Honeywell Thermostat T7351 Users Manual 62 0258 Commercial Programmable
2015-01-23
: Honeywell Honeywell-Honeywell-Thermostat-T7351-Users-Manual-262219 honeywell-honeywell-thermostat-t7351-users-manual-262219 honeywell pdf
Open the PDF directly: View PDF .
Page Count: 12
Download | |
Open PDF In Browser | View PDF |
T7351 Commercial Programmable Thermostat FOR SINGLE- OR MULTI-STAGE CONVENTIONAL/HEAT PUMP SYSTEMS INSTALLATION INSTRUCTIONS APPLICATION The T7351 Commercial Programmable Thermostat controls 24 Vac commercial single zone heating, ventilating and air conditioning (HVAC) equipment. The T7351 consists of a thermostat and subbase. The thermostat includes the display and keypad for 7-day programming. The subbase includes equipment control connections. The subbase mounts on the wall and the thermostat mounts to the subbase. MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly. Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control. If you have questions, call Honeywell Customer Care Center at 1-800-468-1502. INSTALLATION When Installing this Product... 1. 2. 3. 4. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Check ratings given in instructions and on the product to ensure the product is suitable for your application. Installer must be a trained, experienced service technician. After installation is complete, check out product operation as provided in these instructions. CAUTION Location Do not install the thermostat where it can be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall behind the thermostat. IMPORTANT To avoid electrical interference, which can cause erratic performances, keep wiring runs as short as possible and do not run thermostat wires adjacent to the line voltage electrical distribution systems. Use shielded cable. The cable shield must be grounded only at the controlled equipment case. Subbase WHEN USED TO SENSE ROOM TEMPERATURE Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. (See Fig. 1.) WHEN NOT USED TO SENSE ROOM TEMPERATURE When using the remote-mounted temperature (and humidity) sensor(s) to sense ambient conditions, install the thermostat in an area that is accessible for setting and adjusting the temperature and settings. Install the remote-mounted sensor(s) about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature (See Fig. 1). If multiple remote sensors are required, they must be arranged in a temperature averaging network consisting of four sensors (See Fig. 2). NOTE: Only T7770 models with no setpoint adjustment can be used for temperature averaging. Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry. Disconnect power supply before installation. 62-0258 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT SUBBASE T4 YES NO T7770A T NO NO T3 T7770A T T T 5 FEET (1.5 METERS) T7770A T7770A T T T T M4823A Fig. 1. Typical location of thermostat or remote-mounted sensor. Mounting Subbase The subbase mounts horizontally. M19606A Fig. 2. Four T7770A Sensors providing temperature averaging network for T7351 Thermostat. IMPORTANT • When using the internal temperature or humidity sensor, the device must be mounted horizontally (with the LCD facing upwards). Precise leveling is not needed. • When using remote room temperature and humidity sensors, thermostat mounting orientation does not matter. WIRES THROUGH WALL MOUNTING HOLES Wall mounting (using standard drywall screws) is standard. Mounting to a 2 in. by 4 in. (50.8 mm by 101.6 mm) wiring box can be accomplished: — for a horizontal box, no extra hardware is required. — for a vertical box, part 209651A is required. — Mount to European standard wall box (having 2.4 in. (60.3 mm) between mounting screws in a horizontal line) with or without adaptive hardware. 1. WALL ANCHORS (2) Position and level the subbase. MOUNTING SCREWS NOTE: A level wallplate is only for appearance. The thermostat functions properly when not level. 2. 3. 4. 5. 6. 7. Use a pencil to mark the mounting holes. (See Fig. 3). Remove the subbase from the wall and drill two 3/ 16 in. (4.8 mm) holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 in. (5.6 mm) holes. Gently tap anchors (provided) into the drilled holes until flush with the wall. Position the subbase over the holes, pulling wires through the wiring opening. Loosely insert the mounting screws into the holes. Tighten mounting screws. 62-0258 M19608 Fig. 3. Mounting the subbase. Mounting Thermostat on Subbase (Fig. 4) With the subbase installed, mount the thermostat: 1. Engage top subbase tabs into the thermostat top. 2. Swing the thermostat down. 3. Press the lower edge of the case to latch. NOTE: To remove the thermostat from the wall, first pull out at the bottom of the thermostat; then remove the top. 2 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT A. ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE. SETTINGS Using Thermostat Keys The thermostat keys are used to: • set current time and day, • program times and setpoints for heating and cooling, • override the program temperatures, • display present setting, • set system and fan operation. NOTE: See Fig. 5 for keypad information. Setting Temperature B. PRESS LOWER EDGE OF CASE TO LATCH. Refer to Table 2 for the default temperature setpoints. To set the Occupied and Not Occupied Heat and Cool setpoints, simply press the Heat and Cool button under the Occupied or Not Occupied area of the keypad. To set the Standby Heat setpoint, press both the Occupied and Not Occupied Heat buttons simultaneous. To set the Standby Cool setpoint, press the Occupied Cool and Not Occupied Heat buttons simultaneously. Setting System and Fan System default setting is Auto. Fan default setting is On. NOTE: Use System and Fan keys to change settings. System Settings M19609 Fig. 4. Mounting thermostat on subbase. Wiring Follow equipment manufacturer wiring instructions when available. Refer to the Wiring Diagram section for typical hookups. A letter code is located near each terminal for identification. IMPORTANT All wiring must comply with local electrical codes and ordinances. NOTE: Maximum (and recommended) wire size is 18gauge. Do not use wire smaller than 22-gauge. 1. 2. 3. 4. Loosen subbase terminal screws and connect system wires. Securely tighten each terminal screw. Push excess wire back into the hole in the wall. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat. — Auto: Thermostat automatically changes between heating and cooling based on indoor temperature. — Cool: Thermostat controls cooling. — Off: Heating, cooling, and fan are all off. — Heat: Thermostat controls heating. — Em Heat: Auxiliary heat serves as first stage. Compressor stages are locked off. Fan Settings — On: See Table 1. — Auto: Fan always cycles with call for heat or cool. — Conventional: The equipment (i.e. plenum switch) controls fan operation in heat mode. Thermostat controls fan operation in cool mode. — Electric Heat: Thermostat controls fan operation in both heat and cool modes. NOTES: Fan operation can extend (delay Off) after the heating/cooling turns off: — Heating choices are 0 or 90 seconds. — Cooling choices are 0 or 40 seconds. Table 1. Fan On Control Logic. Occupancy Scheduled Call for Heat/Cool Sensor Signal Yes No Occupied Occupied On Occupied Standby On Off a Standby — On On Not Occupied — On Off a a On In heat mode, when set for conventional heat, the equipment (i.e. plenum switch) could power the fan despite the T7351. 3 62-0258 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Set Day/Time Temperature Occupied HEAT Not Occupied COOL HEAT COOL Time System Fan Run Copy HEAT COOL ON AUTO Schedule Schedule Day Clear Occupied Not Occupied Start Time Override Temporary Temporary Occupied Not Occupied Day M19610 Fig. 5. Thermostat key locations. INSTALLER SETUP Setup Using Keypad For most applications, the thermostat factory settings do not need to be changed. Review the factory settings in Table 2. NOTE: When power is first applied to the thermostat, the display will show all segments (see Fig. 6). The installer uses the Installer Setup to customize the thermostat to specific systems A combination of key presses are required to use the Installer Setup feature: 1. To enter the Installer Setup, press and hold both the Run Schedule and the Copy keys until DEGREES 00 (or DEGREES 01) displays. Table 2. Default Setpoints. Control Occupied Not Occupied NOTE: Installer Setup will display WAIT and is unavailable for 30 seconds after power up. Standby Heating 70° F (21° C) 55° F (13° C) 67° F (19° C) Cooling 75° F (24° C) 85° F (29° C) 78° F (26° C) 2. To advance to the next Installer Setup number, press . NOTE: Pressing Run/Copy again while in this mode displays the T7351 firmware version number. Temporary Standby Set Set Schedule Room Not Occupied12 StartTime AM PM System Em Heat % MonTueWedThuFri SatSunHol MinsDays Fan OnAuto Off Cool Auto Dehumid M19611 3. 4. 5. 6. Fig. 6. LCD display of all segments. CAUTION Possible Equipment Damage. Fan must be running when system is operating. Heat pump and electric heat systems must be configured correctly to prevent equipment damage caused by the system running without the fan. To return to a Setup item, cycle through the options. To change a setting, use the up ! or down " key. To exit the Installer Setup, press Run Schedule. Display prompts SAV CFG (save configuration). a. If you want to save the new configuration, use the up ! or down " key to change NO to YES before pressing Run Schedule. b. If you want the configuration to remain as it was before starting this change, ensure the display indicates SAV CFG NO and press Run Schedule. NOTE: Installer Setup is automatically exited after five minutes with no key pressed. Upon this automatic exit, all changes are lost. Configuration Configuration can be done with the keypad using the Installer Setup (ISU). 62-0258 4 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Table 3. Installer Setup. Text Default Choices Notes DEGREES 0 0 -1 Degree Temperature Format 0: Degrees F 1: Degrees C CLOCK 0 0-1 Clock Display Format 0: 12 hour 1: 24 hour KEYLOCK 0 0-3 Keypad Lockout Level 0: None 1: Lockout all keys except Set Day, Set Time, Set Date, Set Holidays, Temporary Occupied, Temporary Not Occupied, System, Fan, Up, Down and Information 2: Lockout all keys except Set Day, Set Time. Set Date, Set Holidays, Temporary Occupied, Temporary Not Occupied, Up, Down and Information 3: Lockout all keys except Information HEATPMP 0 0-2 Application Type Selection 0: Conventional 1: Heat Pump - Cooling (Energize O/B on call for cool) 2: Heat Pump - Heating (Energize O/B on call for heat) COOLSTG 1 0-4 Number of Cooling Stages 0: 0 Stages of Cooling 1: 1 Stages of Cooling 2: 2 Stages of Cooling 3: 3 Stages of Cooling 4: 4 Stages of Cooling (W3 will be used as 4th stage relay) HEATSTG 1 0-3 Number of Heating Stages 0: 0 Stages of Heating 1: 1 Stages of Heating 2: 2 Stages of Heating (This is the max if 4 cooling stages is selected) 3: 3 Stages of Heating AUX STG 0 0-2 Only shown when Heat Pump is selected 0: 0 Aux Stages 1: 1 Aux Stages 2: 2 Aux Stages AUX CON 0 0-3 Aux Contact Functionality 0: Time of Day 1: Economizer 2: Dehumid - Hot Gas Bypass 3: Simple Dehumid WALLMOD 0 0-3 Remote Room Sensor Selection 0: Local sensor only 1: T7770A/D (Remote Sensor, No Remote Setpoint, Bypass 0) 2: T7770B/C (Remote Sensor, Remote Setpoint, Bypass 0) 3: T7771 (Remote sensor, Remote Setpoint, Bypass 1) (Display only if sub-base 2, 3, 4+) (This item is not displayed when OATSENS 0 0-1 Outdoor Air Sensor Selection 0: None 1: Remote Outdoor Air Sensor DATSENS 0 0-1 Discharge Air Sensor Selection 0: None 1: Remote Discharge Air Sensor HUMSENS 0 0-2 Room Humidity Sensor selection 0: None 1: On Board Sensor 2: Remote Sensor OCCSENS 0 0-1 Occupancy Sensor Selection 0: None 1: Remote Occ Sensor FAN HT 0-1 Fan Operation on Heat 0: Conventional (Equipment controls Fan) 1: Electric (Thermostat turns on Fan with call for Heat) 0 5 62-0258 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Table 3. Installer Setup. (Continued) Text Default Choices Notes XFAN HT YES YES or NO Extended Fan on Heat NO: None YES: 90 seconds XFAN CL NO YES or NO Extended Fan on Cool NO: None YES: 40 seconds STRTDEL 0 0 - 15 Sequential Start Delay 0 to 150 seconds in 10 second increments ADVANCE NO YES or NO Advanced Settings NO: Hide YES: Show TMP LIM 3 0-5 Temporary Setpoint Adjustment 0: 0 Deg. F 1: 1 Deg. F 2: 2 Deg. F 3: 3 Deg. F 4: 4 Deg. F 5: 5 Deg. F TMP OCC 3 1-8 Temporary Occupied Duration 1 to 8 hours TMP CAL 0 -4 - 3 Temporary Display Adjustment 0 - 3 = 0 to 3 DDF 4 - 7 = -4 to -1 DDF MINCOOL 45° F (7° C) 45° - 99° F (7° - 37° C) Min Cool Setpoint MAXHEAT 90° F (32° C) 40° - 90° F (4° - 32°) Max Heat Setpoint HEATLCK NO YES or NO Heating Lockout (Only displayed if Outdoor Air Sensor is selected) NO: None YES: Enabled HTLCKSP 70° F (21° C) -40° - 120 ° F (-40° - 49° F) Heating Lockout Temperature (Display only if Remote Outdoor Air Sensor is configured) COOLLCK NO YES or NO Cooling Lockout (Only displayed if Outdoor Air Sensor is Selected) NO: None YES: Enabled CLLCKSP 35° F (2° C) -40° - 120° F (-40° - 49° C) Cooling Lockout Temperature (Display only if Remote Outdoor Air Sensor is configured) DAT LL NO YES or NO Discharge Low Limit (Only displayed if Discharge Air Sensor is Selected) NO: None YES: Enabled DATLLSP 45° F (7° C) 35° - 60° F (2° - 16° C) Discharge Low Temp Limit (Display only if Discharge Sensor is configured) DAT HL NO YES or NO Discharge High Limit (Only displayed if Discharge Air Sensor is Selected) NO: None YES: Enabled DATHLSP 110° F (43° C) 65° - 140° F (18° - 60° C) Discharge High Temperature Limit (Display only if Discharge Sensor is configured) 0-5 Dehumidification 0: None 1: MinOn Time 2: Reset Temp Setpoint 3: Reset w/ MinOn 4: Reheat 5: Reheat w/ Min On DEHUMID 0 DEH MIN 5 5 - 15 Dehumidify Minutes On DEH TMP 2 1-5 Dehumidify Temp Reset MINHTRT 5 0 - 20 DDF/HR Minimum Heat Recovery Ramp Rate MAXHTRT 8 0 - 20 DDF/HR Maximum Heat Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected) MINHTOA 62-0258 0° F -20° - 120° F (-18° C) (-29° - 49° C) Minimum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) 6 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Table 3. Installer Setup. (Continued) Text Default Choices Notes MAXHTOA 40° F (4° C) -20° - 120° F (-29° - 49° C) Maximum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) MINCLRT 3 0 - 20 DDF/HR Minimum Cool Recovery Ramp Rate MAXCLRT 6 0 - 20 DDF/HR Maximum Cool Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected) MINCLOA 90° F (32° C) -20° - 120° F (-29° - 49° C) Minimum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) MAXCLOA 70° F (21° C) -20° - 120° F (-29° - 49° C) Maximum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) DSTMON1 3 0 - 12 DLS Spring Month DSTDAY1 0 - 31, 32 - 74 DLS Spring Day 0 - 31 = Day of Month 32 = Last Day of Month 33 = First Sunday etc… DSTMON2 11 0 - 12 DLS Fall Month DSTDAY2 33 0 - 31, 32 - 74 DLS Fall Day 0 - 31 = Day of Month 32 = Last Day of Month 33 = First Sunday etc… HT RESP 1 0-3 0: Standard - 3 cph 1: Medium - 6 cph 2: Fast - 9 cph 3: Super Fast - 20 cph CL RESP 0 0-1 0: Standard - 3 cph 1: Fast - 4 cph (DayLight Savings options only display when Date is valid) 40 Holidays and 365 - Day Clock The T7351can be configured to schedule up to 10 separate holidays, each with a duration of up to 99 days. To enable this function, the user must set the date: 1. 2. 3. 4. 5. Press Set Day and Set Time keys simultaneously. Use the Up/Down keys to set the date to YES, then press the key. Use the Up/Down keys to set the month, then press the key. Use the Up/Down keys to set the day, then press the key (See Table 4 for valid day choices). Use the Up/Down keys to set the year, then press the key. Holidays can be set in the following manner: 1. Press the “Temporary Occupied” and Temporary Not Occupied” keys simultaneously. 2. The month (MON) of the first holiday is then displayed (00 means the holiday is ignored). 3. Use the Up/Down keys to set the month, then press the key. 4. Use the Up/Down keys to set the day, then press the key (see Table 4 for valid day choices). 5. Use the Up/Down keys to set the duration. The first holiday is now set and pressing the key will take you to programming the second holiday (denoted by the number 2 on the screen). Table 4. Valid Day Values. Value Description 1 to 31 Day of month Value 42 Description Value Description Value Description Second Tuesday 53 Third Saturday 64 Fifth Wednesday 32 Last Day of Month 43 Second Wednesday 54 Fourth Sunday 65 Fifth Thursday 33 First Sunday 44 Second Thursday 55 Fourth Monday 66 Fifth Friday 34 First Monday 45 Second Friday 56 Fourth Tuesday 67 35 First Tuesday 46 Second Saturday 57 Fourth Wednesday 68 Fifth Saturday Last Sunday 36 First Wednesday 47 Third Sunday 58 Fourth Thursday 69 Last Monday 37 First Thursday 48 Third Monday 59 Fourth Friday 70 Last Tuesday 38 First Friday 49 Third Tuesday 60 Fourth Saturday 71 Last Wednesday 39 First Saturday 50 Third Wednesday 61 Fifth Sunday 72 Last Thursday 40 Second Sunday 51 Third Thursday 62 Fifth Monday 73 Last Friday 41 Second Monday 52 Third Friday 63 Fifth Tuesday 74 Last Saturday 7 62-0258 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Table 5. T7351 Key Function Summary. Grouping Information Button Down Arrow Information Up Arrow Temperature Set Override Schedule a Definition " Lowers setpoint, day, or time. When setting times or temperatures, hold key down to continuously decrease value. Also can make temporary change in temperature setpoint. Obtains information (where humidity “high-limit” can be set), cycles through setup options. ! Raises setpoint, day, or time. When setting times or temperatures, hold key down to continuously increase value. Also can make temporary change in temperature setpoint. Occupied Heat Sets Occupied Heat setpoint. Occupied Cool Sets Occupied Cool setpoint. Not Occupied Heat Sets Not Occupied Heat setpoint. Not Occupied Cool Sets Not Occupied Cool setpoint. Day Sets day of week. Tapping key with 'Set Value' segment on increases current day (same effect as Up Arrow key). Time Sets time. Tapping key with “Set Value” segment on increases time in one hour increments. Temporary Occupied Temporary occupied setting for length of time defined by installer. User can modify setpoints. Temporary Not Occupied Sets holiday length. User selects number of days (“0”-”99”), or “---” for continuous override. Day Selects day schedule to modify. (Used also with copy key.) Occupied Selects occupied event start times for specified day. Repeatedly press this key to toggle between two occupied events. Not Occupied Selects not occupied event start times for specified day. Repeatedly press this key to toggle between two not occupied events. Clear Start Time Clears start time for specified period and day. Copy Copies schedule from one day to another. System Selects System Mode. Toggles through Em Heat, Heat, Off, Cool, and Auto. Fan Selects fan operation mode. Toggles between On and Auto.a Run Schedule Resumes running schedule (cancels Temporary Occupied action, Holiday, and/or Temporary setpoint changes.) On: Continuous fan operation (occupied and standby). During not occupied periods, fan cycles with call for heat or cool. Auto: Fan cycles with call for heat or cool during all periods. (See Product Data Sheet, form 63-2605, for more details). NOTES: The display returns to default screen after pressing Run Schedule (or after a period of time without keypress): — ten seconds: when returning from temporary setpoint changes, info screen, temp occ, and temp not occ. — one minute: when returning from setting clock/day. — ten minutes: when returning from System Checkout. — five minutes: when returning from all other modes. Special Functions Restore Factory Configuration (Run/Clear) IMPORTANT This operation erases current configuration and restores factory defaults for all configuration, parameters, setpoints and schedules. To regain the old requires device reconfiguration. 1. Press both Run Schedule and Clear Start Time. 2. The display gives the option to revert to FAC CFG. a. To restore the factory defaults, press up ! or down " until the display indicates YES. b. To cancel this option, ensure the display indicates NO. 3. Press Run Schedule. 62-0258 8 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Get Factory Schedule (Info/Clear) Performing this operation reverts the schedules to the factory defaults: 1. Press both Info and Clear Start Time. 2. The display gives the option to revert to FAC SCH. a. To restore the factory schedule, press up ! or down " until the display indicates YES. b. To cancel this option, ensure display indicates NO. 3. Press Run Schedule. Test Mode (Occupied/Not Occupied/Schedule Day) CAUTION Possible Equipment Damage. Equipment damage can result if compressor is cycled too quickly. The minimum off time for compressors is bypassed during Test Mode. Equipment damage can occur if the compressor is cycled too quickly. Use the Test Mode to check the thermostat configurations and operation. To start the system test: 1. Press Schedule Day, Occupied and Not Occupied simultaneously. 2. The display gives the option to TEST. a. To enter test mode, press up ! or down " until the display indicates IN TEST. b. To cancel this option, ensure display indicates NO TEST. 3. Press Run Schedule. NOTES: — — To verify whether or not the system test is still active, repeat the above process. The system test times out after ten minutes with no key pressed. Save User Schedule (Info/Copy) Performing this operation saves the current schedule (including holidays) to memory, overwriting the old saved schedule: 1. Press both Info and Copy. 2. The display gives the option to revert to SAV SHD. a. To save the current schedule, press up ! or down " until the display indicates YES. b. To cancel this option, ensure display indicates NO. 3. Press Run Schedule. DEHUMIDIFICATION There are five methods through which the T7351 can control for dehumidification. Three of them modify the control algorithm, thus providing limited dehumidification through cooling. The other two use the auxiliary output to control another device. NOTE: The dehumidification high limit can be set within the range of 10 to 90 percent relative humidity. Control Through Cooling Configure using some combination of the following: — Minimum On. — Reheat. — Reset. NOTES: — — Min. ON Time Dehumidifies by increasing the compressor minimum on time (normally 3 minutes) by a programmable amount. This is useful with oversized systems in that it forces the coils to cool to a point where dehumidification can occur. NOTES: — — — Can force wider temperature swings by cooling when setpoint control does not require it. The minimum on time can be set within the range of 5 to 15 minutes. Hysteresis and a minimum timer are used to ensure this behavior does not change with every equipment cycle. Reheat Dehumidifies by operating cooling during typical off time. The T7351 maintains the proper setpoint by running the heat at the same time. IMPORTANT At times during Reheat dehumidification, the T7351 operates heating and the cooling simultaneously. This is normal. NOTES: — — Get User Schedule (Info/Run) Getting the user schedule restores the schedule (including holidays) from saved memory, overwriting the schedule currently in use: 1. Press both Run Schedule and Info. 2. The display gives the option to GET SHD. a. To retrieve the saved schedule, press up ! or down " until the display indicates YES. b. To cancel this option, ensure display indicates NO. 3. Press Run Schedule These methods operate only during cooling. Selecting both Reheat and Reset options can cause frequent setpoint adjustments. This selection is not recommended. The heat stage never energizes during Reheat if more than one cool stage is on. Reheat mode cannot occur during heating. Reset Temp SetPt The room temperature set point resets to a specified number of degrees below the actual set point when room relative humidity (RH) rises above humidity high limit set point. Though this may not technically reduce relative humidity in the room, it reduces the dew point to provide the customer with a sense of comfort due to a lower temperature setting in the room. As long as RH stays above humidity high limit set point, this set point is maintained. NOTE: Hysteresis and a minimum timer prevent the set point from short interval alternation (between standard and reset set points). 9 62-0258 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Options Utilizing Auxiliary Output Dehumid Hot Gas BP There are two dehumidification options that utilize the auxiliary output. They are: — Simple Dehumidification. — Hot Gas Bypass Dehumidification. The auxiliary output operates as shown in Table 6. Simple Dehumid(ification) High more than one De-energized The auxiliary output: — Energizes when RH rises above humidity high limit. — De-energizes when RH drops below humidity high limit. High one or less Energized Low more than one De-energized Low one or less De-energized NOTES: — — Table 6. Hot Gas Bypass Dehumidification Logic. Humidity Cooling Stages Active Auxiliary Output Auxiliary output during call for multiple cooling stages for two reasons: 1. This method assumes that the cooling provides dehumidification. 2. Multiple cooling stages probably provide necessary dehumidification. 3. Hysteresis and a minimum timer prevent short cycling of this output. Hysteresis and a minimum timer prevent short cycling of this output. Unlike Dehumid Hot Gas BP the relay remains energized during calls for multiple cooling stages. WIRING DIAGRAMS OUTDOOR AIR SENSOR T7770 REMOTE SENSOR 9 8 7 6 5 4 3 2 COMPRESSOR CONTACTOR 2 DISCHARGE AIR SENSOR 1 HEAT RELAY 2 SUBBASE T5 T6 T7 T4 HS T3 HC HP OS M OS M AS AS X RH AUX RC W1 W2 Y2 Y1 G 2 HUMIDITY SENSOR COMPRESSOR CONTACTOR 1 3 1 FAN RELAY HEAT RELAY 1 MOTION SENSOR L2 L2 1 L1 (HOT) ECONOMIZER L1 (HOT) HEATING TRANSFORMER COOLING TRANSFORMER 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER. 3 USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS. M25324 Fig. 7. Typical hookup of T7351F2010 in two-stage heat and two-stage cool heat pump system with two transformers. OUTDOOR AIR SENSOR T7770 REMOTE SENSOR 9 8 7 6 5 4 3 2 HEAT RELAY 2 DISCHARGE AIR SENSOR 1 COMPRESSOR CONTACTOR 4 COMPRESSOR CONTACTOR 2 SUBBASE T5 T6 T7 T4 T3 OS OS AS AS HS HC HP M M X RH W3/Y4 Y3 RC AUX W1 W2 Y2 Y1 G COMPRESSOR CONTACTOR 3 HUMIDITY SENSOR MOTION SENSOR 3 HEAT RELAY 1 4 1 2 L2 FAN RELAY COMPRESSOR CONTACTOR 1 ECONOMIZER L1 (HOT) 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD. 3 HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER. 4 USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS. M19768A Fig. 8. Typical hookup of T7351F201U in two-stage heat and four-stage cool conventional system. 62-0258 10 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT 9 8 7 6 5 4 3 4 OUTDOOR AIR SENSOR T7770 REMOTE SENSOR 2 DISCHARGE AIR SENSOR 1 COMPRESSOR CONTACTOR 2 ECONOMIZER HEAT RELAY 3 HEAT RELAY 2 SUBBASE T5 T6 T7 T4 T3 OS OS AS AS HS HC HP M M X RH AUX W3/Y4 Y3 RC AUX W1 W2 Y2 Y1 G COMPRESSOR CONTACTOR 3 HUMIDITY SENSOR 2 1 3 MOTION SENSOR HEAT RELAY 1 FAN RELAY COMPRESSOR CONTACTOR 1 L2 L1 (HOT) 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD. 3 HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER. 4 USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS. M25319 Fig. 9. Typical hookup of T7350F2010 in three-stage heat and three-stage cool conventional system with one transformer. TROUBLESHOOTING GUIDE (TABLE 7) Table 7. Troubleshooting Information. Symptom Possible Cause Action Display will not come on. Thermostat is not being powered. Check that X terminal is connected to the system transformer. Check for 24 Vac between X and RH terminals. If missing 24 Vac: • Check if circuit breaker is tripped; if so, reset circuit breaker. • Check if system fuse is blown; if so, replace fuse. • Check if the HVAC equipment power switch is in the Off position; if so, set to the On position. • Check wiring between thermostat and HVAC equipment. Replace broken wires and tighten loose connections. If 24 Vac is present, proceed with troubleshooting. Temperature display is incorrect. Thermostat is configured for °F or °C display. Press both Run Schedule and Copy, then reconfigure the display. Bad thermostat location. Relocate the thermostat. Display shows three dashes and a T7351 is set for remote sensing and sensor is missing or circuit degree sign (all systems shut is either open or shorted. down). Temperature settings will not change. (Example: Cannot set heating higher or cooling lower.) Upper or lower temperature limits were reached. Check the temperature setpoints: • Heating limits are 40 to 90°F (7 to 31°C) • Cooling limits are 45 to 99°F (9 to 37°C) Occupied setpoint temperature range stops were configured. Check setpoint stops. If necessary, reconfigure the stop(s). Keypad is locked. When a locked key is pressed, LOCKED appears momentarily on the LCD. Press both Run Schedule and Copy, then change keypad lock level. Room temperature is out of control. Remote temperature sensing is not Check all remote sensors. working. 11 62-0258 T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT Table 7. Troubleshooting Information. (Continued) Symptom Heat will not come on. Cooling will not come on. System indicator (flame: heat, snowflake: cool) is displayed, but no warm or cool air is coming from the registers. Possible Cause Action No power to the thermostat. Check that X terminal is connected to the system transformer. Check for 24 Vac between X and RH terminals. If missing 24 Vac: • Check if circuit breaker is tripped; if so, reset circuit breaker. • Check if system fuse is blown; if so, replace fuse. • Check if the HVAC equipment power switch is in the Off position; if so, set to the On position. • Check wiring between thermostat and HVAC equipment. Replace broken wires and tighten loose connections. If 24 Vac is present, proceed with troubleshooting. Thermostat minimum off time is activated. • Wait up to five minutes for the system to respond. • Configure heating response. System selection is set to Off or Cool. Set system selection to Heat or Auto. No power to the thermostat. Check that X terminal is connected to the system transformer. Check for 24 Vac between X and RH terminals. If missing 24 Vac: • Check if circuit breaker is tripped; if so, reset circuit breaker. • Check if system fuse is blown; if so, replace fuse. • Check if the HVAC equipment power switch is in the Off position; if so, set to the On position. • Check wiring between thermostat and HVAC equipment. Replace broken wires and tighten loose connections. If 24 Vac is present, proceed with troubleshooting. Thermostat minimum off time is activated. • Wait up to five minutes for the system to respond. • Configure cooling response. System selection is set to Off or Heat. Set system selection to Cool or Auto. The call for heat or cool is not yet given. Check if any stage indicators (dots next to the system indicator) are displayed. With no display of stage indicators, no call for cool/heat is yet given. Conventional heating equipment Wait one minute after seeing the on indicator and then check turns the fan on only after the the registers. furnace has warmed to a setpoint. Heating or cooling equipment is not operating. Verify operation of heating or cooling equipment in self-test. Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2007 Honeywell International Inc. 62-0258 J.I. 01-07
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Encryption : Standard V1.2 (40-bit) User Access : Print, Copy, Fill forms, Extract, Assemble, Print high-res Page Mode : UseOutlines XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0 (Windows) Creator Tool : FrameMaker 7.0 Modify Date : 2007:01:09 15:59:39-06:00 Create Date : 1999:07:07 12:30:47Z Metadata Date : 2007:01:09 15:59:39-06:00 Format : application/pdf Title : 62-0258 - T7351 Commercial Programmable Thermostat Creator : Honeywell Technical Communications Description : Installation Instructions Document ID : uuid:c48d6373-18e8-4461-baf9-e833c47e6e08 Instance ID : uuid:d1b771f9-d295-4d96-82b9-ce6a391a68c3 Page Count : 12 Page Layout : SinglePage Subject : Installation Instructions Author : Honeywell Technical CommunicationsEXIF Metadata provided by EXIF.tools