Honeywell Thermostat Tb8220U Users Manual 62 0370 03 Commercial VisionPRO Programmable

TB8220U to the manual 633358c5-4a83-4966-bfb6-3c841a68446f

2015-01-23

: Honeywell Honeywell-Honeywell-Thermostat-Tb8220U-Users-Manual-262249 honeywell-honeywell-thermostat-tb8220u-users-manual-262249 honeywell pdf

Open the PDF directly: View PDF PDF.
Page Count: 16

INSTALLATION INSTRUCTIONS
62-3070-03
TB8220U
Commercial VisionPRO™
Programmable Thermostat
APPLICATION
The TB8220U Programmable Thermostat provides electronic control of 24 Vac heating and cooling systems.
See Table 1 for a description.
Table 1. TB8220U Thermostat Description.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Select Thermostat Location
Select a location for the thermostat about 5 ft (1.5m)
above the floor in an area with good air circulation at
average temperature. See Fig. 1.
Feature Description
Powering Methods Battery only
Direct connection to a 24 Vac transformer only
Direct connection to a 24 Vac transformer with battery backup
System Types Conventional (up to 2 Heat, 2 Cool stages)
Heat Pump (up to 3 Heat, 2 Cool stages)
Changeover Manual or automatic changeover (selectable)
System Setting Heat-Off-Cool-Auto
Fan Setting Auto-On
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—03 2
Fig. 1. Select thermostat location.
Do not install the thermostat where it can be affected by:
Drafts or dead spots behind doors and in corners.
Hot or cold air from ducts.
Radiant heat from sun or appliances.
Concealed pipes and chimneys.
Unheated (uncooled) areas such as an outside wall
behind the thermostat.
Separate Wallplate from Thermostat
1. Separate the wallplate from the thermostat. See
Fig. 2.
Fig. 2. Separate wallplate from thermostat.
Install Wallplate (See Fig. 3)
Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wallplate.
2. Position the wallplate on the wall with the arrow
pointing up. Level the wallplate for appearance only.
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill two
3/16 in. holes in the wall (if drywall) as marked. For
firmer material such as plaster, drill two 7/32 in.
holes. Tap the wall anchors (provided) into the
drilled holes until flush with the wall.
5. Pull the wires through the wire hole on the wallplate
and position the wallplate over the wall anchors.
6. Insert the mounting screws into the wall anchors
and tighten.
Fig. 3. Install wallplate.
WIRING
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Use 18 gauge thermostat wire. Shielded cable is
not required.
NOTES:
Sensor wires must have a cable separate
from the thermostat control cable.
Refer to Table 2 for terminal designation
descriptions.
See Fig. 7 through 17 for wiring diagrams for
specific equipment applications.
1. Select set of terminal identifications that correspond
to your system type (conventional or heat pump).
(See Fig. 4).
Fig. 4. Terminal identifications for system type.
2. Loosen screw terminals used for the application.
5 FEET
[1.5 METERS]
YES
NO
M22258
NO
NO
THERMOSTAT
WIRE HOLE
M22267
WALLPLATE
WALL
MOUNTING
HOLES
M19916
MOUNTING
SCREWS (2)
WALL ANCHORS (2)
WIRES THROUGH WALL
AND WIRE SLOT
M22780A
Y2
L
A
W1
S1
S2
RC
R
O/B
Y
G
C
Y2
L
A
W2
S1
S2
RC
R
W
Y
G
C
SCREW
TERMINALS
HEAT PUMP
CONVENTIONAL
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
3 62-3070—03
3. Insert the wires into the terminal block and tighten
each screw terminal. See Fig. 5.
Fig. 5. Insert wires into terminal block.
4. Push excess wire back into the wall opening and
restrict wires to the shaded area. See Fig. 6.
5. Plug the wall opening with nonflammable insulation
to prevent drafts from affecting the thermostat. Fig. 6. Restrict wires to shaded area of wire hole.
Table 2. Terminal Designation Descriptions.
NOTES:
1. When used in a single-transformer system,
leave metal jumper wire in place between Rc
and R. If used on a two-transformer system,
remove metal jumper wire between Rc and R.
2. Common wire is optional when thermostat is
used with batteries. When using separate
transformers for heating and cooling, the
common must come from the cooling
transformer.
3. If thermostat is configured for a heat pump in
the Installer Setup, configure changeover
valve for cool (O-factory setting) or heat (B).
4. Reference economizer literature for wiring
details. When set for economizer operation,
the A terminal provides the occupancy signal.
(Power indicates occupied.)
5. Sensor wires must have a cable separate
from the thermostat control cable.
Terminal “A” Wiring Details for Economizers
Wire the A terminal to the W7212 “N” terminal, or the
W7459 “TR” terminal.
When using dual transformers at the thermostat, the
heating transformer must power the economizer.
The A signal is powered from the R terminal and
energizes the economizer to signal occupied status
and drive the damper to the set minimum position.
Table 3. Wiring Diagrams.
M19917
WALLPLATE
M22266
WALL OPENING
WIRE
SHADED AREA
Terminal Designation Description
Rc (see Note 1) Power for cooling—connect to secondary side of cooling system transformer.
R (see Note 1) Power for heating—connect to secondary side of heating system transformer.
Y Compressor output.
C (see Note 2) Common wire from secondary side of cooling system transformer.
WHeat relay.
G Fan relay.
W2 Second stage heat relay.
Y2 Second stage cooling.
O/B (see Note 3) Changeover valve for heat pumps.
A (see Note 4) Economizer/Time-Of-Day (TOD) output—powered via R terminal.
S1 (See Note 5) Optional outdoor or indoor remote sensor.
S2 (See Note 5) Optional outdoor or indoor remote sensor.
L Powers red LED behind plastic in upper right corner of the thermostat.
W1 Auxiliary Heat Relay Output (Head Pump Mode 2H/1C, 3H/2C)
System Type
Wallplate
Terminal
Identifications
Wiring
Diagram
Figure
Standard Heat/Cool Conventional 7, 8
Heat Only Conventional 9
Heat Only with Fan Conventional 10
Cool only Conventional 11
Standard Multistage
up to 2 Heat/2 Cool
Conventional 12, 13
Heat Pump
(No Auxiliary Heat)
Heat Pump 14, 15
Heat Pump
(with Auxiliary Heat)
Heat Pump 16, 17
Multiple T7770A Sensors 18, 19, 20
Multiple C7189U Sensors 21
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—03 4
Conventional System Wiring
Fig. 7. Typical wiring of single transformer
1H/1C system.
Fig. 8. Typical hookup of dual transformer
1H/1C system.
Fig. 9. Typical hookup of heat-only system.
Fig. 10. Typical hookup of heat-only system with fan.
Fig. 11. Typical hookup of cool-only system.
COMPRESSOR CONTACTOR
M22781A
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY
ECONOMIZER
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
1
2
3
Y2
L
A
W2
S1
S2
2
3
RC
R
W
Y
G
C
L1
(HOT)
L2
1
24 VAC
COMPRESSOR CONTACTOR
M22782A
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT
TO THE COOLING TRANSFORMER SECONDARY.
1
3
2
3
2
Y2
L
A
W2
S1
S2
2
RC
R
W
Y
G
C
ECONOMIZER
L1
(HOT)
L2
1
24 VAC
L1
(HOT)
L2
1
24 VAC
M22783A
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
OPTIONAL.
1
3
2
3
2
L1
(HOT)
L2
1
24 VAC
Y2
L
A
W2
S1
S2
2
RC
R
W
Y
G
C
ECONOMIZER
M22784A
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY
FAN RELAY
ECONOMIZER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
1
2
3
3
Y2
L
A
W2
S1
S2
2
RC
R
W
Y
G
C
L1
(HOT)
L2
1
24 VAC
M22785A
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
1
3
2
3
COMPRESSOR CONTACTOR
Y2
L
A
W2
S1
S2
2
RC
R
W
Y
G
C
L1
(HOT)
L2
1
24 VAC
ECONOMIZER
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
5 62-3070—03
Fig. 12. Typical hookup of single transformer
multistage system (up to 2H/2C). Fig. 13. Typical hookup of dual transformer multistage
system (up to 2H/2C).
M22786A
HEAT RELAY 2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
1
3
2
3
COOL RELAY 1
HEAT RELAY 1
COOL RELAY 2
Y2
L
A
W2
S1
S2
2
RC
R
W
Y
G
C
L1
(HOT)
L2
1
24 VAC
ECONOMIZER
M22787A
HEAT RELAY 2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT
TO THE COOLING TRANSFORMER SECONDARY.
1
3
2
3
COOL RELAY 1
HEAT RELAY 1
COOL RELAY 2
Y2
L
A
W2
S1
S2
2
RC
R
W
Y
G
C
L1
(HOT)
L2
1
24 VAC
L1
(HOT)
L2
1
24 VAC
ECONOMIZER
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—03 6
Heat Pump System Wiring
Fig. 14. Typical hookup of single-stage heat pump
with no auxiliary heat (1H/1C).
Fig. 15. Typical hookup of multistage heat pump with
no auxiliary heat (2H/2C).
Fig. 16. Typical hookup of single-stage heat pump
with auxiliary heat (2H/1C).
Fig. 17. Typical hookup of multistage heat pump
with auxiliary heat (3H/2C).
COMPRESSOR CONTACTOR
M22788A
CHANGEOVER VALVE
FAN RELAY
1
2
3
4
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
Y2
L
A
W1
S1
S2
2RC
R
O/B
Y
G
C
4
L1
(HOT)
L2
1
24 VAC
5
ECONOMIZER
COMPRESSOR 1
COMPRESSOR 2
M22789A
CHANGEOVER VALVE
FAN RELAY
1
2
3
4
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
Y2
L
A
W1
S1
S2
2RC
R
O/B
Y
G
C
4
L1
(HOT)
L2
1
24 VAC
5
ECONOMIZER
COMPRESSOR CONTACTOR
ECONOMIZER
M22790A
CHANGEOVER VALVE
FAN RELAY
1
2
3
4
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
Y2
L
A
W1
S1
S2
2RC
R
O/B
Y
G
C
4
L1
(HOT)
L2
1
24 VAC
5
AUXILIARY HEAT RELAY
COMPRESSOR 1
COMPRESSOR 2
M22791A
CHANGEOVER VALVE
FAN RELAY
1
2
3
4
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A
CABLE SEPARATE FROM THE THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
Y2
L
A
W1
S1
S2
2RC
R
O/B
Y
G
C
4
L1
(HOT)
L2
1
24 VAC
5
ECONOMIZER
AUXILIARY HEAT RELAY
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
7 62-3070—03
Sensor Wiring for Temperature Averaging
Fig. 18. Wiring four T7770A1006 (20K ohm) Sensors.
Fig. 19. Wiring two T7770A3002 (10K ohm) Sensors to
provide a temperature averaging network.
Fig. 20. Wiring two T7770A1006 (20K ohm) Sensors
and one T7770A3002 (10K ohm) sensor to provide a
temperature averaging network
Fig. 21. Wiring four C7189U (10K ohm) Sensors to
provide a temperature averaging network.
M22831
S1 S2
TT
SUBBASE
T7770A
TT
T7770A
TT
T7770A
TT
T7770A
M22933
S1 S2
SUBBASE
T7770A3002
T4 T3
T7770A3002
T4 T3
1
11
THE T7770A3002 IS A 10K OHM SENSOR.
M22934
T4 T3
T7770A3002
1
1
THE T7770A3002 IS A 10K OHM SENSOR.
S1 S2
TT
SUBBASE
T7770A1006
TT
T7770A1006
M22935
WIRES MUST HAVE A CABLE SEPARATE FROM
THE THERMOSTAT CABLE.
1
1
C7189 C7189
C7189 C7189
Y2
S2
W2
S1
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—03 8
POWER THE THERMOSTAT
You can choose from three methods to power the
thermostat:
Batteries only (AAA alkaline).
24 Vac direct connection only.
24 Vac direct connection with battery backup (AAA
alkaline).
Wiring 24 Vac Common
Single-Transformer System—Connect the common
side of the transformer to the C screw terminal of the
thermostat wallplate. Leave the metal jumper wire in
place between Rc and R.
Two-Transformer System—Connect the common side
of the cooling transformer to the C screw terminal of
the thermostat wallplate. Remove the metal jumper
wire between Rc and R.
Installing Batteries
1. Install three AAA alkaline batteries on the back of
the thermostat as marked. See Fig. 22.
Fig. 22. Installing batteries.
2. Locate and remove the tab labeled Remove. See
Fig. 23.
IMPORTANT
This tab must be removed in order to set the
real-time clock.
Fig. 23. Remove tab labeled REMOVE from
thermostat back.
Setting Calendar and Time
Setting Calendar
This thermostat is designed to, under normal use,
automatically keep current time and day in memory for up
to ten years once the calendar is set. There are two ways
to set the calendar for this thermostat:
SETTING CALENDAR WHEN THERMOSTAT IS FIRST POWERED
When the thermostat is first powered, the display is ready
to set the calendar and time. The thermostat proceeds
through a sequence of setup screens. See Fig. 24.
SETTING CALENDAR AFTER THERMOSTAT IS ALREADY
FUNCTIONING
See steps 1 through 4, in the Advanced Settings section,
to set year, month and day.
Fig. 24. Setting calendar and time after initial powerup.
Mount Thermostat to Wallplate
1. Align the terminal screw blocks with the pins on the
back of the thermostat.
2. Push the thermostat straight onto the wallplate until
it snaps into place. See Fig. 25.
M19918
BATTERIES (3)
REMOVE DURING
INSTALLATION
M19920
REMOVE
TAB
REMOVE DURING
INSTALLATION
DONE
MON
MON
TUE WED
WED
THU
THU
FRI
FRI
S
S
A
A
SUN
CHANGE FILTER UV LAMP HUMIDIFIER PAD
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
DONE
MON
MON
WED
WED
THU
THU
FRI
FRI
S
S
A
A
SUN
PM
CHANGE FILTER UV LAMP HUMIDIFIER PAD
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
SET CURRENT DAY
SET MONTH
USE ARROWS TO SET YEAR AND TIME M22761
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
9 62-3070—03
Fig. 25. Mount thermostat to wallplate.
Advanced Settings
The thermostat has advanced settings to match the HVAC
system. These settings can be adjusted to match specific
needs. Access to these settings is obtained as follows:
1. From the main screen, press SYSTEM. Five blank
touch keys show on the bottom of the screen
between DONE and CANCEL.
2. Press and hold the two blank keys on either side of
the center blank key for approximately five seconds.
(See Fig. 26.)
3. The Setup Number displays to the lower-left area of
the screen. It is a four-digit code beginning with
zero. The current setting is displayed to the right.
NOTE: To cycle through the Setup Numbers, press the
up or down arrow.
INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)
Fig. 26. Entering Installer Setup.
Installer System Tests
Use the Installer System Test to test the heating, cooling
and fan. Refer to the latter portion of Table 4.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling
and fan. The setting chosen for System Type
(Installer Setup Number 0170) can prevent some
System Test Numbers from appearing.
WALL
M19919
REMOVE DURING
INSTALLATION
D
O
N
E
CANC
T
U
WE
TH
FR
SA
SU
S
Y
S
T
E
M
EM
HEAT
O
F
F
Followin
g
Sc
h
edu
l
e
In
s
i
de
Se
t T
o
M19923
Table 4. Installer Setup Menu.
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes
0120 Date (Year Upper) 20 20—20xx
21—21xx
Available year range: 2001 - 2178
0130 Date (Year Lower) 04 00-99 Available year range: 2001 - 2178
0140 Date (Month) 6 1-12
0150 Date (Day) 15 1-31 (Month Dependent)
0160 Schedule Options 4 0—Non-Programmable
4—Programmable
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—03 10
0170 System Selection 8 1—1H/1C Conv
2—1H/1C HP
3—1H w/o fan
4—1H with fan
6—1C
7—2H/1C HP (Aux. Heat)
8—2H/2C Conv
9—2H/1C Conv
10—1H/2C Conv
11—2H/2C HP
12—3H/2C HP (Aux.
Heat)
To use the Emergency Heat button, select setting
#7 or #12. See Fig. 16 or 17 for auxiliary heat
wiring.
0175 TOD/Economizer
output (terminal A)
0 0—Unused
1—TOD
2—Economizer
Economizer energizes A during a call for cool.
TOD energizes A during Occupied period, and de-
energizes A during Unoccupied.
0180 Heat Fan Operation 0 0—Fossil
1—Electric
Only shown for conventional system with heat
stages and fan capability selected. If heat pump is
selected, fan defaults to electric.
0185 Pre-occupancy
Purge Duration
0 0—no duration
1—one hour
2—two hours
3—three hours
Shown only if system has fan and schedule
programmable.
Pre-occupancy purge enabled by nonzero duration
(and sends economizer to minimum position).
0190 Reversing Valve
O/B
0 0—O (O/B On Cool)
1—B (O/B On Heat)
Only shown with heat pump system selected.
0220 Cycles Per Hour
(CPH) for first stage
compressor
3 1-6 Only shown for system with cool stages. Selection
in this stage changes default CPH of second stage
cool.
0230 CPH for second
stage compressor
3 1-6 Only shown if two stages of cool selected.
0240 CPH for first stage
conventional heat
5 1-12 Only shown if system is conventional with heat
stages.
Selection in this stage changes default CPH of
second stage heat.
0250 CPH for second
stage conventional
heat
9 1-12 Only shown with at least two stages conventional
heat or 2H/1C heat pump selected.
0260 CPH for third Stage
Heat
9 1-12 Only shown if 3H/2C heat pump is selected.
0270 CPH for Auxiliary
Heat
9 1-12 Only shown if multi-stage heat pump is selected
(heat pump with more heat than cool stages).
0280 Continuous
Backlight
0 0—No
1—Yes
Always shown. If AC power not present the option
is overridden and normal backlight operation
occurs.
0300 Changeover 1 0—Manual
1—Auto
Only shown if system has both heat and cool
stages.
0310 Deadband 3°F
(2°C)
2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
Only shown if Automatic Changeover Selected
0320 Temperature
Indication Scale
0 0—°F
1—°C
0330 Daylight Saving 2 0—Disabled
1—Enabled (US 1987)
2—Enable (US 2007)
3—Enabled (Europe)
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
11 62-3070—03
0340 Remote
Temperature
Sensor
0 0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor
Averaging would not include on-board sensor. It is
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing
compressor lockout while displaying temperature).
0350 Heat Pump
Compressor
Lockout
0 0—None
15(-9.5)—15°F (-9.5°C)
20(-6.5)—20°F (-6.5°C)
25(-4.0)—25°F (-4.0°C)
30(-1.0)—30°F (-1.0°C)
35(1.5)—35°F (1.5°C)
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
Only shown for heat pump systems with more heat
stages than cool selected and remote sensor
selection is outdoor for control.
Must enforce a dead band between this and
Auxiliary Lockout
0360 Heat Pump
Auxiliary Lockout
0 0—None
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
50(10.0)—50°F (10.0°C)
55(13.0)—55°F (13.0°C)
60(15.5)—60°F (15.5°C)
Only shown for heat pump systems with more heat
stages than cool selected and remote sensor
selection is outdoor for control.
Must enforce a dead band between this and Heat
Pump Compressor Lockout.
0535 Temporary
Occupied Duration
Limit
3 0—no duration
1—one hour
2—two hours
3—three hours
4—four hours
0 means no limit
0540 Number of Periods 4 2—2 Periods
4—4 Periods
Does not appear if Non-programmable is chosen.
Applies to all days of the week. With 2 selected the
“Cancel Period” option does not appear on the
display.
0580 Minimum
Compressor Off
Time
50Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
Only shown if system has cool stages.
0600 Heat Temperature
Range Stops
90 40 to 90°F (4 to 32°C) Only shown if system has heat stages.
0610 Cool Temperature
Range Stops
50 50 to 99°F (10 to 37°C) Only shown if system has cool stages.
0640 Clock Format 12 12—12 Hour
24—24 Hour
0650 Extended Fan-on
time Heat
00Off
90—90 seconds
Not displayed with fan set to fossil or with cool-only
systems
0660 Extended Fan-on
time Cool
00Off
40—40 seconds
Only shown if system has cool stages.
0670 Keypad Lockout 0 0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked
Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/
Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.
0680 Temperature
Control Heat
2 1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has heat stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
0685 Recovery Heat
Ramp Rate
5 0-20°F/hour Only shown if system has heat stages.
0 disables ramped recovery (step setpoint change
at period start time).
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—03 12
NOTE: Press the Done button to exit the Installer System Test.
OPERATION
System Settings
HeatThermostat controls the heating system.
OffBoth heating and cooling systems are off.
CoolThermostat controls the cooling system.
AutoThermostat automatically changes between heat
and cool operation, depending on indoor temperature.
Fan Settings
Auto Fan runs only when heating/cooling system is on.
OnFan runs continuously.
Table 5 shows default program settings. See Owner’s
Guide for complete instructions to change the program.
Table 5. Energy Star Default Program Settings.
aThe thermostat default setting is two period only. To use
four periods, change the appropriate setup parameter.
Minimum-Off Timer Compressor
Protection
The thermostat has an adjustable Minimum-Off Timer that
can be set from zero to five minutes (Factory Setting—five
minutes). The Minimum-Off Timer can be bypassed
through the Installer System Test or it can be bypassed
permanently by setting the Minimum-Off Timer to 0
minutes in the Installer Setup. The Minimum-Off Timer is
activated after the compressor turns off:
If the thermostat is system powered (common wire),
the Minimum-Off Timer is also activated upon initial
startup and after power interruptions.
If there is a call for cooling or heating during the
Minimum-Off Time, the thermostat displays “Wait.”
0690 Temperature
Control Cool
2 1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has cool stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
0695 Recovery Cool
Ramp Rate
3 0-20°F/hour Only shown if system has cool stages.
0 disables ramped recovery (step setpoint change
at period start time).
0700 Temperature
Display Offset
0 -3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
This offset applies to both the control temperature
and to the display temperature for indoor sensor
(and remote indoor sensor).
0710 Restore Factory
Defaults
0 0—No
1—Yes
Resets all ISU parameters to default values and
resets the schedule to default Energy Star. Retains
only calendar settings and time.
INSTALLER TESTS
Test 1 Installer Test
Cool
00Off
1—Cool Stage 1
2—Cool Stage 2
Test 2 Installer Test
Fan
00Off
1—Fan On
Test 3 Installer Test
Heat
00Off
1—Heat Stage 1
2—Heat Stage 1 and 2
3—Heat Stage 1,2 and 3
Test 4 Installer Test
Auxiliary Heat
0 0—Auxiliary Heat Off
1—Auxiliary Heat On
Test 8 Installer Test
TOD/Economizer
0 0—TOD/Economizer Off
1—TOD/Economizer On
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting All Settings Notes
Schedule
Period Time
Setpoints Fan
SettingHeat Cool
Occ1 8:00am 70°F
(21°C)
78°F
(25.5°C)
Auto
Unocc1 10:00pm 55°F
(10°C)
85°F
(29.5°C)
Auto
Occ2a——
Unocc2a——
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
13 62-3070—03
When the Minimum Off Timer expires, “Cool On” or
“Heat On” (heat pumps only)” appears solidly in the
display and the compressor and fan turn on.
Outdoor or Indoor Temperature Sensor
Allow outdoor or indoor temperature sensor to absorb the
air for a minimum of five minutes before taking a reading.
See the Sensor instructions for more information.
Economizer/TOD Logic (Table 6)
Table 6. Operation of Terminal A.
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor Sensor
In this operation, there is no external fossil fuel kit (dual
fuel kit) installed; the thermostat controls this function:
1. Choose correct heat pump application in Installer
Setup Number 0170.
2. Choose Outdoor Temperature Sensor for Heat
Pump Temperature Lockouts Option in Installer
Setup Number 0340.
3. Choose appropriate Balance Point Temperature
in Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT
(OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected
Balance Point Temperature (ISU 0350), only the
compressor operates and the fan (G terminal) energizes
when the thermostat calls for heat.
OPERATION IN HEAT MODE BELOW BALANCE POINT
(OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected
Balance Point Temperature (ISU 0350), only the Fossil
Fuel (auxiliary heat) operates and the fan (G terminal)
does not energize when the thermostat calls for heat.
Heat Pump with Auxiliary (Backup) Heat and
Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer
Setup Number 0170.
2. Choose Outdoor Temperature Sensor for
Control Option in Installer Setup Number 0340.
3. Choose Compressor Lockout Temperature in
Installer Setup Number 0350.
4. Choose Auxiliary Lockout Temperature in
Installer Setup Number 0360.
NOTE: There is a 5°F deadband between Compressor
and Auxiliary Heat lockout temperatures.
Operation in Heat Mode
When the outdoor temperature is:
Below the Compressor Lockout Temperature, only the
Auxiliary Heat operates.
Above the Auxiliary Lockout Temperature, only the
Compressor operates. See Fig. 31.
Between the two temperatures, both the Compressor
and Auxiliary Heat operate.
Fig. 27. Heat Pump Operation with Lockout
Temperatures Set.
Effective
Occupancy
Call for
Cool
Terminal A
Economizer TOD
Occupied — Energized Energized
Unoccupied Yes Energized De-energized
No De-energized De-energized
Override — Energized Energized
35
M19950
COMPRESSOR
LOCKOUT
TEMPERATURE
AUXILIARY
LOCKOUT
TEMPERATURE
COMPRESSOR ONLY
BOTH COMPRESSOR AND
AUXILIARY HEAT
AUXILIARY ONLY
50
OUTDOOR TEMPERATURE
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—03 14
TROUBLESHOOTING (TABLE 7)
Table 7. Troubleshooting.
Symptom Possible Cause Action
Display does not come on. Thermostat is not being powered. Check for 24 Vac between C and Rc.
Check that AAA batteries are installed
correctly and are good.
Temperature settings do not
change.
The upper or lower temperature limits
were reached.
Check temperature setpoints.
Check Installer Setup Numbers 0600 and
0610; modify as needed.
The keypad is fully locked. Check Installer Setup Number 0670 to
change keypad locked options.
Heating or cooling does not
come on.
Thermostat minimum off-time is
activated.
Wait up to five minutes for the system to
respond.
System selection not set to Heat or
Cool.
Set system Selection to correct position.
System type Selection is incorrect. Check Installer Setup Number 0170 and
make sure correct System type is chosen.
Thermostat is calling for Heat
(Heat on) or Cool (Cool on) but
no heating or cooling is
running.
Heating or cooling equipment is not
operating.
Check wiring.
Check Installer Setup Number 0170 and
make sure correct system type is chosen.
Verify operation of equipment in System Test
mode.
Heat does not turn on (Heat
On is solid in the display).
Heating equipment failure. Check for 24 Vac at the equipment on the
secondary side of the transformer between
power and common. If voltage is not present,
check the heating equipment to find the
cause of the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the heating equipment to find the cause of
the problem.
Loose or broken wire connection
between thermostat and heating
equipment.
Check for 24 Vac between the heat terminal
(W) and transformer common. If voltage is
not present, check wire connection (loose or
broken) between the thermostat and the
heating equipment.
Heat pump puts out cool air in
the heat mode and warm air in
the cool mode.
Changeover Valve (Installer Setup
Number 0190) is not configured to
match the changeover required by the
installed heat pump.
Set Changeover Valve (Installer Setup
Number 0190) to match the changeover
required by the installed heat pump.
Both the heating and cooling
equipment are running at the
same time.
The heating equipment is not a heat
pump but the System Type (Installer
Setup Number 0170) is set to Heat
Pump.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Heating and cooling wires are shorted
together.
Separate the shorted heating and cooling
wires.
Cooling does not turn on (Cool
On is solid in the display).
Cooling equipment failure. Check for 24 Vac at the equipment on the
secondary side of the transformer between
power and common. If voltage is not present,
check the cooling equipment to find the
cause of the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the cooling equipment to find the cause of
the problem.
Loose or broken wire connection
between thermostat and cooling
equipment.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If voltage is not
present, check the wire connection (loose or
broken) between the thermostat and the
cooling equipment.
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
15 62-3070—03
Fan does not turn on in a call
for heat (electric furnace).
Fan Control in Heating is set to Gas or
Oil Furnace (Setting 0180).
Set Fan Control in Heating to Electric
Furnace (Setting 0180).
Heating equipment is running
in the cool mode.
Heating equipment is not a heat pump
but System Type (Installer Setup
Number 0170) is set to Heat Pump.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Heating equipment does not
turn off and heat temperature
setting is set below room
temperature (Heat On is not in
the display).
Heating equipment is not a heat pump
but System Type (Installer Setup
Number 0170) is set to Heat Pump.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Cannot set the system setting
to Heat.
System Type (Installer Setup Number
0170) is set to Cool Only.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Cannot set the system setting
to Cool.
System Type (Installer Setup Number
0170) is set to Heat Only or Heat Only
with Fan.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Heat On is not in the display. System setting is not set to Heat and/or
temperature setting is not set above
room temperature.
Set the system setting to Heat and set the
temperature setting above the room
temperature.
Cool On is not in the display. System setting is not set to Cool and/or
the temperature setting is not set below
room temperature.
Set the system setting to Cool and set the
temperature setting below the room
temperature.
Wait is in the display. Compressor minimum off timer is
active.
Wait up to five minutes for the cooling or
heating (heat pump) equipment to turn on.
Table 7. Troubleshooting. (Continued)
Symptom Possible Cause Action
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2008 Honeywell International Inc.
62-3070—03 M.S. Rev. 01-08
SPECIFICATIONS
Electrical Ratings:
Temperature Setting Range:
Heating: 40°F to 90°F (4.5°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient Temperature:
0°F to 120°F (-18°C to 49°C).
Shipping Temperature:
-30°F to 150°F (-34.4°C to 65.6°C).
Operating Relative Humidity (Non-condensing):
5% to 90%.
Thermostat Dimensions: 3-3/4 in. (95 mm) high x 6 in.
(152 mm) wide x 1-3/8in. (35 mm) deep.
Accessories:
C7089U Outdoor Sensor: 10K ohm NTC.
C7189U Remote Indoor Sensor: 10K ohm NTC.
C7772 Flush-Mount Remote Indoor Sensor:
20K ohm NTC.
T7770A1006 Wall-Mount Remote Indoor Sensor:
20K ohm NTC.
T7770A3002 Wall-Mount Remote Indoor Sensor:
10K ohm NTC.
Perchlorate Material
This thermostat contains a Lithium battery which may
contain Perchlorate material.
The following statement is required:
Perchlorate Material—special handling may apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate
Terminal
Voltage
(50/60 Hz)
Running
Current
W (Heating) 20 - 30 Vac 0.02 - 1.0A
Y (Cooling) 20 - 30 Vac 0.02 - 1.0A
G (Fan) 20 - 30 Vac 0.02 - 0.60A
A (Economizer/TOD) 20 - 30 Vac 0.02 - 1.0A

Navigation menu