S6065A1003/2001
LIQUID FLOW SWITCHES

SPECIFICATION DATA & MOUNTING INSTRUCTIONS

FEATURES
•
•
•

Cost-effective flow switches for HVAC applications.
High-capacity, fully-encapsulated NC/NO micro-switch.
A single type suitable for pipes with a diameter of 1 to 8".

COMMON SPECIFICATIONS
Switching capacity
Lifetime
Working temperature
Electrical connection
Protection class
Protection standard
Housing material
Accessories

S6065A2001

15 (8) A, 24...250 Vac
50000 cycles at nominal load
-40...+85 °C at 90% rel. humidity,
non-condensing
Screw terminal, wire up to 1.5 mm2
cable ∅ 6...9 mm
I according to EN60730
IP65 according to EN60529
ABS and corrosion-protected steel
PA2 Paddle set

MOUNTING
S6065A1003

GENERAL
The S6065A1003 and S6065A2001 Liquid Flow Switches are
designed for monitoring flow rates in pipes employed in HVAC
applications. They are suitable for monitoring flow in water,
oil, cooling circuits, and lubrication systems. The S6065A2001
is designed for monitoring aggressive liquids.
See Table 1 for the reset and switch points for water. Data for
other media must be determined empirically.

The S6065A1003 and S6065A2001 Liquid Flow Switches can
be mounted in any desired position far from elbows, valves,
and filters.
NOTE: The arrow on the housing must point downstream.
When using multiple paddles, the paddles must be
arranged in order of decreasing length downstream,
i.e. with the longest paddle facing the oncoming
liquid.
In the case of vertical pipes, reset the range to balance the
paddle weight. To prevent malfunction caused by impurities in
the medium, do not mount the device with the housing
pointing downwards.

MODELS
Specification
Flow medium
Mounting
Maximum pipe temperature
Pressure
Paddle material
Lever
Sensor body
Housing dimensions
Weight
Approvals

S6065A1003
non-aggressive liquid
Rp 1" (ISO7/1)
120 °C
11 bar
1.4401
yellow brass
yellow brass
113 x 70 x 65 mm
850 g
TÜV-approved

® U.S. Registered Trademark
Copyright © 2008 Honeywell Inc. • All rights reserved

S6065A2001
aggressive liquid
Rp 1" (ISO7/1)
120 °C
30 bar
1.4401
1.4404
1.4404
108 x 70 x 72 mm
850 g
TÜV-approved

EN0B-0314GE51 R01008

S6065A1003/2001 LIQUID FLOW SWITCHES

65 mm
54 mm

PG11

R1”

29 mm

Fig. 2. S6065A1003 dimensions
135 mm
113 mm

70 mm

132 mm

FIELD WIRING
COMMON

PG11
54 mm

RED

72 mm

reset / switch point

min. flow
max. flow
3
3
(m /h)
(m /h)
1"
1"
3.6
0.6 / 1.0
2.0 / 2.1
1"
1-1/4"
6.0
0.8 / 1.3
2.8 / 3.0
1"
1-1/2"
9.0
1.1 / 1.7
3.7 / 4.0
1"+2"
2"
15.0
2.2 / 3.1
5.7 / 6.1
1"+2"
2-1/2"
24.0
2.7 / 4.0
6.5 / 7.0
1"+2"+3"
3"
36.0
4.3 / 6.2
10.7 / 11.4
1"+2"+3"
4"
60.0
11.4 / 14.7 27.7 / 29.0
1"+2"+3"+Z* 4" Z
60.0
6.1 / 8.0
17.3 / 18.4
1"+2"+3"
5"
94.0
22.9 / 28.4 53.3 / 55.6
1"+2"+3"+Z* 5" Z
94.0
9.3 / 12.9
25.2 / 26.8
1"+2"+3"
6"
120.0
35.9 / 43.1 81.7 / 85.1
1"+2"+3"+Z* 6" Z
120.0
12.3 / 16.8 30.6 / 32.7
1"+2"+3
8"
240.0
72.6 / 85.1 165.7 / 172.5
1"+2"+3"+Z* 8" Z
240.0
38.6 / 46.5 90.8 / 94.2
*For models with the suffix “Z,” the longest paddle must be used to
obtain the values indicated in this table. The Z = 8” paddle must be
cut to the proper length to fit into the pipe without touching the
inside.

126 mm

rec. Qmax
(m3/h)

pipe Ø

135 mm
113 mm

70 mm

3”

paddles (L)

DIMENSIONS

L

Table 1. Reset and switch points for water

1”

The flow switch is factory-set to the min. flow rate. To adjust
the device to other levels, turn the adjustment screw
clockwise. Table 1 lists the reset points and switch points for
water. Data for other media must be determined empirically.

NOTE: If the flow switch is used as a min. flow controller,
another device must be installed downstream for
alarm condition activation.

2”

SWITCH-POINT ADJUSTMENT

NORMALLY OPEN
BLUE

diameter
4.5 mm

1”

NORMALLY CLOSED

R1”

3”

2”

WHITE

L

ADJUSTMENT SCREW
FOR FLOW RATE

Fig. 1. Field wiring
Connect the red and the white contacts. The contact redwhite opens when the flow drops below the switch point.
When the flow is absent, the contact red-blue closes and can
be used as a signal or alarm contact.

29 mm

52 mm

90 mm

Fig. 3. S6065A2001 dimensions

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich
Germany
Phone: (49) 7031 63701
Fax:
(49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0314GE51 R1008



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Count                      : 2
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:3d225b6b-ddba-41f4-be4f-e210e192f810
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Create Date                     : 2008:10:14 08:29:19+02:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2008:10:14 08:29:19+02:00
Document ID                     : uuid:1fdc07d8-aa0c-4511-b73f-c2fc1a183ab9
Format                          : application/pdf
Creator                         : e671781
Title                           : Microsoft Word - en0b0314-ge51r1008.doc
Author                          : e671781
EXIF Metadata provided by EXIF.tools

Navigation menu