
V+
Red
Reserved for Excel Cross-duct Heater
V-
Black
Reserved for Excel Cross-duct Heater
Terminal Block 2
Number
Marking
Color
Description
V+
Red
V+ Sensor Power
V-
Black
V- Sensor Power
mA
White
mA Signal to Sensor
485A
Blue
RS485+ to Sensor
485B
Orange
RS485- to Sensor
485A
Blue
Reserved for SHC-1
485B
Orange
Reserved for SHC-1
Note: OELD is reverse polarity protected.
Spare conductors must be terminated in a spare terminal. Wiring must be in accordance with local,
national and/or company regulations. Bare conductors must be avoided.
Refer to individual sensor manuals for sensor wiring details. Specific wiring diagrams for some commonly used sensors are provided in the Appendix.
The mA loop voltage is Max 32 VDC and current is Max 22 mA.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
4.1 Power Supply
OELD requires an isolated voltage supply of 18 - 32 Vdc (nominal 24 Vdc), which is suitably approved
for the region (for example, UL approved). Power consumption is 2 W maximum.
Refer to individual sensor manuals for sensor specific limits and power consumption.
Ensure that the minimum required supply voltage is present at the sensor, taking into account the
voltage drop due to cable resistance.
Note: Make allowance for the insertion loss resistance.
The maximum loop resistance in the field cable is calculated as follows:
𝑅𝑙𝑙𝑙𝑙 =
𝑉𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 − 𝑉𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 𝑚𝑚𝑚
𝐼𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑
4.1.1 Example Cable Length Calculation
Example – OELD with Searchpoint Optima Plus:
Searchpoint Optima Plus requires a voltage supply of 18 – 32 Vdc. Its power consumption is 5 W.
Therefore total power consumption including OELD is 7 W maximum.
The controller is supplying a nominal 24 Vdc (V controller) and the detector minimum allowable voltage is 18 Vdc (V detector min), therefore the maximum allowable voltage drop between the controller
and detector is 6 Vdc; this means a voltage drop of 3 V in each core (+ve core and -ve core).
Power consumption of the detector is 7 W. The current required to drive the detector at the minimum
voltage is (I = P / V), 7 / 18 = 388 mA (I detector).
So, the maximum field cable loop resistance (R loop) = 6 / 0.388 = 15.4 Ί, or 7.7 Ί per core.
The following tables show the maximum cable distances between the controller and OELD with
Searchpoint Optima Plus for different cable options, assuming a voltage drop of 3 V in each core. The
tables are examples only and actual cable parameters and source power supply voltage for the application should be used to calculate the maximum cable distance allowed at the installation site.
Note: Sufficient operational margins should be allowed
4.2 Cabling Recommendation
The cable used must be appropriate for the hazardous area classification and meet local, national
and/or company regulations. The use of industrial grade, screened field cable is recommended.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
For example, three-core copper cable with screen (minimum 90% coverage) and suitable mechanical
protection (e.g. steel wire armor) to suit M20 gland entry.
The conductor size for the terminals is 0.2 – 2.5 mm (24 - 12 AWG). The OELD terminals will accept
only copper wire sizes in the range 0.2 – 2.5 mm (solid core), 0.2 – 2.5 mm (stranded core), or 24 –
12 AWG and temperature rating of conductor is greater than 80°C. The terminals should be torqued
to 5.5kgf.cm (5 lb-in).
Ensure the cable gland is installed correctly and fully tightened. All unused cable/conduit entries must
be sealed with a suitable certified blanking plug.
4.3 Earth Regimes
Caution: Any earthing regime employed must avoid earth loops.
The following information is provided to assist with proper earthing of OELD:
• OELD has a continuity plate which is in contact with the internal earth points provided (see Electrical
Connections). This is to facilitate connection of the sensor to protective earth.
• Locking rings are supplied which can be used to connect a sensor body or cable gland to the continuity plate where necessary.
• Field cable screens should be connected to instrument earth at the control room. The other end of
the field cable screen may be terminated in a spare terminal of OELD. It should not be connected to
the continuity plate.
4.4 Fix the 4-20mA Input
After electrical commission it is recommended to calibrate current input to OELD by using mobile
device.
The electrical adjustment procedure is as follows.
1. Short or open the current input ports at the OELD
2. Carry out mA input calibration with mobile device (Configure->Local display->Calibrate mA
input)
3. Re-wire the current input (mA)
For more information please refer to 7 OELD Mobile App
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
5 Configuration
5.1 General
OELD has several configurable parameters, which are set using mobile device only. These are the
threshold for local alarm indication, mA input level settings, RS485 communication settings, confidence signal of the green light and sensor settings such as full scale range, measurement unit and
gas name.
1. Threshold for local alarm indication
The gas reading at which OELD indicates an alarm (flashing red lights) can be set between 10 and 65
%FSD. The default setting is 20 %FSD.
Note: This setting is local to OELD and applies only to the red lights in the OELD backlit. Changing
the level will have no effect on alarm levels configured in the sensor, or in the control room.
2. mA input level settings
The sensors transmit specific mA output to indicate the sensor status. The mA input to OELD can be
determined to specific sensor status according to the configured mA input level settings. The mA input
settings are sensor status (warning, fault or inhibit) and message on OELD local display. The default
settings are as below.
Sensor Status
Fault
Inhibit
Warning
Beam Block
Low Signal
Gas Reading
Over-Range
Optima Plus Non-HART
0-1mA
2mA
3mA
4-20mA
21mA +
mA input settings
Optima Plus HART
2mA
3mA
4-20mA
21mA +
Searchline Excel
0mA
2mA
2.5mA
3mA
4-20mA
21mA +
3. Confidence signal of the green light
The green lights indicating normal operation can be set to confidence signal to indicate OELD is alive
by flashing green lights. The flashing interval is 10 seconds. If set the green backlit will flash every 10
seconds in normal condition
4. Sensor settings
The sensor settings are full scale range, measurement unit, display resolution and gas name. The
sensor settings are used to convert the 4-20mA input to gas concentration and to show it on OELD
LCD.
WARNING
Do not use the OELD LCD backlit status indication for safety-related purposes.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
5.2 Configuration Process
Note: Configuration is done by using mobile device only. There is no local interface to configure
OELD.
To configure OELD, it should be connected to mobile device over Bluetooth Low Energy first. The
blue backlit of OELD will flash when a mobile device pairs with OELD so that an operator can easily
find out and identify the target OELD. When OELD is connected to mobile device successfully the
blue backlight will stay on in normal condition. If the sensor is in abnormal condition, appropriate
backlit of OELD will flash according to sensor status instead of indicating BLE connection.
1.
2.
3.
4.
5.
6.
7.
Tab the OELD mobile app icon on the mobile device to execute the app
Log in the mobile app by entering appropriate user ID and password
Scan the BLE devices nearby
Select the target OELD in the scanned BLE device list
Find out and identify the OELD flashing blue backlit
If the identified OELD is correct one, confirm the connection
Mobile app will establish the connection with OELD then move to main status screen
For detailed connection procedure refer to section 6.2 BLE communication.
If OELD is connected to mobile device, a user can configure OELD via configure menu on the mobile
application. For more details on operation of mobile application, refer to 7 OELD Mobile App
After successful configuration, terminate the BLE connection from the OELD so that other mobile
device can communicate with the OELD.
Note: After configuration it is recommended to read back and check the configuration from OELD to
make sure that the intended configuration changes are applied correctly.
Caution: Only one BLE connection is allowed. Terminate the BLE connection when a configuration activity is done
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
6. Operation
6.1 LCD
6.1.1 Start-up
OELD’s start-up sequence takes approximately 60 seconds depending on the sensor outputs. The
first step of the start-up sequence is LCD and backlit test. During LCD test each segment of LCD will
be on one by one while LCD backlit will flash in various colors. And OELD shows software version
and various configuration information as below. During start-up sequence except LCD test, the green
light will be on. After the start-up period the lights will indicate the sensor output status.
Note: Depending on the duration of the sensor start up routine, the sensor may still be initialising.
Therefore OELD may indicate Fault or Inhibit for a short time before indicating Normal status.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
6.1.2 Normal Operation
During normal operation, the LCD backlit provides an indication of the sensor status based on the
sensor 4-20 mA output as follows:
Sensor Output
Less than 1.5mA
1.5 to less than 2.5mA
2.5 to less than 3.5mA
3.5mA to less than Alarm Threshold*
Greater than or equal to Alarm Threshold*
3.5mA to less than Alarm Threshold**
OELD Backlit
Color
Flashing
Yellow
Yes
Yellow
No
G Y G Alternating Yellow
Green
No
Red
Yes
Blue
No
Typical Status
Fault
Inhibit
Warning
Normal
Hazardous Gas Concentration
Normal
* Alarm threshold is configurable between 10 and 65 %FSD (5.6 mA to 14.4 mA)
**When sensor output is normal and BLE connection is established, the OELD backlit will be Blue
Note: The tolerance on the switching thresholds is Âą0.3 mA as default. A user can change the switching threshold by changing the mA input range.
Note: The visual output of OELD is dependent on the sensor 4-20 mA output and OELD unit status.
Use the Bluetooth Low Energy communications to the OELD (where supported) to gain further diagnostic information for the connected sensor and OELD.
6.1.3 Display Screen
The OELD display features an LCD with numeric/bar-graph gas concentration data, alpha-numeric
warning and status indication. The LCD also has a backlit with hi-intensity multi-color LED to show
NORMAL, ALARM and FAULT status.
During normal operation the instrument LCD shows a steady GREEN backlight. In case of Gas Alarm
or Fault it displays a flashing RED / YELLOW backlight. The screen is visible through the window of
the OELD top cover. The display shows the gas concentration (both graphically and numerically), full
scale range, measurement units, alarm/ fault status and etc.
Note: The OELD display may become sluggish in sub-zero temperatures and possibly unclear at
temperatures below -40 °C. The display is not damaged and recovers when the temperature increases.
Note: The refresh rate of OELD display will change up to 6 seconds at lower temperature so that LCD
readability at lower temperature can be maintained
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
Test Pass Icon
Full scale
Warning/Fault Icon
BLE Icon
Bar Graph
Gas name
Inhibit Icon
Alarm Icon
Gas Reading
Measurement
Units
6.2 BLE Communication (Optional)
OELD features an optional BLE interface that allows non-intrusive connection of mobile device to a
sensor that supports RS485 communication. The OELD bridges message transactions between mobile device and sensor by converting the BLE packet to RS485 message and repeating it onto RS485
interface, and vice versa. OELD does not interpret any RS485 messages from mobile device and
sensor.
The BLE interface is accessed by mobile device that supports Bluetooth Low Energy.
Refer to the OELD Mobile App manual for BLE communication information.
Note: The BLE (Bluetooth Low Energy) is different from Bluetooth Classic. Make sure the mobile device has an operating system that supports BLE.
Note: Bluetooth feature should be enabled in the mobile device to allow it to scan BLE devices nearby.
Refer to the Mobile device user’s manual for details of how to use the Bluetooth on the mobile device.
Note: OELD is compatible with the BLE Point-to-Point mode of operation only. If OELD is connected
with one mobile device, it won’t be scanned by other mobile device
If there is no valid BLE communication for 10 minutes, OELD will terminate BLE connection automatically
Note: BLE communication range will vary depending on the field situation and installation location of
OELD. It is recommended to use BLE interface in the line of sight
6.3 Alternative communications (SHC-1)
If the sensor features an RS485 interface (i.e. Honeywell Analytics optical products) this can be accessed using the Honeywell Analytics SHC1 Handheld Interrogator and the SHC Protection Device,
by direct connection to the terminals inside the OELD.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
Note: OELD does not support XPIS terminal. If XPIS terminal is required, an appropriate junction box
should be used instead
WARNING
Do not use BLE communication when the SHC1 Handheld Interrogator is connected to RS485
terminal on the OELD
Refer to the individual sensor manual for details of how to use the SHC1 Handheld Interrogator.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
7. OELD Mobile App
7.1 Install mobile App
Mobile App on the mobile device is used to configure OELD and sensor connected to an OELD. The
OELD configuration is done as part of sensor configuration by mobile app. The sensor considers an
OELD as local display accessory with BLE.
Mobile app runs under Android OS that supports Bluetooth Low Energy. Android OS version should
be 4.3 or higher. OELD Mobile App is available in Google App store.
Installation procedure is as below.
1. Search and download Honeywell OELD Mobile App from Google store
2. OELD mobile app will be automatically installed on the mobile device
7.2 Run OELD Mobile App
1.
2.
3.
4.
5.
Tap the OELD mobile app icon
Upon start-up it will ask a user to agree with EULA (end user license agreement)
Confirm the EULA and proceed
Log in screen will appear to ask a user to log in the app
Create a user account if there is no existing account and you’ll get activation email from Honeywell
6. Confirm the account activation email by clicking on the link in the email
7. Activate / register OELD instrument by scanning the QR code in the registration sheet in the
packaging box
Note: First time log-in requires internet connection to register a user and to activate OELD device
8. It will download user certificate from the Honeywell server.
9. Scan the BLE device nearby and connect target OELD
10. After successful connection to OELD, a user can configure OELD and sensor connected to the
OELD
Note: A user can connect to OELD devices that have been registered to the user account.
For detailed configuration procedure by mobile device, refer to OELD Mobile App user’s manual or
help of OELD mobile app.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
7.3 Configure OELD device
OELD has several configurable parameters, which are set using mobile device only. The configurable
parameters are as shown in the table below.
Configuration Parameters
Device type
Min Value
Max Value
Step Size
Generic 4to20mA transmitter, Optima Plus or
Searchline Excel
Alarm Threshold*
10%
100%
Alarm Trigger*
Rising, falling, disabled
1%
Gas name on display
Full Scale Range for 20mA
Display resolution
Measurement units
Inhibit Current
0mA
3mA
.05mA
Warning Current
0mA
6mA
.05mA
Beam block current
0mA
6mA
.05mA
Over-range Current
20mA
21.6mA
.05mA
Green LED in normal
Off or on
*Note
Alarm threshold and trigger is for local indication at OELD. They do not affect the operation of connected sensor and other alarm devices.
7.4 Configure Optima Plus
OELD mobile helps a user to configure Optima Plus connected to OELD. The configurable parameters are as shown in the table below. A user can configure Optima Plus as he/she does with SHC1
handheld device.
Configuration Parameters
Min Value
Max Value
Auto Zero
Enabled or Disabled
Alarm Threshold
10%
100%
1%
Inhibit Current
0mA
3mA
.05mA
Warning Current
0mA
6mA
.05mA
Over-range Current
20mA
21.6mA
.05mA
Protocol Address
255
Note: Make sure Optima Plus is connected to RS485 terminal on the OELD.
Step Size
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
7.5 Calibrate Optima Plus
OELD mobile app allows a user to calibrate the Optima Plus same as SHC1 handheld device.
1.
2.
3.
4.
5.
6.
After connecting to OELD device, go to Calibrate menu on the mobile app
Click on “Zero” button to start zeroing
Mobile app will initiate zero calibration after inhibiting the 4-20mA output of the Optima Plus
After successful zeroing, click on “Span” button to perform span calibration
Apply calibration gas to the Optima Plus
Wait until span calibration is complete
Refer to Optima Plus User’s manual prior to carrying out gas calibration
Caution: Searchpoint Optima Plus is factory calibrated and does not require routine calibration. In most cases, a re-zero will correct any inaccuracy in the gas reading. It is strongly recommended that a span calibration is not carried out
WARNING
As some calibration gases may be hazardous, ensure that outlets from gassing accessories exhaust safely.
WARNING
A compressed air cylinder (20.9%Vol oxygen) should be used to perform the zero
calibration if the area where the detector is located contains any residual amount
of the target gas.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
8. Maintenance
8.1 General
Periodically inspect OELD and cabling for signs of physical damage. Clean the glass window with a
damp cloth. Do not use solvents or abrasive cleaners.
OELD has no user serviceable parts. Honeywell Analytics recommend that the unit’s configuration
and operation are checked annually.
The gas detectors connected to OELD should be checked and if necessary zero and span calibrated
by following the procedures detailed in their operating instructions.
8.2 Display Module Replacement
The display module can be replaced, for example in the event of failure of the LCD and backlit.
1. Remove the power from OELD and carefully remove the lid.
2. Lift the handle and take out the internal display module with no strain on the internal cables.
3. Disconnect the all wires from the terminal block at the bottom of display module
4. It is recommended to make a note of the original serial number of display module and mark the
serial number inside the enclosure. Retain a record of the original serial number in the maintenance
record for the installation (refer to IEC/EN 60079-29-2).
6. Connect the all wires to the terminal block of the replacement display module in accordance with
Chapter 4 Electrical Connections.
7. Carefully replace the display module with no strain on the cables.
8. Fully tighten the lid
Caution: Take care to avoid trapping cables when replacing the display module.
Note: The replacement lid will have default settings for the threshold for local alarm indication and mA
input level settings, RS485 communication settings, confidence signal of the green light and sensor
settings. It may be necessary to re-program the configuration by using mobile device.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
9. Faults and Warning
Message
Code
Description
Remedial Action
Over Rang
W-01
Over-range warning
Check the sensor by referring to sensor
manual
bEAm Bloc
W-02*
Beam block signal detected
Check the sensor by referring to sensor
manual
Curr Warn
W-03
Warning level input from the
detector
Check the sensor by referring to sensor
manual
Comm Err
F-01
Internal Comm. failure
Reset OELD. If fault still appears, replace the display module
Curr FLt
F-02
Fault level input from the
detector
Check the sensor by referring to sensor
manual
Curr High
F-03
Input current is too high
Check the sensor by referring to sensor
manual
Volt Err
F-04
Supply voltage fault or Internal power supply fault
Reset OELD. If fault still appears, replace the power module
RAM Err
F-05
RAM read/write fault
Reset OELD. If fault still appears, replace the display module
Mem Err
F-06
Info. memory corrupted
Reset OELD. If fault still appears, replace the display module
Code Err
F-07
Code Memory corrupted
Reset OELD. If fault still appears, replace the display module
Cert Err
F-08
Device certificate corrupted
Contact manufacturer
*Note: Warning for beam block is only available when the connected sensor type is Searchline Excel.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
10 Specifications
OELD Specification
Material
Marine-grade aluminium alloy or 316 stainless steel with 5-coat painted finish
Weight
Aluminium version 2.3 kg (5 lb), stainless steel version 5.0 kg (11 lb)
Dimensions
159 x 197 x 114 mm (6 Ÿ x 7 ž x 4 ½ inch)
Cable entries
5 x M25 (ATEX/IECEx version) or 5 x ¾” NPT (cULus version). One reserved
for sensor connection. 3 blanking plugs supplied for unused entries.
Termination
2 x pluggable rising-clamp type for connection to gas detector and field wiring.
Accepts cable sizes of 0.5 to 2.5mm , 12 to 28 AWG
Storage
-25 to +65 °C (-13 to 149 °F)
Temperature
Operational
-40 to +65 °C (-40 to 149 °F)
temperature
-60 to +65 °C (-76 to 149 °F) with optional heater module
Humidity
(non-condensing) 20 to 90% RH continuous, 0 to 99% RH intermittent
Display
LCD module showing digital readout of sensor output, bar chart representation,
units of measurement, status icons for alarm, maintenance and active Bluetooth
connection.
Configurable
Displayed information fully user-configurable using the OELD mobile app.
displayed
Units of measurement (select from %LEL, mg/m3, g/m3, %Vol, ppm, mA, A,
information
kppm, LEL.m, dB, dBA, ppm.m)
Gas name (up to 4 alpha-numeric characters)
Measurement range
Visual
Green/amber/red/blue multi-colour backlight to display for indication of detector
indication
and OELD status. Green (normal) indication can be disabled via app.
Power supply
18 to 32 Vdc (24 Vdc nominal), <2 W
Interfaces
BluetoothÂŽ (BLE) non-intrusive connection to suitable mobile device running the
OELD mobile app. Range up to 10 m (mobile device dependant)
Internal RS-485 connection to Searchpoint Optima Plus or Searchline Excel via
SHC-1 through the protection device
Environmental
IP66 / Type 4X
Protection
Core Approvals
EN 50270: 2015 (EMC)
IEC/EN/UL/CSA 61010 (Electrical Safety)
FCC
RoHS
China RoHS
Safety
ATEX [DEMKO 16 ATEX 1693X]
Approvals
II 2 GD
Ex db IIC T6 (flameproof Ex d version)
Ex tb IIIC T85°C (flameproof Ex d version)
Tamb -40 to +65°C
cULus [E484838]
Class I, Div 1, B, C & D
Class II, E, F & G
Class III
Tamb -55 to +65°C
IECEx [IECEx UL 16.0066X]
Ex db IIC T6 (flameproof Ex d version)
Ex tb IIIC T85°C (flameproof Ex d version)
Tamb -40 to +65°C
CU TR-Ex (Russian Customs Union), Tamb -60 to +65°C*
CCCF*
Inmetro*
NEPSI *
PESO *
Assessed to have no effect on functional safety of connected gas sensor
OELD User Manual (3018M5000_1-3)
Maritime
Approvals*
Other
Approvals
Bluetooth communication security
Revision 1, Issue 3
Type approved to DNV, BV , Lloyds , ABS
EN 60945 (EMC)
IEC 60092-504
BT SIG (Bluetooth), RED, FCC , country-specific wireless approvals
Certificate-based mutual authentication. Encryption to AES128.
OELD User Manual (3018M5000_1-3)
Revision 1, Issue 3
11. Ordering Information
Part Number
Description
OELDBXXXXXADMAX
OELD Smart Junction Box, Display, Ex d, Aluminum, 5 x M25
Cable Entries, Bluetooth, ATEX/IECEx
OELDBXXXXXSDMAX
OELD Smart Junction Box, Display, Ex d, Painted 316SST, 5
x M25 Cable Entries, Bluetooth, ATEX/IECEx
OELDBXXXXXAEMAX
OELD Smart Junction Box, Display, Ex e, Aluminum, 5 x M25
Cable Entries, Bluetooth, ATEX/IECEx
OELDBXXXXXSEMAX
OELD Smart Junction Box, Display, Ex e, Painted 316SST, 5
x M25 Cable Entries, Bluetooth, ATEX/IECEx
OELDBXXXXXADNUX
OELD Smart Junction Box, Display, C1D1 Z1, Aluminum, 5 x
3/4" Cable Entries, Bluetooth, cULus
OELDBXXXXXSDNUX
OELD Smart Junction Box, Display, C1D1 Z1, Painted
316SST, 5 x 3/4" Cable Entries, Bluetooth, cULus
OELDBXXXXXADMRX
OELD Smart Junction Box, Display, Ex d, Aluminum, 5 x M25
Cable Entries, Bluetooth, CU-TR Ex
OELDBXXXXXSDMRX
OELD Smart Junction Box, Display, Ex d, Painted 316SST, 5
x M25 Cable Entries, Bluetooth, CU-TR Ex
OELD User Manual (3018M5000_1-3)
Find out more at www.honeywellanalytics.com
Contact Honeywell Analytics:
Europe, Middle East, Africa, India
Life Safety Distribution AG
Javastrasse 2
8604 Hegnau
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
gasdetection@honeywell.com
Customer Service
Tel: +800 333 222 44 (Freephone number)
Tel: +41 44 943 4380 (Alternative number)
Fax: +800 333 222 55
Middle East Tel: +971 4 450 5800 (Fixed Gas Detection)
Middle East Tel: +971 4 450 5852 (Portable Gas Detection)
India Tel: +91 124 4752700
Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honeywell.com
www.honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific Co., Ltd.
7F SangAm IT Tower
434 Worldcup Buk-ro, Mapo-gu,
Seoul 03922,
South Korea
Tel: +82 (0)2 6909 0300
Fax: +82 (0)2 2025 0388
Please Note:
While every effort has been made to ensure
accuracy in this publication, no responsibility can be
accepted for errors or omissions. Data may change,
as well as legislation and you are strongly advised
to obtain copies of the most recently issued
regulations, standards and guidelines. This
publication is not intended to form the basis of a
contract
analytics.ap@honeywell.com
Issue 3_06/2015
Technical Services
EMEAI: HAexpert@honeywell.comUS
H_MAN0XXX_EMEA
US: ha.us.service@honeywell.com
3011M5001 A0XXXX
AP: ha.ap.service@honeywell.com
Š 2016 Honeywell Analytics
Revision 1, Issue 3

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Author                          : Kim, Jesse
Create Date                     : 2016:07:06 14:22:20+09:00
Modify Date                     : 2016:07:06 14:22:26+09:00
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2016:07:06 14:22:26+09:00
Creator Tool                    : Acrobat PDFMaker 10.1 for Word
Document ID                     : uuid:4dd42a54-eec1-47a6-a711-da03d84b4c41
Instance ID                     : uuid:8d2ddef5-3282-4b71-ad5f-025b667d6f01
Subject                         : 10
Format                          : application/pdf
Title                           : OELD Instruction Manual
Creator                         : Kim, Jesse
Producer                        : Adobe PDF Library 10.0
Source Modified                 : D:20160706052208
Company                         : CodeWrights
Page Layout                     : OneColumn
Page Count                      : 31
EXIF Metadata provided by EXIF.tools
FCC ID Filing: 2AISEOELD

Navigation menu