Honeywell Chronotherm Iv T8600D Users Manual 69 1409 Chronotherm® Deluxe Programmable Thermostats
2015-01-23
: Honeywell Honeywell-Chronotherm-Iv-T8600D-Users-Manual-262002 honeywell-chronotherm-iv-t8600d-users-manual-262002 honeywell pdf
Open the PDF directly: View PDF
.
Page Count: 12
| Download | |
| Open PDF In Browser | View PDF |
T8600D Chronotherm® IV Deluxe Programmable Thermostats INSTALLATION INSTRUCTIONS APPLICATION The T8600 Chronotherm® IV Deluxe Programmable Thermostat provides electronic control of 24 Vac singlestage heating and cooling systems. Refer to Table 1 for a general description of the thermostat. All T8600 thermostats are powered by either heating or cooling system. Table 1. Description of T8600 Thermostats T8600 System Changeover D Heat-Cool Automatic System Selection Fan Selection Heat-Off-CoolAuto On-Auto 3. MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly. Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control. When Installing this Product... 2. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. ® U.S. Registered Trademark Copyright © 2002 Honeywell • System and fan selections are done by keyboard. Installer must be a trained, experienced service technician. After completing installation, use these instructions to check out the product operation. Location Install the thermostat about 1.5m (5 ft) above the floor in an area with good air circulation at average temperature. See Fig. 1. Do not install the thermostat where it can be affected by: INSTALLATION 1. 4. Comments • All Rights Reserved — — — — — drafts, or dead spots behind doors and in corners. hot or cold air from ducts. radiant heat from sun or appliances. concealed pipes and chimneys. unheated (uncooled) areas such as an outside wall behind the thermostat. 69-1409-1 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Wallplate Installation 3. The thermostat can be mounted horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box. Position wallplate horizontally on the wall or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box. 1. 4. Position and level the wallplate (for appearance only). The thermostat will function correctly even when not level. 5. 6. Remove the wallplate from the wall and drill two 3/16 inch (76 mm) holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch (5.56 mm) holes. Gently tap anchors (provided) into the drilled holes until flush with the wall. Position the wallplate over the holes, pulling wires through the wiring opening. Loosely insert the mounting screws into the holes. Tighten mounting screws. WIRING All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 through 5 for typical hookups. A letter code is located near each terminal for identification. YES NO NO 5 FEET [1.5 METERS] NO CAUTION Electrical Hazard. Can cause electrical shock or equipment damage. Disconnect power before wiring. 1. M10106 Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 6. IMPORTANT Use 18 gauge, color-coded thermostat cable for proper wiring. Fig. 1. Typical location of thermostat. 2. 3. 4. WALL WIRES THROUGH WALL Securely tighten each terminal screw. Push excess wire back into the hole. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat. THERMOSTAT WALL ANCHORS (2) G W R RC 2 HEAT RELAY FAN RELAY MOUNTING HOLES 1 L1 (HOT) MOUNTING SCREWS L2 M15044 TRANSFORMER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. Fig. 2. Mounting the wallplate. 2. 2 NOT AVAILABLE ON T8600A MODELS. Use a pencil to mark the mounting holes. See Fig. 2. 69-1409—1 M10346A Fig. 3. Typical hookup in heat only application. 2 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS THERMOSTAT Y O G B W R RC OT FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM). OT FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM). 3 M4826 COMPRESSOR CONTACTOR COOL DAMPER HEAT RELAY 2 FAN RELAY OUTDOOR TEMPERATURE SENSOR Fig. 6. Correct wiring technique. HEAT DAMPER Mounting Thermostat 2 1. 1 2. L1 (HOT) L2 NOTE: To remove the thermostat from the wall, first pull out at the bottom of the thermostat; remove top last. TRANSFORMER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT PUMP SYSTEMS. 3 AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE. M10347A Engage tabs at the top of the thermostat and wallplate. See Fig. 7. Press lower edge of case to close and latch. Fig. 4. Typical hookup in heat and cool system with one transformers A. ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE. THERMOSTAT RC Y O G B W 2 OT R COMPRESSOR CONTACTOR COOL DAMPER FAN RELAY HEAT RELAY 3 OT 4 5 OUTDOOR TEMPERATURE SENSOR HEAT DAMPER B. PRESS LOWER EDGE OF CASE TO LATCH. 3 M14628 1 L1 (HOT) L1 (HOT) L2 L2 1 COOLING TRANSFORMER Fig. 7. Mounting thermostat on wallplate. HEATING TRANSFORMER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM. 3 CAN BE USED FOR CHANGEOVER VALVE ON SINGLE-STAGE HEAT PUMP SYSTEMS. 4 AVAILABLE ON SELECT MODELS. OT WIRES MUST HAVE A SEPARATE CABLE FROM THE THERMOSTAT CABLE. 5 T8600D MODELS REQUIRE POWER TO R TERMINAL AT ALL TIMES. M10348 Fig. 5. Typical hookup in heat and cool system with two transformer. 3 69-1409—1 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Using Thermostat Keys • check Self-Test, • display outdoor temperature (select models), • set the system operation, • set the fan operation. See Fig. 8 for the location of the keys. The thermostat keys are used to: • set current day and time, • program times and setpoints for heating and cooling, • temporarily override program temperatures, • display present setting, • configure Installer Setup, INCREASE TEMPERATURE SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP OPTIONS SET RETURN TIMES AND SETPOINTS SET LEAVE TIMES AND SETPOINTS SET WAKE TIMES INCREASE TIME SETTING AND SETPOINTS OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST DECREASE TEMPERATURE SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP OPTIONS SET CURRENT DAY AND TIME DISPLAY INFORMATION SUCH AS PRESENT SETTINGS AND OUTDOOR TEMPERATURE RETURN TO NORMAL OPERATIONS ENTER INDEFINITE OR TIMED HOLD MODE Time Run Program Hold Temp SET CURRENT OR PROGRAM DAY CHANGE BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME Set Current Day/Time Heat/Cool Settings Day Daylight Time Set Program Leave Wake Return Sleep System Fan SET SLEEP TIMES AND SETPOINTS SELECT FAN OPERATION SELECT SYSTEM OPERATION Copy COPY ONE PROGRAMMED DAY TO ANOTHER DAY CHANGE BETWEEN HEATING AND COOLING SETPOINTS M14624 DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM TEST Fig. 8. T8600D key locations and descriptions. SETTINGS System and Fan Settings The System default setting is Heat and the Fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 9. The fan settings can be set for each program period individually. The system selection is for all the program periods. Time Run Program Set Current Day/Time Hold Temp Day Daylight Time System settings control the thermostat operation as follows: Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling. Auto: The thermostat automatically changes between heating and cooling operation, depending on the indoor temperature. Set Program Wake Heat/Cool Settings Leave Return Sleep System Fan System Copy Fan M14625 Fig. 9. Thermostat System and Fan key locations. Fan settings control the system fan as follows: On: Fan operates continuously. Auto: Fan operates with equipment. NOTE: Always press the keys with your fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard. Temperature Settings Refer to Table 2 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. See Owner’s Guide, form number 69-0940, for complete instructions on changing the program. 69-1409—1 4 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Period Wake Time 6:00 AM System Em Heat Off Cool Auto Fan On Wait Set Program Set Day/Time Temporary Setting Table 2. Default Program Settings. Heat Setpoint Cool Setpoint Fan Setting 70°F (21°C) 78°F (25.5°C) Auto Recovery Hold for AM PM Filter Em Ht Aux Ht Days Mon Tue Wed Thu Fri Sat Sun Repl Batt Room Outdoor Heat Cool Wake Leave Return Sleep DST Auto M14559 Leave 8:00 AM 62°F (16.5°C) 85°F (29.5°C) Auto Return 6:00 PM 70°F (21°C) 78°F (25.5°C) Auto Sleep 10:00 PM 62°F (16.5°C) 82°F (28°C) Auto Fig. 10. Display of all LCD segments. INSTALLER SETUP INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 3) NOTE: For most applications, the thermostat factory settings will not require changing. Review the factory settings in Table 2 and if no changes are necessary, go to the Installer Self-Test section. FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 3) M14618 Fig. 11. Display of Installer Setup number and setting. The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, system changeover, and outdoor temperature display. Installer Setup numbers are listed in Table 3. The table includes all the configuration options and the factory settings for the T8600. CAUTION Electric Heat System Configuration Hazard. Can cause equipment damage. Configure electrical heat system to 1 in Installer Setup number 2 to prevent system running without fan. A combination of key presses is required to use the Installer Setup feature: — To enter the Installer Setup, press and hold the information i key with the increase and decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 10 and 11. — To advance to the next Installer Setup, press the Time ∆ key. — To change a setting, use the increase or decrease key. — To scroll the Installer Setup numbers backward, press the Time ∇ key. — To exit the Installer Setup, press Run Program. IMPORTANT Only configurable numbers are shown on the device. Example: If thermostat does not have a System key, Installer Setup Number 12 will not be displayed. Review Table 3 factory settings and mark any desired changes in the Actual Setting column. When Installer Setup is complete, review the settings to confirm that they match the system. 5 69-1409—1 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Table 3. Thermostat Installer Setup Options. Installer Setup Number (Press Time ∆ key to change) Display Description Display Description Actual Setting Not used. 1 — — — — — Fan operationa. 2 0 Conventional applications where equipment controls fan operation in heat mode. 1 Heat pump or electric heat applications where thermostat controls fan operation in heat mode. Not used. 3 — Heating cycle rate. 4 6 Not used. Select Factory Setting (Press — — 6—6 cph used for conventional heat. 5 thru 11 — 12 1 Manual changeover Adaptive Intelligent Recovery™ control. 13 0 Adaptive Intelligent Recovery™ control is activated (system starts early so setpoint is reached by start of program period). 1 Conventional recovery (system starts recovery at programmed time). Degree temperature display 14 0 Temperature is displayed in °F 1 Temperature is displayed in °C Not used. 15 — Clock format. 16 0 17 and 18 — — — — Extended fan operation in heatinga 19 0 No extended fan operation after the call for heat ends. 1 Fan operation is extended 90 seconds after the call for heat ends. Extended fan operation in cooling 20 0 No extended fan operation after the call for cool ends. 1 Fan operation is extended 90 seconds after the call for cool ends. 21 thru 23 — — — — Not used. 69-1409—1 — — 0 or 2 — — 12-hour clock format. 6 1 — 1—1 cph used for radiant floor heat, gravity system. 3—3 cph used for hot water systems or high efficiency furnaces. 9—9 cph used for electric heat systems. System setting adjustment Not used. — 1, 3, or 9 Other Choices or key to change) — — 0—Auto changeover. 2—Auto only — — — 24-hour clock format. — — T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Table 3. Thermostat Installer Setup Options. (Continued) Installer Setup Number (Press Time ∆ key to change) Display 24 0 Not used. 25 thru 29 — — — Deadband 30 3 Heating and cooling setpoints can be set no closer than 3°F to (1.5°C). 4 thru 10 Not used. 31 and 32 — — — Minimum off time for the compressor. 33 5 Five-minute minimum off time for compressor. 0 thru 4 Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor. Temperature range stops in heating. 34 90 Highest heating setpoint setting. 40 to 89 Temperature range (1°F increments) of heating setpoint settings. Temperature range stops in cooling. 35 45 Lowest cooling setpoint setting. 46 to 99 Temperature range (1°F increments) of cooling setpoint settings/ Not used. 36 — — — — Temperature display adjustment. 37 0 No difference in displayed temperature and actual room temperature. 3 thru -3 1—Display adjusts to 1°F higher than actual room temperature. 2—Display adjusts to 2°F higher than actual room temperature. 3—Display adjusts to 3°F higher than actual room temperature. -1—Display adjusts to 1°F lower than actual room temperature. -2—Display adjusts to 2°F lower than actual room temperature. -3—Display adjusts to 3°F lower than actual room temperature. Furnace air filter timer. 43 30 days (System run time) 0, 1, 3, 4 0 – off 1 – 10 days 3 – 60 days 4 – 120 days (Time is counted when heat, cool or fan is running.) Select Outdoor temperature display (select models) Factory Setting 2 (Press Description No outdoor temperature is displayed 7 Display 1 Other Choices or key to change) Description Actual Setting Outdoor temperature is displayed. Needs a C70891000 Outdoor Temperature Sensor to operate. — — Heating and cooling setpoints can be set no closer than the chosen value: 4—4°F (2°C) 5—5°F (2.5°C) 6—6°F (3°C) 7—7°F (3.5°C) 8—8°F (4°C) 9—9°F (4.5°C) 10—10°F (5°C) — — — 69-1409—1 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Table 3. Thermostat Installer Setup Options. (Continued) Installer Setup Number (Press Time ∆ key to change) Select Factory Setting Display (Press Description Humidifier pad monitor. 44 0 Off Ultraviolet air treatment (UV) lamp monitor. 45 0 Off Actual Setting Description 1 – 90 days 2 – 180 days 3 – 365 days (Time is counted by calendar days in heat mode.) 1 1 – 365 days (Time is counted by calendar days in any mode.) NOTE: If the current time is Daylight Savings Time, press Daylight Time until DST is displayed. Set Day/Time AM Daylight Time Setting Current Day and Time 1. Display 1, 2, 3 IMPORTANT Review the settings to confirm that they match the system. Press Run Program to exit the Installer Setup. The thermostat has saved the Installer Setup changes and initiated a reset in order to operate using the new settings. Be sure to set the current day and time immediately. Other Choices or key to change) Time Run Program Hold Temp Set Current Day/Time Leave Heat/Cool Settings Day Daylight Time Set Program Wake Return Sleep System Fan Tue DST Copy M14622 Press Set Current Day/Time. 4. Press Run Program. . NOTE: On initial powerup or after an extended power loss, 1:00 pm flashes on the display until a key is pressed System Heat AM . Run Program Time Run Program Set Current Day/Time Set Program Wake Leave Return Sleep Fan Hold Temp Heat/Cool Settings Day Daylight Time System Copy Fan Tue Wake Room DST Auto M14623 Set Day/Time Set Current Day/Time Time Run Program Hold Temp Set Current Day/Time Daylight Time PM Set Program Wake Leave Heat/Cool Settings Day Return Sleep System Fan Viewing or Resetting Timer Settings Mon Copy When the thermostat activates a timer, the thermostat flashes Filter until the timer resets. M14619 2. Press Day until the current day is displayed. 1. NOTE: Sun=Sunday, Mon=Monday, Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday. Filter Set Day/Time Time Run Program Day Hold Temp Set Current Day/Time Heat/Cool Settings Day Daylight Time Leave Days PM Set Program Wake Reset the timer by pressing the i key until the expired timer is displayed. Return Sleep System Fan Tue M20243 Copy M14620 3. 2. Press Time ∆ or Time ∇ until the current time is displayed. Press the time key to reset the timer. . NOTE: Tapping the Set Current Day/Time changes the time in one-hour increments. Filter Days Time Set Day/Time AM Time Run Program Hold Temp Set Current Day/Time Day Daylight Time M20244 Set Program Wake Heat/Cool Settings Leave Return System Sleep Fan Tue 3. Copy M14621 69-1409—1 8 Press the Run Program key. T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS NOTE: You can view the number of days remaining at any time by pressing the i key three or four times. If more than one timer is active, all active timers show sequentially when pressing the i key several times. Wait Set Program Set Day/Time Temporary Setting Recovery Hold for AM PM Filter Em Ht Aux Ht Days Mon Tue Wed Thu Fri Sat Sun Repl Batt Room Outdoor Heat Cool Wake Leave Return Sleep DST INSTALLER SYSTEM TEST System Em Heat Off Cool Auto Fan On Auto M14559 Use the Installer System Test to check the thermostat operation. Refer to Table 4 for a list of the available system tests. Fig. 12. LCD segments display. CAUTION Equipment Damage Hazard. Minimum compressor off-time is bypassed during Installer System Test. Avoid cycling compressor quickly. To start the system test: Press and hold the increase and decrease keys at the same time until 10 appears. All segments of the display are displayed before the 10 appears. See Fig. 12 and 13. M14612 Fig. 13. Test number display. Table 4. Tests Available In Installer System Test. Test Number System Test Description 10-19 Heating equipment can be turned on and off. 30-39 Cooling equipment can be turned on and off. 40-49 Fan equipment can be turned on and off. 60 0 to 60 19 Keyboard keys test. 70-79 Thermostat information, including date code and software versions, is displayed. Refer to Table 5 for the directions and results of the specific tests. NOTE: Press Time ∆ to advance to the next test and Time ∇ to go back to the previous test. Press Run Program to exit the system test Table 5. Installer System Test Options. Keys to Press Test Number Description Heating Equipment System Test Time ∆ 10 Enter heating equipment system test. 11 Heat comes on. When Installer Setup number 2 is 1; the system fan is also energized. 10 Heat and system fan turn off. Cooling Equipment System Test Time ∆ 30 Change from heating to cooling equipment system test. 31 Cool and system fan come on. 30 Cool and system fan turn off. Fan Equipment System Test Time ∆ 40 Change from cooling to fan equipment system test. 9 69-1409—1 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Table 5. Installer System Test Options. (Continued) Keys to Press Test Number Description 41 Fan comes on. 40 Fan turns off. Key Operation System Test Time ∆ 60 1 Change from fan to key operation system test. NOTE: Press any key and the displayed numbers change. Press Time ∇ to go to the previous test and Time ∆ to go to the next test. The Run Program key does not exit this test. Press Time ∆ or Time ∇ and then the Run Program key to exit. THERMOSTAT INFORMATION 1. 4. Press the increase key again to display the software revision number (Example: 001 = Revision number 1). 5. Press the increase key again to display the EEPROM identification code. (Example: 314 = EEPROM ID 314). 6. Press the Run Program key to exit the system test. The system test times out after four minutes without any key presses. Press the Time ∆ key to access the thermostat information. M14617 M14613 2. Press the increase key to display the production date code. The first two large digits are the month and the third digit is the last digit of the year (Example: 027 = February 1997) . M14617 M14614 3. Press the increase key again to display the software identification code. (Example: 02 = software ID code 2). CHECKOUT Outdoor Temperature Sensor (Select Models) Allow the outdoor temperature sensor to absorb the outdoor air for a minimum of five minutes before taking a reading. M14615 69-1409—1 10 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS TROUBLESHOOTING GUIDE Table 6. Troubleshooting Guide. Symptom Display does not come on. Possible Cause Thermostat is not being powered. Action • Check for 24 Vac between R and W terminals. — If missing 24 Vac: — check if the circuit breaker is tripped—reset the circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in the Off position—set to the On position. — check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections. — If 24 Vac is present, proceed with troubleshooting. Temperature Room temperature display has display is incorrect. been reconfigured. Enter Installer Setup number 37 and reconfigure the display. Thermostat is configured for °F or °C display. Enter Installer Setup number 14 and reconfigure the display. Bad thermostat location. Relocate the thermostat. Temperature settings will not change. (Example: Cannot set the heating higher or the cooling lower.) The upper or lower temperature Check the temperature setpoints: limits were reached. • Heating limits are 40 to 90°F (4.5 to 32°C). • Cooling limits are 48 to 99°F (7 to 37°C). Heating does not come on. No power to the thermostat. The setpoint temperature range Check Installer Setup numbers 34 and 35 and reconfigure the stops were configured. setpoint stops. • Check for 24 Vac between R and W terminals. — If missing 24 Vac: — check if the circuit breaker is tripped—reset the circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in the Off position—set to the On position. — check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections. — If 24 Vac is present, proceed with troubleshooting. Thermostat minimum off time is • Wait up to five minutes for the system to respond. activated. Cooling does not come on. System selection is not set to Heat. Set system selection to Heat. Heating setpoint is below room temperature. Check heating setpoint. Set heating setpoint to desired temperature. No power to the thermostat. • Check for 24 Vac between R and W terminals — If missing 24 Vac: — check if the circuit breaker is tripped—reset the circuit breaker. — check if the system fuse is blown—replace the fuse. — check if the power switch on the HVAC equipment is in the Off position—set to the On position. — check wiring between thermostat and HVAC equipment—replace any broken wires and tighten any loose connections. — If 24 Vac is present, proceed with troubleshooting. Thermostat minimum off time is activated. • Wait up to five minutes for the system to respond. • Enter Installer Setup number 33. Reconfigure minimum off time (if required). System selection is not set to Cool. Set System selection to Cool. Cool setpoint is above room temperature. Check cooling setpoint. Set cooling setpoint to desired temperature. 11 69-1409—1 T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS Table 6. Troubleshooting Guide. (Continued) Symptom Possible Cause Action Heating or cooling come on momentarily and shut off Heat or cool circuit is opening up or becoming high impedance. Add resistor in parallel with load or install interface relay. System on indicator (flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers. Fan operation set for 0 (conventional heat) when it should be set for 1 (electric heat). Enter Installer Setup number 2 and reconfigure the fan operation. Conventional heating equipment Wait a minute after seeing the on indicator and then check the turns on the fan when the registers. furnace has warmed up to a setpoint. Heating or cooling equipment is Verify operation of heating or cooling equipment in self-test. not operating. Outdoor temperature not displayeda Option not activated. Outdoor Outdoor sensor is connected temperature incorrectly. display is incorrecta Wrong sensor. aSelect Enter Installer Setup number 24 and set to 1. Thermostat must have OT terminals and a C7089B1000 installed. Refer to C7089B1000 Installation Instructions and check wiring between the thermostat and sensor. Replace sensor with C7089B1000 Sensor. models. Automation and Control Solutions Honeywell 1985 Douglas Drive North Golden Valley, MN 55422 69-1409—1 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9 G.H. Rev. 11-02 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. www.honeywell.com/yourhome
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Encryption : Standard V1.2 (40-bit) User Access : Print, Copy, Fill forms, Extract, Assemble, Print high-res Modify Date : 2003:01:07 13:12:38-06:00 Create Date : 1999:07:07 12:30:47Z Subject : Installation Instructions Page Count : 12 Creation Date : 1999:07:07 12:30:47Z Mod Date : 2003:01:07 13:12:38-06:00 Producer : Acrobat Distiller 5.0.5 (Windows) Author : Honeywell Metadata Date : 2003:01:07 13:12:38-06:00 Creator : Honeywell Title : 69-1409 - T8600D Chronotherm® IV Deluxe Programmable Thermostats Description : Installation Instructions Page Mode : UseOutlinesEXIF Metadata provided by EXIF.tools