Honeywell Excell 500 600 Controll System Xcl5010 Users Manual Excel 500/600 Control
500-XCL5010 to the manual 4a5ea441-723a-44df-942d-0f55e8acd332
2015-01-23
: Honeywell Honeywell-Excell-500-600-Controll-System-500-Xcl5010-Users-Manual-261423 honeywell-excell-500-600-controll-system-500-xcl5010-users-manual-261423 honeywell pdf
Open the PDF directly: View PDF .
Page Count: 48
Download | |
Open PDF In Browser | View PDF |
Excel 500/600 CONTROL SYSTEM INSTALLATION INSTRUCTIONS CONTENTS Revision Overview ........................................................................................................................................................................ 4 Safety Instructions ....................................................................................................................................................................... 5 MOUNTING .................................................................................................................................................................................... 6 Control Unit Installation ............................................................................................. 6 Excel 500/600 Housing Layout (not XCL5010) ......................................................... 6 Excel 500/600 Internal Bus Wiring (not XCL5010).................................................... 6 Module Locations (not XCL5010).............................................................................. 7 Coding the Terminal Block (not XCL5010)................................................................ 7 Setting the Module Address (not XCL5010).............................................................. 8 Installation Inside a Control Panel............................................................................. 8 Excel 500/600....................................................................................................... 8 Excel 500-XCL5010............................................................................................ 10 Excel 500-XCL5010 Communication Module ..................................................... 10 Installation through a Control Panel Door (not XCL5010) ....................................... 10 External Installation of XI582AH Operator Interface ............................................... 11 Deactivating Backlit Display of the XI582AH........................................................... 12 Distributed I/O Installation ....................................................................................... 13 Dimensions ............................................................................................................. 14 Excel 500/600..................................................................................................... 14 Excel 500-XCL5010............................................................................................ 15 XI582AH ............................................................................................................. 16 Battery Activation during Commissioning (XC6010, only) ....................................... 17 Replacing the Battery.............................................................................................. 17 Dismantling the Control Panel Unit ......................................................................... 18 Dismantling the Control Panel Door Unit................................................................. 18 Dismantling the Housing Cover............................................................................... 18 Dismantling the Excel 500-XCL5010 Control Panel Unit......................................... 18 Dismantling the XI582AH Operator Interface .......................................................... 19 Electrical Connections ............................................................................................................................................................... 20 Cable Routing ......................................................................................................... 20 Shielding Input / Output Module and Power Supply Cables.................................... 20 Shielding of Data-Transmitting Cables.................................................................... 20 Grounding (XC5010C / XC6010, only) .................................................................... 20 System Ground ....................................................................................................... 20 RFI Suppression ..................................................................................................... 20 XC5010C / XC6010 Cable Lengths and Sizes........................................................ 21 Lightning Protection ................................................................................................ 21 Summary of Internal Modules ................................................................................. 22 ® U.S. Registered Trademark Copyright © 2002 Honeywell Inc. • All Rights Reserved EN1R-1047GE51 R0902 / 95-7524-3 EXCEL 500/600 INSTALLATION INSTRUCTIONS Line Power Supply ............................................................................................. 23 XC6010 Computer Module................................................................................. 23 XC5010C Computer Module .............................................................................. 24 XP502 Power Supply Module............................................................................. 25 XP502 with External UPS XAPU 24-2F (Internal Modules, Only)....................... 25 XP502 with External UPS XAPU 24-2F (Distributed I/O Modules, Only)............ 26 XP502 with External UPS XAPU 24-2F (Distributed I/O and Internal Modules) . 27 XF521A Analog Input Module ............................................................................ 27 XF526 Analog Input Module............................................................................... 28 XF523A Digital Input Module.............................................................................. 29 XF522A and XF527 Analog Output Modules ..................................................... 30 XF524A and XF529 Digital Output Modules....................................................... 30 XF525A Three-Position Output Module.............................................................. 31 Excel 500-XCL5010................................................................................................ 32 Serial Port .......................................................................................................... 32 MMI Connection ................................................................................................. 32 Power Supply ..................................................................................................... 32 Screw Terminal Block Installation Procedure ..................................................... 33 Pull-Up Resistor Handling (O.S. 2.04.00 or higher, except for XFL521A) .......... 34 Communications ........................................................................................................................................................................ 36 LONW ORKS Bus Wiring ............................................................................................ 36 LONW ORKS Bus Termination............................................................................... 36 System Bus (C-Bus) ............................................................................................... 37 Submodule Selection (XC6010) ......................................................................... 37 System Bus Cable Specification......................................................................... 37 C-Bus Extension by Using Repeaters ................................................................ 38 C-Bus Termination (Excel 600) .......................................................................... 38 C-Bus Termination (Excel 500) .......................................................................... 38 C-Bus Termination (Excel 500-XCL5010) .......................................................... 38 Excel 600 Cable Specifications............................................................................... 39 Excel 500 Cable Specifications............................................................................... 40 Excel 500-XCL5010 Cable Specifications .............................................................. 41 MMI Cables ........................................................................................................ 41 Modem or ISDN Terminal Adapter Connections ................................................ 41 Changing Between MMI and Modem Connection .............................................. 41 Remote Communications .......................................................................................................................................................... 43 Modem or ISDN Terminal Adapter Connections..................................................... 43 Modem Requirements ............................................................................................ 43 No Set-up for Standard Modem Behavior .......................................................... 43 Automatic Baudrate Synchronization ................................................................. 44 Auto / Manual Answer Detection ........................................................................ 44 Resetting the Modem ......................................................................................... 44 Set-up for Special Modem Behavior................................................................... 44 Set-up for In-house Telephone Systems ............................................................ 44 Set-up for Limited Communication Speed.......................................................... 44 Troubleshooting.................................................................................................. 44 TCP/IP Dial-Up via TCP/IP Modem XM500 ............................................................ 44 GSM Communication (Europe, only) ...................................................................... 44 M20T Safety Precautions ................................................................................... 45 Required Third-Party Equipment ............................................................................ 45 Serial Cable........................................................................................................ 46 GSM Antenna Requirements ............................................................................. 46 Antenna Examples ............................................................................................. 46 EN1R-1047GE51 R0902 2 EXCEL 500/600 INSTALLATION INSTRUCTIONS GSM Antenna Installation ....................................................................................... 47 M20 Terminal Set-up............................................................................................... 47 Trademark Information Echelon, LON, LONMARK, LONW ORKS, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, LonPoint, Neuron, 3120, 3150, the Echelon logo, the LONMARK logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, and LonMaker are trademarks of Echelon Corporation. 3 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS REVISION OVERVIEW On the following pages, changes have been made compared to the previous release of this document: Page: throughout 21 23 27 30 34 EN1R-1047GE51 R0902 Change: Information regarding Distributed I/O modules has been removed. Please refer instead to Distributed I/O Product Data (EN0B-0090GE51). Fig. 44 has been changed. Fig. 45 has been changed. The technical specifications of the XF521A analog input module have been expanded and Table 7 and Table 8 added. The technical specifications of the XF522A and XF527 analog output modules have been expanded. Section "Pull-Up Resistor Handling (O.S. 2.04.00 or higher, except for XFL521A)" has been added. 4 EXCEL 500/600 INSTALLATION INSTRUCTIONS SAFETY INSTRUCTIONS — When performing any work (installation, mounting, startup), all instructions given by the manufacturer and in particular the safety instructions provided in the Installation Instructions are to be observed. — — Use only accessory equipment which comes from or has been approved by Honeywell. CAUTION The Excel 500/600 controller may be installed and mounted only by authorized and trained personnel. Disconnect the power supply before you start to install the Excel 500/600 Controller. Do not reconnect the power supply until you have completed installation. — If the unit is modified in any way, except by the manufacturer, all warranties concerning operation and safety are invalidated. CAUTION Disconnect the power supply before plugging in or removing the communication module (Excel 500 XCL5010). — Make sure that certain local standards and regulations are observed at all times. Examples of such regulations are VDE 0800 and VDE 0100. 5 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS MOUNTING Control Unit Installation The Excel 500 and 600 controllers have the same housing and can be installed two different ways: — Installation inside a control panel (see page 8). — Installation through a control panel door (see page 10). Fig. 3. Up to five housings can be connected together When housings are alongside one another, a minimum spacing of 1.5 in. (35 mm) should be taken into consideration to enable the hinged cover to be opened. The maximum spacing between housings is limited by tailor-made internal bus cables as shown in Fig. 3. Fig. 1. Excel 500/600 panel door mounting The Excel 500-XCL5010 can be mounted only on a DIN rail; control panel door installation is not possible. Excel 500/600 Internal Bus Wiring (not XCL5010) Each housing has four plug-in module locations. The individual modules are connected by an internal bus in the housing. Configurations comprising more than one housing must have the individual busses in the housings connected to one another. Fig. 2. Excel 500-XCL5010 DIN rail mounting Excel 500/600 Housing Layout (not XCL5010) A controller comprises from one to a maximum of five housings. The housings may be fitted alongside one another or, one above the other. Any combination is possible. EN1R-1047GE51 R0902 Fig. 4. Excel 500/600 bus wiring The connection is made via tailor-made ribbon cables. Two different types are available: — Type XW568 3 in. (80 mm) long (for housings alongside one another) 6 EXCEL 500/600 INSTALLATION INSTRUCTIONS Table 1. Internal module locations — Type XW569 13 in. (330 mm) long (for housings one above the other) Module Type Module location CAUTION CPU XC5010C / XC6010 1 housing, location 4 Incorrectly inserted bus cables can destroy the modules installed. Power supply XP502 1 housing, location 1 AI XF521A / XF526 any AO XF522A / XF527 any DI XF523A any DO XF524A / XF529 not in the 1 housing 3-position output XF525A not in the 1 module housing The internal bus begins at the first housing, containing the power supply and computer modules, and ends at the last housing. The protective bus connection covers must be removed. st st st st Coding the Terminal Block (not XCL5010) The terminal block is coded with pins to prevent mixing the module types during commissioning or servicing. Mixing the modules can damage them. You can code the terminal block by inserting pins into designated location holes on the terminal block in the base. Fig. 5. Removal of bus connection cover The overall internal bus length (bus cable and bus in the housings) must not exceed 6 ft (2m). Bus cables must be routed at least 2 in. (50 mm) away from power cables to prevent possible inductive and capacitive interference. Module Locations (not XCL5010) Each housing has four plug-in module locations. Fig. 7. Inserting the code pin in the terminal block Table 2 shows the coding pin positions for the individual module types: Table 2. Code pin position by module type Module Fig. 6. Internal module numbering Table 1 shows the plug-in location to which each module may be assigned: Type Pin position CPU XC5010C, XC6010 08 Power supply XP502 06 AI XF521A, XF526 07 AO XF522A, XF527 11 DI XF523A 09 DO XF524A, XF529 10 3-position output XF525A 12 NOTE: Distributed I/O modules are coded differently. See Distributed I/O Product Data (EN0B-0090GE51). 7 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS CAUTION Setting the Module Address (not XCL5010) Unplugging a module before switching OFF the power supply could destroy the module. Do not unplug modules with the power still connected. First switch S1 on the power supply module to the 0 position. In the case of application prior to CARE 4.0, you can set the module address using the rotary HEX switches located on the upper surface of the respective input and output modules. The rotary HEX switch of Distributed I/O modules is situated within the housing. The XP502 power supply module and the XC5010C / XC6010 computer modules do not need a hardware address. Installation Inside a Control Panel Excel 500/600 IMPORTANT Observe the minimum spacing of 1.5 in. (35 mm) when installing more than one housing. Do not exceed the maximum spacing; otherwise, the tailormade internal bus cables will be too short. 1. Break off cable entry strip segments. Fig. 8. Internal module HEX switch location The 16 I/O modules (max. including Distributed I/O) are addressed by means of the rotary HEX switch settings 0 to F. Fig. 11. Cable entry strip segments Fig. 9. Close-up of HEX addressing switch 2. Install the base. The relationship between the rotary HEX switch and the module address can be seen on the label located next to the rotary HEX switch. Fig. 10. HEX switch label Care should be taken to ensure that each module gets its own module address. Addressing the modules in ascending order 0 through F is recommended for the sake of clarity for maintenance personnel. Fig. 12. Installing the base in the panel EN1R-1047GE51 R0902 8 EXCEL 500/600 INSTALLATION INSTRUCTIONS 3. Code the terminal block (see section "Coding the Terminal Block (not XCL5010)" on page 7). 4. Make sure that the locking screws are positioned as shown in Fig. 13. 5. Plug in the enclosure. Fig. 15. Excel 500/600 extended wiring base Fig. 13. Housing locking screws and latches Using the extended wiring base the I/O terminals are accessible at run-time. 6. Shift latches inwards until the housing is released. 7. Set the module addresses (see section "Setting the Module Address (not XCL5010)" on page 8). 8. Insert the modules. Fig. 14. Modules and ribbon cable 9. Plug the ribbon cable onto the computer module. 10. Close the cover. Extended wiring base (wall-mounting, only; US, only): As an alternative to the base plate, an extended wiring base may be used. This is available for the U.S. market, only, and can be ordered without cover plate (OS No. 14507274-001) or with cover plate (OS No. 14507274-002). 9 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Excel 500-XCL5010 Plug in the communication module until it snaps into the con troller housing 1. Attach the DIN rail mounting clips to the housing. 2. Mount the controller on the DIN rail. 0000079a NOTE: If the communication module has been replaced or pulled out and plugged in again, push the reset button after power on. 1 Installation through a Control Panel Door (not XCL5010) IMPORTANT Observer the minimum spacing of 1.5 in. (35 mm) when installing more than one housing. Do not exceed the maximum spacing; otherwise, the tailormade internal bus cables will be too short. 1 1, Prepare the door in accordance with the following. dimensions. 2 Fig. 18. Panel door mounting dimensions 3 Fig. 16. Mounting Excel 500-XCL5010 on DIN rail 2. Insert the housing. Excel 500-XCL5010 Communication Module CAUTION 0000043a Always plug in the communication module before connecting the power supply. Always disconnect the power supply before unplugging the communication module. Fig. 19. Inserting the housing in the panel door 3. Insert the retaining clamp. Fig. 17. Inserting the communication module EN1R-1047GE51 R0902 10 EXCEL 500/600 INSTALLATION INSTRUCTIONS External Installation of XI582AH Operator Interface 1. Remove the cover. Fig. 23. Loosening the cover Fig. 20. Housing retaining clamp 4. Turn retaining clamp to fix housing. 5. Code the terminal block (see page 7). 6. Install the base. Fig. 21. Installing the wiring base Fig. 24. Removing cover 7. Complete electrical wiring. 8. Lock the cover. 2. If mounting on a wall, disconnect cable from panel for easier handling. Fig. 25. Disconnecting cable from cover 3. Route cable from the computer module (XC6010, XC5010C, XCL5010). Fig. 22. Locking the MMI cover 11 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Fig. 26. Routing the cable Fig. 29. Making electrical connections 4. If mounting on a wall, remove feet. 8. Reattach the cover. Fig. 27. Removing feet Fig. 30. Reattaching cover 5. Attach the housing to the wall. Deactivating Backlit Display of the XI582AH The XI582AH Operator Interface is equipped with an integrated backlit display to suit the display to the ambient lighting conditions. By default, this backlight is ON. This can be disabled by means of a jumper if required. The jumper is located at the back of the XI582AH cover. Fig. 28. Attaching to wall 6. Make electrical connections (gray wire not used). 7. Reconnect cable to panel if removed in step 2. EN1R-1047GE51 R0902 12 EXCEL 500/600 INSTALLATION INSTRUCTIONS Fig. 32. Backlight OFF jumper position When the jumper is disabled (OFF-position), the backlight is permanently deactivated. The contrast of the display can be adjusted using the potentiometer at the rear of the unit. Fig. 31. Jumper location (backlight ON position) The figure above shows the location of the jumper. To change jumper position, disconnect the connector first, then pull off jumper with tweezers or pincers and move to new position. When the jumper is enabled (ON-position) the backlight will be activated with the first key press of any of the eight operating keys. If no entries are made for approximately two minutes, the backlight turns itself off automatically until the next key is pressed again. Fig. 33. Contrast potentiometer Distributed I/O Installation Please refer to Distributed I/O Product Data sheet (EN0B 0090GE51) for more information. 13 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Dimensions Excel 500/600 Fig. 34. Excel 500/600 outside dimensions EN1R-1047GE51 R0902 14 EXCEL 500/600 INSTALLATION INSTRUCTIONS Excel 500-XCL5010 Fig. 35. Excel 500-XCL5010 dimensions 15 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS XI582AH Fig. 36. XI582AH dimensions EN1R-1047GE51 R0902 16 EXCEL 500/600 INSTALLATION INSTRUCTIONS Battery Activation during Commissioning (XC6010, only) The controller is delivered from the factory with the battery in the computer module electrically isolated from the internal circuitry by a safety tag to prevent the battery from discharging in transit. The controller is delivered from the factory with the battery in the computer module electrically isolated from the internal circuitry by a safety tag to prevent the battery from discharging in transit. 1. Unscrew the computer module cover with a screwdriver. Fig. 39. Battery compartment 2. Remove the safety tag. 3. Install the cover. Replacing the Battery IMPORTANT Batteries must not be disposed of as household waste. The law requires that you as the consumer return the waste batteries. Dispose of the battery according to legal regulations Fig. 37. Accessing the battery compartment During normal operation, the battery is periodically tested under load. If the battery voltage falls below a threshold of 2.45 V during operation or under load, the computer module generates an error message which is displayed on the MMI as a system alarm. The battery must be replaced as soon as possible after the system alarm. IMPORTANT The line power supply must not be interrupted while replacing the battery; otherwise, all data held in RAM is lost. NOTE: In the event that your fingers touch the battery contacts, please clean the contacts with cleaning agent. 1. Unscrew the computer module cover with a screwdriver as shown in the previous section. 2. Release the latch holding the battery in its compartment (See Fig. 39). 3. Remove the old battery. 4. Insert the new battery with the positive contact pointing upwards. Fig. 38. Removing the faceplate Battery type: Lithium battery 3 V, 1000 mAh, e.g. VARTA lithium battery CR1/2 AA – 3 V, 1000 mAh 17 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS NOTE: The CPU modules XC5010C and XCL5010 do not contain a battery. RAM is buffered for 3 days by a capacitor. Dismantling the Control Panel Unit Before dismantling the controller, the low voltage switch S1 of the power supply module must be switched OFF (position 0). To dismantle the control panel unit, reverse the steps of the installation procedure (see page 8). To release the locking screws in order to remove the wiring base, turn them clock wise as shown in Fig. 40. Fig. 41. Housing cover retaining clamp 2. Pull off the cover. Dismantling the Excel 500-XCL5010 Control Panel Unit Before dismantling the system, disconnect the power supply rd (e.g. by removing the terminal block or by an additional 3 party switch which should be installed onto the DIN rail close to the controller; see also warnings and notes in section "Electrical Connections" on page 20). Fig. 40. Releasing housing locking screws Dismantling the Control Panel Door Unit Before dismantling the system, disconnect the power supply. To dismantle the control panel unit, reverse the steps of the installation procedure (see page 10). CAUTION Always plug in the communication module before connecting the power supply. Always disconnect the power supply before unplugging the Communication module. Dismantling the Housing Cover 1. Release the metal retaining clamp. EN1R-1047GE51 R0902 18 EXCEL 500/600 INSTALLATION INSTRUCTIONS Dismantling the XI582AH Operator Interface 2 Use a pencil or similar object to open the XI582AH Operator Interface. 2 1 0000079b 1 Fig. 43. Opening the XI582AH Operator Interface unit Fig. 42. Removing Excel 500-XCL5010 from DIN rail 1. Dismantle the controller housing as depicted. 2. Pull the lower part of the housing off the control panel. 3. Lift the housing from DIN rail. 19 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS ELECTRICAL CONNECTIONS Shielding of Data-Transmitting Cables When connecting the controller, both VDE, National Electric Code NEC (or equivalent) and any local regulations con cerning grounding and zero voltage must be observed. Electrical work should be carried out by a qualified electrician. Under no circumstances should spare controller terminals be used as wiring support points. Doing so could damage the modules. The electrical connections must be made at the terminal blocks. The corresponding connection diagrams are on the individual modules. Connect the shield of the system bus (C-Bus) to system ground on both ends. Each end of the shield on the system bus should be connected to the system ground terminal of the respective computer module. Do not connect it to the control panel earth or any other earth ground points. NOTE: The LONW ORKS bus must not be shielded on the CPU side. WARNING To connect remote operator interface units, ready-made cables are available (XW565; XW582, XW583, etc.) with the shield already connected to the computer module plug end. Switch power OFF before making connections to or removing connections from terminals to avoid electrical shock or equipment damage. Grounding (XC5010C / XC6010, only) The controller should be grounded using as short a cable as possible (minimum 16 AWG [1.5 mm²]) between the control panel and the terminal block of the power supply module. IMPORTANT (FOR EUROPE, ONLY) To comply with CE requirements, devices with a voltage in the range of 50...1000 Vac or 75...1500 Vdc which are not provided with a supply cord and a plug or with other means for disconnection from the supply having a contact separation of at least 3 mm in all poles, must have the means for disconnection incorporated in the fixed wiring. System Ground WARNING High voltage Risk of electrical shock or equipment damage. The controller's system ground must have no connection with the control cabinet ground! Cable Routing The minimum distance to power mains cables is 0.4 in. (10 mm) for shielded cable and 4 in. (10 cm) for unshielded cable. All low-voltage signal and output cables should be regarded as communication circuits in accordance with VDE 0100 and VDE 0800 (or NEC or other equivalent), and should therefore be routed separately from mains cables. Joining sensor cables should be avoided. NOTE: A document providing additional information on system grounding (if required) is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Docu Server under: http://web.ge51.honeywell.de/dep/mc/TAC_Tips. RFI Suppression Honeywell actuators are RFI (Radio Frequency Interference) suppressed as standard in accordance with VDE 0871/B and VDE 0875/N. Shielding Input / Output Module and Power Supply Cables Shielding input and output module and power supply cables is not necessary if the general guidelines for cable routing are observed. If, in certain cases, the routing guidelines cannot be observed, then shielded cable must be used. The shield must not be terminated at a controller; instead, to avoid ground loops, the shield must be grounded (at only one end) at the control panel. To prevent ground loops, shielding of input/output cables leading to peripheral devices must be grounded only at the control panel end. EN1R-1047GE51 R0902 20 EXCEL 500/600 INSTALLATION INSTRUCTIONS XC5010C / XC6010 Cable Lengths and Sizes A cable length of 1300 ft (400m) with a cross sectional area of 2 0.5 mm (20 AWG) is permissible for a two-core, 0 to 10 Vdc signal cable. Table 3. Cable sizing Cross sectional area Type of signal 24 Vac power supply ≤ 550 ft (170 m) ≤ 1300 ft (400 m) ≤ 16 AWG 2 (≥ 1.5 mm ) ≤ 14 AWG 2 (≥ 2.5 mm ) - Lightning Protection Please contact your local Honeywell representative for information on lightning protection. 2 Low voltage 1 signals 1 ≤ 300 ft (100 m) ≤ 20 AWG (≥ 0.5 mm ) 0 to 10V sensors, totalizers, digital inputs, 0 to 10V signals for actuators, etc. MAX. 1300 ft (400 m) MIN. 20AWG (0.5 mm2) PRIMARY VOLTAGE 24 Vac 24 V Y GND Y TRANSFORMER 24 Vac 230 Vac 120 Vac PRIMARY VOLTAGE EXTERNAL TRANSFORMER Fig. 44. Connection of XL500/600 controller and a 24 V actuator with separate transformers 21 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Summary of Internal Modules Table 4. Summary of Excel 500/600 internal modules Module Computer module Name Inputs Outputs XC5010C, XC5210C Computer module XC6010 Power supply module XP502 1 Manual override switches LED display Reset button LONW ORKS service button RS232 front-rear switch LONW ORKS Service LED C-Bus transmit C-Bus receive Normal System error RS232 transmit RS232 receive Ground loop error Reset button Normal System error RS232 transmit RS232 receive C-Bus transmit C-Bus receive 0 (1 x) Power supply Watchdog ext. battery operation Analog input module XF521A 8 Analog input module XF526 8 Analog output module XF522A 8 Analog output module XF527 8 Digital input module XF523A Digital output module XF524A 5 changeover 1 NO contact Digital output module XF529 5 changeover 1 NO contact 6 x Status Three-position output module XF525A + (3 x) 0 3 three-position Auto 3 x Open Close C-bus repeater (10 KBit) XD509 CPU active 0 (5 x) 1 Auto 8 x Output intensity 8 x Output intensity 12 12 x Status, invertible 0 (5 x) 1 Auto 6 x Status NOTE: With XC6010 CPU only, there are submodules for system bus combination, XD505A (10 KBit) / XD508 (1 MBit), and for stand-alone modem communication, XDM506. EN1R-1047GE51 R0902 22 EXCEL 500/600 INSTALLATION INSTRUCTIONS Line Power Supply Table 5. 1450 series transformers data Part # 1450 7287 -001 WARNING -002 A separate CRT 6 or 1450 series (U.S.) transformer must be used for each of the EXCEL 500/600 controller's 24 V supply. No additional loads may be connected ! Each additional XL500/600 controller requires its own transformer. An additional transformer, appropriate to the power require ments, should be used to power input/output peripherals (e.g. actuators). -003 -004 -005 -006 MAX. 1300 ft (400 m) MIN. 20 AWG (0.5 mm2) 24 V Y GND CAUTION 230 Vac 120 Vac Do not unplug the computer module with the power still connected, since this could destroy the module. First, switch S1 on the power supply module to the 0 position. PRIMARY VOLTAGE EXTERNAL TRANSFORMER Fig. 45. Connection of XL500/600 controller and a 24V actuator with separate transformers Primary 24 Vac, 50 VA 2 x 24 Vac, 40 VA, and 100 VA 120 Vac from separate transformer 24 Vac, 100 VA, and 24 Vdc; 120 Vac 600 mA 240/220 Vac 24 Vac, 50 VA 2 x 24 Vac, 40 VA, and 100 VA 240/220 Vac from separate transformer 24 Vac, 100 VA, and 24 Vdc; 240/220 Vac 600 mA XC6010 Computer Module Y TRANSFORMER 24 Vac Secondary side The 1450 series includes built-in fuses, line transient /surge protection and AC convenience outlet, it meets NEC class 2 requirements. PRIMARY VOLTAGE 24 Vac Primary side 120 Vac If one of the C-bus submodules XD505A or XD508 is installed on the XC6010, follow Fig. 47. Secondary +6% 230 VAC -10 % % 220 VAC +10 -15 % 24 VAC ±20% CB-0039a Fig. 46. Excel 500/600 power supply To avoid interference, the cable between the transformer and the power supply module should be kept as short as possible (max. 6 ft (2m)). The transformer should therefore be positioned close to the power supply module. Fuse the transformer primary with its own fast-acting 10 A back-up fuse (or H 16 or L 16 miniature circuit breaker). The primary coil of the CRT 6 contains a 0.8 A / 250 V quick blow fuse. Table 5 gives an overview of the transformers of the 1450 series (U.S.): Fig. 47. Excel 600 CPU module C-Bus connections The system bus is connected to terminal 16 (C+) and terminal 17 (C-). See also section "C-Bus Termination (Excel 600)" on page 38. If the XDM506 Modem Submodule is installed on the XC6010, follow Fig. 48. Use the XW571 modem cable to connect the appropriate modem to the wiring terminals. 23 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Fig. 50. Excel 600 submodule mounting location For information pertaining to system bus baud rates and termination switch settings, see section "C-Bus Termination (Excel 600)" on page 38. Fig. 48. Excel 600 CPU modem connection XC5010C Computer Module The XC6010 has 2 EPROMs for the operating system and one flash EPROM for the application software. Their locations are shown in Fig. 49. CAUTION Do not unplug the computer module with the power still connected, since this could destroy the module. First, switch S1 on the power supply module to the 0 position. The XC5010C computer module contains both the system bus and the field bus. Fig. 51 shows the pin-out of the module. Fig. 49. Excel 600 EPROM locations Communication between several Excel 600 controllers is possible only if the system bus submodule is plugged into every computer module printed circuit board. This submodule must be installed when joining several controllers, when connecting a modem, or when monitoring via a central. XD505A or XD508 can be used for local bus communication, XDM506 is used for modem communication. A stand-alone controller can be operated without a submodule. Fig. 51. Excel 500 CPU module pin-out The system bus is connected to terminal 16 (C+) and terminal 17 (C-). The field bus (LONW ORKS bus) is connected to terminals 12 and 13. The LONW ORKS bus is non-polarized, i.e. there is no + or – pin. See section "LONW ORKS Bus Wiring" (page 36) and "System Bus (C-Bus)" (page 37) for more information. EN1R-1047GE51 R0902 24 EXCEL 500/600 INSTALLATION INSTRUCTIONS NOTE: Shielded cable is not necessary for the LONW ORKS bus. The serial port connections at the back of the module can be used to connect an XI582 MMI or, for CPUs with firmware version V2.1.0 or newer, a modem or ISDN terminal adapter. See section "Remote Communications" on page 43 for more information. Each XC5010C contains an application submodule that is different from the XD505A/XD508 submodule. The sub module for the XC5010C contains the C-Bus, LONW ORKS bus, as well as part of the RAM and flash EPROMs. For infor mation on C-Bus baud rates and the bus termination switch, see section "C-Bus Termination (Excel 500)" on page 38. XP502 Power Supply Module Fig. 53 shows the pin-out of the XP502 Power Supply module. Fig. 53. XP502 Power supply module and watchdog circuit To monitor the line power supply, the watchdog alarm must be provided with its own power or battery supply. Controller in operation: Watchdog relay terminals 17 and 18 connected. Controller non-operational: Watchdog relay terminals 16 and 17 connected. Fig. 52. Excel 500 CPU module front panel The operator interface on the front of the computer modules allow the Xl581AH/XI582AH Operator Interface or the Xl584 Operator and Service Computer to be connected. As an option, the XI582AH can be connected at the rear of the com puter module XC5010C. When connecting to the back of the module, the switch on the front panel of the XC5010C must be set to "Rear". XP502 with External UPS XAPU 24-2F (Internal Modules, Only) The Uninterruptable Power Supply XAPU 24-2F contains a relay contact and 24 Vac, which can be used for external con trols, or for the connection from XP502 terminal A7, A8. In case of failure, the relay contacts C and NO are closed and the 24 Vac supply is interrupted. 25 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Fig. 54. Connection of XAPU 24-2F UPS (internal modules) LED (L3) shows operation by battery. NOTE: The output from the XAPU 24-2F must not be connected with other devices. The fully-equipped Excel 500/600 controller will be completely supported with the battery for at least 15 minutes, without the mains power 230 Vac. Fig. 55. Connection of XAPU 24-2F UPS (Distributed I/O modules) XP502 with External UPS XAPU 24-2F (Distributed I/O Modules, Only) NOTE: There must be no connection between GND of the XC5010C CPU module and the GND of Distributed I/O modules. The wiring diagram below is for Excel 500 installations using only Distributed I/O modules. No internal I/O modules may be used. No other devices may be connected to the XAPU 24 2F. Relay K1 insures that the supply of the Distributed I/O modules will be switched OFF by switching OFF the XP502 Power Supply module. The power consumption of the Excel 500 controller is shown in the table below. For the power consumption of Distributed I/O modules, please refer to the corresponding Product Data (EN0B-0090GE51) Table 6. Power consumption of Excel 500 controller Devices powered EN1R-1047GE51 R0902 26 Supply voltage 24 Vdc 28.8 Vdc XP502, XC5010C, XI581 (backlight ON) 170 mA 155 mA XP502, XC5010C 140 mA 130 mA EXCEL 500/600 INSTALLATION INSTRUCTIONS XP502 with External UPS XAPU 24-2F (Distributed I/O and Internal Modules) XF521A Analog Input Module As shown in the figure below, two XAPU 24-2F UPSs are required when the controller has both internal and Distributed I/O modules connected. Number: eight inputs (AI1 – AI8) Input: 0...10 Vdc (low-input impedance, 25kOhm to 10 V / 200kOhm to GND); 0...20 mA (via external 500-ohm resistor); 4...20 mA (via external 500-ohm resistor); NTC 20K ohm (-50...+150 °C); PT1000 (-50...+150 °C) Protection: up to 40 Vdc / 24 Vac Resolution: 12-bit resolution Accuracy: ±75 mV or 0.75% (0...10 V) Technical Specifications Table 7. Accuracy of analog input sensors Range -58...-4 °F (-50...-20 °C) -4...+32 °F (-20...0 °C) +32...86 °F (0...30 °C) 86...158 °F (30...70 °C) 158...212 °F (70...100 °C) 212...266 °F (100...130 °C) 266...302 °F (130...150 °C) Measurement error (without sensor tolerance) PT1000 NTC 20K ≤ 1.2 K ≤ 5.0 K ≤ 0.7 K ≤ 1.0 K ≤ 0.5 K ≤ 0.3 K ≤ 0.7 K ≤ 0.5 K ≤ 1.2 K ≤ 1.0 K ≤ 1.2 K ≤ 3.0 K ≤ 1.2 K ≤ 5.5 K With current sensors, a terminating resistor of R1 = 499 ohms ± 0.25 % must be connected. Terminal 18 is an auxiliary output voltage (+10 Vdc, Imax = 5 mA) available for various sensor circuits. Fig. 56. Connection of XAPU 24-2F UPS (internal and Distributed I/O modules) XAPU 24-2F number 1 is connected to the XP502 for the controller, only. No other devices may be powered by XAPU number 1. XAPU 24-2F number 2 is connected to the XSL511 LONW ORKS connector modules for powering the Distributed I/O modules. The connection through relay K1 of the XP502 insures that the power supply to the Distributed I/O modules will be switched OFF when the XP502 is switched OFF. Fig. 57. XF521A Analog Input module connections 27 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS XF526 Analog Input Module Fig. 58 shows several connection examples for various sensors: WS21 Wind Sensor; SAF 25 Solar Sensor; and VMP Feedback Potentiometer. Technical Specifications Number: eight inputs (AI1 – AI8) Input: 0...10 Vdc (low-input impedance, 25kOhm to 10 V / 200kOhm to GND); 0...20 mA (via external 500-ohm resistor); 4...20 mA (via external 500-ohm resistor); NTC 20K ohm (-50...+150 °C); PT1000 (-50...+150 °C) PT1000 (0...+400 °C) PT100 (-50...+150 °C) PT3000 (-50...+150 °C) Balco 500 (-50...+150 °C) Protection: up to 40 Vdc / 24 Vac Resolution: 12-bit resolution Accuracy: ±75 mV or 0.75% (0...10 V) Fig. 58. XF521A connection examples Table 8. Accuracy of analog input sensors Fig. 59 shows connections to a TF26. Terminals 1, 3: Terminals 5, 3: Terminals 6, 3: Range temperature adjustment room sensor LED -58...-4 °F (-50...-20 °C) -4...+32 °F (-20...0 °C) +32...86 °F (0...30 °C) 86...158 °F (30...70 °C) 158...212 °F (70...100 °C) 212...266 °F (100...130 °C) 266...302 °F (130...150 °C) Measurement error (without sensor tolerance) PT1000 NTC 20K ≤ 1.2 K ≤ 5.0 K ≤ 0.7 K ≤ 1.0 K ≤ 0.5 K ≤ 0.3 K ≤ 0.7 K ≤ 0.5 K ≤ 1.2 K ≤ 1.0 K ≤ 1.2 K ≤ 3.0 K ≤ 1.2 K ≤ 5.5 K With current sensors, a terminating resistor of R1 = 499 ohms ± 0.25 % must be connected. Terminal 18 is an auxiliary output voltage (+10 Vdc, Imax = 5 mA) available for various sensor circuits. Fig. 59. XF521A and TF26 example EN1R-1047GE51 R0902 28 EXCEL 500/600 INSTALLATION INSTRUCTIONS Fig. 61. Digital input hysteresis The LED functionality of each digital input channel can be altered via 12 internal DIP switches. In the ON position (default), the LED will illuminate when energized (normally open contacts). In the OFF position, the LED will illuminate when de-energized (normally closed contacts). Max. signal voltage from non-Honeywell voltage sources: DC Voltage: Vmax = 40 V AC Voltage: Vmax = 28 V / ≥ 50 Hz Input resistance: Ri = 15k ohms Fig. 60. XF526 Analog Input module connections XF523A Digital Input Module The digital input module can process DC or AC voltage signals. The module has 12 digital inputs. When the input voltage reaches 5 V, the digital signal is set to a status of "1". With a hysteresis of 2.5 V, the digital input signal must fall below 2.5 V before a digital status of "0" is reported. Fig. 62. XF523A connection examples If the inputs are used as totalizers, Table 9 applies. Table 9. Totalizer inputs specifications Input Frequency Pulse duration Pulse internal Chatter time 1, 2 max. 15 Hz min. 20 ms min. 33 ms max. 5 ms 3 to 12 max. 0.4 Hz min. 1.25s min. 1.25 s max. 50 ms The inputs shown in row one (Input 1 to 2) may be used as fast totalizers. In this case, the input signal characteristics of row one are valid. If they are not used as fast totalizers, the values of row two (Inputs 3 to 12) apply to them as well. 29 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS XF522A and XF527 Analog Output Modules XF524A and XF529 Digital Output Modules Technical Specifications Technical Specifications Number: 8 analog outputs Voltage rating: 0 to 10 V, max. 11V Current rating: 1 mA max. Resolution: 8 bit Accuracy: ±150 mV or 1.5% deviation from output voltage Number: 6 digital outputs Voltage rating: 240 Vac max. per contact and per module Current rating: 4 A max. per contact, 12A max. per module Relay contacts: K1 to K5: changeover contact (voltage-free) K6: normally open contact (voltage-free) Manual override switches: XF522A 5 manual override switches (AO1 to AO5) XF527 No manual override switches Fig. 64. XF524A and XF529 Digital Output module NOTE: Maximum voltage for U.S. is 24 V. Fig. 63. XF522A and XF527 Analog Output modules NOTE: Both modules are fully pin compatible. NOTE: The maximum output current of 1 mA must not be exceeded. Beginning with V3.04.00 firmware, the online point attribute normally open/normally closed (NO/NC) defines the relation between the physical input signal and its logical status. See Table 10. NOTE: Both modules are fully pin compatible. Table 10. NO/NC attribute and output characteristic EN1R-1047GE51 R0902 30 Relay On/Off NO/NC attribute Logical status On NO 1 Off NO 0 On NC 0 Off NC 1 EXCEL 500/600 INSTALLATION INSTRUCTIONS XF525A Three-Position Output Module An L 16 miniature circuit breaker or G 10 A quick blow fuse should be used to protect the 240 Vac mains supply. Technical Specifications Voltage rating: 240 Vac or 28 Vdc max. Current rating: 0.2A max. at 240 Vac 1.2A max. at 28 Vdc NOTE: The maximum voltage for the U.S. is 24 V. Fig. 65. XF525A Three-position output module 31 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Excel 500-XCL5010 The Excel 500-XCL5010 housing comprises a removable screw terminal block for direct power supply wiring. For proper installation of the terminal block, follow these instructions: 1. Read the complete chapter "Installation" carefully. 2. Follow the instructions from the chapter Screw Terminal Block Installation Procedure on page 33. Table 11. Signals of serial port Signal type Controller output Controller input Signal ground Transmit The screw terminal block is attached directly to the controller housing. x Receive x Carrier detect x Clear to send x Data terminal ready x 5V x MMI Connection For direct communication the external operator interface XI582 and the PC-based MMI XI584 can be connected to the serial port. Power Supply The Excel 500-XCL5010 controller is powered by an external transformer. Fig. 66. Excel 500-XCL5010 terminal block location Serial Port Comm_Prt IMPORTANT Only the terminals 1 and 2 of the terminal block may be used for power supply. Do not wire any of the terminals 3 to 14. COMMUNICATION MODULE C-BUS CONNECTOR LON-BUS CONNECTOR SERIAL PORT FOR EXTERNAL MMI, MODEM, OR ISDN TERMINAL ADAPTER EXCEL 500XCL5010 HOUSING Fig. 67. Serial port The serial port has a 9-pin sub-D connector and has a default communication speed of 9.6 Kbaud. Fig. 68. Excel 500-XCL5010 power terminals location Terminal 2 is protected by a 4 A quick-acting fuse. Transformer requirements for one Excel 500-XCL5010 Controller: Voltage 21 to 26.5 Vdc or 24 Vac ± 20% Current 1.6A max. The transformer, already installed in the cabinet, can be used to supply several controllers, communication devices, or peripherals like actuators, etc. if the transformer provides sufficient power. EN1R-1047GE51 RR0902 32 EXCEL 500/600 INSTALLATION INSTRUCTIONS Table 13. 1450 Series transformers Fig. 69. Transformer example Use quick-acting backup fuse 10 A (or automatic H16 or L16) to protect transformer primary side. On the primary side of the CRT 2, there is a fusible output of type M 0.315 A (T) 250 V for the purpose of fine fusing. NOTE: When selecting the appropriate transformer, con sider the number of Distributed I/O modules (see worst-case power consumption information below) to be used as well as the power requirements of all active sensors and actuators connected to the transformer. CRT-Series Part # 1450 7287 Primary side -001 120 Vac 24 Vac, 50 VA -002 120 Vac 2 x 24 Vac, 40 VA and 100 VA from separate transformer -003 120 Vac 24 Vac, 100 VA and 24 Vdc 600 mA -004 240/220 Vac 24 Vac, 50 VA -005 240/220 Vac 2 x 24 Vac, 40 VA and 100 VA from separate transformer -006 240/220 Vac 24 Vac, 100 VA and 24 Vdc 600 mA Secondary side Standard Transformers Standard commercially available transformers must fulfill the specifications stated in Table 14. Table 12. Overview of CRT Series AC/DC current Table 14. Requirements for standard transformers Transformer max. AC current max. DC current CRT 2 2A 0.5 A = 500 mA Output voltage Impedance AC current ≤ 1.15 ohms max. 2 A CRT 6 6A 1.3 A = 1300 mA 24.5 Vac to 25.5 Vac CRT 12 12 A 2.5 A = 2500 mA 24.5 Vac to 25.5 Vac ≤ 0.40 ohms max. 6 A 24.5 Vac to 25.5 Vac ≤ 0.17 ohms max. 12 A Screw Terminal Block Installation Procedure WARNING High Voltage Risk of death or electrical shock. — Do not connect line power supply directly to the terminals. — Insulate devices with 120 Vac / 230 Vac by a transformer. Fig. 70. AC/DC current graphs 1450 Series All transformers of the 1450 series are designed for 50/60 Hz AC and have insulated accessory outputs. The transformers include built-in fuses, line transient/surge protection and AC convenience outlets and meet NEC class 2 requirements. 1. Make sure that the power supply of the cabinet is disconnected. 2. Make sure that the power supply of the cabinet is disconnected and the communication module is plugged in the housing. IMPORTANT When installing a separate external transformer, do not connect the cabinet ground to the controller system ground. 3. If the distance between the controller and an actuator or sensor with 24 Vac supply is greater than 550 ft (170m): a) Choose a transformer from the transformers listed in section "Power Supply" on page 32. b) Connect the chosen transformer directly to the actuator or sensor. 33 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS 4. Select one of the transformers of the CRT-series or 1450 series from the tables on the previous page or take a commercially available standard transformer fulfilling the requirements listed in Table 14. 5. Make sure that the communication module is attached to the controller housing. IMPORTANT The transformer feeding the Excel 500 Controller must be in the same cabinet. For the selection of the transformer, the max. DC current must be considered if field devices with DC load are used. The secondary side of the transformer must not be connected to earth ground. Fig. 73. Attaching screw terminal block Fig. 71. Connecting the power supply Pull-Up Resistor Handling (O.S. 2.04.00 or higher, except for XFL521A) 6. Connect the 24 Vac (-) on the secondary side of the transformer to terminal 1 on the Screw Terminal Block. 7. Connect the 24 Vac on the secondary side of the transformer to terminal 2 on Screw Terminal Block. High-Impedance Sensors and Active Sensors When high-impedance sensors and active sensors are connected to the inputs, the recognized value will not differ significantly from the measured value if the pull-up resistor is de-activated as follows: Put the character “@” as the first digit of the chosen input characteristic name in the CARE text editor. Example: Characteristic name: @0-10V; the internal pull-up resistor is disabled. 10 Vdc Vi 200K ohm ground Fig. 72. Connecting to a screw terminal Fig. 74. Analog input / high-impedance sensors IMPORTANT If there already are additional transformers, for example supplying actuators or active sensors, connect the 24 Vac (-) (secondary side) of the transformers together. NTC and Low-Impedance Sensors Characteristic name: NTC; the internal pull-up resistor is enabled. 8. Attach the terminal blocks to the housing as shown in Fig. 73. EN1R-1047GE51 RR0902 34 EXCEL 500/600 INSTALLATION INSTRUCTIONS 10 Vdc Immersion temperature sensor VF 100 Air duct temperature sensor LF 100 Wind sensor: Wind sensor WS21. Further connections: Temperature sensor terminal TF26 25K ohm Vi 200K ohm Table 15. Accuracy of analog input sensors ground Fig. 75. Analog input / low-impedance sensors Range Pt1000 Pull-Up Resistor Handling when Using Analog Inputs as Digital Inputs (O.S. 2.03.xx) When the input is identified as a DI point in CARE (DI subtype AI), the internal pull-up resistor is enabled. 10 Vdc 25K ohm Vi Measurement error (without sensor tolerance) NTC (20k ohms) -58 to –4 °F (-50 to –20 °C) ≤ 1.2 K ≤ 5.0 K -4 to 32 °F (-20 to 0 °C) ≤ 0.7 K ≤ 1.0 K 32 to 86 °F (0 to 30 °C) ≤ 0.5 K ≤ 0.3 K 86 to 158 °F (30 to 70 °C) ≤ 0.7 K ≤ 0.5 K 158 to 212 °F (70 to 100 °C) ≤ 1.2 K ≤ 1.0 K 212 to 266 °F (100 to 130 °C) ≤ 1.2 K ≤ 3.0 K 266 to 302 °F (130 to 150 °C) ≤ 1.2 K ≤ 5.5 K 200K ohm ground Fig. 76. Analog inputs identified as DI point (O.S. 2.03.xx) Pull-Up Resistor Handling when Using Analog Inputs as Digital Inputs (O.S. 2.04.00 or higher) When the input is identified as a DI point in CARE (DI subtype AI), the internal pull-up resistor is disabled. 10 Vdc Vi 200K ohm ground Fig. 77. Analog inputs identified as DI point (O.S. 2.04.00 or higher) Sensors and Transducers Passive sensors (NTC 20k ohms) Room temperature sensor RF20 Inlet temperature sensor VF20A External temperature sensor AF20 Active sensors (0 to 10 V): Duct Humidity Sensor H7011A1000 Duct Humidity Sensor H7012A1009 Active sensors (0 (4) to 20 mA): 35 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS COMMUNICATIONS LONWORKS Bus Wiring IMPORTANT Do not use different wire types or gauges on the same LONWORKS network segment. The step change in line impedance characteristics would cause unpredictable reflections on the bus. NOTE: In the event that the limit on the total wire length is exceeded, then FTT physical layer repeaters (FTT 10A) can be added to interconnect segments and increase the overall length by an amount equal to the original specification for that cable type and bus type for each repeater used. For example, adding repeaters for a doubly-terminated bus using JY (St) Y 2x2x0.8 cable increases the maximum length 3000 ft (900 m) for each repeater. On the Excel 500-XCL5010 controller, the LONW ORKS bus connections are located on the communication module as shown in Fig. 78: Connection between the Distributed I/O modules and the CPU are made from the LONW ORKS connector module XSL511. The LONW ORKS bus is a 78-kilobit serial link that uses transformer isolation so that the bus wiring does not have a polarity; that is, it is not important which of the two LONW ORKS bus terminals are connected to each wire of the twisted pair. The LONW ORKS bus can be wired in daisy chain, star, loop or any combination thereof as long as the maximum wire length requirements given below are met. The recommended configuration is a daisy chain with two bus terminations. This layout allows for maximum LONW ORKS bus length, and its simple structure presents the least number of possible problems, particularly when adding on to an existing bus. Table 16. Doubly-terminated bus specifications Max. bus length Belden 85102 2700 m (8900 ft) LON SERVICE BUTTON Belden 8471 2700 m (8900 ft) POWER, GRN LON SERVICE, RED Level IV, 22 AWG 1400 m (4600 ft) JY (St) Y 2x2x0.8 900 m (3000 ft) C-BUS TxD, YEL C-BUS RxD, YEL RESERVED TIA568A Categ. 5 24AWG, twisted pair 900 m (3000 ft) C-BUS TERMINATION SWITCH IMPORTANT It is recommended that ferrules not be used to terminate stranded wires to be inserted in the Distributed I/O Terminal blocks spring-clamp terminals. Fig. 78. Excel 500-XCL5010 communication module LONWORKS Bus Termination Depending upon the configuration, either one or two termination modules are required for terminating a LONW ORKS bus with FTT devices on it. The following two different LONW ORKS termination units are available for this purpose: • 209541B LONW ORKS Bus Termination Module (see Fig. 79 and Fig. 80) and • XAL-Term LONW ORKS connection and termination module (see Fig. 81), which can be mounted on DIN rails and in fuse boxes. The FTT specification includes two components that must be met for proper system operation. The distance from each transceiver to all other transceivers and to the termination must not exceed the maximum node-to-node distance. If multiple paths exists, the maximum total wire length is the total amount of wire used. Table 17. Free topology (singly-terminated) specifications Max. node-tonode distance Max. total wire length Belden 85102 1650 ft (500m) 1650 ft (500m) Belden 8471 1300 ft (400m) 1650 ft (500m) Level IV, 22AWG 1300 ft (400m) 1650 ft (500m) JY (St) Y 2x2x0.8 1050 ft (320m) 1650 ft (500m) TIA568A Category 5 24AWG, twisted pair 825 ft (250m) 1500 ft (450m) EN1R-1047GE51 RR0902 4 5 6 C-BUS NOT USED LON BUS A1 A2 1 2 3 SHIELD C+ C NOTES: The cable types listed above are as recommended by Echelon in their FTT-10A User Guide. The cable recommended by Honeywell is the level IV, 22 AWG, solid core, nonshielded cable. Belden part numbers are 9H2201504 (plenum) and 9D220150 (non-plenum). Cable type LEDs 00000124 Cable type Fig. 79. Termination Module 209541B connections for doubly-terminated FTT network 36 EXCEL 500/600 INSTALLATION INSTRUCTIONS Submodule Selection (XC6010) Two submodules for system bus communication are available. The selection depends on the communication speed. Table 18. C-Bus submodule baud rates Fig. 80. Termination Module 209541B connections for a singly-terminated FTT network Submodule Possible baud rates XD505A 9600 baud XD508 9600 baud 19200 baud Honeywell XAL-Term plug-in jumper removable screw-type 3-pole terminal block 4 LON Termination FTT/LPT Bus FTT/LPT Free Park Position L O N 76800 baud 5 shield 6 1 shield 0 4 3 3 L O N If the system bus speed throughout the system life-time is restricted to 9600 baud, then a submodule XD505A should be chosen. Otherwise, the XD508 must be used. NOTE: All communication submodules on one bus must be of the same type, i.e. either uniquely XD505A or uniquely XD508. Do not use a mix between submodules XD505A and XD508 on the same bus. Fig. 81. XAL-Term System Bus (C-Bus) IMPORTANT For communication with more than 9600 baud it is required to enable the termination of the first and the last device on the C-bus (see the following sections). The controllers with termination must be switched ON prior to the controllers in the middle of the C-bus. The C-bus might not work if the controllers with termination are switched OFF. Up to 30 controllers can communicate with one another and a PC central via the system bus. Instead of an Excel 500/600 controller, other system bus compatible components can also be connected. (Excel IRC Multicontroller; Excel EMC). The system bus must be connected through the individual controllers (open ring). The maximum communication speed of the XC5010C / XCL5010 is 76800 baud. The XC5010C/XCL5010 can be mounted together with the XC6010 (with XD505A or XD508 submodule) since the XC5010C/XCL5010 communication speed can be changed to match either submodule. In the case of either a daisy chain or free-topology LONW ORKS bus layout, the maximum lengths described above must be adhered to. NOTE: When changing the baud rate of bus devices, proper communication cannot be ensured until all bus devices are set to the same baud rate again. Fig. 82. C-bus topology IMPORTANT Star connection is not permissible because uncontrollable line reflections may occur. For setting up the system bus in the right way, three steps have to be followed: 1. Select submodule for system bus communication (XC6010, only) 2. Specify cable for system bus. 3. Set up submodule (XC6010), CPU module (XC5010C), or communication module (XCL5010). NOTE: When adding or removing a controller to/from the CBus, it may take up to two minutes to re-initialize the bus. During this time, communication on the C-bus is lost. System Bus Cable Specification The maximum cable length is 4000 ft (1200 m). There are regional differences as to whether shielded or unshielded cable must/can be used. IMPORTANT In Europe, only shielded cable is permitted, while in the US, shielded or unshielded cable can be used. 37 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Inside the cabinet: J-Y-(ST)Y 2 x 2 x 0.8 Outside the cabinet: A-Y-(ST) 2 x 2 x 0.8 The XD508 submodule is equipped with a DIP switch which activates (ON position) deactivates (OFF position) a terminating resistor. Depending on where the controller is located on the bus the DIP switch settings must be as follows: Table 21. XD508 DIP switch settings for C-Bus termination In principle, data transmitting cables should be shielded in case of RFI. The following summarizes cable types and gives selection guidance. Note that baud rate and maximum bus length are related to each other. Controller location DIP switch setting beginning or end of bus ON middle of bus OFF Table 19. C-Bus cable types Cable type J-Y-(ST)Y Description shielded, twisted pair Europe shielded, twisted pair Europe AK 3702 unshielded, twisted pair US AK 3740A shielded Belden 9842 twisted pair Belden 9841 shielded US AK 3702 unshielded, twisted pair US AK 3740A shielded 2 x 2 x 0.8 A-Y-(ST)Y 2 x 2 x 0.8 C-Bus Termination (Excel 500) Recommended for The XC5010C CPU module contains a switch for setting different C-Bus baud rates. Inside cabinet Outside cabinet not approved for Europe US (low-cost) not approved for Europe Europe US also possible Fig. 83. XC5010C C-Bus termination switch location The bus termination switch for setting the baud rate has three settings: not approved for Europe US (low-cost) not approved for Europe Table 22. XC5010 C-Bus termination switch settings Each end of the shield on the C-Bus should be connected to the shield terminal of the respective device. Do not connect it to the cabinet ground or any other ground points. Switch setting Baud rate Notes: S1 up to 76800 baud with bus termination same functionality as XD508A, up to 76800 baud S2 up to 76800 baud without bus termination same functionality as XD508A, up to 76800 baud S3 up to 9600 baud same functionality as XD505A - Default setting C-Bus Extension by Using Repeaters The C-Bus length can be extended by using repeaters. Each repeater extends the bus length by 4000 ft (1200 m). For the US the repeater is available either with or without housing. In Europe, only the version with housing is allowed. C-Bus Termination (Excel 500-XCL5010) Table 20. Order no. for repeaters Description US order No. European order no. without housing 14507324-001 - with housing 14507324-002 XD509 The communication module for the XCL5010 is equipped with a DIP switch for the C-Bus to set the bus termination appropriate for the communication speed. C-Bus Termination (Excel 600) The XC6010 CPU module may have either the XD505A or the XD508 submodules mounted on them for C-Bus communication. Table 18 provides baud rate information for selecting the module. EN1R-1047GE51 RR0902 38 EXCEL 500/600 INSTALLATION INSTRUCTIONS For connection to the XI584 Operator and Service Computer, a tailor-made cable is available with plugs on both ends. — XW567 cable, length 7 ft (2.5m) Fig. 84. Excel 500-XCL5010 C-Bus DIP switch location Table 23. DIP switch settings for C-Bus termination (Excel 500-XCL5010) DIP switch setting Communication speed up max. 9.6 Kbaud middle max. 76.8 Kbaud down max. 76.8 Kbaud Controller location Compatibility XD505A, XL20XD middle of XD508, bus XL20XD508 beginning or XD508, end of bus XL20XD508 NOTE: Modules listed in Compatibility column are used in Excel 20/100B/500/600 Controllers. Excel 600 Cable Specifications For connection to the XI582 Operator Interface, two tailor made cables are available. — XW564 cable, length 7 ft (2.5 m) — XW565 cable, length 15 ft (5 m) Fig. 86. Excel 600 / XI584 cable details Fig. 85. Excel 500 / XI582 cable details 39 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Excel 500 Cable Specifications The XI582AH Operator Interface can be connected either to the or the back of the XC5010C. — XW582 cable, front connection, length 15 ft (5 m) — XW583 cable, back connection, length 15 ft (5 m) Fig. 88. Excel 500 / XI584 operator and service computer cable details NOTE: You can also use a standard null modem cable. An adapter cable is needed when the same MMI unit XI582AH or XI584 is used on a site where there is a mix of XC5010C and XC6010 CPU modules. Always use the new cables XW582 and XW585 with the XC5010C CPU module and the additional adapter cable XW584 for connecting to the XC6010 CPU module. Fig. 87. Excel 500 / XI582 cables The XI584 Operator and Service Computer can be connected to the front of the XC5010C computer module with the following cable: — XW585 cable, length 15 ft (5 m) EN1R-1047GE51 RR0902 40 EXCEL 500/600 INSTALLATION INSTRUCTIONS Excel 500-XCL5010 Cable Specifications MMI Cables Modem or ISDN Terminal Adapter Connections Ready-made cables with the shield already connected to the computer module plug end are available for the connection of external MMIs. For remote communications, a modem or ISDN terminal adapter can be connected directly to the serial port of the Excel 500-XCL5010 Controller. The serial port of the Excel 500-XCL5010 controller accepts a standard modem cable with a female 9-pin connector. Use the cable that is supplied with the modem/ISDN terminal adapter. The communication speed is 9600 baud by default but can be set as high as 38.4 Kbaud. For more details, see section "Remote Communications" on page 43. Table 24. Cable specifications MMI type Cable Length XI582 (remote MMI) XW582 17 ft (5m) XI584 (PC-based MMI) XW585 17ft (5m) For connection to the XI584, a standard null modem cable may be used. Changing Between MMI and Modem Connection TO EXCEL 500-XCL5010 WHITE YELLOW BROWN GREEN SHIELD YELLOW BROWN GREEN WHITE TO XI584 TO EXCEL 500-XCL5010 XW585 SHIELD 9 8 7 6 5 4 3 2 1 1 2 3 4 TxD +5VE RxD GND DCD RxD RTS TxD CTS DTR RI GND 9 8 7 6 GND TxD +5VE RxD The Excel 500-XCL5010 will detect when an MMI or modem/ISDN terminal adapter is connected and will adjust the communication speed automatically according to the preset values. This automatic detection can take up to 5 seconds. XI582 5 4 3 2 1 6 7 8 9 1 2 3 4 5 XW582 Fig. 89. Excel 500-XCL5010 / MMI cable details 41 EN1R-1047GE51 R0902 EXCEL 500/600 INSTALLATION INSTRUCTIONS Fig. 90. Excel 500 and Excel 600 used together with XI584 and XI582 Operator Interfaces Fig. 91. XW584 cable details EN1R-1047GE51 RR0902 42 EXCEL 500/600 INSTALLATION INSTRUCTIONS REMOTE COMMUNICATIONS The following applies to the XC5010C and XCL5010, only. For remote communications with up to three XBS Building Centrals, a modem or ISDN terminal adapter can be connected directly to the serial port of the XC5010C CPU (either front or rear connection) or the serial port of the XCL5010. The serial port of the XCL5010 CPU accepts a standard modem cable with a female 9-pin connector. NOTE: Remote communication via modem or ISDN terminal adapter requires firmware version V2.1.0 or higher. NOTE: XBSi building supervisors are not supported for remote communication. Modem or ISDN Terminal Adapter Connections The front serial port of the XC5010C CPU accepts a standard modem cable with a female 9-pin connector. Fig. 93. Serial port location on Excel 500-XCL5010 Use the cable that is supplied with the modem/ISDN terminal adapter. The communication speed is 9600 baud by default but can be set as high as 38.4 Kbaud. NOTE: See section "Serial Port" on page 32, for signals of serial port. Modem Requirements • Modem must support Hayes compatible command set (not V150 or V151 = Microsoft command set) • Modem must support alpha-numeric return codes • Modem must follow serial baud rate of the CPU • Modem must support auto-bauding (baud rate fall-back) • When carrier detect (connect) is reported, the carrier must be on simultaneously at both modems (on CPU side and on XBS side) use same modem • After a switch-ON of the DTR line by the CPU or XBS, the modem must accept a dial command after 3 seconds • Modem must answer AT commands in less than 3 seconds Fig. 92. Serial port locations on Excel 500 Use the cable that is supplied with the modem/ISDN terminal adapter. To connect to the terminals of the rear serial port of the XC5010C, use cable XW571 (length: 6 ft (1.9m)). Table 25. XW571 Connection Pin XC5010C 2 RS232 signal RTS Wire color Blue 3 GND White 4 TxD Yellow 5 RxD Green 6 CTS Violet 7 DTR Black 8 (not used) SG White 9 DCD Brown 10 Shield Clear 11 (not used) RI Red No Set-up for Standard Modem Behavior If no special modem behavior is required, there is no need to set up or initialize the modem/ISDN terminal adapter. The XC5010C/XCL5010 CPU will automatically detect the device (MMI or modem) attached to the serial port and set the appropriate communication speed. The controller will also automatically adapt to alphanumeric return codes used by the modem. This automatic detection and adjustment can take up to 5 seconds. NOTE: It is highly recommended to use a state-of-the-art modem and leave it in its factory setting. NOTE: Pin numbers shown are for the rear connector of the XC5010C Computer Module. 43 EN1R-1047GE51 R0702 EXCEL 500/600 INSTALLATION INSTRUCTIONS Automatic Baudrate Synchronization The default communication speed between the XC5010C/XCL5010 CPU and the local modem/ISDN terminal adapter is 9600 baud. without waiting for a public network dial tone. Save this modem set-up in the modem EEPROM with the command AT&W. Check the modem handbook to verify the correct commands. Note that these commands are executed automatically with the RESET MODEM command. The communication speed between the XC5010C/XCL5010 CPU and XBS modems/ISDN terminal adapters is auto matically synchronized by the two devices to the highest speed that both of the devices are capable of. This feature is called autobauding and is a feature that all state-of-the-art modems/ISDN terminal adapters provide when left in their factory default settings. The communication speed between the XBS and its modem/ISDN terminal adapter is part of the modem set-up at the XBS. 2. Add the prefix required for access to the public telephone network to the destination telephone number. Depending on the in-house telephone system, a certain prefix may have to be added to the destination number in the XBS system configuration/site definition screen prior to sending the set-up to the remote Excel 500 controller. Set-up for Limited Communication Speed The communication speed of the modem can be fixed to a lower rate in case of data transmission errors due to tele phone line limitations. See the XI581/582 Buswide Operator Interface User Guide (EN2B-126GE51) for the procedure for fixing the baud rate. Auto / Manual Answer Detection The XC5010C/XCL5010 CPU will automatically detect whether the modem/ISDN terminal adapter is initialized in auto-answer or manu-answer mode, and it will set the modem to manual answer mode (S0 = 0). Troubleshooting Resetting the Modem In case of any problems the handbook of the modem or ISDN terminal adapter must be consulted. For those cases where it is not clear if the modem to be used is in its factory setting, the modem can be reset to its factory setting by using the RESET MODEM command in the Start up sequence or through the HW Config. part of the System Info. sequence on the MMI. This will allow a quick and easy modem reset without the need to run the modem set-up software or the Windows™ terminal program. A “Frequently Asked Questions and Troubleshooting” document is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the HIVE under: Technical Assistance Center/Controllers/Excel 80 and 100 and 500 and 600/ technical literature/modemfaq.doc or on the Docu Server under: http://web.ge51.honeywell.de/dep/mc/TAC_Tips/Modem FAQ.doc The RESET MODEM command causes the following commands to be sent to the modem: 1. ATZ executes hardware reset on modem 2. AT&FX3&W resets modem to factory configuration settings, configures the modem not to wait for the public phone system dial tone, and writes this to nonvolatile memory. TCP/IP Dial-Up via TCP/IP Modem XM500 The Honeywell TCP/IP modem XM500 allows use of a TCP/IP network (e.g. Ethernet LAN/WAN networks) to achieve a dial-up connection between an XBS building supervisor and an Excel 500 controller. The set-up is identical to that of a telephone modem connection with the exception of the additional need for definition of the Ethernet address. Set-up for Special Modem Behavior If special modem/ISDN terminal adapter behavior is required, the communication device should be set up according to the instructions provided with it. This typically involves running a setup program on a computer with the device connected to the computer serial port or using the Windows™ terminal program. Details can be obtained from the XM500 Product Data Documentation on the Honeywell Intranet under: http://web.ge51.honeywell.de/dep/mc/HVAC_Products/Autom ation_and_Control/CentralPlantControls/Modem Interface/xm500/xm500_pd.zip Set-up for In-house Telephone Systems A common case of special modem behavior is when the modem is connected to an in-house telephone network requiring a prefix to be dialed before the destination number to provide access to the public telephone network. There are two important aspects of the special initialization of the modem to consider: GSM Communication (Europe, only) For communication via the Global System for Mobile communications (GSM), a Siemens M20 Terminal (cellular engine) is required and must be connected directly to the serial port of the Excel 500 controller. The M20T translates the Excel CPU data received in transparent mode into the GSM standard. The M20T behaves like a Hayes-compatible 1. Do not wait for the public network dial tone. Typically the init command ATX3 will trigger the modem to dial EN1R-1047GE51 RR0902 44 EXCEL 500/600 INSTALLATION INSTRUCTIONS modem connected to the Excel controller serial port, and it then transmits via GSM like a cellular (mobile) phone. NOTE: Communication via GSM requires firmware version V2.3.0 or higher. address all questions to a doctor or the manufacturer of the medical device. • The M20 Terminal shall not be used within wet environment, such as in public baths. IMPORTANT With the M20T, data communication is possible only in 900 MHz GSM networks. GSM networks operating at 1800 MHz or 1900 MHz are not supported. • If your M20 Terminal, your SIM card or both go missing, notify your network operator immediately in order to avoid misuse. Required Third-Party Equipment The maximum communication speed is determined by the current GSM standard, which is 9600 baud. Due to a special transmission mechanism, the effective communication throughput is lower than 9600 baud – however this will be noticeable only when high data volumes are transmitted, e.g. when application download is performed. The Siemens M20 Terminal (shown below) is required for GSM communication. In addition, a 3V Mini SIM card with personal identification number (PIN) is required for the M20T. The Mini SIM card, supplied by the GSM Network Provider, must be released for data communication at 9600 baud. M20T Safety Precautions HANDSET INTERFACE CAUTION Use of the M20 Terminal on-board aircraft is forbidden. Use of a Cellular Engine in an aircraft, such as for the purpose of wireless connection of an aircraft based HVAC system to an XBS central, can endanger navigation, it interferes with the cellular network and it is illegal. Failure to comply with this prohibition may lead to temporary suspension or permanent cancellation of Cellular Engine services for the person who disregards this prohibition and/or to legal action against said person. MOUNTING HOLES TOP BOTTOM SIM CARD READER OPERATING STATUS LED CAUTION V.24 INTERFACE SUB-D SOCKET Users are advised to NOT use the M20T in automotive service stations. POWER SUPPLY AND AUDIO INTERFACE FME ANTENNA CONNECTOR Fig. 94. Siemens M20 terminal A separate telephone number is required for data communication with the same SIM card (one telephone number for voice communications and one for data). Users are reminded of the necessity of complying with restrictions regarding the use of radio devices in fuel depots, chemical plants and locations where explosives are ignited. Mechanical characteristics: Weight 145 g Dimensions (max) LxWxH 107.0 x 63.5 x 31.3 mm Temperature range -20°C to 55°C Protection-class IP40 Mechanical vibrations Amplitude 7.5mm at 5 to 200 Hz sine Max. pulse-acceleration 30 g pulse with 18 ms duration Air humidity 5–98% Additional precautions are as follows: • When receiving calls on a public highway, such as a cooling control system of a refrigeration truck being called by an XBS central, the M20T is not permitted to use "warning" devices which causes the vehicle’s horn to sound or the lights to flash. • Drivers are advised not to use the handheld microphone or the telephone handset while their vehicle is in motion, except in emergencies. Use the hands-free facility to speak only if it does not divert your attention from the traffic. Electrical characteristics: Operating voltage range Undervoltage/overvoltage protection: Power consumption at 12V 8 to 28.8 Vdc, ±5% ripple 0 V / 45 V <200 mA speech mode, <14 mA idle mode Max. line-in/out cable length 2 m (e.g. modified NOKIA 2110 for M20T) • Operation of the M20T can disrupt the operability of inadequately protected medical devices. Please 45 EN1R-1047GE51 R0702 EXCEL 500/600 INSTALLATION INSTRUCTIONS Antenna Examples Protection fuse 1 A, fast blow Max. RF power 2 W at 900 MHz Power supply connector 6-pin modular CE conformity: • 89/336/EC (EMC guideline) • 73/23/EC (Low voltage guideline) • 91/263/EC (Telecommunications devices guideline) Standards: • EMC: ETS 300 342-1 • Safety: EN 60950 • GSM network: TBR 19, TBR 20 Serial Cable For connecting the M20T to the Excel 500 controller, a standard RS232 cable (9-pin V24 sub-D sockets) is required. GSM Antenna Requirements All major suppliers of GSM antennas can supply GSM900 Antennas with FME plugs to connect with the M20 Terminal for a variety of applications. Some antenna examples are shown below. Fig. 95. Round radiation antenna, magnetic base, 5 DBi The antenna must satisfy the following electrical requirements: Frequency TX 890-915 MHz Frequency RX 935-960 MHz Impedance 50 ohms VSWR TX: max. 1.7:1 installed VSWR RX: max. 1.9:1 installed Gain > 1.5 dB referenced to λ/2 dipole 3dB width of cone vertical: 80° horizontal: 360° Max. power: 1 W (cw), 2 W peak; at ambient temperature of 55°C Fig. 96. Directional antenna (YAGI), 12 DBi Depending on the application and the RF field at the local site, the GSM antenna may be mounted directly or via cable. The maximum antenna cable length is 8.0 m (including 20 cm M20 Terminal-cable) NOTE: The maximum number of push/pull cycles shall not exceed 100. Fig. 97. Round radiation antenna, 6.5 DBi The antenna interface connector of the M20 unit is a FME connector (of type SMR nano (male)). Hence, the connector on the GSM antenna or antenna cable has to be of type SMR nano (female, or use a double female connector in between). Fig. 98. Window patch antenna, 2 DBi EN1R-1047GE51 RR0902 46 EXCEL 500/600 INSTALLATION INSTRUCTIONS GSM Antenna Installation M20 Terminal Set-up The maximum antenna cable length is 8.0m (including the 20 cm M20 Terminal cable). Use a cable that is specified by the supplier of the GSM antenna. Improper cables with resistances that are too high will reduce the amplification of the antenna. Prior to beginning the set-up, get the M20T manual (or CDROM, if it was delivered with one). Everything is described in it and you will need it. IMPORTANT It is absolutely mandatory to use a serial data line monitor for the set-up of the M20T. Without such a device being connected between the serial port of the PC and the M20T, you will get no information on the set-up process. • Ideally you should know in which direction the next GSM station is located in order to position of the antenna accordingly. 1. Insert the SIM card into the M20T. 2. Connect the serial cable to the M20T and a PC or laptop. 3. Connect the antenna cable and antenna to the M20T connector. 4. Start a terminal program, e.g. Windows™ HyperTerminal 5. Connect the power supply to the M20 Terminal and plug into mains. The M20T LED will be blinking now. 6. Set terminal program to 19200 baud. 7. Verify the correct operation of the M20T serial interface by entering: AT. The M20T will respond: OK. 8. Change the M20T’s baud rate from 19200 (factory default) to 9600: AT+IPR=9600. 9. Set terminal program back to 9600 baud. 10. Command the M20T to cut the line whenever the DTR signal is dropped (OFF) or toggled ON/OFF: AT&D2 11. Store setting in nonvolatile memory: AT&W. 12. You may now enter the PIN number or let the Excel CPU do this. If you want to enter the PIN number now, enter the PIN with the command AT+CPIN=”xxxx”, where xxxx represents the PIN number. • The easiest way to check the signal quality is to operate a cellular (mobile) phone at the very place where you want to place the antenna. — The cellular phone must operate in the same GSM network as the M20T. — Drop-outs in voice communication indicate that the reception is too weak. The data communication will never work where you have drop-outs in voice communication with the cellular phone. The pre ferred way is to set-up the M20T on a terminal program and check the reception with the SIEMENS AT commands – see the M20T handbook. — An alternative way to verify the signal quality is to use the terminal program on the CD that is supplied with the M20T. You will find a special button on it that allows checking on the signal quality. • Dipole antennas - e.g. antennas with a magnetic foot must sit on metal ground to achieve the specified amplification. The larger the metal ground, the better. • The antenna must be mounted vertically, NOT horizontally. • Avoid barriers for the antenna signal. Ideally, within a range of approximately 3 meters there should not be any vertical barriers that would block the antenna signal, such as doors, PCs, cupboards, etc. NOTE: Regarding the PIN entry, the M20T shows the same behavior as a regular cellular phone, as it uses the same type of SIM card. This means, for example, that after 3 false PIN inputs, the SIM card will lock and need to be released via the “PUK” Personal Unlocking Key (Master PIN). • Select the most suitable antenna. Location and mounting limitations may require that special antennas be used, such as antennas with higher amplification or directional antennas. Repeated input of the wrong “PUK” (more than 2 false inputs) will destroy the SIM card irrevocably. • Avoid loose contacts. All connections from the M20T to the antenna must be tight. 13. Once the M20 has accepted the PIN it will log into the GSM net. The terminal window will show “OK”. The M20T LED will be on continuously. 14. Disconnect the serial cable from the PC/laptop and connect it to the Excel CPU. 15. Verify that the M20T dials out on the telephone number for data communication, otherwise, its call will not be recognized by the XBS. The M20T can be forced to do so by adding the letter to the telephone number, e.g.• Increase the distance between the antenna and Excel CPU if you experience electromagnetic interference of the antenna signal to the CPU. An indication of this might be that the functioning of the MMI of the CPU is disturbed or that the outputs behave abnormally. 47 EN1R-1047GE51 R0702 EXCEL 500/600 INSTALLATION INSTRUCTIONS NOTE: As soon as the PIN is entered into the Excel controller, the following mechanisms will take place automatically: — Cyclical check (once per minute) for existence of the PIN number in the M20 (AT+CPIN?) — Sending of PIN number to M20T, if it has lost it. This guarantees communication will resume automatically after exchange of the SIM card or after power to the M20T has been lost. Deletion of the PIN number or resetting the controller will stop the above mechanisms. Verification of the PIN You can verify the PIN without connecting a terminal program by following these steps: 1. 2. 3. 4. 5. 6. 7. 8. Connect the XI582AH MMI. Enter PIN. Disconnect the XI582AH MMI. Connect the M20T. Reconnect the XI582AH MMI. View the “PIN” field. If it shows “0”, the PIN was wrong. If it shows “PIN”, the PIN was correct. Additional information about the M20 terminal may be found at the following website: http://www.siemens.de/ic/products/cd/english/index/products/ cellular/m20t.html Control Products Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524 USA http://www.honeywell.com Control Products Honeywell Limited-Honeywell Limitee 155 Gordon Baker Road North York, Ontario M2H 3N7 Canada http://www.honeywell.ca EN1R-1047GE51 R0902 / 95-7524-3 Control Products Honeywell AG Böblinger Straβe 17 D-71101 Schönaich Germany http://europe.hbc.honeywell.com printed in Germany Subject to change without notice
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Encryption : Standard V4.4 (128-bit) User Access : Print, Copy, Extract, Assemble, Print high-res Tagged PDF : Yes Page Mode : UseNone XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Producer : Acrobat Distiller 4.0 for Windows Modify Date : 2007:05:08 11:44:59-05:00 Create Date : 2002:09:10 14:37:13Z Metadata Date : 2007:05:08 11:44:59-05:00 Creator Tool : Format : application/pdf Title : Excel 500/600 Control System Description : Installation Instructions Creator : Honeywell Europe Document ID : uuid:69b61640-559b-4a78-819f-d8a31a91e9f6 Instance ID : uuid:64a607e5-ce58-41f2-a729-b092c7cfc721 Page Count : 48 Subject : Installation Instructions Author : Honeywell EuropeEXIF Metadata provided by EXIF.tools