Honeywell Security Sensor CoE PP300850SE DUAL TEC Motion Sensor User Manual 800 13827 B DT8050A QIG 12 10 13

Honeywell Security Sensor CoE DUAL TEC Motion Sensor 800 13827 B DT8050A QIG 12 10 13

Contents

User Manual (1 of 2).PDF

DT8050A DUAL TEC
®
Motion Sensor with Anti-Mask - Quick Installation Guide
DT8050A DUAL TEC
®
Motion Sensor with Anti-Mask - Quick Installation Guide (FR)
DT8050A DUAL TEC
®
Motion Sensor with Anti-Mask - Quick Installation Guide (SP)
DT8050A DUAL TEC
®
Motion Sensor with Anti-Mask - Quick Installation Guide (PG)
1
*
* Keep Clear / Tenir à l'écart /
Respetar obligatoriamente /
Manter-se afastado
*
6' 9" - 8' 9"
(2.1 - 2.7 m)
12”
(30 cm)
7' 6"
(2.3 m)
Optimal
Optimal
Optimal
Optimal
2
3
2
1
3
#6
(3.5 mm)
A
A
A
B B
B B
B B
A
B
#6 x 1 1/4"
(3.5 mm x 32 mm)
X X
4
Microwave Range Adjustment
Réglage de la portée Hyperfréquence
Ajuste del rango de detección Microondas
Ajuste de Alcance Microondas
Enabled
Activé
Habilitado
Habilitado
*Disabled
*Désactivé
*Deshabilitado
*Deshabilitado
* Factory default / Réglage usine /
Defecto de fábrica / Padrão de fábrica
ON
OFF
*
Anti-mask
Anti-masque
Antienmascaramiento
Anti-máscara
MW
SENSITIVITY
MAX
*
MIN
*
LED
Internal EOL Resistor DIP Switches
Résistance interne EOL commutateur DIP
Interruptores DIP internos EOL Resistor
EOL interno Resistor DIP Switches
EOL
KOhm
ON
1 2.2 5.62
*
DT8050A
AM LED
EOL
PULL
TO DISABLE
LOOK DOWN
LOOK DOWN
ON
OFF
ON
W1
MW
SENSITIVITY
MAX
KOhm
ON
1 2 2.2 5.6
DRAFT - QUICK INSTALL GUIDE - 12/10/13
- 2 -
5
24-20 AWG
(0.2-0.52mm2)
2
1
2
Tamper
30 mA
25 VDC
Trouble
30 mA
25 VDC
Power
18 mA
9 - 15 VDC
Alarm
30 mA
25 VDC
LED
0 VDC - Vsupply
1.8 mA max
LED TBL T C V-V+
T NCTBL
9 8 6 4 2 15 37
EOL
KOhm
ON
1 2.2 5.62
EOL
WIRING EXAMPLES / WIRING EXAMPLES / WIRING EXAMPLES / WIRING EXAMPLES
To connect all three outputs (sensor alarm, tamper and trouble/anti-
mask) to one zone input: All alarm, tamper and trouble/anti-mask
events are “alarms” when the system is armed or “fault” when disarmed.
FR) To connect all three outputs (sensor alarm, tamper and
trouble/anti-mask) to one zone input: All alarm, tamper and
trouble/anti-mask events are “alarms” when the system is armed or “fault”
ES) To connect all three outputs (sensor alarm, tamper and
trouble/anti-mask) to one zone input: All alarm, tamper and
trouble/anti-mask events are “alarms” when the system is armed or “fault”
whe
n disarmed.
PG) To connect all three outputs (sensor alarm, tamper and
trouble/anti-mask) to one zone input: All alarm, tamper and
trouble/anti-mask events are “alarms” when the system is armed or “fault”
Zone
COM Ground
Zone
#
Anti-mask
Enabled
+12V
Control Panel
(On-Board, Internal EOLR)
LED TBL T C V
-
V
+
T NCTBL
9 8 6 4 2 15 37
EOL
KOhm
ON
1 2.2 5.62
EOL
ON
Sensor
Note: A masking condition can occur when blocking or reflective material is placed in front of the sensor. Keep 12” (30cm) in front
of the sensor clear.
Note: A masking condition can occur when blocking or reflective material is placed in front of the sensor. Keep 12” (30cm) in front
of the sensor clear.
Note: A masking condition can occur when blocking or reflective material is placed in front of the sensor. Keep 12” (30cm) in front
of the sensor clear.
Note: A masking condition can occur when blocking or reflective material is placed in front of the sensor. Keep 12” (30cm) in front
of the sensor clear.
To connect the sensor alarm output to one zone input and the
tamper and trouble/anti-mask outputs to a second zone input: The
alarm relay is wired to one zone; the tamper and trouble/anti-mask are
wired to another zone;
the control panel differentiates alarm conditions
from tamper and trouble/anti-mask conditions.
To connect the sensor alarm output to one zone input and the
tamper and trouble/anti-mask outputs to a second zone input: The
alarm relay is wired to one zone; the tamper and trouble/anti-mask are
wired to another zone; the control panel differentiates alarm conditions
from tamper and trouble/anti-mask conditions.
To connect the sensor alarm output to one zone input and the
tamper and trouble/anti-mask outputs to a second zone input: The
alarm relay is wired to one zone; the tamper and trouble/anti-mask are
wired to another zone; the control panel differentiates alarm conditions
from tamper and trouble/anti-mask conditions.
To connect the sensor alarm output to one zone input and the
tamper and trouble/anti
-mask outputs to a second zone input: The
alarm relay is wired to one zone; the tamper and trouble/anti
-mask are
wired to another zone; the control panel differentia
tes alarm conditions
from tamper and trouble/anti
-mask conditions.
*
Zone
COM Ground +12V
Control Panel
Trouble
Zone
Alarm
Zone
W1
* Off-Board, External EOLR (Not supplied),
best if installed inside the sensor housing.
LED TBL T C V
-
V
+
T NCTBL
9 8 6 4 2 15 37
Cut
Anti-mask
Enabled
EOL
KOhm
ON
1 2.2 5.62
EOL
ON
Sensor
(On-Board, Internal EOLR)
JUMPER
- 3 -
To connect the sensor alarm, tamper and trouble/anti-mask outputs
to three separate zone inputs: The alarm, tamper and trouble/anti-mask
are each wired to a separate zone; the control panel differentiates alarm,
tamper and trouble/anti-mask conditions.
To connect the sensor alarm, tamper and trouble/anti-mask outputs
to three separate zone inputs: The alarm, tamper and trouble/anti-mask
are each wired to a separate zone; the control panel differentiates alarm,
tamper and trouble/anti-mask conditions.
To connect the sensor alarm, tamper and trouble/anti-mask outputs
to three separate zone inputs: The alarm, tamper and trouble/anti-mask
are each wired to a separate zone; the control panel differentiates alarm,
tamper and trouble/anti-mask conditions.
To connect the sensor alarm, tamper and trouble/anti-mask outputs
to three separate zone inputs: The alarm, tamper and trouble/anti-mask
are each wired to a separate zone; the control panel differentiates alarm,
tamper and trouble/anti-mask conditions.
* *
Zone
COM Ground +12V
Control Panel
Tamper
Zone
Alarm
Zone
Trouble
Zone
Zone
COM
LED TBL T C V
-
V
+
T NCTBL
9 8 6 4 2 15 37
W1
Cut
Anti-mask
Enabled
EOL
KOhm
ON
1 2.2 5.62
EOL
ON
* Off-Board, External EOLR (Not supplied),
best if installed inside the sensor housing.
Sensor
(On-Board, Internal EOLR)
6
30 sec
30
0
45
20
10
ON
MW
SENSITIVITY
MAX
MIN
AM LED
Walk Test Reset
4X
(slowly)
< 4 ft /1.2m
7
Top View
Vue de dessus
Vista Desde Arriba
Vista Superior
Side View
Vue de coté
Vista Lateral
Vista Lateral 0
0.5
1.85
2.3m
PLAN VIEW
ALL ZONES
7’
2 m
0
0
13’
4 m
20’
6 m
27’
8 m
33’
10 m
40’
12 m
7’
2 m
13’
4 m
20’
6 m
27’
8 m
33’
10 m
40’
12 m
7’
2 m
13’
4 m
20’
6 m
27’
8 m
33’
10 m
40’
12 m 46’
14 m
53’
16 m
7’
2 m
0
13’
4 m
20’
6 m
27’
8 m
33’
10 m
40’
12 m
46’
14 m
53’
16 m
A B C D
LED Power
Up Walk Test Normal Trouble
Anti-
Mask
Red Slow
Blink
ON
Alarm
ON
Alarm
Fast
Blink OFF
Yellow OFF ON
Microwave
ON
Microwave OFF Fast
Blink
Green OFF ON PIR ON PIR OFF OFF
Zones / Zones / Zonas / Zonas
A
2
Look-down / Basses / Vista Zona 0 /
Vigilância inferior
B
12
Lower / Courtes / Cercana/ Mais baixas
C
10
Intermediate / Intermédiaires / Intermedia /
Intermédias
D
36
Long / Longues / Largo Alcance / Longo
alcance
- 4 -
APPROVAL/ LISTINGS:
FCC part 15, Class B verified
IC ICES-003, Class B verified
UL 639
ULC S306-03
SIA-PIR-01 Passive Infrared detector standard features for false alarm immunity.
Product must be tested at least once each year.
For appropriate wiring methods, refer to the National Electrical Code NFPA 70 and the Canadian Electrical Code (where applicable).
Power must be provided by a power-limited UL603 Listed burglar alarm power supply with minimum 4 hours of standby power capability, or from a
power-limited output of a UL Listed burglar alarm control unit with minimum 4 hours of standby power capability.
For the latest documentation and online support information, please go to:
Pour de l’assistance en ligne, visitez :
Para recibir soporte en línea, visite:
Para qualquer informação adicional, contacte:
http://www.security.honeywell.com/hsc/resources/MyWebTech/
For the latest U.S. warranty information, please go to: www.honeywell.com/security/hsc/resources/wa or
Please contact your local authorized Honeywell representative for product warranty information.
Pour obtenir de l'information sur la garantie de ce produit, veuillez communiquer avec le représentant autorisé de Honeywell
de votre région.
Por favor contacte con su distribuidor Honeywell Security para información sobre la garantía del producto.
Contacte o representante autorizado Honeywell local para obter informações relativas a garantia.
2013 Honeywell International Inc. Honeywell and DUAL TEC are registered trademarks of Honeywell International Inc.
All other trademarks are the properties of their respective owners. All rights reserved. Made in China.
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your
information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the
manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for
a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection
against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
If using an indoor antenna, have a quality outdoor antenna installed.
Reorient the receiving antenna until interference is reduced or eliminated.
Move the radio or television receiver away from the receiver/control.
Move the antenna leads away from any wire runs to the receiver/control.
Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA CLASS B STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause
undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soumis aux conditions
suivantes: (1) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les
interférences causant une réception indésirable.
P/N 800-13827 12/13 Rev B