Honeywell Tv Mount Tr21 Users Manual 62 0267_E TR21, TR22, TR23, And TR24 Wall Modules
TR23 to the manual 06d379f3-c28f-4530-bdf2-d0922e1ae9e1
2015-01-23
: Honeywell Honeywell-Honeywell-Tv-Mount-Tr21-Users-Manual-262600 honeywell-honeywell-tv-mount-tr21-users-manual-262600 honeywell pdf
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
TR21, TR22, TR23, and TR24 Wall Modules INSTALLATION INSTRUCTIONS FEATURES The TR21, TR22, TR23, and TR24 family of wall modules include: • Models with setpoint adjustment. • Models with humidity output. • Models with occupied/unoccupied override (bypass) with LED. • Models with 3-position (auto/0/1) or 5-position (auto/0/1/2/3 speed) fan switch. • LONWORKS® bus jack on all models except the TR21 and TR21-A models. • Locking cover on all models. • Operating range 45° to 99° F (7° to 37° C). • Models (TR22 and TR23) with user-selectable temperature setpoint dials in Fahrenheit, Celsius, and Relative (- to +). PRODUCT DESCRIPTION SPECIFICATIONS The TR21, TR22, TR23, and TR24 are a family of direct-wired wall modules for use with: — Spyder Unitary Controllers: PUL, PVL — Excel 10 W7750, W7751a, W7752, and W7753 controllers — Honeywell Excel 800, 600, 500, 100, and 80 (all fully programmable) controllers — W7761 Controller — ComfortPoint LON Controllers: CP-UL, CP-VL Models: For specific model information, see TR21, TR22, TR23, and TR24 Wall Modules – Specification Data, form 63-1321. All models have a space temperature sensor. Some models have a temperature dial, setpoint adjustment, LONWORKS bus jack, override (bypass) with LED, and fan switch. Approvals: CE; UL94 plastic enclosure; FCC Part 15, Class B NOTE: Refer to the TR21, TR22, TR23, and TR24 Wall Modules – Specification Data, form 63-1321, for specific model features and additional information. a The TR21, TR22, TR23, and TR24 wall modules are not compatible with W7751A,C,E,G Controllers. Environmental Ratings: • Operating Temperature: 45° to 99° F (7° to 37° C). • Shipping Temperature: -40° to 150° F (-40° to 65.5° C). Accessories: 50007298-001 (pack of 12) medium, cover plate; 6-7/8 x 5 in. (175 x 127 mm). Temperature Sensor TR21, TR22, TR23, and TR24 20K Ohm Nonlinearized Sensor: All models are furnished with a 20K Ohm nonlinear NTC temperature sensor that follows a specific temperature resistance curve. See Fig. 1 on page 2. NOTE: The TR21-A wall module model has two (2) 20K Ohm nonlinear NTC temperature sensors in parallel, which provide 10K NTC temperature sensing necessary for averaging. 62-0267-09 TR21, TR22, TR23, AND TR24 WALL MODULES IMPORTANT All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. 80K RESISTANCE (OHMS) 70K 60K — Wall module wiring can be sized from 16 to 22 AWG (1.31 to 0.33 sq. mm) depending on the application. — The maximum length of wire from a device to a wall module is 1000 ft. (305 m). — Twisted pair wire is recommended for wire runs longer than 100 ft. (30.5 m). 50K 40K 30K 20K OHM AT 77oF (25oC) 20K 10K INSTALLATION 30 0 40 50 10 60 70 20 80 90 100 30 TEMPERATURE (DEGREES) 110 oF oC 40 M5874A Fig. 1. Temperature vs. Resistance for Nonlinear Sensor. Communications All wall modules (except the TR21 and TR21-A models) have a LONMARK® bus communications port. If needed, the jack plug must be removed in the field, and terminals 3 and 4 wired according to the installation instructions. The recommended wire size for the LONMARK® bus is Level IV, 22 AWG (0.34 sq.mm) plenum or non-plenum rated, non-shielded, twisted pair, solid conductor wire. Mount the wall module on an inside wall approximately 54 in. (1372 mm) from the floor (or in the specified location) to allow exposure to the average zone temperature. Do not mount the wall module on an outside wall, on a wall containing water pipes, or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun. See “Cover Disassembly” on page 3. The wall module can be mounted on a wall, on a standard utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm wall outlet box (see Fig. 3). When mounting directly on a wall, use the type of screws appropriate for the wall material. STANDARD UTILITY CONDUIT BOX SUBBASE NO. 6 SCREW FRONT COVER TEMPERATURE DIAL, FAHRENHEIT DIAL SHOWN (TR22 AND TR23 MODELS ONLY) 80 60 70 LED (TR23 AND TR24 MODELS ONLY) BYPASS (OVERRIDE) BUTTON (TR23 AND TR24 MODELS ONLY) FAN SWITCH, 3 OR 5 POSITION DEPENDING ON MODEL (TR22, TR23, AND TR24 MODELS ONLY) 60 mm WALL OUTLET BOX LOCKING TAB SLOT (X2) SUBBASE LON CONNECTOR, SHOWN WITH PROTECTIVE CAP IN PLACE (NOT AVAILABLE ON TR21 AND TR21-A MODELS) 3.5 mm SCREW M28125 FRONT COVER Fig. 3. Mounting on Standard Utility Conduit Box or 60 mm Wall Outlet Box (TR23 Shown). Fig. 2. Wall Module Features (TR23-F Shown). BEFORE INSTALLATION CAUTION Erratic System Operation Hazard. Failure to follow proper wiring practices can introduce disruptive electrical interference (noise). Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts, and large power distribution panels. Shielded cable is required in installations where these guidelines cannot be met. Ground shield only to grounded controller case. 62-0267—09 M28126 2 TR21, TR22, TR23, AND TR24 WALL MODULES 3. 3 (76) 4. 1 1/2 (38) 9/16 (14) 1 3/16 (31) 7/8 (22) 4 13/16 (122) 70 NOTE: Wire the Lon connection (terminals 3 and 4) using Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated, unshielded, twisted pair, solid conductor wire. STANDARD UTILITY CONDUIT BOX (2 X 4) MOUNTING HOLES Wiring Examples Table 1 on page 4 illustrates DIP switch settings and terminal connections for the wall modules. Refer to the TR21, TR22, TR23, and TR24 Wall Modules – Specification Data, form 63-1321, for additional DIP Switch information. 80 60 2 3/8 (60) IMPORTANT SW 2 on DIP Switch S2 is used for factory calibration of the temperature setpoint potentiometer. Depending on calibration, this switch may be set in either the On or Off position. DO NOT change the position of this switch. 2 1/4 (57) 3/16 (5) 70 65 75 15 °C + 85 – 80 60 20 25 INSIDE OF FRONT COVER °F Insert the wire in the required terminal location and tighten the screw to complete the termination. Review and verify the terminal connection wiring and DIP switch settings illustrated in Table 1 on page 4. TEMPERATURE LIMIT SCREW POSITION (X12) NOTE: IF DESIRED, INSERT THE TWO SETPOINT SCREWS INTO THE DESIRED POSITIONS. NOTES: 1. 55 M25482 Fig. 4. Wall Module Subbase Dimensions in Inches (mm) and Temperature Limit Set Screw Locations (TR23 Shown). 2. 3. Cover Disassembly A snap-fit locking mechanism is used to attach the cover of the wall module to its subbase. To disassemble the cover from the subbase: 1. Insert a thin, flat blade screwdriver into each of the two slots at the bottom of the module to release the two locking tabs. See Fig. 2 on page 2. 2. Tilt the cover out and away from the subbase to release the top two locking tabs. 3. To change the dial (e.g. from Fahrenheit to Celsius) release the two tabs on the inside of the front cover and remove the old dial. 1/2 (13) The TR21 and TR22 models do not use DIP Switch S1 and S3. DIP Switch S1 is used only on the humidity models, TR21-H and TR23-H. Models TR21 and TR21-A use terminals 1 and 2 only. Model TR21-J uses terminals 1, 2, 3, and 4 only. 1. STRIP 1/2 IN. 2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS). Wiring Attach the wires from the device sensor terminals to the appropriate wall module terminals. See Table 1 on page 4. CONTROLLER OR WALL MODULE E-BUS CONNECTOR TERMINALS (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL. 3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION. M11413 Fig. 5. Attaching Two Wires (20 to 22 AWG) to Wall Module Terminals. CAUTION Improper Electrical Contact Hazard. Screw type terminal blocks are designed to accept no more than one 16 AWG (1.31 sq. mm) conductor. Connect multiple wires that are 16-18 AWG (1.31-0.82 sq. mm) with a wire nut. Include a pigtail with this wire group and attach the pigtail to the individual terminal block. Wiring Wall Modules Wire the terminal block as follows: 1. For single wires, strip 3/16 in. (5 mm); for multiple wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor. 2. If two or more wires (20 to 22 AWG only) are being inserted into one terminal, twist the wires together before inserting. See Fig. 5. 3 Attaching the Cover When all wiring is complete, attach the cover of the Wall Module as follows: 1. Optional: For models with a temperature dial, insert the two setpoint screws into the inside of the cover to set the desired temperature range limit. See Fig. 4. 2. Press the cover straight down onto the subbase until it snaps into place. 3. For models with a temperature dial, insert the desired dial through the opening in the cover. Align the keyed shaft on the knob with the keyed slot into the fitting on the subbase, then press down until it snaps into place. 62-0267—09 TR21, TR22, TR23, AND TR24 WALL MODULES Wiring and DIP switch settings: See Table 1 to determine DIP switch positions and terminal usage for each controller. Table 1. DIP Switch Settings and Terminal Connections. Controller Model(s) No fan switching from sensor DIP SWITCH S1 1 ON 2 3 4 5 OVERRIDE 1 LED M28128 SETPT 1 DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. LON - SW1 SW2 SW3 LON + T7350: Use +/- offset knob only! DIP SWITCH S3 (TR23 AND TR24 ONLY.) GND ON NOT USED ON TR22 DO NOT CHANGE THIS SWITCH POSITION. SW1 SW2 Spyder: PUL, PVL NOT USED ON TR24 DIP SWITCH S2 ON SW1 SW2 TR22-TR24 Terminal Connections SENSOR XL1O: W7750, W7751, and W7752 TR23-TR24 DIP Switch Settings 6 7 8 9 10 11 12 M28133 NOTE: These switch positions are the factory default settings for non-fan models. Fan switching from sensor. DIP SWITCH ON S1 1 4 5 FAN 3 1 DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. DIP SWITCH S1 1 ON ON DIP SWITCH S2 8 4 5 6 7 OVERRIDE FAN 3 LED 2 BYPASS RET 1 M31110 9 10 11 12 ON SW1 SW2 0 TO 5 VDC 4 TO 20 mA ON ON 8 9 10 11 12 SW1 SW2 1 SW1 SW2 M28132 4 HUM 0 TO 10 VDC 2 3 4 5 6 7 REFER TO CONTROLLER SPECIFIC WIRING ABOVE FOR TERMINAL CONNECTIONS 1 THROUGH 10. M31111 24 VAC 8 DIP SWITCH S1 62-0267—09 M31112 SW1 SW2 SW3 1 DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. For humidity models – TR21-H and TR23-H only! 9 10 11 12 NOT USED ON TR22 LON - LON + DIP SWITCH S3 (TR23 and TR24 ONLY.) GND • Used with TR23, TR24, TR22-F5, TR23-F3, and TR23-F5 models. 7 NOT USED ON TR24 DO NOT CHANGE THIS SWITCH POSITION. SW1 SW2 ON 6 SETPT SW1 SW2 M28129 SENSOR Excel 600/500/100/80/50 Any controller noted above. OVERRIDE SETPT 2 LED LON - 1 SW1 SW2 SW3 Spyder: PUL, PVL XL5000: LON + DIP SWITCH S3 (TR23 and TR24 ONLY.) GND SW1 SW2 ON W7753 DO NOT CHANGE THIS SWITCH POSITION. SENSOR SW1 SW2 NOT USED ON TR24 NOT USED ON TR22 DIP SWITCH S2 ON M28137 TR21, TR22, TR23, AND TR24 WALL MODULES TR22 and TR23 Setpoint Adjustment Humidity Settings (DIP switch S1) For the TR22 and TR23 Wall Modules with a setpoint adjustment, the controller must be programmed for the values in Table 2 and Table 3. The humidity sensing control mode is set with this 2-position DIP switch. Refer to Fig. 4 on page 3 for location of DIP switch S1. Table 2. Setpoint Values. NOTE: These switch settings apply only to the TR21-H and TR23-H models. Setpoint Value Program Setting 55°F (13°C) 2.773 V 65°F (18°C) 2.148 V 75°F (24°C) 1.345 V 85°F (29°C) 0.43 V To change the setting, first disconnect the power, then set SW1 and SW2 according to Table 5. Table 5. DIP Switch S1 Settings. Table 3. Wall Module Setpoint Configuration. Setpoint Resistance (Ohms) °F Absolute 55°F 9574 85°F 1426 Relative °C Absolute -9°F offset from 70°F 9574 +9°F offset from 70°F 1426 12°C 9945 30°C 1150 TR21-H TR23-H Description Fahrenheit scale knob (pack of 20) KNOB-O Relative scale knob (pack of 20) OFF ON ON OFF 70 80 60 KNOB-F 0-5 Vdc 4-20 mA The Excel 10 controllers (W7750, W7751, W7752, and W7753) provide timed occupied and unoccupied temperature setpoints for the Wall Module, see Fig. 6. The override pushbutton is used to change the controller into the modes shown in Table 6 and illustrated in Fig. 7 on page 6. The override (bypass) LED displays the override status of the controller. Table 4. Knob Model Numbers Celsius scale knob (pack of 20) OFF When Used With Excel 10 Controllers: The TR23-KL and TR23-H-KL ship in packs of 20 and are supplied without setpoint adjustment knobs. Knobs can be ordered separately. See Table 4 for Knob model numbers. Model 2 OFF TR23 and TR24 Wall Module Override (Bypass) Pushbutton and LED Operation TR23-KL and TR23-H-KL KNOB-C 1 0-10 Vdc Wall Module Model Model Individual Switches Sensing Control LED 1 OVERRIDE (BYPASS) PUSHBUTTON 1 LED AND OVERRIDE (BYPASS) PUSHBUTTON AVAILABLE ONLY ON THE TR23 AND TR24 MODELS. M28144 Fig. 6. LED and override pushbutton locations (TR23-F Wall Module shown). 5 62-0267—09 TR21, TR22, TR23, AND TR24 WALL MODULES TR22-F5, TR23-F3, and TR23-F5 Wall Module Fan Switch Table 6. Wall Module Operation. Pushbutton Held Down Controller Model With the switch in the far left position (Auto), the fan automatically runs at the speed determined by the controller temperature control algorithm. LED Status 0 to 1 second No override Off 1 to 4 seconds Timed occupied override On 4 to 7 seconds Unoccupied override Single blink per second Longer than 7 seconds No override not applicable Continuous occupied Two blinks per second overridea a With the switch in the 0 position, the fan is off. Position 1 is fan speed 1, etc. The wall module fan speed switch overrides the temperature control algorithm. Off When Used With Excel 10 Controllers: The Excel 10 Controllers (W7750, W7751, W7752, and W7753) can be programmed so that the fan speed switch and override button function the way that the application engineer/ programmer wants. See Table 7 for controller-programming resistances. Switch 1 on Dip Switch S2 adds 10k Ohms resistance when OPEN (for Excel 600-80 controllers) and removes it when CLOSED (for Excel 10 controllers). Remote function, which is generated from the network. RESET NOT ASSIGNED (LED OFF) PRESS FOR LESS THAN ONE SECOND PRESS FOR ONE TO FOUR SECONDS Table 7. Program Settings for Wall Modules with Fan Switch using Excel 10 Controllers. BYPASS TIMEOUT OVERRIDE OCCUPIED (LED ON) For Switch Position PRESS FOR FOUR TO SEVEN SECONDS PRESS FOR LESS THAN ONE SECOND UNOCCUPIED (LED BLINK) Comment 1861 ±119 Left most position 0 2686 ±127 Fan Off position 1 3866 ±139 2 3041 ±130 3 4601 ±146 Right most position Override button closed Closed circuit PRESS FOR MORE THAN SEVEN SECONDS M28145 Fig. 7. Override pushbutton operation. When Used With Excel 600/500/100/80/50 Controllers: The application engineer/programmer can program the override (bypass) and LED to operate in any manner desired. The override (bypass) input is a dry contact, normally open, momentary digital input when the wall module does not have a fan switch. When a fan speed switch (basically a series of resistances based on fan switch position) is present, the override button is an analog input. See Table 4 for resistances. When Used With T7350 Thermostat: TR21, TR21-A, TR21-H, TR22, TR23, and TR24 are the models compatible with the T7350 thermostat. When using with the T7350 thermostat be sure to use the relative +/- offset knob only. The Celsius and Fahrenheit knobs will not work properly with the T7350 Thermostat. 62-0267—09 Resistance (Ohms) Auto 6 When Used With Excel 600/500/100/80/50 Controllers: Excel 600/500/100/80 Controllers can be programmed so that the fan speed switch and override button function the way that the application engineer/programmer wants. See Table 8 for controller-programming resistances. Switch 1 on Dip Switch S2 adds 10k Ohms resistance when OPEN (for Excel 600-80 controllers) and removes it when CLOSED (for Excel 10 controllers). Table 8. Program Settings for Wall Modules with Fan Switch using Excel 600/500/100/80 Controllers. For Switch Position Resistance (Ohms) Comment Auto 11.861K ±119 Left most position 0 12.686K ±127 Fan Off position 1 13.866K ±139 2 13.04K ±130 3 14.60K ±146 Override button closed 10K ±100 Right most position TR21, TR22, TR23, AND TR24 WALL MODULES 7 62-0267—09 TR21, TR22, TR23, AND TR24 WALL MODULES LONWORKS® is a registered trademark of Echelon® Corporation. LONMARK® and the LonMark Logo are trademarks of the LonMark Association. Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2009 Honeywell International Inc. 62-0267—09 E.K. Rev. 09-09
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Encryption : Standard V4.4 (128-bit) User Access : Print, Copy, Extract, Assemble, Print high-res Page Mode : UseOutlines XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Format : application/pdf Creator : Honeywell ECC Technical Communications Title : 62-0267_E TR21, TR22, TR23, and TR24 Wall Modules Description : installation instructions Create Date : 1999:07:07 12:30:47Z Creator Tool : FrameMaker 7.0 Modify Date : 2009:10:06 11:32:30-05:00 Metadata Date : 2009:10:06 11:32:30-05:00 Producer : Acrobat Distiller 8.1.0 (Windows) Document ID : uuid:326f5c6e-8d0e-4f00-8a67-167247b9e6c7 Instance ID : uuid:3d13b999-c13a-4aa5-a10d-4710d1f896e1 Page Count : 8 Subject : installation instructions Author : Honeywell ECC Technical CommunicationsEXIF Metadata provided by EXIF.tools