YP7999A1000 ControLinks™ Fuel
Air Ratio Control Panel
INSTALLATION INSTRUCTIONS

FEATURES
• Pre-wired and ready to install
• Includes the R7999A control, wiring subbase and
S7999D1048 touchscreen display
• Commission, monitor and control ControLinks through
the touchscreen interface
• Fuel selector switch
• Alarm light
• Reset button
• Unit shutdown / Emergency stop button
• Auto/manual switch
• Manual operation potentiometer
• S7999D touchscreen display is Modbus ready

APPLICATION

SPECIFICATIONS

The Honeywell YP7999A1000 ControLinks Fuel Air Ratio
Control Panel is a packaged, pre-wired panel that includes the
R7999A ControLinks controller for linkageless fuel/air ratio
control. The included S7999D color touchscreen interface
allows commissioning of the ControLinks system as well as
monitoring and control, all with user-friendly menus. On board
selector switches, buttons and alarm lights are included for
customer convenience. The ML7999A2001 universal direct
coupled actuators are purchased separately.

Electrical Ratings
100 – 120 Vac, 50/60 Hz, 3 Amps
For individual ratings, see component literature for details.

This document provides installation instructions and operation
information. Other applicable publications are:
— 65-0238, R7999 ControLinks Controller
— 65-0240, Q7999A ControLinks Universal Wiring Subbase
— 65-0239, ML7999A Universal Parallel-Positioning
Actuator
— 65-0321, S7999D1048 System Display

Environmental Ratings
Enclosure: NEMA 12.
For individual ratings, see component literature for details.
Humidity
Install the panel where the relative humidity never reaches the
saturation point. The relay module inside the panel is
designed to operate in a maximum 85 percent relative
humidity continuous, non-condensing, moisture environment.
Vibration
Do not install the panel where it could be subjected to vibration in excess of 0.5G continuous maximum vibration.
General
Overall panel size: 24 in. high x 24 in. wide x 8 in. deep
(excluding door and door mounted components)
Panel weight: approx. 64 pounds
Mounting holes are 0.44 in. typical diameter, 18 in. on center.

66-2060-01

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

Electrical Connections

Approvals
Components are individually approved by the nationally recognized agencies. Please see component literature for
details. The panel has UL 508A flame control panel
approval. Panel is assembled and wired to the UL Standards.

1.
2.
3.

INSTALLATION

4.

When Installing This Product…
1.
2.
3.
4.
5.
6.
7.

IMPORTANT
Run line voltage and low voltage wiring in separate
conduit to avoid signal interference.

Read these instructions and the appropriate product literature carefully. Failure to follow them could damage
the product or cause a hazardous condition.
Refer to the installation manuals and wiring diagrams
provided with this panel for the embedded products.
Check the ratings given in the instructions and on the
product to make sure that the product is suitable for your
application.
Installer must be a trained, experienced combustion service technician.
Disconnect the power supply before beginning installation to prevent electrical shock and equipment damage.
More than one disconnect may be involved.
All wiring must comply with the National Electric Code
(NEC) and any applicable local electrical codes, ordinances and regulations.
After installation is complete, check out product operation as provided in the appropriate product installation
instructions.

Carefully check field wiring and terminal designations in this document and the associated wiring diagram. They are different from those of the individual
components.

Panel Inspection
After mounting and wiring, but before powering the panel,
inspect all internal panel wire connections. Each panel is fully
tested at the factory; however, wires may loosen during transit.
Verify that all internal wire connections are secure from the
Q7999 subbase to the components mounted on the door and
the S7999D touchscreen interface.

Final Wiring Check and Static
Checkout

WARNING

All wiring shall be in accordance with the National Electric
Codes (NEC) and local electrical codes.

Fire or Explosion Hazard. Can cause severe injury,
death or property damage.
To prevent possible hazardous burner operation, verify
safety requirements each time a controller is installed
on a burner.

1.
2.
3.

WIRING

4.

Check the power supply circuit. The voltage and frequency must match the specification listed.
Check wiring terminations and routing to ensure proper
connections.
Follow any system checkout recommendations for individual components as found in the component literature.
Restore power to the panel.

CAUTION
Test each limit and interlock to ensure system

WARNING

Electrical Shock Hazard. Can cause serious injury,
death or equipment damage.
Disconnect the power supply before beginning wiring
to prevent electrical shock, equipment and control
damage. More than one disconnect may be involved.

operates correctly as defined in the 7800 Series
“Checkout and Test” document (Form #65-0229).

WARNING

Ground Connection

Explosion and Electrical Shock Hazard.
Can cause serious injury, death or equipment
damage.

Earth ground is required for proper operation of the
ControLinks system. The earth ground must be capable of
conducting enough current to blow the fuse or breaker in the
event of an internal short. Ensure the panel is bonded to a
substantial earth ground. Make sure that mechanically
tightened joints along the ground path are free of
nonconductive coatings and protected against corrosion on
mating surfaces.

66-2060—01

Refer to the appropriate product data sheet for details.
Wire size and length will vary, depending on the component. Refer to the component literature for specific wire
lengths, sizes and type recommendations.
Wire according to specifications, following all local ordinances and requirements.
Field knockouts are required for the wiring. When drilling holes, take care to protect the electronics from metal
pieces and debris.

1.
2.
3.

2

Close all manual fuel shutoff valves before starting
these tests.
Use extreme care while testing the system. Line voltage
is present on most terminal connections when power is
on.
Replace all limits and interlocks that are not operating
properly. Do not bypass limit and interlocks.

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

TROUBLESHOOTING
System Diagnostics
The S7999D touchscreen interface indicates the current fault and keeps a fault history log. The R7999 ControLinks control and
the ML7999A Universal Parallel-Positioning Actuator also have LED fault blink codes. Refer to the appropriate product instruction
sheet for further troubleshooting information and diagnostic codes.

FIELD WIRING
Table 1. Field Wiring and Terminal Designation1.
Terminal #

To Connecting
Device

12

L1 Panel power

Description

GND

120Vac Power Supply, 3A Max.
L1 power to circuit breaker.
L2 Panel neutral Provide disconnect means and overload protection as required.
Panel ground

43

L1

L1 customer convenience wire point – provided for 4 actuators – 120Vac, 50/60Hz

L2

L2 customer convenience wire point – provided for 4 actuators

GND

Panel ground

GND customer convenience wire point – provided for 4 actuators

9

HFP

High Fire Proven output from ControLinks controller to burner control

10

LFP

Low Fire Proven output from ControLinks controller to burner control

11

HF

High Fire drive command input from burner controller

12

MV

Main Valve command input from burner controller

13

LF

Low Fire drive command input from burner controller

14

LCI

Limit Control Input from burner limit string, including on/off control, LWCO, high-limit, etc…

2

23
3

15

LCO

Limit Control Output from ControLinks controller to burner control demand/interlock inputs

2003,4

DR1

Air Actuator DR1 command input

2013,4

DR2

Air Actuator DR2 command input

2023,4

CW

Air Actuator potentiometer CW output

2033,4

S

Air Actuator potentiometer S output

CCW

Air Actuator potentiometer CCW output

GND

Ground

Air Actuator ground

2053,4

DR1

Fuel 1 Actuator DR1 command input

2063,4

DR2

Fuel 1 Actuator DR2 command input

2073,4

CW

Fuel 1 Actuator potentiometer CW output

2083,4

S

Fuel 1 Actuator potentiometer S output

2093,4

CCW

Fuel 1 Actuator potentiometer CCW output

GND3,4

Ground

Fuel 1 Actuator ground

2103,4

DR1

Fuel 2 Actuator DR1 command input

3,4

DR2

Fuel 2 Actuator DR2 command input

3,4

212

CW

Fuel 2 Actuator potentiometer CW output

2133,4

S

Fuel 2 Actuator potentiometer S output

2143,4

CCW

Fuel 2 Actuator potentiometer CCW output

GND3,4

Ground

Fuel 2 Actuator ground

3,4

204

3,4

211

3

66-2060—01

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

Table 1. Field Wiring and Terminal Designation1. (Continued)
Terminal #

To Connecting
Device

2153,4

DR1

FGR/4th Channel Actuator DR1 command input

2163,4

DR2

FGR/4th Channel Actuator DR2 command input

2173,4

CW

FGR/4th Channel Actuator potentiometer CW output

2183,4

S

FGR/4th Channel Actuator potentiometer S output

2193,4

CCW

FGR/4th Channel Actuator potentiometer CCW output

GND3,4

Ground

FGR/4th Channel Actuator ground

Description

223

XmA+

Auxiliary 4-20mA+ input from Stack/Water temperature sensor (used for low fire hold)

220

XmA-

Auxiliary 4-20mA- input from Stack/Water temperature sensor (used for low fire hold)

224

CmA+

4-20mA+ input from Firing Rate control

225

CmA-

4-20mA- input from Firing Rate control

2315

COM 2 A

S7999D COM 2 Modbus A / Data + terminal

2325

COM 2 B

S7999D COM 2 Modbus B / Data - terminal

COM 2 GND

S7999D COM 2 Modbus C / Ground terminal

5

228

1 Carefully

check field wiring and terminal designations in this document and the associated wiring diagram. They are different
from those of the individual components.
2 The circuit protection incorporated into this control panel is designed to serve as supplemental protection only. It is the responsibility of the end user to provide appropriate protection on the service to this control panel. Refer to the National Electric Code
and UL standard 1077 for more information on this subject. Use 16 AWG MTW wire.
3 Low voltage wire to the firing rate actuators must be run in separate conduit. Line voltage wiring to actuators may be obtained
from terminals 4, 2 and GND or provided by customer. Run line voltage wires in separate conduit. Refer to the ML7999A product sheet for details.
4 Connect the shield ground of the ML7999A actuator(s) to the earth ground strip provided in the Q7999 universal subbase, on
the low voltage side. Connect the shield at the controller end only. Refer to the ML7999A product sheet for details.
5 COM 2 on the S7999D is wired to field terminals for customer use. Customer may wire an existing Modbus-capable RM78xxL
burner control and/or Modbus-enabled UDC2500/3200/3500 controls in a daisy-chain fashion to the customer terminals for display on the S7999D. Refer to the S7999D, S7800A or S7810M and UDC control product manuals for further information on wiring and S7999D display set-up.
6 Installation, operation and maintenance shall conform with National Fire Protection Association standards, national and local
codes and authorities having jurisdiction.
7 For detailed device wiring information, refer to the R7999, Q7999A, ML7999A and S7999D1048 product sheets.

66-2060—01

4

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

24 (610)

SS104

P9100

FUEL

PUSH TO STOP
TWIST TO START

24
(610)

LT104

CONTROLINKS
ALARM

SS103

PB114

CONTROL

CONTROLINKS
RESET

MANUAL
OPERATOR

MANUAL

AUTO

5K OHMS

WARNING

ADVERTISEMENT

M34890

Fig. 1. Panel front dimensions in in. (mm).
Table 2. Wire Code.
Function

Color

AWG

120 VAC (HOT)

RED

16 (MTW)

120 VAC (NEUTRAL)

WHITE

16 (MTW)

GROUND

GREEN

16 (MTW)

DRY CONTACTS

YELLOW

16 (MTW)

VDC

BLUE

16 (MTW)

24 VAC

BROWN

16 (MTW)

TYPE K THERMOCOUPLE

YELLOW/RED

20 (POLYVINYL)

FSG RESET/CONTROLINKS RESET/POTENTIOMETER

BELDEN 8760

18 AWG TWISTED PAIR

ACTUATOR INTERFACE

BELDEN 9535

24 AWG, 5 CONDUCTOR

DISPLAY TO TERMINAL STRIP

BELDEN 9535

24 AWG, 5 CONDUCTOR

DISPLAY COM1 & COM2 (FROM TERM STRIP TO DEVICES)

BELDEN 8770

18 AWG, 3 CONDUCTOR

TEMP CTRL MODBUS

BELDEN 8770

18 AWG, 3 CONDUCTOR

5

66-2060—01

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

M34891

Fig. 2. Wiring diagram (part 1).

66-2060—01

6

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

(L)

(N)

M34892

Fig. 3. Wiring diagram (part 2).

Wiring Diagram Key

Wiring Notes
1.

Indicates terminals and wiring in control panel
(main terminal block).
Indicates external wiring.
Indicates terminals in valves.

2.

Indicates component terminals.

7

The circuit protection incorporated into this control
panel is designed to serve as supplemental protection
only. It is the responsibility of the end user to provide
appropriate protection on the service to this control
panel. Refer to the National Electric Code and UL Standard 1077 for more information.
Wire to the firing rate actuator must be run in separate
conduit.

66-2060—01

YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL

3.
4.

Ground shield to subbase earth ground screw on low
voltage side of subbase.
Installation, operation, and maintenance shall conform
with National Fire Protection Association standards,
national and local codes, and authorities having jurisdiction.

21 (533)

FU100

3A
FU121
.5A

1

SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

21
(533)

FUEL/AIR
CONTROL

M34893

Fig. 4. Equipment mounting panel dimensions in in. (mm).

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com

® U.S. Registered Trademark
© 2013 Honeywell International Inc.
66-2060—01 M.S. 06-13
Printed in United States



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Assemble, Print high-res
Author                          : Honeywell ECC Technical Communications
Create Date                     : 1999:07:07 12:30:47Z
Modify Date                     : 2013:06:03 09:13:07-05:00
Subject                         : Installation instructions
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Format                          : application/pdf
Title                           : 66-2060—01 - YP7999A1000 ControLinks™ Fuel Air Ratio Control Panel
Creator                         : Honeywell ECC Technical Communications
Description                     : Installation instructions
Creator Tool                    : FrameMaker 9.0
Metadata Date                   : 2013:06:03 09:13:07-05:00
Producer                        : Acrobat Distiller 9.3.0 (Windows)
Document ID                     : uuid:e864ae17-5275-4e2c-bb05-86eb0455cde1
Instance ID                     : uuid:1cb69ad6-698e-43ed-81aa-0f1c73394fca
Page Mode                       : UseOutlines
Page Count                      : 8
EXIF Metadata provided by EXIF.tools

Navigation menu