Honeywell Thermostat T451A Users Manual 63 2051 T451A, T651A, T694A,B,D,F Light Duty Line Voltage Thermostats

2015-01-23

: Honeywell Honeywell-Honeywell-Thermostat-T451A-Users-Manual-262210 honeywell-honeywell-thermostat-t451a-users-manual-262210 honeywell pdf

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadHoneywell Honeywell-Honeywell-Thermostat-T451A-Users-Manual- 63-2051 - T451A, T651A, T694A,B,D,F Light Duty Line Voltage Thermostats  Honeywell-honeywell-thermostat-t451a-users-manual
Open PDF In BrowserView PDF
T451A, T651A, T694A,B,D,F
Light Duty
Line Voltage Thermostats
T451, T651, T694 Thermostats provide on-off
control of valves, fans, motors, contactors, electric
heat elements, duct furnaces and fan coil units in
heating/cooling systems. Switching subbases provide manual control of heating, cooling and fan.
T451A,
T651A

T694B,D,F

T694A

■ T451A provides heating control only.

■ Thermostats use spst or spdt snap switches activated
by bimetal sensor.

■ T651A provides heating and cooling control.
■ T694A,B,D,F supplied with switching subbase to provide manual control of heating, cooling and fan.
■ Q473A,B switching subbase available for T451A/
T651A.

■ T451A/T651A mount on standard vertical or horizontal junction box.
■ Options include adjustable range stops, locking cover,
concealed setpoint, locking setpoint, positive off control, cover thermometer.

■ Automatic cooling anticipator for 120, 208, 240 and
277 Vac.

CONTENTS
Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 4
Checkout ......................................................... 7

J. H. • Rev. 9-92
1 • ©Honeywell Inc. 1992 • Form Number 63-2051—4

T451A, T651A, T694A,B,D,F
SPECIFICATIONS • ORDERING INFORMATION

Specifications
— Automatic cooling anticipator for 120, 208, 240 and
277 Vac.
— Vertical faceplate with Fahrenheit scale and thermometer.
— Horizontal faceplate with Fahrenheit scale and thermometer.
— Blank vertical faceplate.
— Blank horizontal faceplate.
— Wallplate.
— Adjustable range stops.
— Locking cover screw.

SUPER TRADELINE MODEL
TRADELINE models are selected and packaged to provide
ease of stocking, ease of handling and maximum replacement value. TRADELINE model specifications are the
same as those of standard models except as noted below.
SUPER TRADELINE MODEL AVAILABLE:
T651A2028 Light Duty Line Voltage Thermostat.
FEATURES:
— Temperature scale range 35° F to 95° F.
— Spdt switch breaks heating contacts and makes cooling
contacts on temperature rise.

STANDARD MODELS:
Model
Number
T451A2007a
T451A2015
T651A2028a
T694A2002
T694B2001
T694D2009

T694F2007

a

Application
Heating only.
Heating only with positive OFF.
Heating/cooling.
Heating/cooling. OFF position breaks
fan circuit.
Heating/cooling. OFF position breaks
cooling and fan circuits.
Heating/cooling. Heating circuits isolated
from cooling circuits. OFF position
breaks all control circuits except heat.
Heating/cooling. Heating circuits isolated
from cooling circuits. OFF position breaks
all power to fan and thermostat.

System Switch
—
—
—
ON-OFF

Changeover
Switch
—
—
—
—

Fan Switch
—
—
—
HI-MEDIUM-LO

ON-OFF

HEAT-COOL

HI-MEDIUM-LO

ON-OFF

HEAT-COOL

HI-MEDIUM-LO

ON-OFF

HEAT-COOL

HI-MEDIUM-LO

With thermometer.

Ordering Information
When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the
TRADELINE Catalog or price sheets for complete ordering number, or specify—
1. Order number.
2. Accessories, if desired.
3. Order additional components and system accessories separately.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Satisfaction
Honeywell Inc., 1885 Douglas Drive North
Golden Valley, MN 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitee, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9, International Sales and
Service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

2

T451A, T651A, T694A,B,D,F
SPECIFICATIONS
ELECTRICAL RATINGS (A):
120
8
48

Full Load
Locked Rotor
a

FINISH: Brushed champagne gold and dark pewter faceplate; beige and brown case.

Voltage (Vac)
208/240/277
4a
24

UNDERWRITERS LABORATORIES INC.: Listed.
ACCESSORIES:
Q473A2006 Switching Subbase: Use with T651A for
HEAT-OFF-COOL manual system switching.
Q473B2005 Switching Subbase: Use with T451A/
T652A for AUTO/OFF switching in heating only or
cooling only applications.
220124A Faceplate vertical, Fahrenheit scale, with
thermometer.a
220124B Faceplate vertical, Celsius scale, with thermometer.
220124C Faceplate, horizontal, Fahrenheit scale, with
thermometer.a
220124D Faceplate, horizontal, Celsius scale, with thermometer.
220125A Faceplate, horizontal, Fahrenheit scale, without thermometer.
220125B Faceplate, vertical, Fahrenheit scale, without
thermometer.
220125C Faceplate, horizontal, Celsius scale, without
thermometer.
220125D Faceplate, vertical, Celsius scale, without thermometer.
220126A Faceplate, horizontal, blank (concealed setpoint,
without thermometer).a
220126B Faceplate, vertical, blank (concealed setpoint,
without thermometer).a
220213 Wallplate, covers old T451A/T651A wall marks
when installing new T451A/T651A.a
199242 Wallplate, covers old T694 wall marks when
installing new T694.

Wider temperature differential ranges can occur when
used in cooling applications with current draws that are
more than four amps. If a wider differential range is
unacceptable, use a T6051 Heavy Duty Line Voltage
Thermostat for a smaller differential range.

Pilot Duty: 125 VA.
7.2A Resistive: heating contacts only.
TEMPERATURE SETTING RANGE: 35° F to 95° F [2° C
to 35° C] (with range stops removed).
STORAGE TEMPERATURE: -40° F to 150° F [-40° C to
66° C].
FIXED DIFFERENTIAL: 2° F [1° C].
SWITCHING ACTION:
T451: Spst. Contacts make on temperature fall.
T651: Spdt. Heating contacts break and cooling contacts
make on temperature rise.
T694: Spdt. Heating contacts break and cooling contacts
make on temperature rise.
FIELD WIRING CONNECTIONS: No. 10 screw terminals
on T451A/T651A; color-coded leads on T694 models.
DIMENSIONS: See Figs. 1 and 2.

a

Supplied with SUPER TRADELINE model T651A.

Fig. 1—T451A, T651A mounting dimensions in in. [mm].
15
1
32
[35]

9
16
[14]

70

60
50

80

40

90

417
32
[114]

3
4
[45]

1

F
40 50 60 70 80 90

2 13
16
[70]

11
8
[22]

15
16
[24]

113
16
[48]

9
3
32
[83]
COOL HEAT COM

1
8
[37]

1

17
32
[14]
M6130

3

63-2051—4

T451A, T651A, T694A,B,D,F
INSTALLATION

Fig. 2—T694A,B,D,F mounting dimensions in in. [mm].
1 7
8
[48]

SYSTEM
ON

70

60
50

80

40

OFF

90
HEAT
COOL

F
FAN

47
8
[124]

3 9
32
[83]

3
[76]

HI
MED
LOW

4 29
32
[125 ]

15
32
[35]

1 9
16
[40]

(T694B SHOWN)
1 13
32
[36]

M6129

Installation
Do not use on electric heat. Possible fire hazard if
T694A,B,D used on electric heat. T694F can be
used on electric heat.

Do not install the thermostat where it may be affected by:
• drafts, or dead spots behind doors and in corners.
• hot or cold air from ducts.
• radiant heat from sun or appliances.
• concealed pipes and chimneys.
• unheated (uncooled) areas behind the thermostat,
such as an outside wall.

WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product operation as provided in these instructions.

WIRING AND MOUNTING
Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
All wiring must comply with applicable electrical codes,
ordinances and regulations. Use copper wire only. Make
sure that thermostat electrical rating is sufficient for current
requirements of controlled equipment, and that listed voltage matches power supply.

!

!

WARNING

T451A/T651A THERMOSTATS (Fig. 3)
T451A/T651A Thermostats mount vertically on a 2 x 4
in. or 4 x 4 in. junction box. See Fig. 3. Use 2 x 4 in. cover
plate with 4 x 4 in. junction. For horizontal mounting, the
appropriate horizontal faceplate is required. Horizontal
with thermometer and horizontal blank faceplates are
packaged with the T651A2028 SUPER TRADELINE
model. For additional faceplates or T451 applications, see
Accessories. When replacing old style T451A/T651A, use
a wallplate to cover previous wall marks. This wallplate is
packaged with the T651A2028 SUPER TRADELINE
model. For T451 applications, see Accessories.

CAUTION
Disconnect power supply before making wiring
connections to prevent electrical shock and equipment damage. Use copper wire only.

LOCATION
Select the same location as control to be replaced, or
select a new location about 5 ft. [1.5 m] above the floor, on
an inside wall where there is good air circulation at average
room temperature.

4

T451A, T651A, T694A,B,D,F
INSTALLATION
1. Before mounting thermostat, connect system wiring
to proper terminals at rear of thermostat. Follow equipment manufacturer instructions or refer to Fig. 4 for
typical system hookup.
2. Remove cover assembly from thermostat. Attach
thermostat to junction box with two screws provided. Replace cover assembly. See Fig. 3.
3. Use 1/16 hex Allen wrench to install Allen locking
cover screw.

2. Remove thermostat cover assembly. Attach thermostat to junction box with two screws provided. Replace
thermostat cover assembly.
Fig. 4—T652A in heating-cooling system.

Fig. 3—Mounting T451A/T651A.

220213 WALLPLATE
ACCESSORY
(OPTIONAL)
(COVERS OLD T651A
WALL MARKS WHEN
INSTALLING NEW T651A)

Fig. 5—Mounting T694A,B,D,F.

TABS HOLD
COVER ASSEMBLY
AT TOP (SNAP
IN AT BOTTOM)

MOUNTING
SCREWS (2)

70
60

USE 2x4
JUNCTION
BOX

COVER PLATE

4x4 JUNCTION
BOX

80
90

TABS HOLD
COVER ASSEMBLY
AT TOP (SNAP
IN AT BOTTOM)

50

40
F

40

50

60

70

80

90
EM

ST

SY

ON

MOUNTING
SCREWS (2)

F

OF

AT

HE

OL

CO

N

FA

M6131

HI
D
ME
W

LO

USE 2x4 OR 4x4
JUNCTION BOX

70
60

T694A,B,D,F THERMOSTATS (Fig. 5)
All T694A,B,D,F Thermostats mount vertically on a 2 x
4 in. or 4 x 4 in. junction box. See Fig. 5. Use 2 x 4 in. cover
plate with 4 x 4 in. junction box.
1. Before mounting, connect system wiring to proper
color-coded leads at rear of thermostat. Follow equipment
manufacturer instructions or refer to Figs. 6-9 for typical
system hookups.

80
90

50
40
F

(T694B SHOWN)

M6135

5

63-2051—4

T451A, T651A, T694A,B,D,F
INSTALLATION

Fig. 6—T694A in heating-cooling system with
independent valve and fan circuits.

Fig. 8—T694D with isolated switching for heating
and cooling.

Fig. 7—T694B connected for positive-off switching in COOL position.

Fig. 9—T694F with positive-off position.

6

T451A, T651A, T694A,B,D,F
CHECKOUT

Checkout
After the thermostat is wired and mounted, perform the
following system checkout procedure.

T694
NOTE: System switch must be in ON position to check
out system.

T451/T651
IN HEATING APPLICATION:
1. Close disconnect switch (if used).
2. Adjust setpoint above room temperature and check
that heating system turns on.
3. Adjust setpoint below room temperature and check
that heating system turns off.
4. Adjust thermostat for desired room temperature.

1. Close the disconnect switch (if used) and press
HEAT switch; adjust setpoint above room temperature
and check that heating system turns on.
2. Adjust setpoint below room temperature and check
that heating system turns off.
3. Press COOL switch; adjust setpoint below room
temperature. Check that cooling system turns on and fan
runs continuously.
4. Press fan LO, MED, HI switches and check that fan
control operates properly.
5. Adjust setpoint above room temperature and check
that cooling system turns off. Fan operates continuously.
6. Adjust thermostat for desired room temperature.

IN COOLING APPLICATION:
1. Close disconnect switch (if used).
2. Adjust setpoint below room temperature and check
that cooling system turns on.
3. Adjust setpoint above from temperature and check
that cooling system turns off.
4. Adjust thermostat for desired room temperature.

If questions arise regarding this product, contact your
distributor or local Honeywell representative.

NOTE: Wider temperature differential ranges can occur
when used in cooling applications with current draws
that are more than four amps. If a wider differential
range is unacceptable, use a T6051 Heavy Duty Line
Voltage Thermostat for a smaller differential range.

7

63-2051—4

Home and Building Control
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Printed in U.S.A.

Home and Building Control
Honeywell Limited—Honeywell Limitée
740 Ellesmere Road
Scarborough, Ontario
M1P 2V9

8

Helping You Control Your World

QUALITY IS
KEY



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V1.2 (40-bit)
User Access                     : Print, Copy, Fill forms, Extract, Assemble, Print high-res
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 5.00 for Macintosh
Keywords                        : 
Create Date                     : 2002:04:26 18:08:01Z
Modify Date                     : 2009:02:26 09:15:42-06:00
Metadata Date                   : 2009:02:26 09:15:42-06:00
Creator Tool                    : Adobe PageMaker 6.5
Format                          : application/pdf
Creator                         : Honeywell ACS Technical Communications
Description                     : Product Data
Title                           : 63-2051 - T451A, T651A, T694A,B,D,F Light Duty  Line Voltage Thermostats
Document ID                     : uuid:d0ecbbcd-4845-4529-86e0-ca7053774bf7
Instance ID                     : uuid:6fef57b9-6433-4e68-b046-6017ec47fae0
Page Count                      : 8
Subject                         : Product Data
Author                          : Honeywell ACS Technical Communications
EXIF Metadata provided by EXIF.tools

Navigation menu