HE365A,B PoweredFlow-ThroughHumidifier

TRADELINE ®
READAND SAVE THESE INSTRUCTIONS

APPLICATION

H

The Enviracaire Elite TM HE365A, B Powered Flow-Through Humidifier
works with the warm air furnace blower to provide humidification for the
whole house. The HE365A, B works with virtually any Honeywell
humidity control, and can be integrated to the temperature control in
the home when controlled by the Honeywell Perfect Climate Comfort
Center TM control.

M12813

Fig. 4. Position securing clips.

INSTALLATION

7. Position the humidifier housing in the hole (be sure it is level), so
the locking tabs are in place on the upper and lower sheet metal
edge of the hole.
8. Push in securing clips until completely seated.
9. Drill holes and install the three sheet metal screws at the top of
the humidifier housing. Secure the housing with the three
remaining screws.
10. Reinstall the humidifier pad assembly in the humidifier housing.

When Installingthis Product...
1. Read these instructions carefully. Failure to follow them could
damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to
make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as
//_provided

M12808

Fig. 1. Typical humidifier installation locations.

in these instructions.

([

CAUTION

m
-o

Hazardous Voltage.
Improper drilling can cause equipment damage or personal
injury.
Do not cut or drill into any air conditioning or electrical

r-

)>
m

11. Hook the top of the cover to the housing and secure with the
thumbscrew located at the bottom of the cover.

/\
/

Freezing Water, Flooding or Static Pressure Hazard.
Can cause water damage or permanent equipment
damage.
• Locate the humidifier where the ambient temperature is
between 32°F (0°C) and 160°F (71°C) or property damage
can occur.
• Do not install humidifier where freezing temperatures could
occur.

•

Be sure supply plenum static pressure is no greater than 0.4
in. wc and water pressure is no greater than 125 psi.

\
\
\

WARNING

\

I

I
MI2812

Fig. 2. HE360 Humidifier location in relation to air conditioning
cooling coils.

Voltage Hazard.
Moving parts can cause electrical shock and injury.
• Disconnect power supply before installation or servicing.
• This device contains a moving fan blade; do not operate the
humidifier without the cover securely attached.
All wiring must comply with applicable local codes, ordinances and
regulations.

FEED TUBE
WATER
DISTRIBUTION

For H808 Humidistat, H8908 or H908 Convertible Humidity
Control Wiring Connections:

HUMIDIFIER
PAD

IMPORTANT
•
Mount the humidifier at least 3 in. (76 mm) above the furnace
jacket to allow adequate space for the drain line. Check that
there is adequate space above the humidifier to remove and
install the humidifier cover. Do not install on a fumace jacket.

IMPORTANT
•
Select models of fan centers include humidifer taps so the
current sensing relay or sail switch is not needed.
•
If not using a current sensing relay or sail switch, the 120V
humidifier plug must be energized during blower motor cycles
for proper operation.

1. Determine the best location for the humidifier and draw a level
line on the plenum. See Fig. 1 and 2.
IMPORTANT
To assure optimal product performance,
is level before marking.

--I

\

/

/

CAUTION

,<
ILl
I--

WIRING

/\

/

accessory.

ILl
I-n

/

Z_

IMPORTANT
For proper operation, be sure the mark on the end of the
humidifier pad is facing up. Check that the water feed tube is
placed in the guide slots of the humidifier housing.

be sure the template

HUMIDIFIER
HOUSING
"_"_COVER

1.
Wire the current sensing relay or sail switch.
2. Connect only the two yellow wires to the humidistat (red wire
connections are not used for mechanical humidistats). See the
typical wiring diagrams in Fig. 5 through 7.

ASSEMBLY

2. Tape this piece of paper in position as your template and trace
around the template.
3. Remove the template and carefully cut the rectangular opening.
4. Loosen the thumbscrew on the bottom of the humidifier and
remove the cover.
5. Remove the humidifier pad assembly by grasping the top of the
tray and pulling the assembly out of the housing. See Fig. 3.
6. Position the securing clips as shown in Fig. 4.

® U.S. Registered Trademark
Copyright © 2000 Honeywell

For additional mounting and wiring information,
installation instructions.

refer to the humidistat

Fig. 3. Humidifier components.

IIII
IIIII
IIIIIII
II
69-1428

• All Rights Reserved

TEMPLATE

TO BLOWER
MOTOR
IGNITION BOX

For H1008 Automatic Humidity Control wiring connections:

p 120vAo

IMPORTANT
• Current sensing relay or sail switch is not needed with the
Automatic Humidity Control.
• Use 18-22 gauge insulated wire forproper wiring. We
recommend stranded - tinned wire.

A

'

A

',1

IMECHANtCALI
HUM,DISTAT
|_
HUMIDIF,ER
"4__ YELLOW WIRES
Z_POWER
SUPPLY.
PROVIDE DISCONNECT
OVERLOAD PROTECTION
AS REQUIRED.
Z_24V

MEANS

AND

2.

NOTE:

c.

WIRING.

1. Connect 24 Vac power to the 24 Vac HOT and COM terminals on
the H 1008A.
2. Connect the humidifier to the two HUM terminals on the H1008A
as shown in Fig. 8.

M12686

Fig. 5. Typical wiring diagram for humidifier using fan control to
cycle blower motor fan and humidifier simultaneously.

HU MIIDtSTAT

For additional mounting and wiring information,
Control installation instructions.

A
|

refer to the Humidity

/2_
HUMIDIFIER

_

YELLOW

/_

//_

For Perfect Climate Comfort Center TM Control connections:

Z_
120 VAC

p

1. Connect only the two yellow wires to the W8900 (red wire
connections are not used). See the typical wiring diagram in
Fig. 9.

WIRES

For additional mounting and wiring information, refer to the Perfect
Climate Comfort Center installation instructions.

POWER SUPPLY.
PROVIDE DISCONNECT
MEANS AND OVERLOAD
PROTECTION
AS REQUIRED.

TM

PlumbingSaddleValve

24V WIRING.
Mt2684

Fig. 6. Typical wiring diagram of current sensing relay with
humidifier.

I MECHANICAL_

Hot or cold water, either hard or softened, can be used in the
humidifier.
1. Use the self-piercing saddle valve (included) to tap into the water
supply line at an appropriate location.

/k

H UMIDtS_L_

_::::::_

120 VAC

A POWER
SUPPLY
PROV,DE
DISCONNECT
s A2ES ,. O/ERLOAD
PROTECT,ON
Z_24V

Fig. 7. Typical wiring

WIRING.

diagram

M12685

of sail switch with humidifier.

Slope hose downward for correct drainage.

Connect a 1/2 in. hose to the humidifier drain fitting and run it to
a suitable drain.

CHECKOUT
1. Open the saddle valve.
NOTE:

The furnace blower must be on for the humidifier to
operate.

2. Set the thermostat setpoint 10°F (6°C) above the room
temperature.
3. Set the convertible humidity control to a high humidity setting, or
place the H1008AAutomatic
Humidity Control in the test position.
4. Observe the water running out of the drain line to be sure the
humidifier is working correctly.
5. Check for leaks.
6. Reset the thermostat to a comfortable setting or the Automatic
Humidity Control to the desired frost factor setting.

CAUTION

_)

PC8900

Chemical Hazard.
Can cause personal injury or equipment damage.
Do not use any line connected to an air conditioner.

E,,OWW, ES
1 LN..za

Do not over-tighten the compression nut. Moderate
tightness prevents leaking.

Insert the tubing into the solenoid valve fitting and support
the valve while tightening the compression nut.

NOTE:
3.

I MECHANICAL_

Use 1/4 in. O.D. copper tubing and connect the saddle valve to
the inlet side of the solenoid valve.
a. Place the brass compression nut over the copper tubing.
b. Slide the brass ferrule over the tubing.

Lightly clean the copper tubing ends with fine
sandpaper before making any connections.

®

A
OPTIONAL
OUTDOOR
AIR SENSOR

®
®
1@

IMPORTANT
•
The saddle valve is not designed to regulate water flow, the
valve is either open or closed.
•
To prevent debris from clogging the solenoid in-line filter, be
sure to install the saddle valve handle pointing toward the
ceiling.
NOTE:

W8900B

CO2 $

_OUT

®

_HE36O

I

®1

LED

®
O/B

@G

RH___

120

/3\ >L

$ ux
_w2

®1
ROOM

THERMOSTAT

A

Z_

POWER SUPPLY. PROVIDE DISCONNECT
PROTECTION
AS REQUIRED.

Z_

OPTIMAL

Z_RED

CONTROL

WIRES

ACHIEVED

ARE NOT USED

WHEN

MEANS

AND OVERLOAD

USING OUTDOOR

tN THIS APPLICATION.

AIR SENSOR.
MI2819A

Fig. 9. Typical wiring diagram for humidifier using PC8900/W8900.
120
VAC

A
FURNACE
TRANSFORMER
L1
(HOT)

AUTOMATIC
CONNECTO_

HUMIDITY

CONTROL

FROST FACTOR
SETPOINT DIAL

SOLENOID
Z_

Z_

POWER SUPPLY.
PROVIDE DISCONNECT
MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

Z_

24v WIRING

HEAT ONLY APPLICATIOtN
SHOWN. SIMILAR WIRING
REQUIRED tN HEAT AND COOL SYSTEM WITH ONE
OR TWO TRANSFORMERS.

M12820B

Fig. 8. Typical wiring diagram for humidifier using H1008A Automatic Humidity

Control.

Honeywell
Home

and Building

Control

Honeywell

and Building

Honeywell

1985 Douglas
Golden

Home

Drive

Valley,

North

MN 55422

35 Dynamic
Scarborough,
MIV 429

Control

Limited-Honeywell

Limitde

Drive
Ontario

_rt
Printed

69-1428

G.H.

8-00

in U.S.A. on recycled

paper containing at least 10%
post-consumer
paper fibers.

www.honeywell.com/yourhome/



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 2
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 4, 0, 0, 13
Create Date                     : Sun Mar 07 04:12:09 2010
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu