L8148A,E,J
Aquastat® Relays
INSTALLATION INSTRUCTIONS

APPLICATION

Scale Range: 140°F to 240°F (60°C to 116°C) or 180°F
to 240°F (82°C to 116°C).

The L8148A,E,J Aquastat® Relays are immersion-type
controllers for use with forced hydronic heating systems.
The combination high limit and intermediate switching
relay works with a low voltage (24V) thermostat to control
burner and circulator circuits. A call for heat by the
thermostat starts both the burner and the circulator.
When boiler-water temperature exceeds the high-limit
settings, the burner circuit is broken; the circulator
continues to operate during the thermostat call for heat.

Differential: Nonadjustable.

The L8148A controls line-voltage burner circuits; the
L8148E,J control low-voltage burner circuits; the L8148J
controls millivoltage burner circuits. All models control
line-voltage circulator circuits.

Maximum Bulb Temperature: 40°F over setpoint, up to
265°F (4°C over setpoint, up to 129°C).

L8148A,E,J have provisions for adding low-limit
controllers; L8148E,J can power valves in multizone
systems.

Material Safety Data Sheets (MSDS): For information
on heat-conductive compound, see form number
69-0955.

L8148E is available with a plug and 50 VA transformer for
use with Honeywell Smart Valve SV9500/SV9600.

SPECIFICATIONS

Maximum Ambient Temperature: 150°F (66°C) with
1.2A, 24V load; 77°F (25°C) with 1.4A, 24V load.

Thermostat Heat Anticipator Setting: 0.2A.

INSTALLATION
1.

Table 1. Circulator Control Circuit (A):
120 Vac
7.4

3.7

Locked Rotor

44.4

22.7

Table 2. Burner Control Circuit:
Voltage

Electrical Rating

L8148A

Line

Same as circulator control
circuit.

L8148E,J

Low

0.8A maximum at 24 Vac.

® U.S. Registered Trademark
Copyright © 2002 Honeywell •

2.

240 Vac

Full Load

Model No.

Maximum Pressure on Immersion Well: 255 psi (1758
kPa).

When Installing This Product…

Electrical Ratings:

Type

High Limit Dial Stop: Adjustable.

•All Rights Reserved

3.
4.

Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.

WARNING

Explosion Hazard.
Can cause severe injury, death or property
damage.
This product is intended for use only in systems
with a pressure relief valve.

95- 6940- 12

L8148A,E,J AQUASTAT® RELAYS

WARNING

Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
1. Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage.
2. Never apply a jumper across (or short)
terminals B1, B2, or B3. This burns out the
transformer.

Mounting
The L8148A,J has a case that can be converted to either
horizontal or vertical mounting (Fig. 1).

NOTE: Some models have an adjustable tubing length
to 3 in. (76 mm). For these models, pull out
extra tubing from inside the case, if needed.
7.

Fit the case into the well so the clamp on the case
slides over the flange on the well.

IMPORTANT
Best thermal response is obtained with a well
that snugly fits the sensing bulb. Insert the bulb
until it rests against the bottom of the well. Use
a well of correct length and bend the tubing, if
necessary, to hold the bulb against the bottom
of the well, but do not make a sharp bend in the
tubing.
If the well is not a snug fit on the bulb, use the
heat-conductive compound (furnished with
TRADELINE® models) as follows: Fold the
plastic bag of compound lengthwise and twist it
gently. Then snip off end of bag and work the
open end of bag all the way into the well. Slowly
pull the bag out while squeezing it firmly to
distribute compound evenly in the well. Bend
the tubing, if necessary, to hold the bulb against
the bottom of the well and to hold outer end of
the bulb in firm contact with the side of the well.
See Fig. 2. Wipe excess compound from the
outer end of the well.

BRACKET POSITION FOR
VERTICAL MOUNTING

Replacement Installation

BRACKET POSITION FOR
HORIZONTAL MOUNTING
M8890

Fig. 1. Case is designed for vertical
or horizontal mounting.

Turn off all power and remove the old control. Refer to
the cover insert of the old control to identify and tag each
external lead as it is disconnected. If old well is
unsuitable for new installation, remove it and proceed
with instructions for new installation. If old well is suitable,
use it and a 124904 immersion well adapter (ordered
separately from form 68-0040, Wells and Fittings for
Temperature Controllers) for the installation. (If the well
clamp fits directly over the flange of the existing well
spud, adapter use is not necessary.) The adapter has a
flange at the wide end that fits into the well clamp and is
slotted lengthwise to accommodate both the capillary
tube and the short length of tube extending from the bulb.

New Installation

1.

Order well assemblies and 124904 Well Adapter for the
Aquastat Relay separately; refer to form 68-0040, Wells
and Fittings for Temperature Controllers. Boilers usually
have tappings that allow the well to be mounted
horizontally so boiler water of average temperature can
circulate freely.

2.

1.
2.
3.

Turn off all power and drain the boiler.
If no tapping is provided, prepare properly sized
and threaded tapping near the top of the boiler.
Coat the well threads sparingly with pipe dope;
install the well in the boiler tapping and tighten
securely.

NOTE: Do not attempt to tighten by using the case as a
handle.
4.
5.
6.

Refill boiler and check for water leakage.
Insert the bulb element into the well until it bottoms.
If necessary, slightly bend the tube inside the case
to hold the bulb against the bottom of the well.
Center the loop of excess tubing in front of the
immersion well so it cannot touch any electrical
parts.

95-6940—12

Loosen but do not remove the well clamp screw on
the side of the control case.
Pull out the capillary until the bulb bottoms in the
well. Place adapter (if used) around the capillary
tube so it fits into the slot. See Fig. 2. Center the
loop of excess capillary tubing in front of the
immersion well so it cannot touch any electrical
parts.

NOTE: Some models have a tubing length adjustable to
3 in. (76 mm). For these models, extra tubing
inside the case can be pulled out, if needed.
3.

4.
5.

Make sure the wide end of the adapter fits into the
hole in the case. Position immersion well clamp
snugly over the flange on the adapter and tighten
the clamp screw.
Insert sensing bulb into well as shown in Fig. 2.
(Distribute the heat-conductive compound in the
tube prior to bulb insertion.)
Securely tighten setscrew (if present on old well)
against adapter.

L8148A,E,J AQUASTAT® RELAYS

CONTROLLER
CASE
IMMERSION
WELL CLAMP

BACK OF
CONTROLLER
CASE

BOILER

IMMERSION
WELL CLAMP

1
IMMERSION
WELL SPUD

ADAPTER

ADAPTER

OLD IMMERSION
WELL ASSEMBLY

IMMERSION
WELL CLAMP
SCREW

SENSING
BULB

(A)
(D)

(C)

(B)

2

HEAT-CONDUCTIVE COMPOUND
1

CAPILLARY
TUBE

2
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE
TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING
BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D).

SETSCREW
IMMERSION
WELL CLAMP SCREW

BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD
THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).

SHORT TUBE
FITS IN CENTRAL
RECESS OF ADAPTER

M8830

Fig. 2. Proper position of sensing bulb in immersion well, and use of well adapter in existing well.

WIRING

If the B1 terminal on the device being replaced is a 1/4 in.
tab terminal, use the existing wiring harness terminals to
install the replacement device. If the B1 terminal on the
device being replaced is a screw terminal, insert the
provided tab terminal to screw terminal adapter onto the
1/4 in. tab terminal of the replacement device. After the
adapter is installed, reuse the existing wraparound wire
end to make an electrical connection to the B1 terminal.

IMPORTANT
The terminals of these Aquastat® Relays are
approved for use with copper wire only.

WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before making wiring
connections to prevent electrical shock or
equipment damage.

CAUTION

Equipment Damage Hazard.
Can cause incorrect operation.
1.If L8148E,J are used to power zone valves,
low voltage (24 Vac) load must not exceed
1.4A; a 1.2A load is the maximum permissible
when ambient temperature exceeds 77°F
(25°C). Use additional transformer(s) when
load exceeds these ratings.
2.When L8148E is used to power SV9500/
SV9600, use separate transformer to power
zone valves.

All wiring must comply with local electrical codes and
ordinances. Do not exceed the specifications in the
Application section when applying this control.
L8148J can power up to two V8043 Zone Valves.
Additional valves, in groups of two or less, require an
additional transformer. Follow the appropriate wiring
diagrams when using zone valves or a low limit
controller. See Fig. 3 through 7.

3

95-6940—12

L8148A,E,J AQUASTAT® RELAYS

L1
L2
HOT

1

24V
THERMOSTAT

3
G

L2

L1

T

T

L8148A

2

R
3
W
B

HIGH
LIMIT

B

L6006
LOW LIMIT
CONTROLLER

R
4
C2

C1

B2

B1

TO LINE
VOLTAGE
OIL BURNER
RELAY OR
GAS VALVE

CIRCULATOR
G
L1

B
JUMPER
T

T

R
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOADPROTECTION AS REQUIRED.

1K1

3

1K

2 REMOVE JUMPER WHEN ADDING L6006 LOW
LIMIT CONTROLLER.

1K2

3 CONTROL CASE MUST BE CONNECTED TO EARTH
GROUND. USE GROUNDING SCREW PROVIDED.

C1
L2

4

C2

L8148A

B2

4 B1 IS 1/4 IN. TAB TERMINAL.
B1

M2842A

Fig. 3. External connections and internal schematic for L8148A.

24V
THERMOSTAT
W
R

TV

L6006
B
LOW LIMIT
CONTROLLER

TP

3

TH2

PP

TH1

T

Z

2

B

MILLIVOLTAGE
POWERPILE® GAS VALVE
PP

W

HIGH
LIMIT

R
C1 C2
B1 B2

B3

G

1

CIRCULATOR

TH

TR
LOW VOLTAGE
GAS VALVE
(eg, VR8300)

L2

L1

5

G

L8148J

4
L1 L2
(HOT)

THTR

1K3

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

2

REMOVE Z-W JUMPER IF SERIES 60 LOW LIMIT IS USED.
WIRE LOW LIMIT CONTROLLER OR ZONE VALVES AS
SHOWN. USE WITH 24V (B1-B3) CIRCUIT ONLY.

3

FOR 24V BURNER, WIRE B1-B3 AND USE JUMPER Z-W
AND TP-Z. FOR POWERPILE® (MILLIVOLTAGE) GAS
VALVES, REMOVE JUMPER TP-Z AND WIRE BURNER
B1-B2. JUMPER Z-W REMAINS IN POSITION.

4

CONTROL CASE MUST BE CONNECTED TO EARTH
GROUND. USE GROUNDING SCREW PROVIDED.

5

B1 IS 1/4 IN. TAB TERMINAL.

1K1
B

TP

R

1
Z

W

T

AUTO
MANUAL
SWITCH

1K2

TV

C1
B3

L2

1

L8148J

L1

B2

5

B1

C2

M1793B

Fig. 4. Internal schematic and external connections for L8148J with either low voltage or
millivoltage gas valves. Low limit added in hookup with 24V gas valve.

95-6940—12

L8148A,E,J AQUASTAT® RELAYS

T87F

T87F

T87F
R845

R845
RELAY

T
1

T

2

L1
(HOT)

1

T
3

4

5

1

6

2

PUMP

R845

T

T
3

4

1

6

5

PUMP

T
2

3

4

5

6

PUMP

L2
L8148A
ORANGE
G

2

L2

L1

T

F

T
3

C1

C2

B2

WHITE

C554

F

B1

BLACK

BURNER
AND
IGNITION

T
T
R8184G

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
M2843A

3 B1 IS 1/4 IN. TAB TERMINAL.

Fig. 5. Wiring L8148A in oil-fired, forced hot water, tankless, zoned, pump system.

24 VAC
THERMOSTAT
D892/M892

4

197516A
CABLE

L8148E1265

4

4

TV

T

W

Z

1K

2

3

HIGH LIMIT
CONTROLLER

2

3 FUSE
R
1K2

3
B
2

5

1

1

POLARIZED 4-PRONG
MALE MOLEX PLUG AND
4-PRONG FEMALE
MATING PLUG ON CABLE

1

6-PRONG FEMALE MOLEX
B1
RECEPTABLE IN L8148E
AND 5-PRONG MALE
5
MOLEX PLUG ON CABLE

C1

C2

L1

L2

1K1
B2

CIRCULATOR

1
L1
(HOT)

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

L2

S8600

2

REMOVE PLUG-IN THAT JUMPERS PINS 2 AND 3 WHEN USING VENT
DAMPER.

3

AFTER VENT DAMPER IS PLUGGED INTO L8148E1265, FUSE BLOWS
WHEN THERMOSTAT FIRST CLOSES. AFTER FUSE BLOWS, L8148E1265
OPERATES ONLY WHEN VENT DAMPER IS CONNECTED.

4

SEE VENT DAMPER PRODUCT SPECIFICATIONS FOR INTERNAL
SCHEMATICS.

5

B1 IS 1/4 IN. TAB TERMINAL.

24V GND
24V

M2763C

Fig. 6. Wiring L8148E1265 with internal plug directly to vent damper in hydronic intermittent pilot system.

5

95-6940—12

L8148A,E,J AQUASTAT® RELAYS

ZONE 2

ZONE 3
24 VOLT
THERMOSTAT

V8043F

ZONE 1

24 VOLT
THERMOSTAT

END SWITCH

24 VOLT
THERMOSTAT

V8043F
2

L8148J

1

TV

V8043F

END SWITCH

L1
HOT
L2

4

END SWITCH

4

TP
3

W
Z
T

MILLIVOLTAGE
GAS VALVE

B1
TR

6
B2

THTR

LOW VOLTAGE GAS
VALVE (eg, VR8300)

TH

TH1

PP

TH2

PP

POWERPILE®

B3
C1
CIRCULATOR
C2
L1

L1
HOT

L2

L2

G

5

1

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2

L8184J POWERS TWO V8043E OR F ZONE VALVES, OR ONLY ONE V8043 WHEN AMBIENT
TEMPERATURE EXCEEDS 77oF (25oC). USE AN ADDITIONAL TRANSFORMER(S) TO
POWER ADDITIONAL VALVES.

3

LINK MUST BE USED WHEN USING 24 VOLT GAS VALVE HOOKUP (B1–B3). REMOVE LINK
WHEN MILLIVOLTAGE GAS VALVE IS USED (B1–B2).

4

ADD JUMPER.

5

CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW
PROVIDED.

6

B1 IS 1/4 IN. TAB TERMINAL.

M2887A

Fig. 7. Wiring L8148J for multizone control.

OPERATION AND SETTING
High Limit
The high limit switch shuts off the burner when the boiler
temperature exceeds high-limit setting. Because heating
systems differ, the correct temperature setting for one
system might not be correct for another. Follow the boiler
manufacturer recommendation for proper setting. To set,
remove cover, and turn dial until the desired setting is
directly below the pointer.
The dial stop is factory-set at the high end of the limit
scale. To adjust, use a small screwdriver to hold the stop
away from the dial face, and turn the dial until the desired
setting is below the pointer. See Fig. 8. Release pressure
on screwdriver, and make sure the stop rests flat against
the dial face.

WARNING
Explosion Hazard.
Can cause severe injury, death or property
damage.
This product is intended for use only in systems
with a pressure relief valve.

95-6940—12

Switching Relay
The switching relay is controlled by the room thermostat.
On a call for heat, the relay coil is energized, completing
the line voltage circulator circuit and also the burner
circuit, if the boiler water temperature is below the high
limit setting.

Auto-Manual Switch
The AUTO-MANUAL switch (only L8148J millivolt
models) makes it possible to operate the burner (in a
system with a millivoltage gas valve) during an electrical
power failure. With switch at MANUAL, the burner
operates continuously until either the high limit setting is
reached or the switch is reset to AUTO. The circulator,
requiring line voltage, is inoperative. When power is
restored, the switch must be set to AUTO to resume
automatic burner operation.

L8148A,E,J AQUASTAT® RELAYS

INSERT CORNER OF SMALL
SCREWDRIVER IN THIS
NOTCH AND PRY STOP
UPWARD FROM DIAL FACE

CAUTION

Equipment Damage Hazard.
Improper procedure will damage equipment.
Never apply a jumper across (or short) terminals
B1, B2, or B3. This burns out the transformer.

POINTER

WHILE HOLDING STOP AWAY
FROM DIAL FACE WITH
SCREWDRIVER, TURN
DIAL UNTIL DESIRED HIGH
LIMIT SETTING IS ALIGNED
WITH POINTER

HIGH LIMIT
STOP

CHECKOUT
Put the system into operation and observe through at
least one complete cycle to be sure control operates as
described above.

RELEASE SCREWDRIVER;
MAKE SURE HIGH-LIMIT
STOP RESTS FLAT
AGAINST DIAL FACE

DIAL FACE
M8889

Fig. 8. Setting high limit stop.

7

95-6940—12

L8148A,E,J AQUASTAT® RELAYS

$XWRPDWLRQDQG&RQWURO6ROXWLRQV
+RQH\ZHOO
'RXJODV'ULYH1RUWK
*ROGHQ9DOOH\01

95-6940—12

+RQH\ZHOO/LPLWHG+RQH\ZHOO/LPLWpH
'\QDPLF'ULYH
6FDUERURXJK2QWDULR
09=

G.R. Rev. 1-02

Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.

www.honeywell.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Fill forms, Extract, Assemble, Print high-res
Author                          : Honeywell
Create Date                     : 1999:07:07 12:30:47Z
Modify Date                     : 2014:12:07 14:56:39+08:00
Subject                         : Installation Instructions
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03
Producer                        : Acrobat Distiller 5.0 (Windows)
Metadata Date                   : 2014:12:07 14:56:39+08:00
Creator Tool                    : FrameMaker 6.0
Format                          : application/pdf
Creator                         : Honeywell
Title                           : 95-6940 - L8148A,E,J Aquastat Relays
Description                     : Installation Instructions
Document ID                     : uuid:3891919e-2380-1542-aecf-80fe04578ddc
Instance ID                     : uuid:71b0dd14-7e42-d14b-bec0-2110a10624db
Page Mode                       : UseOutlines
Page Count                      : 8
EXIF Metadata provided by EXIF.tools

Navigation menu