Honeywell Ml6421 Users Manual 63 2515 ML6421, ML7421 Non Spring Return Electric Linear Valve Actuators

ML6421 63-2515

ML7421 to the manual bafade24-1e70-4b80-a052-9050692ad876

2015-01-23

: Honeywell Honeywell-Ml6421-Users-Manual-261114 honeywell-ml6421-users-manual-261114 honeywell pdf

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadHoneywell Honeywell-Ml6421-Users-Manual- 63-2515 - ML6421, ML7421 Non-Spring Return Electric Linear Valve Actuators  Honeywell-ml6421-users-manual
Open PDF In BrowserView PDF
ML6421, ML7421
Non-Spring Return
Electric Linear Valve Actuators
PRODUCT DATA

FEATURES
• Quick and easy installation.
• No separate linkage required.
• 3/4 in. (20 mm) stroke on ML6421A and ML7421A.
• 1-1/2 in. (38 mm) stroke on ML6421B and ML7421B.
• No adjustments required.
• Accurate valve positioning.
• Low power consumption.
• Selectable 0(2) to 10 Vdc or 0(4) to 20 mA input signal
with ML7421.
• Position feedback with ML7421.
• High close-off ratings.
• Direct/reverse acting with ML7421.
• Force-limiting end switches.
• Manual operator.
• Synchronous motor.

APPLICATION

• Corrosion-resistant design.
• Maintenance free.

The ML6421A,B Non-Spring Return Electric Linear Valve
Actuators are suitable for use with low-voltage, single-pole
double-throw (spdt), Series 60 two-position and floating
controllers. These actuators operate standard Honeywell
valves in heating, ventilating, and air conditioning (HVAC)
applications.

• Conduit connector knockout.

The ML7421A,B Non-Spring Return Electric Linear Valve
Actuators are modulating control actuators used with controls
that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc.
These actuators operate standard Honeywell valves in HVAC
applications. An internal selector plug can be used to reverse
the direction of action.

Contents
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Operation ..........................................................................
Checkout ..........................................................................

® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved

1
1
2
2
3
6
7

®
63-2515-4

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

SPECIFICATIONS
Models:

Close-off Pressure Ratings: See Table 1.

Model
ML6421A

Stroke in
in. (mm)

Run Time in
sec at 60 Hz

3/4 (20)

95

1-1/2 (38)

175

ML7421A
ML6421B

Cable Entry: Two knockout holes for 1/2 in. conduit standard
on actuator case.

Description
Electric Linear
Valve Actuator

Ambient Ratings:
Temperature:
Ambient Range: 14°F to 122°F (-10°C to +50°C).
Storage Range: -40°F to +158°F (-40°C to +70°C).
Humidity Range: 5 to 95 percent relative humidity,
noncondensing.

ML7421B
Dimensions: See Fig. 1.

Approvals:
Canadian Standards Association Listed.
Underwriter’s Laboratories, Inc. UL94-5V Flame Retardant
(file E181716).
Meets CE requirements.

Weight: 5.1 lb (2.3 kg).
Electrical Ratings:
Power Input: 24 Vac (+10%, -15%), 60 Hz.
Power Consumption: 11 VA maximum at 24 Vac.

Protection Standard: IP54.

Signal Inputs:
ML6421:
24 Vac across T1 and W: Drives stem downward.
24 Vac across T2 and B: Draws stem upward.
ML7421: 0 to 10 Vdc or 2 to 10 Vdc.

Accessories:
43191679-101 Single Auxiliary Potentiometer for ML6421A.
43191679-102 Single Auxiliary Potentiometer for ML6421B.
43191679-103 Dual Auxiliary Potentiometer for ML6421A.
43191679-104 Dual Auxiliary Potentiometer for ML6421B.
43191680-102 Dual Auxiliary Switch (for 24 Vac use only).
43196000-001 High Temperature Kit (for actuators with 3/4 in.
stroke). Increases maximum temperature to 428°F (220°C).
43196000-102 High Temperature Kit (for actuators with 1-1/2 in.
stroke). Increases maximum temperature to 428°F (220°C).

Actuator Material:
Cover: ABS plastic.
Yoke and Base: Diecast aluminum.
Stem Force: 405 lbf (1800N).

Table 1. Close-off Ratings for ML6421, ML7421 Electric Linear Valve Actuators and Honeywell Valves (psi).
Type

Valve

Flange V5011A,B,C

NPT

1/2 in. 3/4 in. 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 4 in.a 5 in.a 6 in.a
—

—

—

—

—

—

77

53

29

18

12

V5011B

—

—

—

—

—

—

—

—

V3350/51/60/61;V3450/51/60/61

—

—

—

—

—

—

63b

45b 25b

16b

11b

V5011F,G

150c

150c

150c 150c

150c

150c 100

61

—

—

V5011N1xxx, V5011N3xxx,
V5013N

230

230

230

230

126

—

V5011N2xxx

100d

100d

100d 100d

100d

100d

V5013F

150

150

150

150

150

230

150

—

—

a For

use with ML6421B or ML7421B Actuators only.
maximum pressure difference between the outlet and either of the two inlets.
c Do not exceed 100 psi with V5011G valves used in steam applications.
d Rating is for steam at maximum 100 psi. Ratings for water applications are the same as for the V5011N1xxx.
b Represents

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2515—4

2

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

ML6421A,ML7421A

ML6421B, ML7421B
7 (178 ) X 7 (178)

7 (178 ) X 7 (178)
2-1/2
(64)

2-1/2
(64)

16-7/8
(430)
MINIMUM
CLEARANCE

14-1/4
(360)
MINIMUM
CLEARANCE

12-3/4
(326)

10-3/8
(264)
KNOCKOUTS
(2)
7/8 (22)

KNOCKOUTS
(2)
7/8 (22)

9-3/8
(239)

5-5/8
(142)

11-7/8
(301)

8
(204)

YOKE DIAMETER 1-3/8 (35)

YOKE DIAMETER 1-7/8 (48)

M17430

Fig. 1. Approximate dimensions of ML6421, ML7421 Electric Linear Valve Actuators in in. (mm).

INSTALLATION

CAUTION

When Installing this Product…
1.
2.
3.
4.

Read instructions carefully. Failure to follow them could
damage the product or cause a hazardous condition.
Check ratings and description given in the specifications
to make sure the product is suitable for your application.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.

Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.

Location
Install the actuator in a location that allows enough clearance
for mounting accessories and for servicing.

CAUTION

Equipment Damage Hazard.
Can damage actuator due to condensation or a
valve gland leak.
Install the actuator in a position above horizontal.

3

63-2515—4

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

Mounting
1.

Wiring

Place the actuator on the valve with the U-bolt around
the valve collar. See Fig. 2.

CAUTION

IMPORTANT
When tightening the set screws, first tighten the right
set screw. See Fig. 2.
2.

Place the U-bolt against the valve collar and secure the
actuator to the valve by turning each U-bolt nut clockwise.
NOTE: To assure even pressure on the collar, first
tighten the nuts finger-tight and then alternate
turning each U-bolt nut until both are snug.

3.
4.
5.
6.
7.

Push aside the stem button retaining clip and hold. See
Fig. 2.
Lift the valve stem until the head of the valve stem
button is inside the large slot of the stem button
retaining clip on the actuator.
Release the stem button retaining clip to secure the
stem button. Check to make certain the stem button is
secured by the retaining clip.
Pull off the manual operation knob.
Remove the cover from the actuator using a Phillips or
crosspoint screwdriver. See Fig. 3.

Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.

IMPORTANT
1. All wiring must comply with local electrical codes,
ordinances and regulations.
2. Voltage and frequency of the transformer used with
the actuator must correspond with the characteristics
of the power supply and those of the actuator.
NOTE: See Fig. 5 through 8 for typical wiring hookups.
1.

CAUTION

Equipment Damage Hazard.
Conduit connection or removal can break an
unsupported connector.
When removing or attaching conduit, use a wrench to
support the motor connector.

2.
3.
4.

TIGHTEN RIGHT
SET SCREW FIRST

Feed power and control wires through the conduit
connector located on the bottom of the actuator case.

5.

Using the appropriate wiring diagram (see Fig. 5 through
8), connect power and control wires to the actuator.
Make sure that all wiring is correct.
For the ML7421 only: Check selector plugs for proper
settings. See Signal Input Failure section for details.
When wiring is complete, replace the actuator cover
and control knob (see Fig. 9).
Apply power and control signals to the actuator.

M17431

Fig. 2. Attaching actuator to valve.

M6630

Fig. 4. Connecting wiring to the actuator.

M17432

Fig. 3. Removing actuator cover.
63-2515—4

4

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

ML6421A,B
ML7421

WIRING
STRIP

2
L1
(HOT)
L2
1

T1
T2

WIRING
STRIP

W
R

1

POWER SUPPLY. PROVIDE DISCONNET MEANS AND
OVERLOAD PROTECTION AS REQUIRED.

2

ALL WIRING BLOCKS HAVE THE SAME NUMBER
OF TERMINALS (8), BUT THE ONLY TERMINALS
THAT ARE ACTIVE ON THIS BLOCK ARE T1,W,AND B.

3

1

THE R-W-B AND T-Y-G TERMINALS ARE A SIX
TERMINAL WIRING BLOCK SEPARATE FROM THE
MAIN BLOCK. THEY DO NOT APPEAR ON ALL
MODELS BECAUSE R-W-B ARE FOR A SINGLE
FEEDBACK POTENTIOMETER AND T-Y-G ARE
FOR A SECOND FEEDBACK POTENTIOMETER
(BOTH POTENTIOMETERS ARE 220 OHMS). THE
REQUIRED WIRING BLOCKS ARE PART OF THE
POTENTIOMETER ACCESSORY KITS.
M17433

G
3

2

1

SINGLE
TRANSFORMER
40 VA, 24 VAC

T775 (WITH 2 TO 10 VDC OUTPUT)

R

T

6

O1

B

Y

5

L1
(HOT)
L2
1

O2

B

4

+

SPDT

W

3

T2

CONTROLLER

3

2

T1

B
W

SENSOR
1

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

M17436A

Fig. 8. ML7421 wiring using voltage input control and a
common transformer.

Fig. 5. ML6421 typical wiring diagram.

ML7421
WIRING
STRIP

L1

1

L2
T1
T2

–

+

+

2
OUTPUT

O1
O2

M17434A

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

2

0 TO 10 OR 2 TO 10 VDC CONTROL SIGNAL
(DEPENDING ON ACTUATOR MODEL).

M17464

Fig. 9. Replacing actuator cover.

Fig. 6. ML7421 typical wiring diagram.

Auxiliary Potentiometers
L1

The 43191679 Auxiliary Potentiometers can be used as feedback potentiometers and to provide remote indication of the
valve position. See the Accessories section for part numbers.
See Installation Instructions packed with the potentiometers
for details.

1

L2
ML7421
WIRING
STRIP

SENSOR
1

2

3

4

5

6

Auxiliary Switches

T1
T2

L1

+

L2

The 43191680 Dual Auxiliary Switch can be used on both the
ML6421 and ML7421 Electric Linear Valve Actuators.
Switching points are adjustable over the full actuator stroke.
For example, the switch can be used to switch pumps or to
provide remote indication of any stroke position. See the
Installation Instructions packed with the auxiliary switch for
details.

1

O1

3

2

1

O2

DUAL
TRANSFORMERS

T775 (WITH 2 TO 10 VDC OUTPUT)
1

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

IMPORTANT
Use the 43191680 Dual Auxiliary Switch only with
24 Vac applications.

M17435A

Fig. 7. ML7421 wiring using voltage input control and
separate transformers.

5

63-2515—4

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

OPERATION
General

ML7421

The drive of the actuator synchronous motor is converted into
the linear motion of the actuator stem by using a worm gear
transmission. A button retainer clip connects the actuator
stem to the valve stem.

Signal Input Failure

The internal force sensor, using installed microswitches, turns
off the actuator when the specified stem force is reached.

Manual Operation
The ML6421 and ML7421 are equipped with a manual
operator knob (see Fig. 10) to open or close the valve in the
event of power failure:
1. Turn off or disconnect the power supply before manually
operating the actuator.
2. Push down on the manual operator knob and turn the
knob:
a. Counterclockwise to drive the stem downward.
b. Clockwise to draw the stem upward.
IMPORTANT
Manual operation allows very high closing force that
can jam the actuator spindle, exceed the force switch
ratings, and stop the motor. After a manual valve
close-off operation, release the spindle one turn by
turning the manual operator knob. This will ensure
automatic disengagement of the manual operator
upon power resumption.

Using selector plug W1, the actuator can be set to run to one
of three positions in event of a signal failure:
• 0%: Actuator position corresponds with 0 or 2 Vdc signal.
• 50%: Actuator stem in mid-position.
• 100%: Actuator position according to 10 Vdc signal.
NOTE: If W4 is set to the mA position, the actuator always
runs to 0 percent.

Output Signal Feedback (F)
An analog output signal (2 to 10 Vdc) that represents the
actual actuator stem position is available at Terminal F. It can
be used for remote indication of the stem position.
With the actuator stem fully down, the output signal is 10 Vdc.
The output of the signal does not change when the actuator
action reverses using W3 or W4 (see Signal Input Failure
section and Fig. 11).

W3

10V (20mA)

W1

0% 50% 100%

W4
10V (20mA)

NOTE: If the manual operator knob is not pushed in while
turned, it will rotate only a short distance before
disengaging without power resumption.

mA

V

W2

2-10V
(4-20mA)

0-10V
(0-20mA)

M17437

Fig. 11. Location of selector plugs.

M6640

Fig. 10. Manual operator knob.

63-2515—4

6

ML6421, ML7421 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

Actuator Override
To override the control signal (for freeze protection or similar
applications), connect the 24 Vac common (T2) to either
terminal O1 or O2. Connecting to terminal O1 fully extends
the actuator stem. Connecting to O2 fully retracts the actuator
stem.

ML7421

The control signal (+) is ignored when the override signal is
applied to terminal O1 or O2. This override can be achieved
with a switch or a relay. See Fig. 12.

WIRING
STRIP

2

F

F

+
–

+
–

INPUT
(FEEDBACK)
OUTPUT
3

T2
T1
O1

SP3T
OVERRIDE
SWITCH

O2

Direction of Action

4

The direction of action can be changed by repositioning the
selector plug W3.

1
L1
(HOT)
L2

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

2

2-10 Vdc FEEDBACK SIGNAL. SEE OUTPUT SIGNAL
FEEDBACK SECTION.

3

0-10Vdc OR 2-10 Vdc CONTROL SIGNAL. SEE SIGNAL
INPUT (+) SECTION.

4

SEE OVERRIDE SECTION FOR DETAILS ON
M17438
OVERRIDE OPERATION.

Fig. 12. Connections for overriding control signal to drive
actuator to a specific position.

CHECKOUT
The actuator can be checked out either directly or using a controller.

Direct Checkout
1.
2.
3.
4.
5.

Controller Checkout

Mount the actuator for the required application.
Check the valve position and make sure that 24 Vac is
correctly applied to the actuator.
Apply the control signal to the appropriate leadwires to
move the valve in the required direction.
If the actuator does not move, make sure the actuator is
properly installed.
If the actuator is correctly installed and does not run,
replace the actuator.

1.
2.
3.
4.
5.
6.

7

Adjust the setpoint of the controller to call for opening or
closing the valve. Observe the actuator.
If the valve is closed, it should begin to open.
If the valve remains closed, move the setpoint further
toward the open setting.
If the valve does not move, check for 24 Vac in the
actuator power input.
If 24 Vac is present and the actuator does not operate,
reverse the controller leadwires to determine if the
device is incorrectly wired.
If wiring is correct, 24 Vac is present on the power input
terminals, and the actuator does not run, replace the
actuator.

63-2515—4

Automation and Control Solutions

Honeywell International

Honeywell Europe S.A.

Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422

Control Products
Honeywell Building
17 Changi Business Park Central 1
Singapore 486073

3 Avenue du Bourget
1140 Brussels
Belgium

63-2515—4

Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9

B.B. Rev. 1-03

Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.

Honeywell Latin American
Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325

www.honeywell.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Assemble, Print high-res
Page Mode                       : UseOutlines
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 4.05 for Windows
Modify Date                     : 2007:05:07 13:56:23-05:00
Create Date                     : 2002:01:29 15:08:35Z
Metadata Date                   : 2007:05:07 13:56:23-05:00
Creator Tool                    : FrameMaker 6.0
Format                          : application/pdf
Creator                         : HONEYWELL
Description                     : Product Data
Title                           : 63-2515 - ML6421, ML7421 Non-Spring Return Electric Linear Valve Actuators
Document ID                     : uuid:e08e33cc-e58d-4ebc-9644-2e5b55d74d9e
Instance ID                     : uuid:0012566e-b710-461f-81a0-ebfd83a468c2
Page Count                      : 8
Subject                         : Product Data
Author                          : HONEYWELL
EXIF Metadata provided by EXIF.tools

Navigation menu