Direct Drive Damper Actuator
M847D
Application
The M847D is a two position, 24 Vac spring return damper
actuator designed to operate directly driven zone dampers,
used to control air flow in ducts. The synchronous motor
actuator can be driven open (or closed) using any 24 volt
rated two position switch - eg. a wall switch or a thermostat
subbase switch.
The M847D replaces the RDMH and RDMZ damper
actuators for use on Trol-A-Temp® ARD and ZD dampers.

Specifications
Electrical Rating: 24 Vac 60 Hz 0.32 Amp., 8 VA
Electrical Connection: 1/2" conduit
Nominal Angular Rotation: 90° ( max. 105° )
Torque: Min. 423 mNm (milli newton meter) [60 in.oz] output
torque available when motor is energized and device is at
the spring returned initial start position.
Nominal Motor Timing: (@25°C ambient)
Energized at rated load - 30 seconds.
De-energized (spring return) - 10 seconds.
Ambient Temperature Rating: 5 to 60°C (+40 to 140°F)
Finish: zinc plated steel, anodized aluminium
Direction of Shaft Rotation: clockwise, when energized
and viewed from the base or shaft end.
Mounting Means: direct connection to damper shaft.
Mounting Position: Multi-poise.
Dimensions: See Figure 1.

Nominal Device Dimension
mm
in

A
60
2-3/8

B
84.5
3-3/8

C
88
3-1/2

D
8.2
5/16

mm
in

G
15.8
5/8

H
58.6
2-5/16

J
29.3
1-3/16

K
33.5
1-5/16

E
31.5
1-1/4

F
19.3
3/4

L
6.4
1/4

M
40.4
1-9/16

Fig. 1 - Dimensional Details

INSTALLATION AND CHECKOUT

!

CAUTION

1. Read these instructions carefully. Failure to follow them could
cause a hazardous condition.
2. Disconnect powersupply before beginning of installation and
wiring of control to prevent electrical shock or equipment
damage.
3. Check the ratings given in the instructions and on the product
to make sure the product is suitable for your application.
4. All wiring must comply with local electrical codes, ordinances,
and regulations.
5. Installer must be a trained, experienced service technician.
6. After installation is complete, check out the product operation
as provided in these instructions.

WARNING
1. DO NOT install this actuator on a flue damper.
2. DO NOT attempt to rotate the actuator by turning the
connection coupling or the damper shaft when it is
connected to the actuator or damage to the gear train
may occur.
STANDARD MOUNTING (For 5/16" dia. damper shaft)
The M847D can be attached directly to the protruding 5/16"
diameter damper shaft using the sleeve of the output shaft. Drill
A 5/16" (8mm) hole 1-5/16" (33.5mm) directly below the damper
shaft opening to accept the anti-rotation shaft protruding from
the base of the motor. The length of the damper shaft to which
the connection coupling is attached is such as to firmly hold the
actuator in a position to adequately engage the anti-rotation pin
in the warm air duct. See Figure 1. for the critical dimensions.
11-01 © Honeywell Limited. 2001 • Form Number: 95C-10905-1

M847D
INSTALLATION AND CHECKOUT CONTINUED
Replacing M847D on aTrol-A-Temp® ARD damper
1. Disconnect the motor wiring.
2. Using a 1/8 in. hex wrench to loosen the motor coupling from
the blade shaft, remove the existing motor assembly.
3. Observe that the damper blades are in the normal, spring
open or spring closed position.
4. Place the new motor onto the shaft and tighten the coupling.
5. Reconnect the motor wiring.
ALTERNATE MOUNTING (For 7/16"dia. coupling style
dampers)
Before installing the M847D actuator to a damper with a 7/
16" coupling, insert the drive shaft extension into the drive
shaft and tighten with the set screw provided. See Fig. 2.
Also install the anti-rotation extension to the end of the
anti-rotation rod. Install the actuator on the damper and
tighten the coupling screw.
Fig 2. For 7/6" COUPLING MODEL DAMPERS ONLY

Replacing M847D on aTrol-A-Temp® ZDS or ZDB damper
1. Disconnect the motor wiring.
2. Using a 3/16 in. hex wrench to loosen the Allen screw located
above the faceplate at the motor coupling.
3. Remove the existing motor.
4. Observe that the damper blades are in the open position with
the setscrew pointing toward the damper label.
5. Attach the new motor to the coupling. Make sure that the
standoff on the motor is positioned in the grommet on the
faceplate.
6. Tighten the set screw.
7. Reconnect the motor wiring.

CHECKOUT
After completing the installation, check that the equipment
operates correctly as follows:
1. When 24 Vac is applied to the motor leads, the motor powers
to the closed or open position.
2. When power is removed, the motor releases and spring
returns to the normal position.
If full opening and closing is not achieved, check the lower
adjustment lever is to the extreme left and the upper lever is to
the extreme right. See Fig. 4 (Air Flow Adjustments)
AIR FLOW ADJUSTMENTS
Note: The following describes the adjustments available with
the actuator installed in the power closed mode. If the damper
you are installing is to operate in the power open mode, the
function of the upper and lower levers is reversed.
1. When viewed on end, the lower lever is normally positioned
to the extreme left. (See Fig. 4) This position allows the
damper to fully open 90° when de-energized.
2. To restrict the air flow in the open position, loosen (do not
remove) the wing nut and move the lower lever to the right
until the desired position is reached. Tighten the wing nut. In
the extreme right position the damper should open approx.
50° with the power off.
3. The upper lever is normally positioned to the right to
provide complete shut off when the acutuator is energized.
(See Fig. 4)
4. If desired, to prevent complete closure of the damper, loosen
(do not remove) the wing nut on the bottom of the unit and
move the upper lever to the left until the desired position is
achieved. Tighten the wing nut. In the extreme left position
the damper should close to approx. 40° with the power on.
5. If additional rotation is required beyond 90°, an additional 15°
may be obtained by removing the Upper Lever. To do this,
first, remove the actuator from the damper. Remove the wing
nut and retaining ring then remove the levers. Reassemble
and install.

Fig. 4 - Air Flow Adjustment

WIRING
See Figure 3. for typical wiring hook-ups of the M847D.

UPPER LEVER
WING NUT
LOWER LEVER

Figure 3 - Typical M847D Hookup
Zoning Switch
1

Orange

24 VAC
60 Hz

Yellow

1

PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

2

NOMINAL CURRENT 0.32 AMP

Automation and Control Solutions
Environment Control Products
1985 Douglas Drive North
Golden Valley, MN
55422-3992

In Canada:
Honeywell Limited
35 Dynamic Drive
Toronto, ON
M1V 4Z9

2

Operator
Motor

This material is proprietary to
Honeywell Limited and shall not be
reproduced, copied or used in any manner
without prior written consent of Honeywell Limited.
Printed In Canada

Helping You Control Your World



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Assemble, Print high-res
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Create Date                     : 2001:12:05 09:40:37Z
Creator Tool                    : PageMaker 6.5
Modify Date                     : 2010:07:14 11:07:30-05:00
Metadata Date                   : 2010:07:14 11:07:30-05:00
Format                          : application/pdf
Creator                         : Honeywell ECC Technical Communications
Title                           : 95C-10905 - M847D Direct Drive Damper Actuator
Description                     : Product Data
Producer                        : Acrobat Distiller 4.05 for Macintosh
Document ID                     : uuid:31736d98-5500-426e-8b7b-22996892732f
Instance ID                     : uuid:9e2e3408-7781-40e1-8baf-201642529249
Page Count                      : 2
Subject                         : Product Data
Author                          : Honeywell ECC Technical Communications
EXIF Metadata provided by EXIF.tools

Navigation menu