H8908B Humidistat H8908C Dehumidistat INSTALLATION INSTRUCTIONS APPLICATION The H8908B Humidistat and H8908C Dehumidistat (humidity controllers) provide automatic low voltage control of humidifiers and dehumidifiers or ventilators, respectively, in central heating and air conditioning systems. They have a spst, snap-acting, dust-proof switch and are designed for wall or surface duct mounting. Humidity Control Régulateur d'humidité OUTDOOR TEMPERATURE -20 °F -30 °C -10 °F -25 °C 0 °F -20 °C +10 °F -10 °C +20 °F -5 °C Over 20 °F Over 0 °C HUMIDITY SETTING 15% 20% 25% 30% 35% 40% INSTALLATION When Installing this Product... 1. 2. 3. 4. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. Installer must be a trained, experienced service technician. After installation is complete, check out product operation as provided in these instructions. CAUTION Personal Injury Hazard. Power supply can cause electrical shock. Disconnect power supply before beginning installation. Location and Mounting HOLE FOR WIRING THE DUCT MOUNTING INSTALLATIONS Wall Mounting IMPORTANT Mount the control in an area with average room temperature and average relative humidity. The following mounting instructions are for mounting the H8908 on the wall next to the T8600. When installing the H8908 at another location, modify the procedure to fit the installation. 1. NOTE: The H8908 electrical connections are not shared with the thermostat. 3. 4. 2. 5. •All Rights Reserved M13371 Fig. 1. H8908B Humidistat. The styling of the H8908 is designed to blend with the latest T8600 family of Honeywell Chronotherm® IV Deluxe Programmable Thermostats. A mounting template is included for mounting the H8908 next to the T8600. The H8908 can also be mounted at any other convenient location in the living area or equipment room. See Fig 1. ® U.S. Registered Trademark Copyright © 1999 Honeywell Inc. • CASE REMOVAL SLOT Hold the mounting template (included) next to the T8600. Select the mounting side for the H8908. The template is reversible for mounting on either the left or right side of the T8600. See Fig. 2. Mark the holes for the two mounting screws (included). Then mark the hole for the low voltage wiring on the template that corresponds with the side selected in step 1. Remove the template and drill the holes. Run low voltage wiring to the location and pull about 6 in. (152 mm) of wire through the hole. Plug the hole with nonflammable insulation to prevent drafts from affecting the control operation. 69- 1341 H8908B HUMIDISTAT H8908C DEHUMIDISTAT 6. 7. 8. Remove the H8908 case from the base. See Fig. 1. Position the base on the wall with the arrow up. Use the two 1 in. (25 mm) mounting screws to secure the base to the wall. THERMOSTAT WALLPLATE ALTERNATE LOCATION RETURN AIR MOUNTING TEMPLATE RETURN AIR 6 in. (152 mm) MINIMUM 15 in. (381 mm) MINIMUM BEST LOCATION RETURN AIR DUCT M13369 MOUNTING HOLES (2) WIRING HOLES FOR MOUNTING ON RIGHT. USE LEFT HOLES FOR MOUNTING ON LEFT. Fig. 3. Selecting duct location for control. M13370 1. Fig. 2. Positioning mounting template. IMPORTANT Use 18- to 22-gauge wire for proper wiring. 2. 3. Connect the low voltage wires to the leads on the H8908. 10. Replace the H8908 case. 9. 4. 5. 6. 7. Duct Mounting IMPORTANT When mounting near an elbow area, locate the control 6 in. (152 mm) upstream from the elbow so the element is exposed to the normal airflow (Fig. 3). 8. 9. Locate the control at least 8 in. (203 mm) upstream from the humidifier (or dehumidifier/ ventilator supply) in the return air duct. See Fig. 3. Apply the duct template to the duct location. Use the duct template, Fig. 4, to make the opening and mounting holes for the H8908. Remove the H8908 case from the base. See Fig. 1. Position the foam gasket on the H8908 base. Position the base on the duct with the arrow up. Use the four 1 in. (25 mm) mounting screws to secure the base to the duct. Connect the low voltage wires to the leads on the H8908. Replace the H8908 case. IMPORTANT Use 18- to 22-gauge wire for proper wiring. 4X DRILL 7/64 IN. DIAMETER PERCER 4 X 7/64 PO. DUCT TEMPLATE GABARIT DE GAINE CAUTION Equipment Damage Hazard. Be careful when selecting control location and cutting hole in ductwork. Do not cut or drill into air conditioning or electrical accessories. Do not install control on supply (hot air) ductwork. To use template: 1. Remove backing and apply template to duct. 2. Cut along template dotted line and drill the mounting holes. MISE EN GARDE Risque d'endommager le matériel. Faire attention au moment de choisir l'emplacement du régulateur et de percer les trous dans la gaine. Ne pas couper ou percer les accessoires électriques ou de climatisation. Ne pas installer le régulateur sur la gaine d'alimentation (air chaud). Utilisation du gabarit: 1. Retirer l'endos du gabarit et placer le gabarit sur la gaine. 2. Couper le long de la ligne pointillée du gabarit et percer les trous de fixation. M13373 Fig. 4. Positioning return air duct template. 69-1341 2 H8908B HUMIDISTAT H8908C DEHUMIDISTAT WIRING H8908B WATER SOLENOID LEAD WIRE 2 CAUTION TRANSFORMER Personal Injury Hazard. Power supply can cause electrical shock and injury. Disconnect power supply before installation or servicing. L2 L1 1 (HOT) CURRENT LO SENSING RELAY C HI All wiring must comply with applicable local codes, ordinances and regulations. Make wiring connections according to humidifier (or dehumidifier/ventilator) instructions, if available; otherwise, see typical wiring diagrams in Fig. 5 through 12. HUMIDIFIER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24V WIRING. IMPORTANT Select models of fan centers include humidifer taps so the current sensing relay or sail switch is not needed. M13386 Fig. 7. Typical wiring diagram of current sensing relay with humidifier. SAIL SWITCH H8908B If not using a current sensing relay or sail switch, the humidifier must be energized during blower motor cycles for proper operation. 2 TRANSFORMER On multispeed blower applications, do not wire the high voltage side of the transformer to the same power source that services the furnace blower. Premature transformer burnout can occur. 1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24V WIRING. On HE360 fan powered humidifier models, only the two yellow wires are connected to the control. The remaining two red wires are only used with electronic humidity controls. FAN WIRING TERMINALS 1 1 FAN CONTROL 1 FURNACE FAN MOTOR HUMIDISTAT TERMINALS 1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24 VAC WIRING. M13368 NOTE: FOLLOW THE INSTALLATION INSTRUCTIONS INCLUDED WITH THE STEAM HUMIDIFIER TO WIRE THE SYSTEM FAN. M13387 Fig. 9. Typical wiring diagram for steam humidifiers. Fig. 5. Typical wiring diagram for system with fan interlock. H8908C CHRONOTHERM® IV THERMOSTAT B FAN CONTROL HUMIDIFIER 24V WIRING. HUMIDIFIER 1 POWER SUPPLY TO SYSTEM FAN 2 H8908B TRANSFORMER L1 (HOT) M13385 Fig. 8. Typical wiring diagram of sail switch with humidifier. H8908B L1 (HOT) POWER SUPPLY L2 HUMIDIFIER L1 (HOT) L2 2 O W Y R G H8908B L2 DPST SWITCHING RELAY 1 H L C 2-SPEED FAN MOTOR TRANSFORMER HEATING RELAY OR VALVE COIL COOLING CONTACTOR COIL HUMIDIFIER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24 VAC WIRING. 1 M13384 Fig. 6. Typical wiring diagram for system with 2-speed fan motor. PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. FAN RELAY COIL 1 M13366 Fig. 10. Typical parallel wiring of humidity controller with Chronotherm® IV Thermostat for dehumidification and mildew control. 3 69-1341 H8908B HUMIDISTAT H8908C DEHUMIDISTAT ADJUSTMENTS CHRONOTHERM® IV THERMOSTAT Humidity Control Adjustment B O W Y G R H8908C HEATING RELAY OR VALVE COIL COOLING CONTACTOR COIL To maintain optimum humidity control without causing condensation on cold surfaces such as windows, the homeowner must adjust the setpoint as the outdoor temperature changes. To reduce the relative humidity, reduce the setpoint approximately three percent relative humidity every 24 hours. To increase the relative humidity, increase the sepoint approximately three percent relative humidity every 24 hours. FAN RELAY COIL Setpoint Adjustment 1 1 PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED. M13367 Fig. 11. Typical series wiring of humidity controller with Chronotherm® IV Thermostat for dehumidification and mildew control. Set the humidity setpoint according to the prevailing outdoor temperature. See Table 1 for recommended settings. Table 1. Recommended Humidity Controller Settings. Outdoor Temperature H8908C VENTILATOR/DEHUMIDIFIER DEHUMIDISTAT TERMINALS M13383 Fig. 12. Typical wiring diagram for HR150, HR200, ER150 and ER200 Ventilator or HD220 Dehumidifier applications. °F °C Recommended Humidity Controller Setting -20 -29 15 -10 -23 20 0 -18 25 +10 -12 30 +20 -7 35 >+20 >-7 40 OPERATION AND CHECKOUT Place the system in operation and observe through at least one complete cycle to make certain that all components are functioning properly. Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524 69-1341 G.H. 10-99 Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 Printed in Taiwan R.O.C. www.honeywell.com
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : Yes Encryption : Standard V4.4 (128-bit) User Access : Print, Copy, Extract, Assemble, Print high-res XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Create Date : 1999:10:04 11:49:44Z Creator Tool : FrameMaker 5.5.6p145 Modify Date : 2007:05:07 15:49:09-05:00 Metadata Date : 2007:05:07 15:49:09-05:00 Format : application/pdf Description : Installation Instructions Creator : H&BC Technical Communications Title : 69-1341 - H8908B Humidistat H8908C Dehumidistat Producer : Acrobat Distiller 4.0 for Windows Document ID : uuid:3bd554b3-a3ee-461b-aeac-49fea77e74d1 Instance ID : uuid:745ad063-adbf-4c3a-bded-645b5dd7171a Page Count : 4 Subject : Installation Instructions Author : H&BC Technical CommunicationsEXIF Metadata provided by EXIF.tools