NetAXS-123
Access Control Unit
Installation Guide

May 2010

© 2010 Honeywell. All rights reserved.

800-05779, Revision A

Copyright© 2010 Honeywell. All rights reserved.

All product and brand names are the service marks, trademarks, registered trademarks,
or registered service marks of their respective owners. Printed in the United States of
America. Honeywell reserves the right to change any information in this document at
any time without prior notice.
Ordering Information

Please contact your local Honeywell representative or visit us on the web at
www.honeywellaccess.com for information about ordering.
Feedback

Honeywell appreciates your comments about this manual. Please visit us on the web at
www.honeywellaccess.com to post your comments.

CONTENTS

Installing the NetAXS-123 Panels
1.0 Introduction .......................................................................................................................................... 2
1.1 Access Control Overview .................................................................................................. 2
1.2 NetAXS-123 Overview...................................................................................................... 2
2.0 Panel Components and Descriptions................................................................................................ 3
2.1 Supervised Input Wiring .................................................................................................... 5
2.2 NetAXS-123 Access Control Unit..................................................................................... 7
NetAXS-123 Add-On Board ........................................................................................... 7
Supported Readers ........................................................................................................... 8
Real-Time Clock Protection ............................................................................................ 9
2.3 Power Supply ..................................................................................................................... 9
2.4 Battery.............................................................................................................................. 10
2.5 Suppressors ...................................................................................................................... 10
3.0 Installation.......................................................................................................................................... 11
3.1 Installing the Compact Enclosure Panel .......................................................................... 11
Installing on a Wall ....................................................................................................... 11
Installing over a Gang Box ............................................................................................ 15
Installing on a Flat Surface ............................................................................................ 16
3.2 Installing the Standard Enclosure Panel .......................................................................... 17
3.3 Installing the Add-On Board............................................................................................ 26
3.4 Wiring the Readers .......................................................................................................... 29
3.5 Wiring Door Strikes......................................................................................................... 33
3.6 Setting DIP Switches and Jumpers .................................................................................. 35
Controller Board DIP Switch and Jumper Settings ....................................................... 35
Add-On Board DIP Switch and Jumper Settings .......................................................... 40
3.7 Communications .............................................................................................................. 42
USB Communications ................................................................................................... 42
RS-485 Communications .............................................................................................. 44
Ethernet TCP/IP Communications ................................................................................ 47
4.0 System Configuration ....................................................................................................................... 48
4.1 Ethernet Connection ........................................................................................................ 48
4.2 USB Connection .............................................................................................................. 49

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

iii

4.3 RS-485 Connection via PCI-3 ......................................................................................... 50
4.4 RS-485 Connection via NetAXS-123.............................................................................. 51
4.5 RS-485 Connections with Multidrop Panels at Both Ends of the Cable ......................... 52
4.6 M-56K Dial-up Modem, RS-485 Connection via Hub (PCI-3) ...................................... 54
4.7 Fiber Converter to RS-485 Connection via PCI-3........................................................... 55
4.8 Fiber Converter to RS-485 Connection via NetAXS-123 ............................................... 56
4.9 N-485-PCI-3/NetAXS-123 Access Controller Panel Connection Detail ........................ 57
4.10 NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail ...................... 58
4.11 Mixed Loops .................................................................................................................. 59
5.0 Hardware Specifications .................................................................................................................. 60
5.1 Relay Contacts ................................................................................................................. 60
5.2 Reader Interface ............................................................................................................... 60
5.3 Maximum Output Loading .............................................................................................. 60
5.4 PoE Power Limitations .................................................................................................... 60
5.5 Mechanical....................................................................................................................... 61
5.6 Environment..................................................................................................................... 62
5.7 Cable ................................................................................................................................ 62
6.0 Basic Standalone Operation ............................................................................................................ 63
6.1 Card Read / Door Lock Operation................................................................................... 63
6.2 Door Egress / Door Lock / Door Status Operation .......................................................... 63
7.0 Maintenance ....................................................................................................................................... 64
8.0 Troubleshooting ................................................................................................................................ 65
9.0 Technical Support ............................................................................................................................. 66
9.1 Normal Support Hours..................................................................................................... 66
9.2 Web .................................................................................................................................. 66

iv

www.honeywell.com

LIST OF FIGURES

Figure 1: NetAXS-123 Compact Enclosure Wiring and Components ....................................... 3
Figure 2: NetAXS-123 Standard Enclosure Panel Wiring and Components ............................. 4
Figure 3: NetAXS-123 Add-On Board Wiring and Components .............................................. 5
Figure 4: Typical Supervised Input Wiring Diagram ................................................................. 6
Figure 5: Wiring Readers to the Controller Board ................................................................... 29
Figure 6: Controller Board DIP Switch and Jumper Location ................................................. 35
Figure 7: NetAXS-123 Controller Board Jumpers ................................................................... 39
Figure 8: Add-On Board DIP Switch and Jumper Location .................................................... 40
Figure 9: RS-485 Configuration via N-485-PCI-3 ................................................................... 45
Figure 10: RS-485 Configuration via NetAXS-123 Gateway .................................................. 46
Figure 11: Ethernet TCP/IP Configuration .............................................................................. 47
Figure 12: Ethernet Connection ............................................................................................... 48
Figure 13: NetAXS-123 USB Connection ............................................................................... 49
Figure 14: RS-485 Connection via PCI-3 ................................................................................ 50
Figure 15: RS-485 Connection via NetAXS-123 ..................................................................... 51
Figure 16: RS-485 Connection via NetAXS-123 with Multidrop Panels at Both Ends .......... 52
Figure 17: RS-485 Connection via PCI-3 with Multidrop Panels at Both Ends ...................... 53
Figure 18: M-56K Dial-up Modem, RS-485 Connection via Hub ........................................... 54
Figure 19: Fiber Converter to RS-485 Connection via PCI-3 .................................................. 55
Figure 20: Fiber Converter to RS-485 Connection via NetAXS-123 ...................................... 56
Figure 21: N-485-PCI-3/NetAXS-123 Access Controller Panel Connection Detail ............... 57
Figure 22: NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail ............... 58

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

v

vi

www.honeywell.com

LIST OF TABLES

Table 1: Supervised Input Terminal Blocks ................................................................................ 5
Table 2: Supervised Tamper Terminal Blocks ............................................................................ 6
Table 3: NetAXS-123 Input/Output Options .............................................................................. 7
Table 4: Readers Supported by NetAXS-123 ............................................................................. 8
Table 5: Factory Default Configuration Settings for Door 1 .................................................... 30
Table 6: Factory Default Configuration Settings for Door 2 .................................................... 31
Table 7: Factory Default Configuration Settings for Door 3 .................................................... 32
Table 8: NetAXS-123 SW1 DIP Switch Settings ..................................................................... 36
Table 9: NetAXS-123 SW2 DIP Switch Settings ..................................................................... 38
Table 10: Reader Wiring ........................................................................................................... 62
Table 11 Troubleshooting Problems and Solutions .................................................................. 65

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

vii

viii

www.honeywell.com

Installing the NetAXS-123 Panels

In this chapter ...
Introduction

2

Panel Components and Descriptions

3

Installation

11

System Configuration

48

Hardware Specifications

60

Maintenance

64

Troubleshooting

65

Technical Support

66

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

1

Installing the NetAXS-123 Panels
Introduction

1.0 Introduction
This document describes how to install the NetAXS-123 Standard Enclosure access control unit and
the NetAXS-123 Compact Enclosure access control unit.

1.1 Access Control Overview
An access control system protects and preserves an enterprise’s resources by providing authentication,
authorization, and administration services. Authentication is a process that verifies a user’s identity. If
the user is verified, the system then either grants or denies access to specific areas and resources.
Administration includes the creation and modification of user accounts and access privileges.
An access control system consists of hardware and software, usually configured in a network
environment over a standard network protocol. Access control units, readers, door strikes, and video
and other devices, for example, are configured to control and monitor the access to a company site.

1.2 NetAXS-123 Overview
A NetAXS-123 access control is a full-featured one-door web-based access control system that
supports up to three doors when supplemented with an add-on input/output board. The NetAXS-123
panel includes a built-in web server, built-in Ethernet and USB support, and Power over Ethernet
(PoE) capability. You can manage the access control system using either a web browser or WIN-PAK.
For supported configurations, see “System Configuration“ on page 48 to view illustrations of the
supported NetAXS-123 system configurations.

2

www.honeywell.com

Installing the NetAXS-123 Panels
Panel Components and Descriptions

2.0 Panel Components and Descriptions
Note: This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.

The NetAXS-123 panel consists of a web-browser-enabled controller, a one- or two-door add-on board
that supports additional inputs and outputs, a power-over-Ethernet (PoE) power supply (NetAXS-123
Compact only), and a battery (NetAXS-123 Standard only).
The following figures show the NetAXS-123 panel wiring and components.
Figure 1:

NetAXS-123 Compact Enclosure Wiring and Components

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

3

Installing the NetAXS-123 Panels
Panel Components and Descriptions

Figure 2:

NetAXS-123 Standard Enclosure Panel Wiring and Components

Maintain at least a .25-inch distance between the non-power limited wiring (115 VAC/60 Hz
input wiring, power line filter wiring, and battery backup/charger wiring) and all other wiring, which is
power-limited Class 2 wiring.

Note:

4

www.honeywell.com

Installing the NetAXS-123 Panels
Panel Components and Descriptions

Figure 3:

NetAXS-123 Add-On Board Wiring and Components

2.1 Supervised Input Wiring
The supervised inputs are located on the following terminal blocks:
Table 1: Supervised Input Terminal Blocks
Board Configuration

Terminal Block

1-Door (Controller Board)

C-TB2
C-TB10

1-Door (Add-On Board)

IO-TB2

2-Door (Add-On Board)

IO-TB2 (as 1-door Add-On
Board)
IO-TB6

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

5

Installing the NetAXS-123 Panels
Panel Components and Descriptions

Tampers can also be supervised. They are located on the following terminal blocks:
Table 2: Supervised Tamper Terminal Blocks
Board Configuration

Terminal Block

1-Door (Controller Board)

C-TB3/TMPR A
C-TB4/TMPR B

1-Door (Add-On Board)

IO-TB3/TMPR A
IO-TB4/TMPR B

2-Door (Add-On Board)

IO-TB3/TMPR A
IO-TB4/TMPR B
IO-TB7/TMPR A
IO-TB8/TMPR B

Door Status (STS) and Request to Exit (REX) for all three doors may be configured for Normally
Open or Normally Closed contacts as supervised or non-supervised. Inputs 5 (generic) and 6 (power)
are on C-TB10. All seven inputs on the Controller Board and four inputs on the Add-On Board have
default functions, but they can be configured for general purpose inputs.
The following figure shows the typical wiring for a supervised input.
Figure 4:

Typical Supervised Input Wiring Diagram

The figure above shows standard 2,200 ohm resistors. The NetAXS-123 panel accepts 1,000, 2,200,
4,700, or 10,000 ohm values. Note that both resistors must have the same value.
In addition, the Reader tampers can be supervised and capable of being used as additional inputs if the
default functionality is not needed.
The wire used for the inputs should be shielded and cannot exceed 30 ohms over the entire length of
the cable. Remember that the distance from the panel to the door must be doubled to determine the
total resistance.
Caution: The

cable shield should be grounded only at the panel earth ground. Grounding at both ends
can cause ground loops which can be disruptive.

6

www.honeywell.com

Installing the NetAXS-123 Panels
Panel Components and Descriptions

Caution: The

system has not been verified for compliance with UL1076 Burglar Alarm units and

systems.

2.2 NetAXS-123 Access Control Unit
The NetAXS-123 panel is a one-door access control unit that you can supplement with an add-on
board that supports second and third doors. The following table shows the NetAXS-123 input/output
options:
Table 3: NetAXS-123 Input/Output Options
Board

Readers

Inputs/Outputs

Controller

1 door/2 readers

1 lock output
1 aux output
1 status input
1 Request to Exit
2 reader tamper/AUX
inputs

Add-On (1 Door)

1 door/2 readers

1 lock output
1 aux output
1 status input
1 Request to Exit
2 reader tamper/AUX
inputs

Add-On (2 Door)

2 doors/4 readers

2 lock outputs
2 aux outputs
2 status inputs
2 Request to Exits
4 readers tamper/AUX
inputs

You can use the NetAXS-123 panel as a standalone panel with independent card and transaction
storage or, with a host software upgrade, as a fully monitored online access control device.
Panel inputs are capable of four state supervision: Normal, Alarm, Short and Cut. One input is used for
request to exit on each door and one input is used for door status on each door. Supervised inputs for
External Power Fail and Reader Tampers are supplied as well, and they can be used as additional
inputs when not required for their default purpose.

2.2.1 NetAXS-123 Add-On Board
The NetAXS-123 Add-On Board enables you to expand from one door to either two or three doors.
The board easily connects to the NetAXS-123 controller board (see the NetAXS-123 Add-On Board
Installation Guide (800-05787).
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

7

Installing the NetAXS-123 Panels
Panel Components and Descriptions

2.2.2 Supported Readers
Supported readers include the following:
Table 4: Readers Supported by NetAXS-123
Series

Reader Model

Honeywell Part
Number

OmniProx

OP-10

OP10GENE
OP10HONE

OP-30

OP30GENE
OP30HONE

OP-40

OP40GENE
OP40HONE

OP-45

OP45GENE
OP45HONE

ProxPoint Plus

6005B

MiniProx

HU/5365EGP00

Thinline II

HU/5395CB100
HU/5395CG100
HU/5395CK100

ProxPro

HU/5355AGN00

ProxPro II

HU/5455BGN00

ProxPro K

HU/5355AGK00

EntryProx

4045CGNU0

MaxiProx

HU/5375AGN00

OM40

OM40BHONB
OM40GHONB

OM41

OM41BHONB
OM41GHONB

OM55

OM55BHONB
OM55GHONB

OM70

OM70BHONB
OM70GHONB

HID

Omni-Class

8

www.honeywell.com

Installing the NetAXS-123 Panels
Panel Components and Descriptions

Series

Reader Model

Honeywell Part
Number

OmniAssure

OT30

OT30HONA

OT31

OT31HONA

OT35

OT35HONA

OT36

OT36HONA

OT70

OT70HONA

OT75

OT75HONA

DR 4200K

92042000000

DR 4220

92042200000

NexWatch

Note:

For NetAXS-123 reader specifications, see Hardware Specifications, page 60.

2.2.3 Real-Time Clock Protection
The panel RTC is backed up using a super capacitor. The super capacitor will power the real-time
clock for 24 hours in the absence of primary power or backup battery.

2.3 Power Supply
The NetAXS-123 Compact Enclosure is powered by Power Over Ethernet (PoE) injector. This PoE
injector can supply a total system current of 800mA to 900mA @ 12VDC. However the NetAXS-123
controller board consumes 400mA of current, and it therefore leaves 450mA of total current for the
12VDC external power. See Hardware Specifications, page 60, for further details on current limits
using PoE.
The Standard Enclosure uses a 12VDC 4A power supply with an international input of 100VAC to
240VAC. The supply also charges and monitors the condition of the battery. Wire the unswitched
electrical power to the supply per the National Electrical Code as well as any local electrical codes,
including the safety ground wire.
An input power indicator is supplied, and it is illuminated when input voltage is present. If the
indicator is off, the input voltage is off, or too low to operate the system.
Caution: Disconnect

the battery and AC power before servicing the fuse. For continued protection
against the risk of electric shock and fire hazard, replace the input fuse with a GMA type fuse with the
rating of 1A, 250V. The fuse is located in the lower-left corner in the cabinet, as shown below.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

9

Installing the NetAXS-123 Panels
Panel Components and Descriptions

2.4 Battery
For the NetAXS-123 Standard Enclosure panel, one CASIL CA1270, 12 VDC, 7A-hour sealed
lead-acid battery (Honeywell order number 3-000066). The battery provides standby backup power,
depending upon system configuration and activity. When AC is lost, the power supply automatically
switches to the backup battery for continuous 12VDC power. Replace the battery every 2 to 2.5 years,
or more often if the system has a high rate of backup use.

2.5 Suppressors
Two suppressors (HAS number S-4) are required for each door lock. One suppressor is installed on the
panel control board, and the second must be installed at the door lock.

10

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

3.0 Installation
3.1 Installing the Compact Enclosure Panel
Perform the following steps to install the NetAXS-123 Compact panel:
Warning: Use a static strap whenever touching the panel to ensure protection from Electrostatic

Discharge (ESD).

3.1.1 Installing on a Wall
1. Review the panel layout, cable runs, and power needs.
2. Mount the enclosure’s back at the proper location on the wall:
a. Drill the screw holes in the wall, using the panel’s back as a template, and then pull the
power and all I/O wires to the enclosure and through the knockout holes, and properly
mark each wire for its use.

b. Screw the back of the panel to the wall, using either drywall screws or threaded wall
anchors.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

11

Installing the NetAXS-123 Panels
Installation

3. Mount the board onto the back of the panel.

4. Choose the tamper type (standard or off-the-wall tamper) and wire the tamper.
• Wiring a standard tamper:

12

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

• Wiring an off-the-wall tamper:

5. Set the tamper, using pliers at the four locations indicated below.

Warning: Do

not apply power at this time.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

13

Installing the NetAXS-123 Panels
Installation

6. Connect the Ethernet cable and the Tamper wire, as shown below.

7. Set DIP switch settings for the panel address, communication termination and biasing. See DIP
Switch Settings, page 36.
8. Check all wiring at this time.
Caution: Improper wiring can cause damage to the NetAXS-123 at power up and result in a loss
of warranty.

9. Apply power to the panel.
10.Check for the Run LED for a successful power-up. If the LED is blinking green, the panel is
powered up successfully.
11.Close the cover.

14

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

3.1.2 Installing over a Gang Box
1. Review the panel layout, cable runs, and power needs.
2. Mount the back of the panel on the gang box.

3. Pull the wires from the gang box through the knockout holes in the base of the enclosure.

4. Perform steps 3 through 10 in the preceding section ( Installing on a Wall, page 11) to complete
the installation of the panel over a gang box.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

15

Installing the NetAXS-123 Panels
Installation

3.1.3 Installing on a Flat Surface
1. Review the panel layout, cable runs, and power needs.
2. Mount the back of the enclosure on the surface, either with drywall screes or threaded wall
anchors.

3. Break off the appropriate plastic wiring tabs, using pliers.

4. Perform steps 3 through 10 in Installing on a Wall, page 11 to complete the installation of the
panel over a horizontal surface.

16

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

3.2 Installing the Standard Enclosure Panel
Perform the following steps to install the NetAXS-123 Standard Enclosure panel:
Warning: Use a static strap whenever touching the panel to ensure protection from Electrostatic

Discharge (ESD).
1. (Optional) Remove the green ground wire and the door.

2. Partially install the four power supply screws.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

17

Installing the NetAXS-123 Panels
Installation

3. Install the power supply.
a. Fit the power supply screws through the key holes in the left side of the cabinet, and seat
the power supply by pulling down.

b. From the outside of the cabinet, tighten the screws to lock the power supply in place.

18

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

c. Inside the cabinet, screw in the two self-tapping screws (supplied in the product box) at
the top and bottom of the power supply.
Warning: These

screws must be installed to ground the power supply to the enclosure.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

19

Installing the NetAXS-123 Panels
Installation

d. Plug the connector that is attached to the blue and brown wires into the power supply.

20

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

4. Select one of the following three possible entry points for the power cable:
Warning: Do not apply power at this time. Be sure the power cable is disconnected from the
external power source before following this step.

• Through the bottom conduit
knockout, which directly connects
AC power to the terminal block.

• Through the side conduit knockout,
which also directly connects AC
power to the terminal block.

• Through the optional AC input
receptacle. Note: the brown and blue
wires must be twisted together from
the point of entry at the AC input
receptacle to the Terminal Block.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

21

Installing the NetAXS-123 Panels
Installation

5. Use a pencil to mark the location of the holes on the wall.

6. Screw the NetAXS-123 Controller Board with the four captive screws

22

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

7. Hold the Add-On Board over the Controller Board and seat the board-to-board connector into
the Controller Board. Secure the Add-On Board onto the Controller Board with the four captive
finger screws. For more explanation of the Add-On Board installation, see the next section,
Installing the Add-On Board.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

23

Installing the NetAXS-123 Panels
Installation

8. Connect the wiring harness, as shown.
Warning: DO

NOT CONNECT the AC power or the battery wires yet!

9. Power up the NetAXS-123 Controller Board and configure the system. Refer to the
NetAXS-123 Startup Guide (800-05780) for instructions.

24

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

10.Connect the battery.

11.Attach the door to the cabinet.
12.Re-connect the green ground wire to the cabinet door.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

25

Installing the NetAXS-123 Panels
Installation

3.3 Installing the Add-On Board
Warning: To

prevent damage to the NXC1 Controller Board, remove power from the
NetAXS-123 panel before installing or removing a NetAXS-123 Add-On Board.
1. On the NetAXS-123 Controller Board, locate the four posts called out in the image shown
below:

NetAXS-123 Controller Board

26

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

2. Pick up the Add-On Board and notice the four posts on the bottom.

3. Seat the Add-On Board posts into the four posts on the NetAXS-123 Controller Board, aligning
the terminal-block edge of the Add-On Board with the terminal-block edge of the Controller
Board.

4. With your fingers, tighten the posts’screws.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

27

Installing the NetAXS-123 Panels
Installation

5. Set the relay jumpers.
a. Use the following figure to locate the jumpers.

b. See Add-On Board DIP Switch and Jumper Settings, page 40, to set the power source
(12VDC power or external power) and the relay contact position (Normally Open or
Normally Closed).
6. Wire the door strikes. See Wiring Door Strikes, page 33, for instructions.

28

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

3.4 Wiring the Readers
Each reader port supports one or two readers (entry and exit readers) with Wiegand output format. The
maximum power draw is 500 mA for readers and AUX Power combined.
To fully utilize each reader port, a shielded 7-conductor cable (18-22 AWG) is required. If you don’t
need the HOLD LINE feature, you can use the standard 6-conductor cable (HAS part number
NC186-BL).
Note:

If you are using additional HOLD lines for readers, you will need an 8-conductor cable.

The cable shield should be grounded at the panel only. Grounding at both ends can cause ground loops
which can be disruptive. The maximum recommended length of wiring is 500 feet per reader.
Figure 5 shows a one-door panel, with the readers wired to terminal blocks C-TB3 and C-TB4 on the
Controller Board, and to terminal blocks IO-TB3, IO-TB4, IO-TB7, and IO-TB8 on the Add-On
Board. The wires are color-coded to their labeled terminals. If this were a two-door panel, the two
additional readers would be wired to terminal blocks C-TB1 and C-TB2 on the Controller Board, and
to terminal blocks IO-TB1 and IO-TB2 on the Add-On Board.
Figure 5:

Wiring Readers to the Controller Board

Reader A and Reader B share LED, DO, D1, GND, and +12V connections. Each reader has its
own Tamper and Hold.

Note:

The following three tables list the factory controller board I/O default settings for door-1, door-2, and
door-3 configurations. These are the mappings for readers, inputs, and outputs. Reader A and Reader B
share many common connections.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

29

Installing the NetAXS-123 Panels
Installation

Table 5 shows the input/output factory default wiring for a one-door configuration on the Controller
Board.
Table 5: Factory Default Configuration Settings for Door 1
Type

Purpose

Web
Default
Name

Terminal
Block
Label

Reader A

Reader B

Input

Egress/
Request to
Exit (REX)

Input 1:
Door 1
Egress

C-TB2

Input 1a

Input 1a

Door Status

Input 2:
Door 1
Status

C-TB2

Input 2a

Input 2a

Reader
Tamper

Input 3:
Door
TMPR-A

C-TB3
TMPR A

Reader
Tamper

Input 4:
Door
TMPR-B

C-TB4
TMPR B

General

Input 5:
GENERAL
PURPOSE

C-TB10
IN5

Input 5

Power/
General

Input 6:
POWER

C-TB10
IN6 (PWR
FAIL)

Input 6

Panel
Tamper

PANEL
TAMPER

ALTER_T
MPR

Input 20

Lock Relay

Output #1

C-TB1
LOCK

Output 1a

Output 1a

Reader LED

Output #2

C-TB3
LED

Output 2a

Output 2a

AUX Relay

Output #3

C-TB1
AUX

Reader
Buzzer

Future
Feature

C-TB3
BZR

Output

a Readers

30

A and B share the same connection.

www.honeywell.com

Other

IN1 (REX)

IN2 (STS)
Input 3

Input 4

Output 3

Output 4a

Output 4a

Installing the NetAXS-123 Panels
Installation

Notes:

• The Controller Board includes Inputs 7 and 8 but they are reserved for system use.
• The Controller Board also includes Output 5, a general-purpose output, and Output 6, which is
reserved by the system to control the boards’ RUN LEDs and thus is unavailable for user
control.
• Reader LED, while it is an output, should never be used to control anything other than its
associated reader’s LED.
Table 6 lists the factory I/O board default settings for a door 2. These mappings should be used for the
readers, inputs, and outputs when either a 1- or 2-door Add-On Board is attached to the board-to-board
connector on the Controller Board.
Table 6: Factory Default Configuration Settings for Door 2
Type

Purpose

Web
Default
Name

Terminal
Block
Label

Reader A

Reader B

Input

Egress/
Request to
Exit (REX)

Input 9:
Door 2
Egress

IO-TB2

Input 9a

Input 9a

Door Status

Input 10:
Door 2
Status

IO-TB2

Input 10a

Input 10a

Reader
Tamper

Input 11:
Door
TMPR-A

IO-TB3
TMPR A

Reader
Tamper

Input 12:
Door
TMPR-B

IO-TB4
TMPR B

Lock Relay

Output #7

IO-TB1
LOCK

Output 7a

Output 7a

Reader LED

Output #8

IO-TB3
LED

Output 8a

Output 8a

AUX Relay

Output #9

IO-TB1
AUX

Reader
Buzzer

Future
Feature

IO-TB3
BZR

Output

a Readers

Other

IN9 (REX)

IN10 (STS)
Input 11

Input 12

Output 9

Output 10a

Output 10a

A and B share the same connection.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

31

Installing the NetAXS-123 Panels
Installation

Table 7 lists the factory Add-On Board default settings for a door 3. These mappings should be used
for the readers, inputs, and outputs when either a 1- or 2-door Add-On Board is attached to the
board-to-board connector on the controller board.
Table 7: Factory Default Configuration Settings for Door 3
Type

Purpose

Web
Default
Name

Terminal
Block
Label

Reader A

Reader B

Input

Egress/
Request to
Exit (REX)

Input 9:
Door 2
Egress

IO-TB2

Input 9a

Input 9a

Door Status

Input 10:
Door 2
Status

IO-TB2

Input 10a

Input 10a

Reader
Tamper

Input 11:
Door
TMPR-A

IO-TB3
TMPR A

Reader
Tamper

Input 12:
Door
TMPR-B

IO-TB4
TMPR B

Lock Relay

Output #11

IO-TB5
LOCK

Output 11a

Output 11a

Reader LED

Output #12

IO-TB7
LED

Output 12a

Output 12a

AUX Relay

Output #13

IO-TB5
AUX

Reader
Buzzer

Future
Feature

IO-TB7
BZR

Output

a

Other

IN9 (REX)

IN10 (STS)
Input 11

Input 12

Output 13

Output 14a

Output 14a

Readers A and B share the same connection.

Notes:

• Reader LEDs, while they are outputs, should never be used to control anything other than their
associated reader LEDs.
• Incorrect wiring of the reader to the panel can cause the panel to abnormally stop operating or
to operate erratically.

32

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

• NetAXS-123 supports a variety of Wiegand reader models. Some readers have only one brown
wire for LED control; others have two possible LED control inputs--orange for the green LED
and brown for the red LED. RED is the normal state of the Reader LED operation. The LED
turns GREEN for two seconds after a valid card read. Although readers operate similarly, LED
control can vary, depending on the manufacturer. Therefore, your readers may require some
testing to identify the right LED wire when the reader uses Dual LED wires. If you are using
Dual Line LED control, it’s recommended that you try the ORANGE-colored wire for a
GREEN LED.
• The Reader Buzzer feature is not currently supported on the NetAXS-123 panels.

3.5 Wiring Door Strikes
Follow these steps to wire the door strikes to the Controller and Add-On Boards:
1. Use the following figure to locate the door strike terminals on the board.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

33

Installing the NetAXS-123 Panels
Installation

2. Use the following figure to wire the door strike/mag lock according to the power supply used.
Be sure to use the S4 suppressor kits as shown below.

On-Board
+12VDC
Configuration

NO/NC
Dry C
Return

NO/NC
Dry C
Return
S4

External
Power Supply
Configuration

OR

S4

S4

S4

Locking
Device

Locking
Device

+ DC

DC

Notes:
• As shown in the illustration above, the Dry C terminal for the On-Board option should
not be connected. Similarly on the External Power Supply side, the Return terminal
should not be connected.
• The On-Board option is used when jumpers are set for 12VDC. The External Power
Supply options is used when the jumpers are set to External Power (see Jumper Settings,
page 39 for details).

34

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

3.6 Setting DIP Switches and Jumpers
3.6.1 Controller Board DIP Switch and Jumper Settings
Figure 6 locates the NetAXS-123 DIP switch panel and the output 1 and output 3 relay jumpers.
Figure 6:

Controller Board DIP Switch and Jumper Location

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

35

Installing the NetAXS-123 Panels
Installation

DIP Switch Settings
Use the following DIP switch configurations to set the panel address.
Table 8: NetAXS-123 SW1 DIP Switch Settings

36

S1

S2

S3

S4

S5

ON

OFF

OFF

OFF

OFF

Address 1
(default)

OFF

ON

OFF

OFF

OFF

Address 2

ON

ON

OFF

OFF

OFF

Address 3

OFF

OFF

ON

OFF

OFF

Address 4

ON

OFF

ON

OFF

OFF

Address 5

OFF

ON

ON

OFF

OFF

Address 6

ON

ON

ON

OFF

OFF

Address 7

OFF

OFF

OFF

ON

OFF

Address 8

ON

OFF

OFF

ON

OFF

Address 9

OFF

ON

OFF

ON

OFF

Address 10

ON

ON

OFF

ON

OFF

Address 11

OFF

OFF

ON

ON

OFF

Address 12

ON

OFF

ON

ON

OFF

Address 13

OFF

ON

ON

ON

OFF

Address 14

ON

ON

ON

ON

OFF

Address 15

OFF

OFF

OFF

OFF

ON

Address 16

ON

OFF

OFF

OFF

ON

Address 17

OFF

ON

OFF

OFF

ON

Address 18

ON

ON

OFF

OFF

ON

Address 19

OFF

OFF

ON

OFF

ON

Address 20

ON

OFF

ON

OFF

ON

Address 21

www.honeywell.com

S6

S7a

S8b

S9b

S10

Selection

Installing the NetAXS-123 Panels
Installation

Table 8: NetAXS-123 SW1 DIP Switch Settings (continued)
S1

S2

S3

S4

S5

S6

OFF

ON

ON

OFF

ON

Address 22

ON

ON

ON

OFF

ON

Address 23

OFF

OFF

OFF

ON

ON

Address 24

ON

OFF

OFF

ON

ON

Address 25

OFF

ON

OFF

ON

ON

Address 26

ON

ON

OFF

ON

ON

Address 27

OFF

OFF

ON

ON

ON

Address 28

ON

OFF

ON

ON

ON

Address 29

OFF

ON

ON

ON

ON

Address 30

ON

ON

ON

ON

ON

Address 31

S7a

S8b

S9b

S10

Selection

OFF

Downstream
Panel

ON

Gateway Panel
(Default)
OFF

Uses the User
Provided
Ethernet IP
address (Default)

ON

Uses the Default
Ethernet IP
Address
(192.168.1.150)
OFF

OFF

RS-485_1
termination
(EOL)
DISABLED
(Default)

ON

ON

RS-485_1
termination
(EOL)
ENABLED
(Default)

OFF Future Use
(Default)
ON

Future Use

a. DIP Switch 7 does NOT require a panel reboot to take effect. This does not affect
the USB IP address.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

37

Installing the NetAXS-123 Panels
Installation

b. Both DIP Switch 8 and DIP Switch 9 need to be either ON or OFF to be properly
configured.

Table 9: NetAXS-123 SW2 DIP Switch Settings
S1a

S2a

Selection

OFF

OFF

RS-485_2 termination (EOL) DISABLED

ON

ON

RS-485_2 termination (EOL) ENABLED (FUTURE) (Default)

a. Both DIP Switch 1 and DIP Switch 2 need to be either ON or OFF to be properly
configured.
Note: When you use the DIP switches to reset a panel to the original factory default

values, the Event History is lost and any customized databases are removed, so the
panel is reset with the original factory default database. This does not affect the
Ethernet IP address.
You can also use this ASCII command:
_I=pn_R
This command resets the panel to the original factory default values, but it only
removes the customized databases and restores the original factory default
database. The Event History is retained.
To reset the panel to the factory default values:

1. Make a note of the existing settings on SW1 DIP switches.
2. While the panel is powered up, turn all DIP switches to the OFF position.
3. Power down, then power the panel back up.
4. Wait for the panel to come up. The RUN LED should flicker fast.
5. Set the DIP switches back to their original positions.
6. Power down, then power the panel back up.
7. After the the panel comes up, the RUN LED should flash normal.
The panel is now reset to the original factory default values.
Note:

38

Address 0 is not a valid setting.

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

Jumper Settings
The NetAXS-123 Controller Board provides two jumper sets, one each for output relay 1 and output
relay 3. Each relay has two 3-pin jumpers associated with it. One jumper selects either external power
(EXT) or self-whetted (on-board, +12V) power to be applied to the relay contact load. The other
jumper is used to select Normally Open (NO) or Normally Closed (NC) relay contacts. There is a total
of four 3-pin jumpers (two per relay) on the Controller Board.
Figure 7:

NetAXS-123 Controller Board Jumpers

Each relay is associated with two jumpers. As shown below, a relay’s left jumper configures the relay’s
load source (12VDC or External), and the right relay jumper configures the relay contact type
(Normally Closed or Normally Open).
• Setting the jumpers to configure the power source:
12VDC

External

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

39

Installing the NetAXS-123 Panels
Installation

Note: The power source selected by the jumper settings shown above configure the power source for
the relay. It does not configure the power source for the panel.
• Setting the jumpers to configure the relay contact type:
Normally Open

Normally Closed

3.6.2 Add-On Board DIP Switch and Jumper Settings
Figure 8 locates the NetAXS-123 Add-On Board DIP switch panel and the output 1 and output 3 relay
jumpers.
Figure 8:

Add-On Board DIP Switch and Jumper Location

The figure above shows a one-door Add-On Board configuration. If you are instead using a
two-door Add-On Board, you will see an additional two relays (and their corresponding jumper sets) to
the right of the relays shown. The additional relays and jumpers will configure output 11 and output 13,
and all of the jumpers are configured in the same manner.

Note:

The NetAXS-123 Controller Board provides two jumper sets, one each for output relay 1 and output
relay 3. Each relay has two 3-pin jumpers associated with it. One jumper selects either self-whetted
(on-board, +12V) or external power (EXT) to be applied to the relay contact load. The other jumper is

40

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

used to select Normally Open (NO) or Normally Closed (NC) relay contacts. There is a total of four
3-pin jumpers (two per relay) on the controller board.
• Setting the jumpers to configure the power source:
12V

External

• Setting the jumpers to configure the relay position:
Normally Open

Normally Closed

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

41

Installing the NetAXS-123 Panels
Installation

3.7 Communications
3.7.1 USB Communications
The NetAXS-123 Controller Board provides a version 2.0 USB port that connects to the web browser
or to a WIN-PAK host. The following figure identifies the location of the port on the board.
Note:

USB communication requires the USB A to MicroUSB B cable that is supplied with the panel.

You will need to install a USB driver to support the connection. Follow these steps:
Warning: Do

NOT connect the USB cable to the panel until AFTER the drivers are installed.

1. Insert the NetAXS-123 Product CD into your Windows-based computer. The NetAXS-123
product menu opens in the web browser.
Note: If the product menu does not open automatically in your browser, right click on the Start button
and select Explore. In the folder tree, find and click the CD drive that is reading the NetAXS-123

Product CD.

42

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

2. Click Install USB Drivers on the product menu to start the USB driver installation wizard.

3. Click Next to display the Ready to Install the Program screen.
If confirmation dialog boxes pop up before or during the installation, click the
appropriate boxes to allow or approve the installation.

Note:

4. Click Install to initiate the installation.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

43

Installing the NetAXS-123 Panels
Installation

5. When the installation is complete, the closing screen appears:

6. Click Finish.
7. Connect the computer to the NetAXS-123 controller with a USB-A to Micro USB-B cable.
8. Turn on the power to the NetAXS-123 controller.
For login information, go to https://192.168.2.150.

3.7.2 RS-485 Communications
If a NetAXS-123 panel is to be placed onto a prexisting RS-485 dropline loop (NetAXS) it must be
setup as the Gateway panel. The interface allows the wiring of a Multidrop communication network of
up to 4,000 feet (1200 m) in length. Only one host converter device per dropline is supported.
NetAXS-123 must be the Gateway panel on an existing NetAXS loop. The NetAXS-123 panel
cannot be placed as a Downstream panel when the Gateway is a NetAXS system.

Note:

DIP switch position 6 on the NetAXS-123 panel selects whether the panel is a Gateway or
Downstream panel. The switch in the OFF position configures the panel as a Downstream panel; ON
configures a Gateway. The panel must be power cycled for a new switch setting to be recognized. DIP
switch positions 1-5 are used to select the panel’s address on the network. Refer to Table 8 for DIP
switch setting information.

44

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

DIP switch SW1 positions 8 and 9 are provided for supplying biasing and end-of-line termination for
the RS-485 network. The board ships with the switches active. For a Multidrop RS-485 Line, you must
turn ON both switch positions 8 and 9 of SW1. (terminated and biased) at the two end-point panels. At
all other panels, set DIP switches 8 and 9 in the OFF position. Both switches on a given panel must be
set the same. Note that biasing and termination on both ends are present. Use the SW1 positions 8 and
9 ON on both ends of the RS-485 network.
Note:

For more information on end of line (EOL) termination, contact Honeywell technical support.

Note: If an RS-485 network has a NetAXS-123 Gateway panel, no N1000-II, N1000-III, N1000-IV, or
NS2 are allowed on the same network. If they are added to a network with a NetAXS-123 Gateway
panel, they will not be able to communicate with the host computer. In order to use these panels, a
N-485-PCI-3 is required, as shown in Figure 9.

Figure 9:

RS-485 Configuration via N-485-PCI-3

This configuration supports a combined total of 31 N1000 III, N1000 IV, NetAXS, NetAXS-123, and
NS2 panels per Multidrop line.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

45

Installing the NetAXS-123 Panels
Installation

Figure 10:

RS-485 Configuration via NetAXS-123 Gateway
Reader 1

Ethernet

NetAXS-123
Gateway

..
.

Terminal

RS-485 Multidrop Line

..
.

..
.

..
.

Reader 4

Reader 3

Reader 4

This configuration supports a total of 31 NetAXS and NetAXS-123 panels per Multidrop line.

46

www.honeywell.com

Installing the NetAXS-123 Panels
Installation

3.7.3 Ethernet TCP/IP Communications
Figure 11:

Ethernet TCP/IP Configuration

Ethernet

Network Interface Card
inside PC

Up to 255 TCP/IP Connections
per System

Terminal

Reader 1
Ethernet 10/100

NetAXS-123
Gateway

RS-485 Multidrop Line

Reader 1

NetAXS
Panel

..
.
Reader 4

Reader 3

Reader 1

NetAXS-123
Panel

..
.

..
.

Reader 1

NetAXS
Panel

Reader 3

..
.
Reader 4

This configuration supports a total of 31 NetAXS and NetAXS-123 panels per Multidrop line.
Each NetAXS-123 panel has a port for an Ethernet TCP/IP interface. The Ethernet TCP/IP interface
provides 10/100 MB Ethernet support for each panel.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

47

Installing the NetAXS-123 Panels
System Configuration

4.0 System Configuration
This section provides wiring diagrams for each of the NetAXS-123 system configurations.

4.1 Ethernet Connection
Figure 12:

Ethernet Connection

NIC

100BaseT (CAT 5) 328 Ft. Max.

NetAXS-123
Panel

EG

EG
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: ON: 485 Termination ON

EG

EG
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: ON: 485 Termination ON

You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an
Earth Ground.

Note:

48

www.honeywell.com

Installing the NetAXS-123 Panels
System Configuration

4.2 USB Connection
Figure 13:
Note:

NetAXS-123 USB Connection

The USB connection is intended to be used for system maintenance and troubleshooting.

You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an
Earth Ground.

Note:

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

49

Installing the NetAXS-123 Panels
System Configuration

4.3 RS-485 Connection via PCI-3
This connection supports thirty-one NetAXS-123 panels for each drop line. Note that PCI-3 units can
also be wired in interior, as well as in endpoint, positions. See Figure 16 on page 52 and Figure 17 on
page 53.
Figure 14:

RS-485 Connection via PCI-3

RS-232 (50 Ft. Max.)

RS-485 (4000 Ft. Max.)

Terminal

S2 - ON
S3 - ON

See RS-485
Cable note

NetAXS-123
Panel

EG
Only Earth Ground (EG) one side of cable

EG

EG

If you use the PCI-3 connection, you cannot access the web, since the PCI-3 does not support the
NetAXS-123 web interface.

Note:

50

www.honeywell.com

Installing the NetAXS-123 Panels
System Configuration

4.4 RS-485 Connection via NetAXS-123
This connection supports a total of 31 NetAXS-123 panels (including the Gateway) for each drop line.
Figure 15:

RS-485 Connection via NetAXS-123

You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an
Earth Ground.

Note:

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

51

Installing the NetAXS-123 Panels
System Configuration

4.5 RS-485 Connections with Multidrop Panels at Both Ends of the Cable
You can connect Multidrop panels at both ends of an RS-485 cable via either a NetAXS-123 panel or a
PCI-3 device.
Figure 16:

RS-485 Connection via NetAXS-123 with Multidrop Panels at Both Ends

You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an
Earth Ground.

Note:

52

www.honeywell.com

Installing the NetAXS-123 Panels
System Configuration

Figure 17:

RS-485 Connection via PCI-3 with Multidrop Panels at Both Ends

COM Port

RS-232 (50 Ft. Max.)

See RS-485
Cable Note

RS-485 (4,000 Ft.)

PCI3

DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: ON: 485
Termination ON

DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: OFF: 485
Termination OFF

DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: ON: 485
Termination ON

DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: OFF: 485
Termination OFF

EG

Only Earth Ground (EG)
one side of cable

Only Earth Ground (EG)
one side of cable
EG

EG

EG

EG

You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an
Earth Ground.

Note:

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

53

Installing the NetAXS-123 Panels
System Configuration

4.6 M-56K Dial-up Modem, RS-485 Connection via Hub (PCI-3)
This configuration supports 31 NetAXS-123 panels for each drop line.
Figure 18:

M-56K Dial-up Modem, RS-485 Connection via Hub
M-56K
FAX/MODEM
COM Port

Straight Through Cable

Female 9 Pin

Terminal

Male 25 Pin

(RX) 2

Analog
Phone
Line

Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)

3 (RX)

(TX) 3
(Comm) 5

2 (TX)
7 (Comm)

Dedicated
analog
phone

M-56K
FAX/MODEM

DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: ON: 485
Termination ON

DIP Switch Settings
S1-S5 Panel Address
S6: OFF
S7: OFF
S8-S9: OFF: 485
Termination OFF

NetAXS-123
Panel

EG

Only Earth Ground (EG)
one side of cable

EG

It is recommended to Earth Ground (EG)
each NetAXS enclosure Individually

RS-485 Cable

DB 9 / DB 25 Connectors
13

Female

25

1
14

5
9

1
6

Male

13
25

1
14

5
9

1
6

NetAXS-123 Panels
C-TB9 - A
C-TB9 - B
C-TB9 - COM
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)

You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an
Earth Ground.

Note:

54

www.honeywell.com

Installing the NetAXS-123 Panels
System Configuration

4.7 Fiber Converter to RS-485 Connection via PCI-3
This connection supports 31 NetAXS-123 panels for each drop line.
Figure 19:

Fiber Converter to RS-485 Connection via PCI-3

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

55

Installing the NetAXS-123 Panels
System Configuration

4.8 Fiber Converter to RS-485 Connection via NetAXS-123
This connection supports 31 NetAXS-123 panels for each drop line.
Figure 20: Fiber Converter to RS-485 Connection via NetAXS-123

You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an
Earth Ground.

Note:

56

www.honeywell.com

Installing the NetAXS-123 Panels
System Configuration

4.9 N-485-PCI-3/NetAXS-123 Access Controller Panel Connection Detail
Figure 21: N-485-PCI-3/NetAXS-123 Access Controller Panel Connection Detail

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

57

Installing the NetAXS-123 Panels
System Configuration

4.10 NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail
Figure 22:

NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail

DIP Switch Settings
S1-S5: Panel Address
S6: ON: GATEWAY
S7: OFF
S8-S9 ON: 485 Termination ON

Ground Shield

NetAXS-123
C-TB9
DC Out
A
B
COM
+24VDC in

485 +
485 485 Com

NetAXS-123
C-TB9
485 +
485 485 Com

DIP Switch Settings
S1-S5: Panel Address
S6: ON: GATEWAY
S7: OFF
S8-S9 ON: 485 Termination ON

DC Out
A
B
COM
+24VDC in

DO NOT CONNECT or
GROUND SHIELD

NetAXS-123
C-TB9
485 +
485 485 Com

DIP Switch Settings
S1-S5: Panel Address
S6: OFF
S7: OFF
S8-S9 OFF: 485 Termination OFF

Ground only one
side of cable shield
Shield

485 Common
485 485 +
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)

58

www.honeywell.com

X

DC Out
A
B
COM
+24VDC in

Installing the NetAXS-123 Panels
System Configuration

4.11 Mixed Loops
This mixed-loop configuration supports a combined total of 31 N1000 III, N1000 IV, NetAXS,
NetAXS-123, and NS2 panels per Multidrop line.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

59

Installing the NetAXS-123 Panels
Hardware Specifications

5.0 Hardware Specifications
The specifications in this section apply to both the Standard Enclosure and Compact Enclosure panels.

5.1 Relay Contacts
Maximum of six Form-C SPDT relays, 3A (at dry contact) or 0.5A (at self-whetted) @ 30VDC (PTC
limited in the self-whetted mode). The Form-C SPDT relays are configured as Normally Open or
Normally Closed outputs only. Normally Open and Normally Closed contacts cannot be used
simultaneously.

5.2 Reader Interface
•
•
•
•

Reader Power: 12VDC nominal with 500mA maximum for each reader port.
Reader LED Output: Open collector driver capable of sinking up to 8mA.
Reader Tamper: Supervised or non-supervised input.
Reader Data Input: TTL compatible inputs.

5.3 Maximum Output Loading
Use the following guidelines unless you are using Power Over Ethernet (PoE):
• Maximum current per reader port for any of the three reader outputs is 500mA.
• Maximum current for any of the six relay outputs on the Songchuan 892N-1CH-1F-V is 3A at
dry contact, or 0.5A at self-whetted.
• Maximum battery charge current for the battery wired in series is 250mA.
• External power on C-TB9 is limited to 1.5A @ 12VDC.

5.4 PoE Power Limitations
If you are using the NetAXS-123 Standard Enclosure and powering the panel with PoE (Power over
Ethernet), you must comply with these specifications for proper operation:
• A NetAXS-123 panel powered by PoE is 802.3af compliant, providing a maximum of 15.4W
of input power to the panel. This input power is split between on-board power consumption and
external load consumption. A maximum current capacity of 450 mA @ 12VDC is available for
all external devices combined.
Notes:

• Two readers per door can still be supported as long as the total current is within the
external load capacity stated above.
• You can either find the devices’ power consumption amounts by referring to the
products’ documentation or by using a current meter.

60

www.honeywell.com

Installing the NetAXS-123 Panels
Hardware Specifications

Example:
Device Element

Current

Door strike or magnetic
lock current

250 mA

Reader A maximum
current

50 mA

Reader B maximum
current

50 mA

Buzzer or sounder current

20 mA

Door position switch

20 mA

Request to exit switch

30 mA

Total current for this
example

420 mA

If the total current consumption of your external devices exceeds the 450mA maximum current
maximum, then use one of the following system configurations:
• Power the panel with an external 12VDC power supply.
• Power some or all of the external devices with an external power supply to lower the
total external current powered by the NetAXS-123 panel below 450mA.
• The maximum power available in the 802.3af standard is 15.4W. This limit is generally at
48VDC, and it is measured at the output of the power injector or PoE switch. Line losses cause
a decrease in the power available at the panel when you use longer Ethernet cable lengths. You
can minimize these line losses by using either of the following methods:
• Connecting the NetAXS-123 panel to the power injector or PoE switch with the shortest
possible Ethernet cable length.
• Using a high-power 802.3at power injector or PoE switch with a voltage of 56VDC. This
reduces line losses and thus increases available power at the NetAXS-123 panel.
Note: The NetAXS-123 panel will not benefit from the increased power capabilities of a
high-power 802.3at power injector. Its use only reduces line losses over the Ethernet
cable.

5.5 Mechanical
• Standard Enclosure dimensions: Height = 14 inches (355.6 mm), Width = 12 inches (304.8
mm), and Depth = 5 inches (127 mm).
• Compact Enclosure dimensions: Height = 7.5 inches (190.5 mm), Width = 7.5 inches (190.5
mm), and Depth = 2.25 inches (57.15 mm).

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

61

Installing the NetAXS-123 Panels
Hardware Specifications

5.6 Environment
• Temperature: 0C to 49C operating, -55C to +85C storage.
• Humidity: 5% to 85% RHNC.

5.7 Cable
Use industry-standard cables that meet the following specifications:
Table 10: Reader Wiring
Cable Specifications

62

Description

AWG

Maximum Distance:
Feet (Meters)

Readers

6 Conductor, Shielded

18

500 (153)

Alarm Input

Twisted Pair, Shielded

18

2,000 (610)

Relay Outputs

Twisted Pair, Shielded

18

2,000 (610)

www.honeywell.com

Installing the NetAXS-123 Panels
Basic Standalone Operation

6.0 Basic Standalone Operation
6.1 Card Read / Door Lock Operation
1. Present a card to a reader.
2. The reader sends the card number to a reader input on the panel.
3. The panel searches its database and:
• If it is a valid card, then energize the door relay associated with the particular reader
input. The card is valid when it is in the card database on the panel and the current time
and date conforms to the time zone associated with the card.
• If it is not a valid card, the door relay remains locked.

6.2 Door Egress / Door Lock / Door Status Operation
1. Activate the door egress input.
2. The panel energizes the door relay associated with the particular door egress input for a default
time of 10 seconds.
3. If the door status goes from close to open to close again during the 10 second door open period,
the door relay will be immediately de-energized.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

63

Installing the NetAXS-123 Panels
Maintenance

7.0 Maintenance
Perform the following maintenance on the NetAXS-123 enclosure:
• Change the backup battery every two to two-and-a-half years.
• Oil the lock once per year.
• Use the following procedure to change the 1A, 250V, Bussan type GMA fuse in the fuse
terminal block Power Supply module.
Warning: Be

sure to disconnect the AC power before replacing the terminal block fuse.

Warning: To

reduce the risk of fire, replace the fuse only with a 1A, 250V, Bussan type GMA

fuse.
1. Disconnect the AC power.
2. Replace the fuse with a new 1A, 250V, Bussan type GMA fuse.
3. Re-connect the AC power.
Note: The

power supply contains no serviceable parts. There is no replaceable fuse inside the
power supply.
• Use the following procedure to change the 1A, 250V, Bussan type GMA fuse in the power inlet
terminal block.
Warning: Be sure to disconnect the AC power before removing the fuse holder from the power
inlet terminal block.
Warning: To

reduce the risk of fire, replace the fuse only with a 1A, 250V, Bussan type GMA

fuse.
1. Disconnect the AC power.
2. Remove the fuse holder from the power inlet terminal block to identify the location of the
power inlet terminal block).
3. Replace the blown fuse in the lower section of the fuse holder with the new fuse. The
upper section of the fuse holder provides a convenient location for a spare fuse.
4. Slide the fuse holder back into the power inlet terminal block.
5. Re-connect the AC power.

64

www.honeywell.com

Installing the NetAXS-123 Panels
Troubleshooting

8.0 Troubleshooting
Table 11 Troubleshooting Problems and Solutions
Problem

Solution

The panel
powers up, but it
does not respond
to any
communication,
cards reads, or
input activation.

Ensure that the Address DIP switches are set to a value other than zero.
Turn off the power (including battery), change the settings, and re-apply
the power.

No
communications
exist with the
Ethernet port.

Only a panel set to be a Gateway (DIP switch 6 = ON) will have
communications on the Ethernet port. If you need to use that port to
access the panel, turn off the power (including the battery), change the
switch setting, and reapply the power. Note that if the panel is normally
not a Gateway on a Multidrop communication bus, then the Host
RS-485 connection (C-TB9) should also be disconnected while DIP
switch 6 is ON. After completion of the Ethernet session, turn off the
power (including the battery), change the switch setting, re-connect the
Host RS-485 terminal block, and re-apply the power.

The panel
address is
unknown.

Option 1: Set the NetAXS-123 panel’s DIP switch 7 to ON. This will
default the IP address to 192.168.1.150.
Option 2: Connect to the panel through the USB port using the provided
USB A to MicroUSB B cable and the USB driver on the product CD.
The default USB Ethernet IP address is: 192.168.2.150.

The N1000 and
NS2 panels on
the Multidrop
bus do not
report.

N1000 and NS2 panels are not supported downstream from a
NetAXS-123 panel. To enable the NetAXS-123 to communicate with
the N1000 and NS2 panels, the loop must be configured with an
N-485 PCI-3 as the Gateway. However, in this configuration, web
functionality is lost. It is recommended that the user swap-out N1000
and NS2 panels with NetAXS-123 panels.

The NetAXS-123 EOL network is AC-coupled. There is no resistance
difference between the RS-485 positive and negative terminals if the EOL network is
on or off (SW1, switches 8 and 9).
Note:

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

65

Installing the NetAXS-123 Panels
Technical Support

9.0 Technical Support
9.1 Normal Support Hours
Monday through Friday, 7:00 a.m. to 7:00 p.m. Central Standard Time (CST), except
company holidays: (800) 323-4576.

9.2 Web
For technical assistance please visit http://www.honeywellaccess.com

66

www.honeywell.com

Installing the NetAXS-123 Panels
Technical Support

This page is left blank for printing purposes.

NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A

67

Honeywell Access Systems
135 W. Forest Hill Avenue
Oak Creek, WI 53154
United States
800-323-4576
414-766-1798 Fax
www.honeywellaccess.com

Specifications subject to change
without notice.
© Honeywell. All rights reserved.
Document 800-05799, Revision A



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-702
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : FrameMaker 7.1
Modify Date                     : 2010:05:07 18:02:48-04:00
Create Date                     : 2010:05:07 17:50:08Z
Metadata Date                   : 2010:05:07 18:02:48-04:00
Format                          : application/pdf
Title                           : NetAXS_123_Standard_Compact_Install.book
Creator                         : richardg
Document ID                     : uuid:10f60c81-cad6-4f5e-875c-d1a6d469b46b
Instance ID                     : uuid:e8022b88-fab6-4dc0-9cde-6c86ba828d67
Has XFA                         : No
Page Count                      : 76
Author                          : richardg
EXIF Metadata provided by EXIF.tools

Navigation menu