Honeywell Q179A Users Manual 60 2032 Q179A,B Gas Pilot Burner Assemblies
Honeywell Burner Q179B 60-2032
Q179A to the manual 2fb97a07-ddba-4b09-af79-bcc2f46315ac
2015-01-23
: Honeywell Honeywell-Q179A-Users-Manual-261179 honeywell-q179a-users-manual-261179 honeywell pdf
Open the PDF directly: View PDF .
Page Count: 8
Download | |
Open PDF In Browser | View PDF |
Q179A,B Gas Pilot Burner Assemblies PRODUCT DATA GENERAL Q179A,B Gas Pilot Burner Assemblies use the flame rectification principle to prove the flame. Q179A,B are used in conjunction with a suitable electronic flame safeguard control on industrial or commercial gas and gas pilot ignited oil burners. FEATURES • Q179A is a gas pilot assembly with a flame electrode (rod) and ignition electrode, making it suitable for applications requiring an interrupted or intermittent electrically ignited gas pilot burner. • Q179A1183 is an “I” port burner with an ignition electrode (spark) only. • Q179B has only the flame electrode and is suitable for use in continuous pilot applications. • Primary aerated type burner is equipped with stainless steel fins that provide the proper flame rod area to ground area ratio for maximum flame signal and flame stabilization. • Stainless steel electrode(s) are mounted in ceramic insulators, which permit electrode adjustment. Contents General ............................................................................. Features ........................................................................... Ordering Information ........................................................ Specifications ................................................................... Installation ........................................................................ Checkout .......................................................................... 60-2032-05 1 1 2 2 4 5 Q179A,B GAS PILOT BURNER ASSEMBLIES SPECIFICATIONS Mounting Dimensions: See Fig. 2. Model Number: Q179A—Gas pilot assembly with ignition and flame electrodes. Use with intermittent or interrupted ignition. Ignition electrode is for use with 6,000V grounded secondary-ignition transformer. (Q179A1183 has ignition electrode [spark] only.) Q179B—Gas pilot assembly with flame electrode (rod) only. Use with continuous pilot. Maximum Temperature: See Fig. 3. E Burner: Primary aerated. Stainless steel fins provide proper flame contact area to ground area. Flame electrode and ground bracket are furnished with each tip. Available tips are illustrated in Fig. 1, and listed in Table 1. A 45° LEFT HAND "ELL" "I" PORT Mounting Means: Bracket has holes for side mounting and two lugs for end mounting. F "T" PORT G 45° "Y" PORT H 45° "T" PORT 1 Type of Gas: Natural; for LP gas, order LP orifice separately (see Accessories). B 45° "I" PORT Gas Consumption: Approximately two cu ft/hr. Electrodes: Stainless steel, maximum temperature 1750°F (954°C). Electrode Insulator(s): Ceramic. D 45° RIGHT HAND "ELL" Electrical Connector: Rajah connector (both male and female supplied). Approvals: Underwriters Laboratories Inc. listed, File No. MP268; Industrial Risk Insurers acceptable; CSA certified, Master File No. LR-95329-1; Factory Mutual approved; American Gas Association certified, No. G140.401. 1 NOTE THAT GROUND PRONG IS CUT OFF CLOSE TO BASE. M5007 Fig. 1. Pilot tip assembly styles. ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A. 60-2032—05 2 Q179A,B GAS PILOT BURNER ASSEMBLIES LOCATION OF OPTIONAL THERMOCOUPLE FLAME ELECTRODE 3 GROUND BRACKET IGNITION ELECTRODE (ON Q179A ONLY) MOUNTING EARS FOR END MOUNTING 1-1/2 (38) ELECTRODE INSULATORS CLAMP SCREW INSULATOR BRACKET 2 1-5/16 (33) 4-7/64 (104) 7/32 (6) 7/32 (6) 1 MOUNTING HOLES 7/32 DIA. FOR SIDE MOUNTING 13/32 (10) 1-3/16 (30) 13/32 (10) 1-11/16 (43) 1-29/32 (48) 3 (74) 1 THIS DIMENSION WILL VARY DEPENDING ON THE FLAME ELECTRODE AND INLET FITTING USED. FORMATION OF THE FLAME ELECTRODE AND GROUND FINS WILL VARY WITH THE BURNER TIP USED. 2 GAP BETWEEN IGNITION ELECTRODE AND BURNER TIP MUST BE 1/16 TO 3/32 INCH. 3 Q179A1183 DOES NOT HAVE FLAME ELECTRODE OR GROUND BRACKET. M24193 Fig. 2. Approximate mounting dimensions in inches. (mm) and arrangement of parts. FLAME ELECTRODE 1750F (954C) GROUND SHIELD 1300F (704C) Inlet Fittings: 1/4 inch compression coupling factory-installed on all models. Q179A Replacement Parts (See Table 1): 37356 Rajah Connector—for ignition electrode. 104312 Rajah Connector—for flame electrode. PILOT BURNER TIP 1500F (816C) Accessories: High temperature (higher than 125°F [52°C]) cable: Flame Rod Lead wire—part no. R1298020 (specify length) rated at 400°F (204°C). Ignition Lead wire—part no. R1061012 (specify length), rated at 350°F (177°C). High Tension Cable—part no. 32004766-003 (specify length), rated at 482°F (250°C). INSULATOR 1050F (566C) IGNITION ELECTRODE 1750F (954C) PILOT ORIFICE 780F (416C) IGNITION CONNECTOR 750F (399C) FLAME ELECTRODE CONNECTOR 750F (399C) M7859 Fig. 3. Component maximum temperature ratings. (Q179A1126 model shown) 3 60-2032-05 Q179A,B GAS PILOT BURNER ASSEMBLIES Table 1. Additional Q179A, B Replacement Parts Orifice Assembly Tip Style Tip I Natural Gas 395390-25a 45° I 105064A Flame Rod and Insulator Assembly LP Gas 395390-13b 133448A 395390-25a 45° RH 395390-25a 45° LH 395390-25a T 395390-28c 45° Y 395390-28c 45° T 395390-28c Large I 395390-25a 133451A 133448A a Orifice 0.025 in. (0.635 mm) diameter. 0.0130 in. (0.330 mm) diameter (order separately). c Orifice 0.028 in. (0.711 mm) diameter. b Orifice INSTALLATION Gas Pressure Regulation When Installing this Product… Use a pressure regulator in the line supplying the Q179 pilot. Adjust the regulator for a maximum inlet gas pressure of eight inches water column. The minimum inlet gas pressure must be two inches water column to assure reliable lightoff of the main flame. 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced, flame safeguard control technician. 4. After installation is complete, check out product operation as provided in these instructions. Follow instructions provided by burner manufacturer if available. If no instructions are furnished, use the following recommendations. Install the Q179A,B Install the pilot assembly so the pilot flame has full contact with the gas stream from the main burner heads or jets. Mount the flame electrode just inside the junction of the main and pilot flame to prove both flames. Mount the pilot so that it fires in the same direction as the draft at the mounting point, rather than where the draft is at right angles to flame travel. Keep the pilot burner below or behind the main burner so that the burner frame and refractory will help protect the pilot from radiant heat. Locating the pilot in the secondary air stream will also provide considerable cooling. The primary air adjustment must be accessible and outside the high temperature area. Mounting The Q179 has two mounting ears at the burner and two mounting holes in the bracket (see Fig. 2). If the mounting holes in the bracket are used, it may be necessary to break off one of the mounting ears so that the bracket fits flush with the burner.All models are supplied with a factory-installed 1/4 inch compression coupling inlet fitting. When a fitting is used, remove the compression nut and install the new fitting. Do Not Install the Q179A,B— — — — — — 60-2032-05 4 Where ambient temperatures exceed those specified in Fig. 3. Where excessive draft turbulence can deflect the pilot flame away from the main burner or flame electrode. Where the ignition electrode is within arcing distance of any metal other than the pilot burner head. Where the flame electrode contacts any metal part of the installation. Where the flame electrode is closer than one inch from a radiant refractory. Q179A,B GAS PILOT BURNER ASSEMBLIES WIRING measuring the flame signal developed with the pilot operating. The flame signal (current/voltage) measurement requires the use of an appropriate volt-ohmmeter. Most existing Honeywell Flame Safeguard Controls incorporate a flame current jack in the control plug-in amplifier or in the control itself. The flame current measurement can be made with a Honeywell W136A Test Meter, which has a 0 to 25 microampere dc scale (see Fig. 4). With the W136A selector switch positioned to the 0 to 25 microampere scale, connect the meter leads to the two ends of the meter connector plug, positive (red, +) to positive, negative (black, -) to negative. The Meter Connector Plug part no. 196146 is provided with the W136A Meter. If a W136A Meter or connector plug is not available, a dc ammeter with a 0 to 25 microampere scale can be wired in series with the F lead of the flame detector circuit. A minimum flame current of 2.0 microamperes is considered acceptable. The Honeywell 7800 SERIES Flame Safeguard Control flame signals are measured in dc volts. A one megohm/volt meter is recommended for 7800 SERIES controls. The flame signal voltages are measured as illustrated in Fig. 5. The minimum acceptable flame signal voltage for the 7800 SERIES controls is 1.25 Vdc (maximum expected is 5.0 Vdc). If the flame signal is less than the minimum acceptable for the Honeywell Flame Safeguard Control used, adjust the flame electrode (rod) to increase the flame signal to at least the minimum acceptable level by loosening the clamp screw and turning the electrode (rod) slightly to the right or left as required. After the flame electrode (rod) is adjusted, check the gap between the ignition electrode and burner tip (Q179A). The gap must be between 1/16 and 3/32 inch. Perform the pilot turndown test as described in the Flame Safeguard Control Instructions to ensure the pilot flame is adequate to ignite the main burner. CAUTION Disconnect power supply to prevent electrical shock and equipment damage. More than one disconnect may be involved. Wiring must conform to local codes and ordinances. Rajah connectors are furnished for making connections to the ignition and flame electrodes. The ignition electrode (A models only) takes a receptacle connector. The flame electrode (both A and B models) takes a plug connector and has a snap-action spring terminal. Use high tension wire, of a type found acceptable by a nationally recognized testing agency, for the wiring to the ignition electrode (Q179A). High tension wires should be rated electrically equivalent to type GTO-10 and should have temperature and humidity characteristics adequate for the application. If the ignition lead is exposed to temperatures above 125°F (52°C), use Honeywell R1061012 Ignition Cable rated at 350°F (177°C) or equivalent. For ignition installations in a contaminated environment, use Honeywell 32004766-003 High Tension Cable rated at 482°F (250°C) or equivalent. For wiring between the F terminal of the relay and the flame electrode, use wire with moisture-resistant insulation. Number 14 single-conductor TW wire is adequate; however, those portions of the lead wire exposed to temperatures over 125°F (52°C) should also be heat resistant. For both heat and moisture-resistant applications, use part no. R1298020 Flame Rod Lead wire rated at 400°F (204°C) continuous duty or equivalent. Run a ground wire from the pilot burner to the relay to assure a continuous, unchanging ground. For detailed wiring diagrams, see the Instructions packed with the flame safeguard control. W136A VOLTOHMMETER W136A SELECTOR SWITCH CHECKOUT CAUTION 196146 METER CONNECTOR PLUG PLUG Check to ensure the main valve opens only when the pilot flame is strong enough to ignite the main burner. Perform the pilot turn-down test as described in the Honeywell Flame Safeguard Control instructions. The proper pilot burner orifice must be selected for the gas being used (natural, LP gas) so that the pilot burns with a medium hard flame. This type of flame provides the maximum flame signal. The flame safeguard control relay will chatter if excess secondary air velocity or a severe draft condition causes the pilot flame to make intermittent contact with the flame electrode (rod) or grounding bracket. The performance of the pilot assembly can be determined by FLAME SIGNAL METER JACK RED (+) METER LEAD PLUG-IN FLAME SIGNAL AMPLIFIER RED CONNECTOR BLACK (–) METER LEAD BLACK CONNECTOR M6532A Fig. 4. Measuring microamp flame signal. 5 60-2032-05 Q179A,B GAS PILOT BURNER ASSEMBLIES Pilot Turndown Test If the flame rod is used to prove a pilot flame before the main fuel valve(s) can be opened, perform a pilot turndown test. Follow the procedures in the Instructions for the appropriate Flame Safeguard Control, and in the burner manufacturer’s instruction POSITIVE (+) METER LEAD NEGATIVE (-) METER LEAD ONE MEGOHM/VOLT METER M7382 Fig. 5. Measuring 7800 SERIES Control flame signal voltage. 60-2032-05 6 Q179A,B GAS PILOT BURNER ASSEMBLIES 7 60-2032-05 Q179A,B GAS PILOT BURNER ASSEMBLIES Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2011 Honeywell International Inc. 60-2032-05 JPG Rev. 03-11 Printed in U.S.A.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes Encryption : Standard V2.3 (128-bit) User Access : Print, Copy, Extract, Assemble, Print high-res Page Count : 8 Page Mode : UseOutlines XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:ee71563b-a2ce-44d9-9a0f-9f80922a8059 Producer : Acrobat Distiller 6.0 (Windows) Creator Tool : FrameMaker 7.2 Modify Date : 2011:05:03 04:59:30-05:00 Create Date : 1999:07:07 12:30:47Z Metadata Date : 2011:05:03 04:59:30-05:00 Document ID : uuid:744960a2-3345-4029-970c-806d429e4c58 Format : application/pdf Title : 60-2032 Q179A,B Gas Pilot Burner Assemblies Creator : Honeywell ECC Technical Communications Description : Product Data Author : Honeywell ECC Technical Communications Subject : Product DataEXIF Metadata provided by EXIF.tools