Honeywell 202150TXR Thermostat User Manual E528 Product Guide v7 0 PG

INNCOM International Inc. Thermostat E528 Product Guide v7 0 PG

Manual

Download: Honeywell 202150TXR Thermostat User Manual E528  Product Guide v7 0 PG
Mirror Download [FCC.gov]Honeywell 202150TXR Thermostat User Manual E528  Product Guide v7 0 PG
Document ID1905005
Application IDdBL8+vaDfnxqJ4WqyIe9Pw==
Document DescriptionManual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize128.88kB (1610950 bits)
Date Submitted2013-02-22 00:00:00
Date Available2013-08-21 00:00:00
Creation Date2013-01-21 11:51:49
Producing SoftwareGPL Ghostscript 8.15
Document Lastmod2013-01-21 11:51:49
Document TitleMicrosoft Word - E528__Product_Guide_v7.0_PG.doc
Document CreatorPScript5.dll Version 5.2.2
Document Author: mahussain

Global Leader in Integrated Room Automation Systems
Confidential
Copyright © 2010 INNCOM
e528 Smart Digital Thermostat
Product Guide
Overview
INNCOM's e4 Smart Digital Thermostat is a powerful, multi-purpose Direct Digital Control (DDC) device that
can control virtually any HVAC system found in hotel guestrooms.
The three e4 models meet different application requirements. The e528 and e527 are
wired and are typically used for new installation. The e529 is battery-powered and is
designed to meet the needs of existing properties where rewiring is not practicable.
This document describes Model e528; information on the e529 and e527 can be found
in their respective product guides.
Application
In its most basic form, the e528 functions as a programmable DDC thermostat,
automatically adjusting fan speeds and valves to achieve set temperature (Note:
Guests can manually select heat or cool by pressing the OFF/AUTO button and
cycling through OFF, AUTO, HEAT and COOL). The e528 is also an “intelligent”
Figure 1 e528 Digital Thermostat
device capable of linking ancillary sensors and serving as an information gateway.
For example, coupled with a magnetic door switch (wired or wireless), motion detectors, and other devices, the
e528 becomes the brain of a highly effective Energy Management System (EMS) application, communicating EMS
information requirements to central servers. It comes standard with five relays and can be equipped with an onboard Infrared (IR) or radio frequency (RF) transceiver and Passive Infrared (PIR) motion detector.
The e528 interfaces with all common HVAC unit voltage configurations (24 volt to 277 volt). The e528 can be
installed in a wired or wireless INNCOM guestroom control system, which makes installation feasible and
affordable in either new construction or retrofit installations.
Through interfaces with other devices and sensors, the e528 supports the following functions:
•
•
•
•
•
•
•
•
•
•
•
•
Remote HVAC control
Guestroom HVAC diagnostics
Remote room occupancy indication
Automatic lighting control
Remote mini-bar access reporting
Remote smoke detector annunciation
Central Electronic Lock control
Humidity control
Remote drape control
Outside temperature display
Peak demand load shedding
Property/Building Management System (PMS/BMS) interface
E528 Product Guide
Page 2 of 18
A centrally controlled EMS package is created when the e528 is connected to the property's Central Interface
Network (CINET) with a pair of low voltage wires or by the property’s high-speed TCP/IP network with the
addition of a TCT (an Ethernet gateway device). RF networking is possible with radio equipped models.
The e528 features a guest-friendly graphic interface with intuitive controls (Figure 2). A user guide for the e528,
written primarily for installers and facility management personnel, is available (see References below).
Figure 2 e528 Graphic Interface
Wireless Communication
2.4Ghz wireless RF
Table 1 e528 RF Characteristics
Performance
RF Data Rate
Antenna Type
Indoor Range
0dB
20dB
250kbps
SMT
250kbps
SMT
70ft
100ft
540ft
1mW
1000ft+
10mW
Receive Sensitivity
Frequency Band
-94.6dBm
2.4Ghz
-94.6dBm
2.4Ghz
Encryption
AES-128
AES-128
Protocol
Frequency Channels
802.15.4
11-26
802.15.4
11-26
Outdoor/ RF line-of-sight range
Transmit Power
Ranges are determined by performing an RF link quality test using two identical e528 thermostats containing
radios as defined in tables 2 and 3. The maximum distance threshold is based on a 95% overall link quality.
Outdoor ranges were conducted in a low noise, free air environment. Indoor ranges are for reference. Indoor
ranges are impacted by the ambient environmental noise floor, and building construction materials.
E528 Product Guide
Page 3 of 18
IR5 (Infrared)
Table 2 e528 IR5 Characteristics
Performance
IR5
Indoor Range
IR Data Rate
Up to 80ft
2500 bps
The IR Eye5 works within INNCOM's System-5 protocol and can be used in a fluorescent light environment.
However, it may be subject to interference from plasma televisions, and care must be taken in situating the device
if a plasma television is present.
Installation Requirements
Location: The e528 must be located on a partitioning interior wall, approximately 1.5 m (5 ft) above the floor, in a
site of average temperature. It is important to ensure that the thermostat is located away from direct sunlight or
radiant heat, air discharge grills, stairwells, outside doors, steam or water pipes, warm air stacks,
unheated/uncooled areas, or sources of electrical or radio interference. The unit should not be placed on an outside
wall or behind a door. It is essential that the e4 is mounted flush to the wall and mounted level in both the horizontal
and vertical planes; incorrect mounting can degrade IR, PIR, and temperature measurement performance.
Installation Requirements for e4 equipped with PIR Motion Detection
The e4 thermostat can be equipped with a PIR detector to augment the energy management scheme by detecting
motion in the guestroom. Consider the PIR’s view angle, range characteristics, and mounting position to ensure
proper coverage. Figure 3 below shows the ranges of the flat and standard PIRs.
Flat PIR Detection Range (Single Pyro)
Standard PIR Detection Range (Dual Pyro)
Figure 3 PIR Detection Ranges
E528 Product Guide
Page 4 of 18
Mounting: The e528 is usually mounted on a standard double-gang (4 x 4) junction box. If mounted on a singlegang box, the left side (display side) of the e528 overlaps the wall area to the left of the junction box. A lowvoltage mounting plate, mud ring, or low-voltage caddy may be used for mounting 24 volt applications.
To mount the e528:
1) Remove the two small screws at the base of the e528.
2) Pull the bottom of the back-mounting plate slightly away from the front housing and then pull the backmounting plate down.
3) Position the back plate insulator within the mounting plate as shown in Figure 4.
4) Attach the mounting plate to the junction box, using the mounting screws provided with the e528. Ensure
that the plate is mounted with the raised arrow pointing UP.
Figure 4 Mounting Assembly
To simplify installing and removing the e528, the headers and sockets described below and shown in Figure 5 are
located on the back of the e528. These accept pre-made wiring harnesses provided by INNCOM. (Note: Take care
to note which e528 model is being used. Each model has slightly changed headers and connectors as identified in
the drawings below.)
E528 Product Guide
Page 5 of 18
Figure 5 Back View Showing Headers and Sockets
E528 Product Guide
Page 6 of 18
Headers
The headers for the e528.2G, 3G and 4G* thermostats are substantially the same, though the layouts and labeling on
the PCB are slightly different (see Figure 5 above). The statements and tables below detail only the headers that differ
in function.
Low Voltage comm / device connector: This header accepts the provided 6-pin harness used to connect low
voltage communication, door/window position switch, and other room devices to the e528. Table 3 shows the
pinout for the 2G low voltage comm / device connector and lists typical functions for each pin. Table 3a shows
pinout and function for the 3G and 4G. For specifics, refer to the as-built wiring diagrams.
Table 3. e528 2G Low Voltage Harness (P/N 62-1462) Pinout
Wire Color
Brown
Red
Orange
Yellow
Green
Blue
Female
Connector
Male
Connector
Function
Common
12VDC Out/In
S5 Bus Data Tx/Rx or IN 2
IN 1
CINET B
CINET A
Comment
GND
12VDC Supply
Communication Bus
Door, Window, PIR, Other
RS485 Twisted Pair
RS485 Twisted Pair
Table 3a. e528 3G/4G Low Voltage Harness (P/N 62-1467) Pinout
Wire Color
Brown
Red
Orange
Yellow
Green
Blue
Female
Connector
Male
Connector
Function
Common
12VDC Out/In
S5 Bus Data
Digital Input
No Connection
No Connection
Comment
GND
12VDC Supply
Communication Bus
Door, Window, PIR, Other
External temperature control sensor: This header accepts the wiring harness from an external temperature probe
that can be used to supply the e528 with remote temperature measurements. The e528 uses a 10K 1% thermistor
for external temperature measurement. This external temperature sensor can be used to monitor room
temperature at a different location from where the e528 is mounted or to monitor pipe water temperature.
RS485 Networks: (refer to Figure 5)
E528.2G can be connected to the RS485 FLN5 network by installing the 02-9496 module, then connecting the
RS485 network to pins 5 and 6 of the low voltage comm /device connector as described in Table 3 above.
E528.3G cannot act as the media gateway for in-room traffic towards the RS485 network. The most common
way to connect the e528.3G is to connect a PC-485.S5 (P/N: 01-9905) on the S5bus.
E528.4G
E528.4G to 2G RS485 Networked Application: with or without door switch input (See Figure 6 below)
•
•
Using the adapter (P/N 203-251), connect the harness from the wall box (P/N 62-1462) previously
connected to the thermostat being replaced to H1 of the adapter.
Connect the harness H3 (rainbow) of 203-251 to the low voltage comm/device connection of the e528.4G
“2G,” “3G,” and “4G” are internal INNCOM product designations used for convenience to differentiate
individual hardware configurations. No difference in device capability or effectiveness is implied. Due to end-oflife for certain 2G and 3G components, the e528.4G is now the standard INNCOM install, but 2G and 3G
installations are still supported.
E528 Product Guide
•
Page 7 of 18
Connect the harness H2 (black) of 203-251 to the RS485 header of the e528.4G
NOTE: Take care to not reverse the connections to the e528.4G!
Figure 6 4G to 2G RS485 Networked Application
E528.4G New Installation
Stand alone application with/without door switch input
•
Using the harness (P/N 62-1467), make the appropriate wire connections, then plug the harness into the
low voltage comm/device connection of the e528.4G
RS485 Networked Application with/without door switch input (See Figure 7)
•
•
•
Using the harness (P/N 62-1467), make the appropriate wire connections, then plug the harness into the
low voltage comm/device connection of the e528.4G.
Using the adapter (P/N 203-250) and P/N 62-1532-B.12 cables, connect the RS485 A pair to the two pin
RS485 In header and the RS485 B pair going to the next thermostat to RS485 Out header on the 203-250.
Connect the harness of 203-250 to the RS485 network header of the e528.4G.
Figure 7 E528.4G New RS485 Networked Application
E528 Product Guide
Page 8 of 18
E528.4G Retrofit Installation
The e528.4G can be used to retrofit an application where a legacy e528 was used. Follow the procedure below:
4G to 2G Standalone application: with/without door switch input (no backhaul network)
•
Using the adapter (P/N 203-013) connect the harness from the wall box (P/N 62-1462) previously
connected to the thermostat being replaced to H1 of the adapter (see Figure 8).
•
Connect the harness of 203-013 to the low voltage comm/device connection of the e528.4G.
Figure 8 e528.4G to 2G Standalone application
Molex 10-position female socket: This female socket accepts the provided 10-pin Molex connector pre-wired
with 8-inch, color-coded wiring leads. These leads should be connected to the 24VAC or 100–277VAC power,
valve/fan control wiring from the FCU, or other HVAC device with wire nuts inside in the wall junction box in
accordance with the wiring diagram provided by INNCOM.
Note: For installations in which all leads are not required, the extraneous leads should be cut off at the Molex connector.
Figure 8 shows the pinout for the 10-position Molex male connector supplied with all relay output models of the
thermostat. The end view of the male connector from the wire insertion side with the pin numbers is indicated.
This is the same as looking at the female connector point on the back of the e528.
Typical functions for each wire are listed in Tables 4 and 5. For specifics, refer to the as-built wiring diagrams.
Figure 9 10-Pin Molex Connector (Part No. 62.1455 or 62.1464.R)
Table 4. 24VAC Harness Color Code, Pinout, and Typical Functions
E528 Product Guide
Page 9 of 18
24VAC harness (INNCOM Part # 62-1464 R)
Pin
Color
Green
Red
Black
Blue
Brown
Yellow
White
10
Grey
Violet
Orange
Typical Function
Ground
24VAC
Common
High Fan
Medium Fan or Second Stage Heat
Cold Water Valve (FCU) or Compressor Signal
(Heat Pump)
Hot Water Valve (FCU) or Reversing Valve
(Heat Pump)
Valve Power
Fan Power
Low Fan
Table 5. 100-277VAC Harness Color Code, Pinout, and Typical Functions
100-277VAC harness (INNCOM Part # 62-1455)
Pin
Color
Green
Black
White
Yellow
Orange
Red
Brown
10
Grey
Violet
Blue
Typical Function
Ground
Line
Neutral
High Fan
Medium Fan or Second Stage Heat
Cold Water Valve (FCU) or Compressor Signal (Heat
Pump)
Hot Water Valve (FCU) or Reversing Valve (Heat
Pump)
Valve Power
Fan Power
Low Fan
Wiring: The steps below provide an overview of the wiring process. Refer to the as-built wiring diagrams
provided for exact details.
1.
If applicable, use wire nuts to connect the 6-pin low-voltage harness wires to the applicable low-voltage
communication (if e528 is part of a wired RS485 centrally controlled system), door/window switch, or
external PIR wiring within the electrical box (Figure 8). Plug the 6-pin low voltage harness onto the e528 low
voltage comm. / device connection header.
2.
Use wire nuts to connect the 10-pin Molex wiring harness to the power and valve/fan control signal wires
within the electrical box.
3.
Plug the pre-wired 10-pin connector into the female receptacle at the back of the e528.
4.
Hook the tabs at the top rear of the e528 housing into the matching depressions at the top of the mounting
plate and rotate the bottom of the housing toward the wall until it snaps into place on the mounting plate.
5.
Secure the housing to the mounting plate with the two small screws removed in Step 1 of the Mounting section.
6.
Apply power to the e528 by closing the applicable supply breaker. Verify that the e528 powers up. Several
values should begin appearing on the LCD display.
7.
Once installed and connected to power, the e528 Digital Thermostat typically requires some configuration,
specifically:
•
If installing the e528 as part of a networked, centrally controlled EMS, a unique network address must be
assigned to the e528. This is done by entering Service Parameter mode on the e528 and changing the
E528 Product Guide
•
Page 10 of 18
values of Parameters 10, 11, and 12, which hold the 5-digit network address of the e528. This 5-digit
number is typically the room number in most applications. A “Room List” document is typically
available that lists all rooms and the associated values to set into Parameters 10, 11, and 12. Refer to
Reference A, Section 5.1, for complete instructions for setting the e528 network address.
If the particular HVAC equipment installed was not known when the e528 was shipped, the fan and
heat/cool control outputs of the e528 must be configured to correctly operate the installed HVAC
equipment. Setting the appropriate HVAC control parameters of the e528 to the required values and
resetting the device reconfigures the e528 to properly control most HVAC units. Refer to Reference A,
Section 5.2, for instructions on changing the e528 HVAC related parameters, if required.
NOTE: If installing 01-9560 64K memory e528 Digital Thermostats, be aware that these devices support the
INNCOM ES-1 Flash Memory Module. The ES-1 provides the ability to copy HVAC related parameter settings
from a “golden” e528 that has previously been installed in a room and had its HVAC related parameters set
correctly and verified operationally with the HVAC equipment. Once these settings are copied to the ES-1
module, plugging the ES-1 into a new thermostat automatically uploads the settings.
Figure 7 Electrical Box Connections Line and Low Voltage
E528 Product Guide
Page 11 of 18
Figure 8 Electrical Box Connections 24VAC
Load Specifications
The following load specification table (Table 6) describes the submitted load characteristics for testing and UL
certification of UL 873. The device complies with the requirements of CAN/CSA C22.2 No. 24-93.
Table 6. Load Specifications
MODEL
Voltage
24VAC
24VAC
24VAC
100-240VAC
Heat
Relay K4-5
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
240 VA PD
240 VA PD
e528-C0L2I0P000WH
220277VAC
240 VA PD
240 VA PD
240 VA PD
240 VA PD
2.2 FLA
13.2 LRA
3.6 FLA
21.6 LRA
3.6 FLA
21.6 LRA
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3.6 FLA
21.6 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA
Cool
Relay K4-5
High Fan
Relay K1
Medium Fan
Relay K2-3
Low Fan
Relay K2-3
e528-A2L2-I0P000WH
e528-A3L2-I0P000WH
e528-A1L2I0P0-00WH
e528-B0L2I0P0-00WH
e528-B1L2-I0P000WH
100-277VAC
E528 Product Guide
Page 12 of 18
Technical Specifications
Table 7. Technical Specifications
Power Requirements
Relay Contact Rating
Triac Relay Contact Rating
Recommended Wire Size
Thermostat Measurement Range
Outdoor Air Temperature
Display Resolution
Standard Deadband
Degrees C/Degrees F Display
Ambient Operating
Ambient Storage
Dimensions
Shipping Weight
Approvals
RF Specifications
24 VAC at 50/60 Hz, 24 VDC nominal, 2.4 VA (e528-3xx/7xx and e528-4xx)
100 to 277 VAC at 50/60 Hz, 2.4 VA (e528-8xx)
See Table 4.
50 m at minimum, 250 m at maximum (e528-4xx)
18 gauge
33 to 99 degrees F (1 to 37 degrees C)
0 to 99 degrees F (-18 to 37 degrees C)
Whole degree F, 0.5 degree C (0.1 degree F in test mode)
2 degrees F (1 degree C) between heating and cooling
Toggle Button located on front display
41 to 149 degrees F (5 to 65 degrees C), 0-95% RH noncondensing
33 to 149 degrees F (1 to 65 degrees C)
(H x W x D) 4.7 x 4.7 x 1.2 in. (120 x 120 x 30 mm)
0.6 lb (0.27 kg)
UL listed #873, CAN/CSA C22.2 No. 24-93 File #E202540/Part 15 of the FCC Rules
See TXR RF Datasheet
Warning: Power supply MN PS564 must be used to provide power.
FCC ID: GTC202150TXR, or GTC202152TXR
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one of the following measures:
— Reorient or relocate the receiving antenna.
— Increase the separation between the equipment and receiver.
— Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
— Consult the dealer or an experienced radio/TV technician for help.
Any changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate this equipment.
IC ID: 1609A-202150TXR, or 1609A-202152TXR
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two
conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference
that may cause undesired operation of the device.
E528 Product Guide
Page 13 of 18
Le présent appareil est conforme aux CNR d’industrie Canada applicables aux appareils
radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes: (1)
l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter
tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en
compromettre le fonctionnement.
Ordering Specifications
Note: Ordering schemes are based on the latest PCB revision. The tables and examples in this section are correct
only to the date of this document version. Verify part numbers and inventory availability before ordering.
The IR-only e4 ordering part number (OPN) scheme uses only 3 digits to indicate power supply and options:
Figure 9 IR Only E528.2G OPN Scheme
The “X” number is the first of the three digits and designates the power supply type
Table 8. IR only e528 Power Supply Ordering
Power Supply Type
12VDC S5BUS (Power Supply removed, powered by external X06 or X05
24VAC 50/60 Hz
24VAC Triac
Nominal Voltages: 100–240VAC 50/60 Hz w/ 3.6 FLA High Fan Relay
Nominal Voltages: 265–277VAC 50/60 Hz w/ 3.6 FLA High Fan Relay
24VAC 50/60 Hz (02-9561)
100-277VAC Hz (02-9560)
24VAC 50/60 Hz (02-9565)
E528 Product Guide
Page 14 of 18
The “YY” numbers are the second and third digits and designate the option or combination of options. When
more than one option is selected, the “YY” option numbers are added, as in Examples B and C shown below.
YY Option #
Option
Description
00
None
No Options
01
IR3
02-9464.1 IR3 PCBA option
02
IR5
02-9467 IR5 PCBA option
03
IR3+
02-9464.3 IR3+ PCBA option
04
Humidity Sensor
08
PIR
Passive IR Motion Sensor
16
DM
Do-Not-Disturb & Make-Up-Room Buttons
32
P2
Flat PIR
Example A
100V-277VAC e4 with no options = Model e4-800 [X = 8, YY = 00] (with 2.2 FLA high fan relay)
Example B
100-277V e4 with H + PIR options = Model e4-812 [X = 5, YY = (04 {H} + 08 {PIR}) = 12] (with 3.6 FLA high fan relay)
Example C
OLD 24V e4 with IR5 + PIR options =
Model e4-310
[X = 3, YY = (02 {IR5} + 08 {PIR} = 10]
NOTE: This assembly would be 01-9560.310 and calls for a 03-9460 which uses old P supply and 9496.
For the RF capable thermostats, the complexity engendered by the multiplicity of power supplies, logic boards,
and communications and other option call for a larger OPN incorporating a more granular scheme (Figure 13,
below). Table 9 lists the options available for the RF E528:
Figure 10 e528 3G OPN
Figure 11 RF Capable e528 OPN
Table 9. RF capablee528 Ordering Options
Model
This character set defines the model name for the e528.
OP/N Code
e528
Description
DDC Thermostat
Part Number
01-9911
E528 Product Guide
Page 15 of 18
Power Supply
This character set defines the power supply options available for the e528.
OP/N Code
A0
A1
A2
A3
B0
B1
C0
Power Supply Type
No power supply
24VAC 50/60Hz power supply (300 series)
24VAC 50/60Hz power supply (700 series)
24VAC 50/60Hz power supply (900 series*)
110-240VAC 50/60Hz w/ 3.6FLA high fan relay (500 series)
120-277VAC 50/60Hz w/ 2.2FLA high fan relay (800 series)
265-277VAC 50/60Hz w/ 3.6FLA high fan relay
Part Number
02-9461
02-9561
02-9565.C1
02-9460.5
02-9560
02-9460.6
Logic Board
This character set defines the logic board options available for the e528.
OP/N Code
L0
L3
L4
L6
L7
Logic Board Type
No logic board
e528 3G hermetic enclosure w/ 0dB radio
e528 3G hermetic enclosure w/ 20dB radio
E528 4G logic board with 0dB radio
E528.4G logic board with 20dB radio
Part Number
02-9911.L1
02-9911.L2
202-150
202-152
Communication
This character set defines the auxiliary communication options for the e528.
OP/N Code
I0
Auxiliary Communication Type
No auxiliary communication device
I5
IR5 only
Part Number
02-9467.e8d
Motion Detection/Output
This character set defines the motion detection/output options for the e528s (Note: photos are for reference only.
Actual product models may differ slightly in appearance).
P0
OP/N Code
Motion Detection/Output Type
Blank
53-0446
Part Number
P1
Standard PIR
02-9465-B
E528 Product Guide
OP/N Code
Page 16 of 18
P2
Motion Detection/Output Type
Flat PIR
02-9499
Part Number
Q0
DND/MUR only
53-0448
Q1
Manual heat/cool selection only
TBD
Q2
ecoMODE only
53-9209
R0
Standard PIR with DND/MUR
53-0448
R1
Standard PIR with heat/cool
output
TBD
E528 Product Guide
Page 17 of 18
R2
OP/N Code
Motion Detection/Output Type
Standard PIR with ecoMODE
53-9210
Part Number
R4
Flat PIR with ecoMODE
53-9211
Humidity Sensor
This character set defines the humidity sensor options for the e528.
OP/N Code
Humidity Sensor Option
No humidity sensor
Humidity sensor
Part Number
02-9463
Logo/Housing
This character set defines the housing logo for the e528.
OP/N Code
Logo Option
No logo
INNCOM logo
JCI logo (Johnson Controls)
Part Number
Color
This character set defines the housing color options for the e528.
OP/N Code
WH
EA
BK
XX
Housing Color Option
White
Eagle Almond
Black
Custom
Part Number
Ordering Example:
e528-A1-L2-I5-P2-1-O-WH = An e528 with a 24VAC 50/60Hz power supply (300 series), 64K logic board, IR5
auxiliary communication device, flat PIR motion detector, humidity sensor, no logo, manufactured in white.
Figure 14 indicates the area of the thermostat that has options VISIBLE to the guest.
E528 Product Guide
Page 18 of 18
Figure 12 Area of Thermostat with Options Visible to the Guest
References
e528 Operation Manual, INNCOM Document 3000, Version 2.0, Dated April 29, 2005
Document Revision History
REVISION
First issue
v1
DATE ISSUED
26-Apr-2006
30-Jul-2007
v2
v3
Not issued
27-Jun-2008
v4
v5
v6
v6.1
v6.2
v7.0
30-Jun-2008
30-Jun-2008
18-Feb-2010
22-Apr-2010
28-Oct-2010
05-Apr-2012
REASON FOR CHANGE
Reformatted for consistency with other product guides. Information
about the other e4 models added to the Overview section. Information on
all ordering options and new features added to the Ordering section.
Product photos updated. Part number corrected. Figure 3 redrawn.
New Figure 2 added (PIR range figures) and figure numbers changed to
accommodate the added figure.
Switched to new document format.
Error in Figure 4 corrected; font discrepancies corrected.
Reformatted to new template, RF data updated
OP/N rewritten to include old scheme; photos updated.
Added 3G pinout note
Added 4G information

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Count                      : 18
Producer                        : GPL Ghostscript 8.15
Create Date                     : 2013:01:21 11:51:49
Modify Date                     : 2013:01:21 11:51:49
Title                           : Microsoft Word - E528__Product_Guide_v7.0_PG.doc
Creator                         : PScript5.dll Version 5.2.2
Author                          : mahussain
EXIF Metadata provided by EXIF.tools
FCC ID Filing: GTC202150TXR

Navigation menu