HZ432 TrueZONE

Zone Panel Professional Installation Guide

69-2198-01

Installation Guide

Table of Contents
Specifications.................................................................................................................................. ii
Accessories.....................................................................................................................................1
Mounting..........................................................................................................................................2
Wiring...............................................................................................................................................3
Heat Pump.......................................................................................................................................6
Dual Fuel..........................................................................................................................................8
Basic Configuration...................................................................................................................... 10
Advanced Configuration............................................................................................................... 12
Operation....................................................................................................................................... 13
Checkout....................................................................................................................................... 13
Warranty........................................................................................................................................ 14

Specifications
Input Ratings:
Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA
or more.
Current Draw:
Zone Panel: 8.5 VA max.
All VA specifications at 24 VAC.
Wiring:
18- or 20-gauge solid (not stranded) wire.
13.42
(341)

Humidity Ratings:
5% to 90% RH non-condensing.
Temperature Ratings:
Shipping: -20° to 150°F (-29° to 66°C)
Operating: -40° to 165°F (-40° to 74°C)
Dimensions:
See below.
Emissions:
Complies with FCC Class B, part 15 requirements.

8 (203)

1.86 (47)
M24797

Fig. 1. HZ432 TrueZONE panel dimensions in in. (mm).

Need Help?
For assistance with this product please visit http://yourhome.honeywell.com
or call Honeywell Zoning Hotline toll-free at 1-800-828-8367

Read and save these instructions.
® U.S. Registered Trademark. Patents pending.
Copyright © 2008 Honeywell International Inc. All rights reserved.

HZ432 TrueZONE

Accessories
Table 1. Recommended Thermostats.
System NonProgrammable

Table 3. Maximum Dampers.*

Programmable

SingleStage

TH5110D, TH3110D, TH8110U, TH6110D,
T87N
TH4110D

MultiStage

TH5220D

TH8320U, TH8321U,
TH6220D, YTH9421C

HeatPump

TH5220D (2H/1C
only)
TH3210D (2H/1C
only)
TH5320U* (Up to
3H/2C)

TH8320U (Up to 3H/2C)
TH8321U (Up to 3H/2C)
TH6320U* (Up to 3H/2C)
TH6220D (2H/1C only)
TH4210D (2H/1C only)
YTH9421C

Wireless

TH5320R

TH6320R

Zone

Spring-open/ ARD
power-closed

Zone

Power-open/ MARD/ For recommended
power-closed RRD
dampers call the
Honeywell Zoning
Hotline at
1-800-828-8367.

Bypass Static pressure regulating damper

	

SPRD

28.8

160°F (71°C)

16.8

Accessory

Description

40 VA transformer*

AT140A1042*

75 VA transformer

AT175A1008

Discharge Air Temperature DATS C7735A1000*
Sensor *

Table 2. Recommended Dampers.
Round

100°F (38°C)

Table 4. Accessories.

*	This thermostat cannot control two stages of fossil
fuel when in emergency heat mode.

Honeywell
Damper

Maximum Damper VA per Zone

*	Use an SDCR (Slave Damper Control Relay) for additional dampers.
	 Maximum dampers per panel is limited by transformer
size.
	 Ensure transformer is large enough to power the panel
(10 VA) and dampers.

Note: All versions of the model numbers listed above
will work with the applications they're listed for.

Type

Ambient Temp.

Rectangular
ZD

Wired Outdoor Air
Temperature Sensor

C7089U1006 (hard wired)

Wireless Outdoor Air
Temperature Sensor

C7089R1013 (wireless)

Wireless Adapter

THM4000R1000

TAZ-4

TotalZone® Add-A-Zone
Control Panel

SDCR

Slave Damper Control
Relay

Wireless Remote Control

REM5000R1001

TM

*	Included in HZ432K kit.

SPRD

	

69-2198—01

Installation Guide

Mounting

1

Mount the HZ432 TrueZONE panel near the HVAC
equipment; locate it on a wall, stud, roof truss, or coldair return.
NOTE:	 The HZ432 TrueZONE panel can be mounted in
any orientation; level it for appearance only.
Please refer to TrueZONE Panel Frequently Asked
Questions form 50-9694 for operating details.

SPRD BYPASS
DAMPER

ZD SERIES
ZONE DAMPERS

SUPPLY
DUCT

DATS
(ALTERNATE
LOCATION)
TrueZONE PANEL
MOUNTED ON
RETURN DUCT

TrueZONE PANEL
MOUNTED ON WALL

DATS
(AT LEAST 3 FT
FROM PLENUM)
FURNACE OR
AIR CONDITIONER

M24738

Fig. 2

2

Separate the zone panel cover from the base, and use the base as a template to drill mounting holes.
Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).

Use two screws for attaching to a stud or roof truss, or
four screws for duct or drywall/plaster installations.

Fig. 3

69-2198—01	

M24807



HZ432 TrueZONE

Wiring
CAUTION: Voltage Hazard.
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
Wire entire panel before applying transformer power.
Follow these steps for wiring all systems. However, wiring will vary depending on equipment. For conventional systems, refer to this page. For heat pump systems, see pages 6 and 7. For dual fuel systems, see pages 8 and 9.

3

Install thermostats using instructions provided with thermostats.
Connect thermostat to zone panel. To connect wire to the panel, strip
approximately 1/4 in. of insulation and push wire into terminal. To
release wire, press the button on top of the terminal.

Rc
R
C
W
W2
Y
Y2
G

THERMOSTAT ZONE 4
DAMPER

Wiring must comply with applicable codes, ordinances, and regulations. Use the following wiring diagrams to wire
the zone panel to the thermostats and dampers.

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
M24808

Fig. 4
The HZ432 offers many innovations for wire management and organization: wires can be run
behind the panel, through wire channels on its sides, and must be attached to a wiring anchor
with a cable tie.

M24743

Fig. 5

4

Install dampers using instructions provided with dampers.
Connect dampers to zone panel.
NOTE: Multiple dampers can be wired in parallel.
ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED

M4 OPEN

ZONE 1
DAMPER

ZONE 3
DAMPER

M1 COMMON
M1
M4
M6
R

M6 CLOSED
RRD OR MARD DAMPER POWER-OPEN POWER-CLOSED

ARD OR ZD DAMPER SPRING-OPEN POWER-CLOSED
ZONE 2
DAMPER

Fig. 6

M24920

	

	

69-2198—01

Installation Guide

5

SENSOR

Wiring
Connect DATS as shown.

DATS
DATS

M24804

C7735A1000

Fig. 7

OT
OT

SENSORS

6

Connect outdoor air temperature sensor
as shown. Required for dual fuel systems;
optional for other multistage systems.

C7089U1006
OUTDOOR
TEMPERATURE
SENSOR

M28207

Fig. 8

7

Connect equipment as shown.
The DS/BK terminal is used with a variable-speed fan.
Connect the DS, BK, ODD, or DHUM terminal on the
HVAC equipment to this terminal. When 1 zone is calling
(or 25% on systems with more than 4 zones) this terminal will be de-energized of 24 VAC. This reduces blower
speed on most variable speed blowers.

HVAC
24 VOLT TRANS.

C

R

W
EQUIPMENT

W2
FAN RELAY

G

Y2
Y

RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK

M24809

COMPRESSOR
RELAY

8

If using any wireless device, connect
the ABCD terminals for the wireless
interface module.

WIRELESS

Fig. 9

THM4000R
POWER

WIRELESS SETUP
CONNECTED

A
B
C
D

CONNECT

M28193

WIRELESS
ADAPTER

Fig. 10

9

Connect transformer as shown.

R

POWER

L1
(HOT)

C
DEDICATED
TRANSFORMER

M24806

Fig. 11

69-2198—01	

R
C

L2



HZ432 TrueZONE

Conventional
The following diagram is an overall view of wiring for a conventional system as depicted in steps 3–9.

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

Rc
R
C
W
W2
Y
Y2
G

HVAC
24 VOLT TRANS.

C

R

W

FAN RELAY

EQUIPMENT

G

Y2
Y

C7089U1006
OUTDOOR
TEMPERATURE
SENSOR

C7735A1000
DATS

THM4000R
POWER

WIRELESS SETUP

POWER
ACCESSORIES

C
DEDICATED
TRANSFORMER

SENSORS

L2

RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

R
C

HZ432

HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
Rc
R
C
W
W2
Y
Y2
G

ZONE 1
ZONE 2
ZONE 3
ZONE 4

AZ1
AZ2

OT
OT

Rc
R
C
W
W2
Y
Y2
G

EMERGENCY
HEAT

DATS
DATS

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 3 THERMOSTAT
DAMPER

COMPRESSOR
RELAY

R

WIRELESS

L1
(HOT)

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 2 THERMOSTAT
DAMPER

W2

M6 CLOSED

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 1 THERMOSTAT
DAMPER

THERMOSTAT ZONE 4
DAMPER

M1 COMMON RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
M4 OPEN

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

Rc
R
C
W
W2
Y
Y2
G

A
B
C
D
HOME
CONFIG
CHECK OUT

CONNECTED
CONNECT

ADJUST SETTING

WIRELESS
ADAPTER
M28196

Fig. 12. Zone panel wiring—conventional.

	

	

69-2198—01

Installation Guide

Heat Pump
Use the following diagram for wiring a 2-heat/1-cool heat pump with electric auxiliary heat.
NOTE: You can use a conventional thermostat for a heat pump system; however, em heat can only be controlled by
heat pump thermostats. The diagram below shows a heat pump thermostat used with a heat pump system.

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED

M1 COMMON
M4 OPEN

2

THERMOSTAT ZONE 4
DAMPER

AIR
HANDLER

G
O/B
L

24 VOLT TRANS.

C

R

EM. HEAT

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 1 THERMOSTAT
DAMPER

1

Rc
R
C
E
AUX
Y

M6 CLOSED
Rc
R
C
E
AUX
Y
G
O/B
L

1

2

E

W2

FAN RELAY

EQUIPMENT

G
Y

Y

C
DEDICATED
TRANSFORMER

C7089U1006
OUTDOOR
TEMPERATURE
SENSOR

WIRELESS

C7735A1000
DATS

THM4000R

R
C

HZ432

HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT

Rc
R
C
E
AUX
Y

1

2

ZONE 1
ZONE 2
ZONE 3
ZONE 4

AZ1
AZ2
OT
OT

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

G
O/B
L

EMERGENCY
HEAT

DATS
DATS

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 3 THERMOSTAT
DAMPER

REVERSING
VALVE

L2

POWER

R

R

ACCESSORIES

C

L1
(HOT)

SENSORS

HEAT PUMP

3

ZONE 2 THERMOSTAT
DAMPER

AUX. HEAT

A
B
C
D

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

Rc
R
C
E
AUX
Y
G
O/B
L

1

2

POWER

WIRELESS SETUP

HOME
CONFIG
CHECK OUT

CONNECTED
CONNECT

WIRELESS
ADAPTER

ADJUST SETTING

1

ALTERNATIVELY LABELED W2 ON SOME THERMOSTATS.

2

FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR
COOL CHANGEOVER VALVES, AND ATTACH B FOR HEAT CHANGEOVER VALVES.

3

IF EQUIPMENT DOES NOT HAVE SEPARATE E AND W2 TERMINALS, JUMPER
E TO W2 ON PANEL AND WIRE TO E.

M24794

Fig. 13. Zone panel wiring—heat pump, 2-heat/1-cool with electric auxiliary heat.

69-2198—01	



HZ432 TrueZONE

Heat Pump
Use the following diagram for wiring a 3-heat/2-cool heat pump with electric stage 3 heat.

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

THERMOSTAT ZONE 4
DAMPER

AIR
2
HANDLER

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

24 VOLT TRANS.

C

R

EM. HEAT

M6 CLOSED
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

E

AUX. HEAT

W3

FAN RELAY

EQUIPMENT

G

Y2
Y

L2

C
DEDICATED
TRANSFORMER

REVERSING
VALVE

C7089U1006
OUTDOOR
TEMPERATURE
SENSOR

C7735A1000
DATS

THM4000R

R
C

HZ432

HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT

ZONE 2
ZONE 3
ZONE 4

AZ1
AZ2

OT
OT

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

1

2

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED
Rc
R
C
E
AUX
Y
Y2
G
O/B
L

1

2

ZONE 1

EMERGENCY
HEAT

DATS
DATS

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 3 THERMOSTAT
DAMPER

Y2

R
POWER

Y

L1
(HOT)

ACCESSORIES

R

SENSORS

C

WIRELESS

HEAT PUMP

3

ZONE 2 THERMOSTAT
DAMPER

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 1 THERMOSTAT
DAMPER

1

M1 COMMON RRD OR MARD DAMPER
POWER-OPEN
M4 OPEN
POWER-CLOSED

A
B
C
D

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

1

2

POWER

WIRELESS SETUP

HOME
CONFIG
CHECK OUT

CONNECTED
CONNECT

ADJUST SETTING

WIRELESS
ADAPTER

1

ALTERNATIVELY LABELED W2 ON SOME THERMOSTATS.

2

FOR THERMOSTATS WITH SEPARATE O AND B TERMINALS, ATTACH O FOR
COOL CHANGEOVER VALVES, AND ATTACH B FOR HEAT CHANGEOVER VALVES.

3

IF EQUIPMENT DOES NOT HAVE SEPARATE E AND W2 TERMINALS, JUMPER
E TO W2 ON PANEL AND WIRE TO E.

M24795

Fig. 14. Zone panel wiring—heat pump, 3-heat/2-cool with electric stage 3 heat.

	

	

69-2198—01

Installation Guide

Dual Fuel
Use the following diagram for wiring a dual-fuel system with single-stage furnace and single-stage heat pump.
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

C

THERMOSTAT ZONE 4
DAMPER

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

M6 CLOSED
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

R

W
FAN RELAY

EQUIPMENT

G
Y

L2

C
DEDICATED
TRANSFORMER

C7089U1006
OUTDOOR
TEMPERATURE
SENSOR

C7735A1000
DATS

THM4000R
POWER

WIRELESS SETUP

R
C

HZ432

HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

ZONE 1
ZONE 2
ZONE 3
ZONE 4

AZ1
AZ2

OT
OT

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

EMERGENCY
HEAT

DATS
DATS

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 3 THERMOSTAT
DAMPER

REVERSING
VALVE

R
POWER

Y

L1
(HOT)

ACCESSORIES

R

SENSORS

C

WIRELESS

HEAT PUMP

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

ZONE 2 THERMOSTAT
DAMPER

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 1 THERMOSTAT
DAMPER

FURNACE
24 VOLT TRANS.

M1 COMMON RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED
M4 OPEN

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

A
B
C
D
HOME
CONFIG
CHECK OUT

CONNECTED
CONNECT

ADJUST SETTING

WIRELESS
ADAPTER
M24796

Fig. 15. Zone panel wiring—dual fuel: single-stage furnace and single-stage heat pump.

69-2198—01	



HZ432 TrueZONE

dual Fuel
Use the following diagram for wiring a dual-fuel system with two-stage furnace and two-stage heat pump.
ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

M1 COMMON

C

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

M6 CLOSED
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

R

HEAT 1

W

HEAT 2

EQUIPMENT

W2

FAN RELAY

G

Y2
Y

Y2
REVERSING
VALVE

L2

C
DEDICATED
TRANSFORMER

C7089U1006
OUTDOOR
TEMPERATURE
SENSOR

C7735A1000
DATS

R
C

HEAT 1
HEAT 2
HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

ZONE 1
ZONE 2
ZONE 3
ZONE 4

AZ1
AZ2

OT
OT

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

EMERGENCY
HEAT

DATS
DATS

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 3 THERMOSTAT
DAMPER

Y

ACCESSORIES

R

POWER

R

SENSORS

C

L1
(HOT)

WIRELESS

HEAT PUMP

HZ432

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

ZONE 2 THERMOSTAT
DAMPER

M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L

ZONE 1 THERMOSTAT
DAMPER

FURNACE
24 VOLT TRANS.

THERMOSTAT ZONE 4
DAMPER

M4 OPEN

RRD OR MARD DAMPER
POWER-OPEN
POWER-CLOSED

ARD OR ZD DAMPER
SPRING-OPEN
POWER-CLOSED

Rc
R
C
E
AUX
Y
Y2
G
O/B
L

A
B
C
D
HOME
CONFIG
CHECK OUT

THM4000R
POWER

WIRELESS SETUP
CONNECTED
CONNECT

ADJUST SETTING

WIRELESS
ADAPTER
M24793

Fig. 16. Zone panel wiring—dual fuel: two-stage furnace and two-stage heat pump.

	

	

69-2198—01

Installation Guide

Configuration
To enter Configuration:
WIRELESS

1

Press the Mode button (the Config LED will
light up).
BACK

2

3

Use the Back and Next buttons to navigate
through the configuration menus. Pressing
Next enters the selected option for that
menu item and advances to the next menu.
Adjust settings up or down by pressing the
Adjust Setting button.

HOME
CONFIG
CHECK OUT

WIRELESS
MODE

ADJUST SETTING

NEXT

BACK

M24799

HOME
CONFIG
CHECK OUT

MODE

ADJUST SETTING

NEXT

M24810

Fig. 17

The flow chart below illustrates basic zone panel configuration. For additional configuration, see
Advanced Configuration on page 12. The label on the inside cover of the HZ432 Zone Panel also contains configuration information.

Fig. 18

69-2198—01	

10

HZ432 TrueZONE

Connect Wireless Devices
WIRELESS

4

Press the Mode button until the Wireless LED lights
up. The TrueZONE must be configured for wireless
devices to select Wireless mode.

BACK

HOME
CONFIG
CHECK OUT

MODE

ADJUST SETTING

NEXT

M28194

Press Next to add devices.
While the display alternates the Press Connect and
Exit screens, push the Connect button(s) on the wireless device(s).
-ORFollow the instructions that came with the wireless
device(s).
Press Next to exit.

Fig. 19

If using more than 4 zones, use the TAZ-4 Add-A-Zone
Control Panel. Follow instructions with the TAZ-4 for
installation (form 69-1366).
Note: If using a wireless device, a maximum of 4 zones
may be configured.

TM

5

	

11	

69-2198—01

Installation Guide

Advanced Configuration
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page
10 for instructions on using these buttons.
Table 5. Advanced Configuration.
Menu Name

Stage 2 Timer

Menu Title (LCD
top line)
HEAT FAN
CONTROL
STAGE 2 TIMER

Stage 3 Timer

STAGE 3 TIMER

Purge Timer

PURGE TIME

Purge Fan

FAN IN PURGE

Heat Fan

Menu Options (LCD bottom
line; defaults in bold)
[HVAC] PANEL
HVAC [PANEL]
[5 MIN] > – < [60 MIN]
[5 MIN] >
[5 MIN] > – < [60 MIN]
[5 MIN] >
[2] 3.5 5 MIN
2 [3.5] 5 MIN
2 3.5 [5] MIN

[HVAC] PANEL
HVAC [PANEL]
Purge Dampers
PURGE DAMPERS [UNCHANGD] OPEN
UNCHANGD [OPEN]
Auto Changeover Delay CHANGEOVER
[15] 20 30 MIN
DELAY
15 [20] 30 MIN
15 20 [30] MIN
DATS Enabled
DISCHARGE
[NO] YES
SENSOR
NO [YES]
DATS High Limit
DAT HIGH LIMIT
[110 F] > – < [180 F]
< [160 F] >
DATS Low Limit
DAT LOW LIMIT
[30 F] > – < [60 F]
< [40 F] >
Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES]
[NO] YES
Dual Fuel Changeover DUALFUEL
[OT] MULTISTG
CHGOVR
OT [MULTISTG]

Dual Fuel Mstage
Changeover Time
OT Temp Enabled

CHANGEOVER
DELAY
OT SENSOR

[15 MIN] > – < [180 MIN]
[30 MIN] >
[NO] YES
NO [YES]

Multistage OT Temp
Lockout

MSTG OT
LOCKOUT

[NO] YES
NO [YES]

OT Balance
OT BALANCE
Temperature (Dual Fuel) TEMP

[0 F] > – <
[30 F] >

[50 F]

<

OT Trip point for multistage lockout

OT LOCKOUT
TEMP

[0 F] > – <
[50 F] >

[50 F]

<

LCD Contrast Adjust

LCD CONTRAST

Save Changes

SAVE CHANGES?

Reload Defaults

RELOAD
DEFAULTS?

69-2198—01	

[1]
>–<
< [5]
>
[NO] YES
NO [YES]
[NO] YES
NO [YES]

[10]

Menu option description

Notes:

Fan control by HVAC
Fan control by Panel
5 minutes–60 minutes

In heat mode, fan controlled by HVAC or turned
on by panel in call for heat.
Number of minutes to delay before engaging
second stage.
Number of minutes to delay before engaging
third stage.
Number of minutes panel will purge following
call for heat or cool.

5 minutes–60 minutes
2.0 minutes
3.5 minutes
5.0 minutes
Fan control by HVAC
Fan control by Panel
Dampers Unchanged
Dampers All Open
15 minutes auto changeover timer
20 minutes auto changeover timer
30 minutes auto changeover timer
Disabled
Enabled
110 deg F–180 deg F

Fan controlled by HVAC or panel during purge.

30 deg F–60 deg F

Low temperature limit.

Damper position unchanged or all dampers
open during purge.
Number of minutes to delay auto changeover
when one zone is calling for heat and another
is calling for cooling.
Enables or disables DATS. If Disabled, the
Multistage DATS Inhibit setting is Disabled.
High temperature limit.

Enabled
Allow panel to downstage multistage equipment when near DATS high or low limit.
Disabled
Dual Fuel Changeover by OT Temp Allow panel to changeover from heat pump to
Dual Fuel Changeover by OT Temp + fossil fuel based on outdoor temperature, or
allow second stage call to changeover panel
multistage call
to fossil fuel for a minimum of one hour when
outdoor temperature is above OT balance temperature setting.
Sets fossil fuel changeover delay
Sets number of minutes to delay fossil fuel
time.
when calling for second stage heat.
Disabled
Enables or disables outdoor temperature
sensor. If Disabled, the Multistage OT Temp
Enabled
Lockout setting is Disabled.
Disabled
When outdoor temperature is above OT
Lockout temperature, locks out second or third
Enabled
stage (only for conventional and heat pump
configurations).
0 deg F–50 deg F
Selects the temperature at which a dual fuel
configuration will change from heat pump to
fossil fuel.
0 deg F–50 deg F
The temp that locks out second or third stage
(only for conventional and heat pump configurations, not dual fuel systems).
Contrast value 1–10
Sets LCD display contrast for ease of viewing.
Lowest contrast is 1, highest contrast is 10.
Disabled
Saves or rejects the configuration settings.
Enabled
Disabled
Restores the panel's default configuration settings.
Enabled

12

HZ432 TrueZONE

Operation
The HZ432 TrueZONE panel contains an LED display that communicates system and
zone status. The LEDs indicate the following information.
Much of this information, as well as configuration information, is listed on the label
on the inside of the HZ432 cover. For users who prefer French or Spanish labels,
they are provided in form 69-2198FS. Cut them out and attach them to the inside of
the HZ432 cover.
Table 6. LED Operation.

HEAT 1

LED

Description

HEAT 1

Solid when in heat stage 1. Blinking when DATS high limit mode has been
reached.
Solid when in heat stage 2, 3. Blinking when stage 2, 3 locked out due to
DATS or OT.
Solid when in cool stage 1. Blinking when DATS low limit mode has been
reached.
Solid when in cool stage 2. Blinking when stage 2 locked out due to DATS.

HEAT 2, 3
COOL 1
COOL 2
PURGE
FAN

HZ432

HEAT 2

Solid when in purge (at power-up and after a call for heat or cool).
Blinking when the DATS sensor has failed, or the wires are shorted or
open. Will blink for 3 minutes at power-up if DATS is not present.
Solid with a call for fan.

EM HEAT

Solid when in emergency heat mode. This light does not indicate a call for
heat. Emergency heat will only run when both HEAT and EM HEAT are lit.

ZONE 1, 2,
3, 4

Solid green when open or opening. Solid red when closed or closing.
Blinking amber when there is a damper or thermostat short circuit (circuit
breaker trip).

HEAT 3
COOL 1
COOL 2
PURGE
FAN
EM HEAT

ZONE 1
ZONE 2
ZONE 3
ZONE 4

EMERGENCY
HEAT

M24798

Fig. 20

Checkout
To enter Checkout, with the zone panel cover off, press the Mode button until the Check out LED lights up. Use the
Adjust Setting and Next buttons to work through the checkout menu as listed below. See the Configuration section on
page 10 for instructions on using these buttons.
Steps 3–10 cycle through heating and cooling stages and open and close dampers to verify proper operation.
Steps 11–14 verify thermostat operation and correct wiring. This is done by making the thermostats call for heat or
cool and viewing the active wires as displayed on the LCD screen.
Table 7. Checkout.
Checkout Step
1. Display shows OT
2. Display shows DATS
3. Heat stages test

Line 1 display
OT SENSOR VAL
DAT SENSOR VAL
TEST HEAT

Line 2 Display
current OT temp (dynamic)
current DATS (dynamic)
[OFF] 1 2 3

4.
5.
6.
7.
8.
9.
10.
11.

TEST EMERG HEAT
TEST COOL
TEST FAN
TEST Z1 DAMPER
TEST Z2 DAMPER
TEST Z3 DAMPER
TEST Z4 DAMPER
ZONE1 STAT INPTS

[OFF] 1 2
[OFF] 1 2
[OFF] ON
[OPEN] CLOSED
[OPEN] CLOSED
[OPEN] CLOSED
[OPEN] CLOSED
Displays active Tstat1 terminals
less thermostat operation
Displays active Tstat2 terminals
less thermostat operation
Displays active Tstat3 terminals
less thermostat operation
Displays active Tstat4 terminals
less thermostat operation
(NEXT = EXIT)

EM Heat stages test
Cool stages test
Fan Test
Damper 1 test
Damper 2 test
Damper 3 test
Damper 4 test
View Tstat1 inputs

12. View Tstat2 inputs

ZONE2 STAT INPTS

13. View Tstat3 inputs

ZONE3 STAT INPTS

14. View Tstat4 inputs

ZONE4 STAT INPTS

15. Exit checkout mode?
16. Exiting checkout mode

EXIT CHECKOUT?
EXITING CHECKOUT

	

13	

Notes:
All zone dampers open, all other relays OFF.

or displays wire-

Heat turns on (fan also turns on if configured for
fan on in heat).
Emergency heat turns on (fan also turns on).
Cooling turns on (fan also turns on).
Fan cycles on and off.
Cycles damper position with fan on.
Cycles damper position with fan on.
Cycles damper position with fan on.
Cycles damper position with fan on.
Tests thermostat connection with HVAC off.

or displays wire-

Tests thermostat connection with HVAC off.

or displays wire-

Tests thermostat connection with HVAC off.

or displays wire-

Tests thermostat connection with HVAC off.

69-2198—01

Warranty
Honeywell warrants the products in this catalog (except those parts designated on Honeywell’s price lists as not covered by this warranty) to be free from defects due
to workmanship or materials, under normal use and service, for the following warranty periods. Honeywell VisionPRO®, Commercial VisionPRO , FocusPRO®, PRO
4000, PRO 3000, LineVolt PRO, Digital Round , and Modern Round (T87K, N) Series Thermostats with a date code of 0501 or later: sixty (60) months from date of
installation. CommercialPRO, PRO 2000 and PRO 1000 thermostats: twenty-four (24) months from date of installation. All other Honeywell thermostats and thermostats with a date code of 0452 or earlier: twelve (12) months from date of installation, unless specified otherwise. Honeywell Air Cleaners, Humidifiers, Ventilators,
Ultraviolet Treatment and Zoning Products with a date code of 0501 or later, excluding replacement maintenance parts: sixty (60) months from date of installation. All
other Honeywell indoor air quality and zoning products with a date code of 0452 or earlier: twenty-four (24) months from date of installation, unless specified otherwise. Variable frequency drive devices (VFD) and accessories: new products for thirty-six (36) months and factory refurbished drives for twelve (12) months from date
of installation when start-up and commissioning is performed by Honeywell VFD Authorized and trained personnel. All VFD warranty return products must have prior
authorization (Form No. 87-0284) and be returned only to the VFD Service Center in Chattanooga, TN. MS, MN and Fact Acting 2-position Direct Coupled Actuators:
sixty (60) months from date of installation. The warranty period for all other products is twelve (12) months from date of installation.
TM

TM

TM

TM

If a product is defective due to workmanship or materials, is removed within the applicable warranty period, and is returned to Honeywell in accordance with the procedure described below, Honeywell will, at its option, either repair, replace or credit the customer for the purchase price of the product, in accordance with the procedure described below. This warranty extends only to persons or organizations who purchase products in this catalog for resale.
The expressed warranty above constitutes the entire warranty of Honeywell with respect to the products in this catalog and IS IN LIEU OF ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL
HONEYWELL BE RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY NATURE WHATSOEVER.

Automation and Control Solutions
Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Toronto, Ontario M1V 4Z9

customer.honeywell.com
® U.S. Registered Trademark.
© 2008 Honeywell International Inc.
Patents pending
69-2198—01 M.S. 02-08

Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Fill forms, Extract, Assemble, Print high-res
Tagged PDF                      : Yes
XMP Toolkit                     : 3.1-702
About                           : 228e060d-a1f3-11da-8050-9e7bea7aa414
Create Date                     : 2008:01:15 07:24:20-06:00
Metadata Date                   : 2008:02:21 12:08:16-06:00
Modify Date                     : 2008:02:21 12:08:16-06:00
Creator Tool                    : Adobe InDesign CS2 (4.0.5)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 10240 bytes, use -b option to extract)
Instance ID                     : uuid:82527e99-6a16-4924-b3b7-c15560e9e3d8
Document ID                     : adobe:docid:indd:4595b474-c2c0-11dc-bc1b-ff3681cf1aa4
Rendition Class                 : proof:pdf
Derived From Instance ID        : 4595b473-c2c0-11dc-bc1b-ff3681cf1aa4
Derived From Document ID        : adobe:docid:indd:6e26b8e4-a4d2-11dc-8de1-bd4680e2d8a1
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 300.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 300.00, 72.00, 300.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:640B05DD830FDC118B0FBA1F1936A747, uuid:98DFE844681DDB1180CDBC23D795DD81, uuid:976CDC4F7B0FDC11A33B973BCDAFD42B, uuid:507196FDC2C2DC1184EEAD2882D5F982, uuid:41299477B124DC11BC049ED6C6085913, uuid:63E16FD36634DC119D79A69A2DA30BE0, uuid:2841836FD3A4DC11BB5C9AE1F7ABAA64, uuid:1307FBEC8A2EDC11826AC440291065B0, uuid:C4DE4E62A404DC118A31AC33B1C6A264, uuid:6139CE30731DDB1180CDBC23D795DD81, uuid:99E96331B233DC11A1EFE2A4FD905E64, uuid:5279E3DF0C03DC11B382E03A627C4250, uuid:5479E3DF0C03DC11B382E03A627C4250, uuid:12C0A88DA134DC119D79A69A2DA30BE0, uuid:739FA998B7BEDC118BBFA4E9F8FAB82D, uuid:72F7D3F5B8BEDC118BBFA4E9F8FAB82D, uuid:759FA998B7BEDC118BBFA4E9F8FAB82D, uuid:769FA998B7BEDC118BBFA4E9F8FAB82D, uuid:779FA998B7BEDC118BBFA4E9F8FAB82D, uuid:789FA998B7BEDC118BBFA4E9F8FAB82D, uuid:799FA998B7BEDC118BBFA4E9F8FAB82D, uuid:B531BC986CA2DC11B31FC74037D07486, uuid:B631BC986CA2DC11B31FC74037D07486, uuid:42B4E89C76A4DC11AAF6A155AABF4D77, uuid:B37567A7C3A4DC1184F2C45413DF4734, uuid:B67567A7C3A4DC1184F2C45413DF4734, uuid:E8A1C501F009DC11A5FAFD515FC49294, uuid:98DFE844681DDB1180CDBC23D795DD81, uuid:F48FAE7A292DDB118B39ACE99AA29D97
Manifest Reference Document ID  : uuid:24F5EDC071F2DB11B15EC6FAB289FDE4, uuid:114D8CF2EF3FDA1198179458FCECD626, uuid:384BA8C854FADB1187A7C53C756306DE, uuid:5A8CCEF6C2C2DC1184EEAD2882D5F982, uuid:F54B75E976FDDB11B9918178955294A6, uuid:F6CADA89E502DC11B382E03A627C4250, uuid:2441836FD3A4DC11BB5C9AE1F7ABAA64, uuid:D50E743342F4DB118D33AD394FC22EB7, uuid:18263A5D9EFCDB119AFBD361947D9D53, uuid:E7417D665ABEDA118018E2EA77DEB2A9, uuid:395305BFD902DC11B382E03A627C4250, uuid:6527C59937ECDB119C958DA5453ECB41, uuid:6527C59937ECDB119C958DA5453ECB41, uuid:18263A5D9EFCDB119AFBD361947D9D53, uuid:6527C59937ECDB119C958DA5453ECB41, uuid:7A9FA998B7BEDC118BBFA4E9F8FAB82D, uuid:B87567A7C3A4DC1184F2C45413DF4734, uuid:18263A5D9EFCDB119AFBD361947D9D53, uuid:F35AFA8C2CFEDB1191C7FCD3C9106C9B, uuid:A689D14869FDDB11B9918178955294A6, uuid:A3B95A417704DC11B312F6CD50E4D321, uuid:F95AFA8C2CFEDB1191C7FCD3C9106C9B, uuid:C7DE4E62A404DC118A31AC33B1C6A264, uuid:41B4E89C76A4DC11AAF6A155AABF4D77, uuid:B17567A7C3A4DC1184F2C45413DF4734, uuid:B57567A7C3A4DC1184F2C45413DF4734, uuid:C5BB43C77CFDDB11B9918178955294A6, uuid:114D8CF2EF3FDA1198179458FCECD626, uuid:2184E468D61FDA11A85980F80C0AA5D7
Format                          : application/pdf
Title                           : 69-2198-01 - TrueZONE Zone Panel Professional Installation Guide
Creator                         : Honeywell
Description                     : Professional Installation Guide
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 16
Subject                         : Professional Installation Guide
Author                          : Honeywell
EXIF Metadata provided by EXIF.tools

Navigation menu