69-1957-1.fm Page 1 Tuesday, June 20, 2006 11:06 AM L7224 Series Oil Electronic Aquastat® Controller TECHNICIAN’S QUICK REFERENCE GUIDE The following service procedure provides a quick overview for L7224 Series Controllers. For more information, refer to form 69-1384. On the L7224U the High Limit, High Limit Differential, Low Limit, and Low Limit Differential can be adjusted to the settings recommended by the boiler OEM. Adjusting Settings To discourage unauthorized changing of Aquastat® settings, a procedure to enter the adjustment mode is required. To enter the adjustment mode, press the UP, DOWN, and I buttons simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed: • HL—High Limit. • LL—Low Limit. • Ldf—Low Limit differential. • F - C—°F or °C. Then press the UP and/or DOWN buttons to move the set point to the desired value. After 60 seconds without any button inputs, the control will automatically return to the READ mode. To use the L7224U in a cold start boiler application, disable the Low Limit function by pressing the UP arrow button, DOWN arrow button and I buttons simultaneously for three seconds. Then push the I button until LL is displayed. Then press the down arrow button until OFF is displayed. Display In the RUN mode, the Aquastat® will flash “bt” (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C. To read boiler settings, press the I key to read the parameter of interest. For example, press I (HL) High Limit is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C. 69-1957—1 69-1957-1.fm Page 2 Tuesday, June 20, 2006 11:06 AM L7224 SERIES Pressing the I button again will display the LL (Low Limit) followed by a three-digit number and the corresponding degree designator. See the table below for an explanation of display readout. After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press and release any key. Text Description bt Boiler Temperature HL High Limit LL Low Limit Hdf High Limit Differential Ldf Low Limit Differential tt Local Thermostat Status tte Enviracom Thermostat Status brn Burner Status cir Circulator Status Zc Zone Control Zr Zone Request err Error Code f c Display Shows Degrees Fahrenheit Degrees Celsius M22149 Table 1. LED Error Codes Error Code Err1 Err2 Err3 Err4 Err5 Err6 Err7 Err8 69-1957—1 Cause/Action Sensor fault; check sensor. ECOM fault; check EnviraCOM. wiring. Hardware fault; replace control. B1 fault; check B1 wiring/voltage. Low Line; Check L1-L2, 110 Vac. Fuse; Check ECOM wires, Replace fuse. EEPROM, HL, LL, Hdf, Ldf, Reset to default values. Repeated B1 fault (voltage present at B1 when output is turned off); check B1 wiring/voltage. 2 69-1957-1.fm Page 3 Tuesday, June 20, 2006 11:06 AM L7224 SERIES Table 2. L7224 Controller Operating Sequence Action Thermostat calls for heat. System Response Circulator starts when water temperature is above Low Limit setting (if applicable). Boiler temperature is checked. Burner starts when water temperature is below High Limit setting. Boiler exceeds Burner is turned off. Burner restarts when the the High Limit. water temperature drops below the High Limit setting minus the differential. Thermostat is Circulator and burner turn off. satisfied. Error conditions If an error condition is detected, all outputs 1-5. except ZC are shut down. Burner is off. Control continues to function and restarts when error is corrected. During the error check sequence, the system checks for drift in the sensor and corrosion in the connections. Error conditions If error condition 6 or 7 occurs, the control has 6-7. reset the High Limit, Low Limit and Differential Setting to a default setting and will continue to run at those settings. Performance of the system will be degraded. Error condition If the error condition is detected, all outputs 8. except ZC are shut down. Burner is off. Control continues to function and restarts when all three user keys have been pressed longer than 60 seconds. Troubleshooting When attempting to diagnose system performance, reference the LED display to help identify specific areas not working properly. The LED display will scroll “err”, followed by a digit (1-8). See Table 1 for a description of the error and suggested actions. See below for a troubleshooting guide. Table 3. Troubleshooting Guidea. System Diagnostic Condition Condition Boiler is Display is OFF cold, house is Display is ON; cold TT-LED is OFF Display is ON; TT-LED is OFF Check Action 120 Vac system Turn system power on. power. 24 Vac T-T No 24V; replace control 24V present; Boiler starts, check disconnect wiring and thermostat thermostat, short T-T a. Refer to Fig. 5 for Display and LED locations. . ZC LED ON indicates ZC terminal power is OFF. c . ZC LED OFF indicates ZC terminal power is ON. b 3 69-1957—1 69-1957-1.fm Page 4 Tuesday, June 20, 2006 11:06 AM Table 3. Troubleshooting Guidea. System Diagnostic Condition Condition Boiler is Display is ON; cold, TT-LED is ON house is B1 LED is ON cold Display is ON; TT-LED is ON Boiler is Display is ON; hot, house TT-LED is ON is cold C1 LED is ON Display is ON; TT-LED is ON C1 LED is OFF; ZC LED is ONb Display is ON; TT-LED is ON ZC LED is OFFc Check Action 120 Vac at B1- • If no, replace control. B2 • If yes, check burner and wiring Refer to err on — display 120 Vac at C1- • 120 Vac at C1-C2, C2 check wiring to pump • Wiring ok, is pump running? If not, replace the pump. • If pump is running, check for trapped air or closed zone valves. Boiler below the Low Limit temperature, wait for boiler to go above Low Limit temperature. Boiler above • If no 120 Vac, LL? If yes, replace control. check for 120 • If yes, check zone Vac between ZC relays, circulators and L2 and wiring. a . Refer to Fig. 5 for Display and LED locations. . ZC LED ON indicates ZC terminal power is OFF. c . ZC LED OFF indicates ZC terminal power is ON. b Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2006 Honeywell International Inc. 69-1957—1 Rev. 06-06
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Encryption : Standard V4.4 (128-bit) User Access : Print, Copy, Extract, Assemble, Print high-res Page Mode : UseOutlines XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Producer : Acrobat Distiller 7.0 (Windows) Creator Tool : FrameMaker 7.0 Modify Date : 2007:05:07 16:01:02-05:00 Create Date : 1999:12:20 09:38:57Z Metadata Date : 2007:05:07 16:01:02-05:00 Format : application/pdf Title : 69-1957-1 L7224 Series Oil Electronic Aquastat Controller Creator : Honeywell ECC Technical Communications Description : Technician's Quick reference Guide Document ID : uuid:4c3ae1f5-dfd0-465e-a419-f31eb2bf7f0d Instance ID : uuid:86eddf2e-e89c-4f79-bca3-76db1c6851f9 Page Count : 4 Subject : Technician's Quick reference Guide Author : Honeywell ECC Technical CommunicationsEXIF Metadata provided by EXIF.tools