7800 SERIES
EC7810A, EC7820A Relay Modules
SPECIFICATION DATA

FEATURES
•

•
•
•
•
•
•
•
•

GENERAL
The Honeywell EC7810/EC7820A Relay Module is a
microprocessor-based integrated burner control for
automatically fired gas, oil or combination fuel single burner
atmospheric (EC7810A) or atmospheric with fan (EC7820A)
applications. The EC7810A/EC7820A system consists of the
relay module, wiring subbase, amplifier and purge card. The
optional keyboard display module (KDM) can be mounted on
the relay module or on the face of a panel door. The KDM can
also be mounted remotely from the panel if this is approved
for the application.
The EC7810/EC7820 is programmed to provide a level of
safety, functional capability and features beyond the capacity
of conventional controls.
The basic functions of the EC7810/EC7820A include
automatic burner sequencing, flame supervision, system
status indication, system or self-diagnostics and
troubleshooting.

® U.S. Registered Trademark
Copyright © 1998 Honeywell Inc. • All Rights Reserved

•
•
•

Safety features:
— Interlock check.
— Dynamic AMPLI-CHECK™
— Closed loop logic test.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Expanded safe-start check.
— Internal hardware status monitoring.
— Low Fire Start Switch test.
— Tamper resistant timing and logic.
Ignition attempts: 1 or 5. Selectable by model number.
Access for external electrical voltage checks.
Application flexibility.
Dependable, long-term operation provided by microcomputer
technology.
First-out annunciation and system diagnostics provided by a
2 row by 20 column vacuum fluorescent display (VFD)
located on the KDM (optional).
Five sequence information light emitting diodes (LED)with
symbols for Power, Pilot, Flame, Main and Alarm (see Fig. 1).
Interchangeable plug-in flame amplifiers.
Nonvolatile memory; EC7810/EC7820 retain history files and
sequencing status after loss of power.
Remote reset (subject to application approval; optional).
Remote mounting of KDM (subject to application approval).
Burner control data available on the optional KDM:
— Flame signal strength.
— Hold status.
— Lockout/alarm status.
— Sequence status.
— Sequence time.
— Total cycles of operation.
— Total hours of operation.
— Fault history providing the six most recent faults:
• Cycles of operation at the time of the fault.
• Fault message and code.
• Hours of operation at the time of the fault.
• Sequence status at the time of the fault.
• Sequence time at the time of the fault.
— Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time (FFRT).
• Manufacturing code.
• On/off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of relay module and
optional KDM.
• Status of configuration jumper.
• Status of Run/Test Switch.

66-2040

7800 SERIES EC7810A, EC7820A RELAY MODULES

BURNER CONTROL
1

127

127
1

133

REMOVE ONLY FOR TERMINAL TEST ACCESS.

M12821

Fig. 1 Mounting dimensions of relay module and wiring subbase in millimeters only.

SPECIFICATIONS
Table 1A. EC7810A Terminal Ratings.
Terminal No.

Abbreviation

Description

Ratings

G



Flame Sensor Ground a



Earth G



Earth Grounda



N



Line Voltage Common
(Neutral)



3

L1

Line Voltage Supply (L1)

220-240 Vac (+10%/-15%), 50/60 Hz (±10%). b

4

AL

Alarm (Normally Open)

220/230/240 Vac, 1A, 10A inrush for 5000 cycles.

6

RT

Limits and Burner Control

220/230/240 Vac, 5A (maximum).

7

LD2

Airflow Switch Input

220/230/240 Vac, 1 mA.

8

PV1

Pilot Valve 1 (interrupted)

220/230/240 Vac, 4A at PF = 0.5, 20A inrush.c

9

MV

Main Fuel Valve

220/230/240 Vac, 4A at PF = 0.5, 20A inrush.c

10

IGN

Ignition

220/230/240 Vac, 4A at PF = 0.2.c

Flame Signal

136 to 220 Vac, current limited.

F(11)



13

COM

Firing Rate Common

220/230/240 Vac, 4A at PF = 0.5.d

14

MOD

Firing Rate Modulate

220/230/240 Vac, 4A at PF = 0.5.d

16



Control Voltage

220-240 Vac (+10%/-15%).

17

ES2

Preignition Interlock Input

220/230/240 Vac, 1 mA.

18

ES1

Low Fire Switch Input

220/230/240 Vac, 1 mA.

20

LOS

Lockout Input

220/230/240 Vac, 1 mA.

21

PV2

Pilot Valve 2 (Intermittent)

220/230/240 Vac, 4A at P.F.= 0.5, 20A inrush. c

22

SHTR

Shutter

220-240 Vac, 0.25A.e

a See Table 2.
b 2000 VA maximum connected load to 7800 SERIES Relay Module Assembly.
c Total load current, excluding burner/boiler motor and firing rate outputs cannot exceed 5A, 25A inrush.
d Can also be 24 Vac, 3A at PF = 0.5.
e 220-240 Vac to 120 Vac, 10 VA (minimum) stepdown transformer (not provided) required to drive shutter.

66-2040

2

7800 SERIES EC7810A, EC7820A RELAY MODULES

Table 1B. EC7820A Terminal Ratings.
Terminal No.

Abbreviation

Description

Ratings

G



Flame Sensor Ground a



Earth G



Earth Grounda



N



Line Voltage Common (Neutral)



3

AL

Alarm (Normally Open)

220/230/240 Vac, 1A, 10A inrush for 5000 cycles.

4

FAN

Burner/Blower Motor

220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.

5

L1

Line Voltage Supply (L1)

220-240 Vac (+10%/-15%), 50/60 Hz (±10%).b

6

RT

Limits and Burner Control

220/230/240 Vac, 5A (maximum).

7

LD2

Airflow Switch Input

220/230/240 Vac, 1 mA.

8

PV1

Pilot Valve 1 (interrupted)

220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.c

9

MV

Main Fuel Valve

220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.c

10

IGN

Ignition

220/230/240 Vac, 4A at P.F. = 0.2.c

Flame Signal

135 to 220 Vac, current limited.

F(11)



13

COM

Firing Rate Common

220/230/240 Vac, 4A at P.F. = 0.5.d

14

MOD

Firing Rate Modulate

220/230/240 Vac, 4A at P.F. = 0.5.d

16



Control Voltage

220-240 Vac (+10%/-15%).

17

ES2

Preignition Interlock Input

220/230/240 Vac, 1 mA.

18

ES1

Low Fire Switch Input

220/230/240 Vac, 1 mA.

20

LOS

Lockout Input

220/230/240 Vac, 1 mA.

21

PV2

Pilot Valve 2 (Intermittent)

220/230/240 Vac, 4A at P.F.= 0.5, 20A inrush. c

22

SHTR

Shutter

220-240 Vac, 0.25A.e

a See Table 2.
b 2000 VA maximum connected load to 7800 SERIES Relay Module Assembly.
c Total load current, excluding burner/boiler motor and firing rate outputs cannot exceed 5A, 25A inrush.
d Can also be 24 Vac, 3A at PF = 0.5.
e 220-240 Vac to 120 Vac, 10 VA (minimum) stepdown transformer (not provided) required to drive shutter.

Table 2. Recommended grounding practices.
Ground type
Earth ground (subbase and relay module).

Recommended Practice
1.
2.
3.

Signal ground (KDM, Data ControlBus
Module™, Communications Interface
ControlBus™ Module).

Use to provide a connection between the subbase and the control panel of
the equipment. Earth ground must be capable of conducting enough current
to blow the 20A fuse (or breaker) in the event of an internal short circuit.
Use wide straps or brackets to provide minimum length, maximum surface
area ground conductors. If a leadwire must be used, use 14 AWG copper
wire.
Make sure that mechanically-tightened joints along the ground path are free
of nonconductive coatings and protected against corrosion on mating
surfaces.

Use the shield of the signal wire to ground the device to the signal ground
terminal 3(c) of each device. Connect the shield at both ends of the daisy chain
to earth ground.

3

66-2040

7800 SERIES EC7810A, EC7820A RELAY MODULES
Table 3. Sequence Timing for Normal Operation.

Device

Initiate

Standby

Purge or
Waiting Preignition

First
Safety
Time

Pilot
Stab.

Main
Trial
Time***

Main
Stab.

Run

Ignition
Attempts

EC7810A1027

2 sec

*

**

3 sec

5 or 10 sec

5 sec

5 or 8 sec

5 sec

*

1

EC7810A1035

2 sec

*

**

3 sec

5 or 10 sec

5 sec

5 or 8 sec

5 sec

*

5

EC7820A1026

2 sec

*

**

3 sec

5 or 10 sec

5 sec

5 or 8 sec

5 sec

*

1

EC7820A1034

2 sec

*

**

3 sec

5 or 10 sec

5 sec

5 or 8 sec

5 sec

*

5

* Standby and Run can be an infinite period.
** Waiting Time is determined by the ST7800A Purge Card selected.
*** Second Safety Time is Main Trial Time plus Flame Failure Response Time.

Electrical Ratings (See Tables 1A and 1B):
Voltage and Frequency: 220 to 240 Vac (+10%/-15%),
50/60 Hz (±10%).
Keyboard Display Module (Optional): 13 Vdc peak
fullwave rectified (+20%/-15%).
Power Dissipation:
Relay Module: 10W maximum.
KDM: 3W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing (Total Connected Load): 20A, type FRN or
equivalent.

Oil Approvals:
EC7810A1027: DIN-5F104/96.
EC7820A1026: DIN-5F105/96.
EN298: “Automatic gas burner systems for gas burners
and gas burning appliances with or without fans.”
Please note the following to comply with EN60730 for remote
mounting of the KDM and/or remote reset. It is necessary to
provide electrical separation using insulation at least
equivalent to double or reinforced insulation. Accomplish this
by either:
• Optically isolating the communication and/or remote
reset lines from the control cabinet or
• Providing physical separation from the communication
and/or remote reset lines using electrical conduit and a
remote display cover assembly (part no. 204718A) or
other suitable enclosure that meets IP40 class of
protection.

Environmental Ratings:
Ambient Temperatures:
Operating: -40°C to 60°C (-40°F to 140°F).
Storage: -40°C to 66°C. (-40°F to 150°F).
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
Dimensions:
See Fig. 1 and 2.

Mounting:
Q7800A Wiring Subbase for Panel Mount: To meet EN60730
requirements, mount the relay module in a secured panel
which meets IP40 class of protection.

Weight:
Relay Module: 0,730 kg unpacked.
KDM: 0,113 kg unpacked.

Required Components:
Plug-in Flame Signal Amplifier: See Table 2.
ST7800A Plug-in Purge Timer Cards: Selectable from two
seconds to 30 minutes.
Q7800A Wiring Subbase.

IMPORTANT
Flame Detection System available for use with
EC7810/EC7820. Select your plug-in Flame Signal
Amplifier and applicable Flame Detector from Table 4.

Accessories:
Keyboard Display Modules (KDM) (Optional):
S7800A1001 English language.
S7800A1035 French language.
S7800A1043 German language.
S7800A1050 Italian language.
S7800A1068 Spanish language.
S7800A1118 Katakana (Japanese) language.
S7800A1126 Portuguese language.
S7800B1009 Chinese language.

Approvals:
This product complies with the following European directives:
Gas Appliance Directive (90/269/EEG).
Low Voltage Directive (73/23/EEG).
EMC Directive (89/336/EEG).
GASTEC (CE-63AP3070/1).
Factory Mutual: J.I.0Y0A9.AF.

66-2040

4

7800 SERIES EC7810A, EC7820A RELAY MODULES
Miscellaneous:
S7820A1007 Remote Reset Module.
203541 Data ControlBus Connector, 5-wire.
203765 Remote Display Mounting Bracket.
221729 Relay Module Dust Cover.
204718A Keyboard Display Module Cover, NEMA 4, clear.
204718B Keyboard Display Module Cover, NEMA 1, clear.
204718C Keyboard Display Module Cover, NEMA 4, clear
with reset button.
205321B Flush Display Mounting Kit.
221818A Extension Cable, display, (1524 mm).
221818C Extension Cable, display, (3048 mm).
123514A Rectification Flame Simulator.
203659 Ultraviolet Flame Simulator.
203968A Remote Display Power Supply, 13 Vdc, plug-in.

Communications:
Q7700B1004 Network Interface Unit with universal 100 to
250 Vac, 50/60 Hz external power supply, external
modem required.
QS7800A1001 ControlBus Module, standard.
QS7800B1000 ControlBus Module, multidrop.
QS7800C1009 ControlBus Module, data acquisition
modules.
QS7800D1008 ControlBus Module, Armstrong.
QS7800E1007 ControlBus Module, Pulsafeeder.
QS7850A1006 ControlBus Module, General Purpose
Interface.
ZM7850A1001 Combustion System Manager™ Software.
ZM7850B1000 SYSNet™ Facilities Integration Software.
S7810A1009 Data ControlBus™ Module (if no KDM is
used).
S7810B1007 Data ControlBus™ Module, Multi-Drop
Switch Module.

Table 4. Flame Detection System
Plug-in Flame Signal Amplifiers

Type

Color

Self-Checking

Rectification

Green

No

R7847A

No

Ultraviolet

Purple

Blue

Model

Applicable Flame Detectors
Flame Failure
Response
Time

Fuel

Type

Models

1 or 2 sec
maximum.

Gas

Rectifying
Flame Rod
Holdersa

C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.

R7847A

1 or 2 sec
maximum.

Oil

Rectifying
Photocell

C7003, C7010, C7013,
C7014.b

Dynamic
Ampli-Check™

R7847B

1 or 2 sec
maximum.

Gas

Rectifying
Flame Rod
Holdersa

C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.

Dynamic
Ampli-Check™

R7847B

1 or 2 sec
maximum.

Oil

Rectifying
Photocelld

C7003, C7010, C7013,
C7014.b

No c

R7849A

1 or 2 sec
maximum.

Gas, oil

Ultraviolet
(Minipeeper)

C7027,C7035, C7044d.

Dynamic
Ampli-Check™

R7849B

1 or 2 sec
maximum.

Gas, oil

Ultraviolet
(Minipeeper)

C7027,C7035, C7044d.

Dynamic
Self-Check

R7861A c,f

1 or 2 sec
maximum.

Gas, oil

Ultraviolet

C7061.g

Dynamic
Self-Check

R7886A c,f

2 sec
maximum.

Gas, oil,
coal

Ultraviolet
(Adjustable
Sensitivity)

C7076.g

a Order flame rod separately; see holder instructions.
b Use only Honeywell Photocell part number 38316.
c Dynamic Self-Check ultraviolet amplifiers should be used only on burners that cycle on-off at least once every 24 hours.

Appliances with burners that remain on continuously for 24 hours or longer should use C7061A Flame Detector with R7861A
Amplifier.
d C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once every 24 hours.
Appliances with burners that remain on continuously for 24 hours or longer should use C7061A Flame Detector with R7861A
Amplifier as ultraviolet flame detection system.
e Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the boiler if the
amplifier fails.
f Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during
burner operation and shuts down the burner if the detection system fails.
g A 220/240 Vac to 120 Vac 10 VA step-down transformer (not provided) must be used to drive the shutter.

5

66-2040

7800 SERIES EC7810A, EC7820A RELAY MODULES

66-2040

6

7800 SERIES EC7810A, EC7820A RELAY MODULES

7

66-2040

7800 SERIES EC7810A, EC7820A RELAY MODULES

Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524

Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7

Honeywell Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325

Honeywell Europe S.A.
3 Avenue du Bourget
1140 Brussels
Belgium

66-2040 G.R. 3-98

Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper 8
fibers.

Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong

www.honeywell.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Create Date                     : 1998:03:09 14:39:04
Producer                        : Acrobat Distiller 3.0 for Power Macintosh
Subject                         : Specification Data
Creator                         : Adobe PageMaker 6.5
Title                           : 66-2040 - 7800 Series EC7810A, EC7820A Relay Modules
Author                          : H&BC Technical Communications
Modify Date                     : 1999:04:20 08:21:07
Page Count                      : 8
EXIF Metadata provided by EXIF.tools

Navigation menu