V4055A,B,D,E
On-Off Fluid Power Gas
Valve Actuator
PRODUCT DATA
• The V4055 Actuator can be used with the characterized
guide model of the V5055 or V5097 Gas Valve to
enhance lightoff smoothness.
• The standard model has an opening time of 26
seconds at 60 Hz or 32 seconds at 50 Hz. A fastopening model is available with timings of 13 seconds
at 60 Hz or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets
code, standard and insurer requirements.
• Models available with damper shaft, with or without
spring return; shaft extends out both sides and rides in
Teflon-like Delrin bushings; used with standard
7616BR Damper Crank Arm.
• Red OPEN indicator attached to actuator stem shows
when valve is even slightly open; yellow SHUT
indicator on valve stem shows only when gas valve is
fully closed.
• Models available with adjustable max flow limit switch.

APPLICATION
The V4055 Gas Valve Actuator, in combination with a
VE5000a, V5055 or V5097 Gas Valve, controls the gas supply
to commercial and industrial burners.
When replacing a V4034 with a V4055, the V5034 gas valve
must also be replaced with a V5055 or V5097 gas valve.

FEATURES
• The V4055 Actuator, when used with the VE5000a,
V5097 or V5055 Valve, is rated for final safety shutoff
service.

• Ambient temperature rating is -40°F to +150°F (-40°C to
+66°C) for 60 Hz models and -10°F to +158°F (-23°C to
+70°C) for 50 Hz and 50/60 Hz models.
• Valve and actuator combinations can be mounted in
any position, with the exception of the 220 to 240 Vac,
50/60 Hz models, which are mounted vertically.
• Models available with factory-installed single pole
double throw (spdt) field-adjustable Auxiliary Switch.
Field-addable Auxiliary Switch kits are also available.
• Standard enclosure meets NEMA 1 (IP30)
requirements; models available with NEMA 4 (IP54)
weatherproof enclosure.
• V4055D and high pressure V4055E with Proof-ofClosure Switch and V5055/V5097C or E with valve seal
overtravel interlock (double seal) to meet specific
code, standard and insurer requirements.
a VE5000 is a European manufactured and approved valve for

European use only.

Contents
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Checkout and Service ......................................................

60-2309-13

1
1
2
2
4
6
7

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

SPECIFICATIONS
Table 1. Nominal Opening Time (seconds).

Models:
V4055A Actuator, with V5055, V5097 or VE5000 Gas Valves,
provides on-off control of fuel. With proper adapter (see
Accessories), it replaces the V4034 Actuator on a V5034
Gas Valve.
V4055B Actuator is a high pressure version of V4055A.
V4055D Actuator is identical to V4055A, except has a
Proof-of-Closure Switch. Used with V5055C/V5097C
(double seal) for valve seal overtravel interlock.
V4055E Actuator is identical to V4055B, except has a
Proof-of-Closure Switch. Used with V5055E/V5097E
(double seal) for valve seal overtravel interlock.
NEMA 4 weatherproof models available.

Model

50 Hz

60 Hz

Standard

32

26

Fast-opening

16

13

Maximum Closing Time: One second when de-energized.
Ambient Operating Temperature Ratings:
60 Hz Models: -40°F to +150°F (-40°C to +66°C).
50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to +70°C).
Mounting: V4055 Actuator attaches directly to V5055/V5097
Valve with two sets of screws positioned 90 degrees apart.
Combination is multipoise.

Nominal Opening Time: See Table 1.

NOTE: 220 to 240 Vac, 50/60 Hz models are vertical
mount only.
Pressure Ratings: See Table 2.
Table 2. Pressure Ratings of Valve-Actuator Combinations.
STANDARD PRESSURE ACTUATORS
V4O55A, D, F, G
Model
STANDARD
PRESSURE VALVES
V5055A, B, C, F,
V5097A, B, C
HIGH PRESSURE
VALVES V5055D, E,
V5097D, E

Max. Rated
Pressureb

M.O.P.D.a

Pipe Size

HIGH PRESSURE ACTUATORS
V4O55B, E
M.O.P.D.a

Max. Rated
Pressure b

3/4” to 1-1/2”c

5 PSI

340 mbar 15 PSI

1.0 Bar

15 PSI

1030 mbar 15 PSI

1.0 Bar

2” to 3”d

5 PSI

340 mbar 15 PSI

1.0 Bar

15 PSI

1030 mbar 15 PSI

1.0 Bar

3 PSI

207 mbar 15 PSI

1.0 Bar

5 PSI

340 mbar

15 PSI

1.0 Bar

5 PSI

340 mbar 75 PSI

5.0 Bar

25 PSI

1720 mbar 75 PSI

5.0 Bar

5 PSI

340 mbar 45 PSI

3.0 Bar

15 PSI

1030 mbar 45 PSI

3.0 Bar

e

4” flanged

3/4” to 1-1/2”

c

2” to 3”d

a

Max Operating Pressure Differential (UL) or Max Operating Pressure (CSA): maximum allowable pressure drop from inlet to
outlet for proper operation .
b Max rated pressure (UL) or Max Close-off Pressure (CSA) : maximum pressure that the valve can be exposed to without leakage or damage to the valve.
c Applies for small-body V5097 valves 3/4” up to 2” pipe size.
d Applies for large-body V5097 valves 2” up to 3” pipe size.
e V5055A, B, C only.
Electrical Ratings: See Tables 3 and 4.

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2309—13

2

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

Table 3. V4055A,D Electrical Ratings.
Opening (Standard)
Voltage and Frequency

Inrush

(W)

(A)

Opening (Fast)
VA)

Inrush

(W)

Holding

(A)

(VA)

(W)

(A)

(VA)

100/50-60a

—

43.0

0.91

91

—

58.0

1.30

130

10.4

0.16

16

100/50-60b

—

33.0

0.6

67

—

43.0

0.91

91

8.4

0.14

14

120/60

3.9

50.0

0.94

115

5.4

71.0

1.33

160

9.5

0.12

14

a

—

68.0

0.79

158

—

88.0

1.10

220

10.6

0.09

18

200/50-60b

—

48.0

0.52

104

—

63.0

0.72

144

9.0

0.07

14

220/50

1.6

55.5

0.55

121

3.0

76.0

0.80

176

9.0

0.06

14

240/50

—

81.5

0.79

190

—

95.0

1.00

240

9.1

0.06

14

240/60

2.6

51.0

0.45

115

4.0

71.5

0.68

160

9.2

0.06

14

220-240/50-60c

—

—

—

—

—

70.3

0.59

136

7.2

0.07

16

220-240/50-60d

—

—

—

—

—

58.6

0.46

106

5.9

0.06

14

200/50-60

a

50 Hz power supply.
60 Hz power supply.
c 230 Vac, 50 Hz power supply.
d 230 Vac, 60 Hz power supply.
b

Table 4. V4055B,E Electrical Ratings.
Voltage and
Frequency

Opening (Standard)
Inrush

(W)

(A)

Opening (Fast)
(VA)

Inrush

(W)

Holding

(A)

(VA)

(W)

(A)

(VA)

120/60

—

60

0.94

115

—

60.0

0.94

115

9.5

0.16

19

220-240/50-60a

—

—

—

—

—

68.9

0.58

133

6.7

0.08

18

220-240/50-60b

—

—

—

—

—

58.2

0.46

106

5.3

0.06

14

a
b

230 Vac, 50 Hz power supply.
230 Vac, 60 Hz power supply.

Auxiliary Switch and Proof-of-Closure Switch Ratings:
See Table 5.

NOTE: Damper shaft drives damper crank arm in one
direction only; optional return spring is available on
damper shaft to turn damper crank arm in opposite
direction. See Table 6.

Table 5. Auxiliary Switch and Proof-of-Closure
Switch Ratings (1/2 hp [0.37kW]a).
Load

120V

Full Load

9.8A

4.9A

Locked Rotor

58.8A

29.4A

aMaximum

1800 VA.

Table 6. Actuator Torque (With and
Without Return Spring).

240V

-40°F to +20°F
(-40°C to -7°C)
lb

V4055 Model

total connected power to both switches (if used) is

With return spring

20°F to 150°F
(-7°C to +66°C)

N

lb

N

5

22.2

10

44.5

Mounting Dimensions: See Fig. 1 and Table 7.

Without return spring 5

22.2

20

89.0

Damper Shaft: Shaft is 3/8 in. (9.5 mm) square, for use with
7616BR Damper Crank Arm (ordered separately) and with or
without damper shaft return spring.

Approvals:
Underwriters Laboratories Inc. Listed: File No. MH1639, Guide
No. YIOZ.
Factory Mutual: Listed.
Canadian Standards Association certified: General Listed file
numbers 158158 Class 3371
For U.S.A. and Canada: certified 60 Hz models only.
Swiss Re (Formerly GeGap/IRI) Acceptable.
Some V4055 Actuators are approved as Class A valves in
accordance with EN161:
When used with V5055 Valves: Pin: CE-0063AR1359.
When used with VE5000 Series Valves: Pin: CE0063AP3075.

Maximum Damper Shaft Rotation: 52 angular degrees.
Maximum Force: 2-11/16 in. (68.3 mm) radius for 7616BR
Damper Crank Arm ordered separately (see Accessories
section).

3

60-2309—13

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

Accessories:
133568 Auxiliary Switch Bag Assembly (not for models with
maximum flow limit switch).
133569 Valve-Closed Indication Switch Bag Assembly.

7616BR Damper Crank Arm (damper arm and clip).
Available Models: V4055 with NEMA 4 enclosure
(weatherproof).

NOTE: Check local codes for acceptance of adding the
switch and using the valve seal overtravel V5055C or
V5055E valves.
6-3/4 (172)

KNOCKOUT FOR
1/2 INCH CONDUIT (4)

3-23/32 (95)

5 (127)

27/32 (21)

1-9/32
(33)
1

A
C

B
VALVE

VALVE

D
1 ALLOW 4 INCH (102 MM) CLEARANCE FOR ACTUATOR REMOVAL. M17755A

Fig. 1. Approximate mounting dimensions of V4055 Actuators in in. (mm).
Table 7. Approximate Mounting Dimensions of V4055 Actuators with V5055 and V5097 Valves.
V5055
Dim. A
Valve Sizea (in.)
Small
Body

Large
Body

a

in.

Dim. B

mm

in.

mm

V5097
Dim. C
in.

mm

Dim. D
in.

Dim. A

mm

in.

Dim. B

mm

in.

Dim. C

mm

in.

Dim. D

mm

in.

mm

3/4

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-1/2

64

1

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-/12

64

1-1/4

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-1/2

64

1-1/2

11-1/8

283

2-3/4

70

8-3/16

208

5-3/4

146

11-1/8

283

2-3/4

70

8-3/16

208

2-1/2

64

2

11-1/8

286

2-7/8

73

8-5/16

211

8-3/8

213

11-3/4

298

3-3/8

86

8-3/8

213

4

102
102

2

11-3/4

298

3-3/8

86

8-13/16 224

9-1/4

235

1-3/4

298

3-3/8

86

8-3/8

213

4

2-1/2

11-3/4

298

3-3/8

86

8-13/16 224

9-1/4

235

11-3/4

298

3-3/8

86

8-3/8

213

4

102

3

11-3/4

298

3-3/8

86

8-13/16 224

9-1/4

235

11-3/4

298

3-3/8

86

8-3/8

213

4

102

4

14-1/8

359

5-13/16 148

11-7/32 285

12-1/2

318

—

—

—

—

—

—

—

—

Valve size using accessory pipe adapter fitting.

INSTALLATION

3.
4.

When Installing This Product...
1.
2.

Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.

60-2309—13

Installer must be a trained, experienced flame
safeguard control technician.
After installation is complete, check out product
operation as provided in these instructions.

WARNING

Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.

4

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

Mount Actuator on Valve

IMPORTANT
1. All wiring must comply with all applicable electrical
codes, ordinances, and regulations. All wiring must
be NEC Class 1.
2. Voltage and frequency of the power supply connected
to this control must agree with those marked on the
device.
3. Loads connected to the Auxiliary Switch and/or Proofof-Closure Switch, if used, must not exceed the ratings given in the Specifications section.

1.

2.

Check the final position of the valve body to be sure that
the actuator is in the proper position when mounted on
the valve. This is especially important when the actuator
is used to drive a damper.
If two smaller sized valves are mounted very closely
together, as in an Industrial Risk Insurers approved type
of valve train, it may be necessary to mount the
actuators off center to provide adequate clearance.

Install Valve
The actuator is mounted directly on the valve bonnet after the
valve is installed in the gas supply line. Refer to the instructions
packed with the gas valve for installation details. When
installing the gas valve, make sure:
1.
2.
3.

133568
AUXILIARY
SWITCH

Sufficient clearance is left to install and service the actuator.
Ambient temperatures at the valve location do not
exceed actuator ratings. See Specifications section.
Position of the valve permits hookup to the damper if one
is controlled.

133569
VALVECLOSED
INDICATION
SWITCH

Install Accessory Switches (If
Needed)

ADJUSTING
SCREW FOR
AUXILIARY
SWITCH

An spdt switch can be installed to operate an auxiliary load up
to 1/2 hp (0.37 kW). See Table 5. The switch can be adjusted
to operate at any point in the valve stroke.
A Proof-of-Closure Switch can also be installed with a V5055/
V5097C or E Valve (with double seal) on any V4055 Actuator
to provide a valve seal overtravel interlock. The spdt
Proof-of-Closure Switch is installed to make or break a circuit
when the valve is in the closed position. The switch is not
adjustable.

EACH SWITCH SECURED BY
TWO SCREWS FROM UNDERSIDE OF BASE.
IF ONLY ONE SWITCH IS USED, INSTALL BARRIER
IN OPEN POSITION.

Fig. 2. V4055 Actuator with cover removed.
3.

NOTE: Mark the actuator or valve to indicate any changes
made.
To install the switches:
1.
2.
3.
4.

5.
6.

M7326B

4.

Remove the actuator faceplate (two screws).
Remove the silver-colored barrier to expose the actuator
stem.
Insert the Auxiliary Switch in the position indicated in Fig.
2. Fasten with two screws through the actuator base.
Insert the Proof-of-Closure Switch in the position shown
in Fig. 2. The switch mounts against the side of the
actuator housing. The mounting holes are spaced to
assure mounting the switch in the correct position.
Fasten with two screws through the actuator base. (The
Proof-of-Closure Switch is not adjustable.)
If only one switch is used, install the narrow barrier
included with the switch in the unused space.
Mount the actuator before making wiring connections
and adjustments to the Auxiliary Switch.

Slip the bottom collar of the actuator over the
valve bonnet assembly. Rotate the actuator to the
desired position and use a 5/32 in. Allen wrench to
securely tighten the two setscrews to 50 to 60 lb-in.
(5.7 to 6.8 N•m).
Connect the damper linkage, if used. Refer to the
instructions packed with the damper arm.

Mount and Adjust 7616BR
Damper Crank Arm (If Used)
IMPORTANT
When a damper crank arm is used with a NEMA 4
actuator that is exposed to ice or sleet, a suitable
shield must be installed to prevent ice or sleet
buildup.
Follow installation and adjustment directions included with
damper crank arm. Maximum pushrod travel is 2-5/16 in.
(59 mm) through a stroke of 52 degrees. See Fig. 3.

5

60-2309—13

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

stroke.
L1
HOT
1

7616BR
DAMPER
ARM

52 DEGREE
ANGULAR
ROTATION
2-5/16 (58.7)
MAXIMUM
TRAVEL

2

1

L2

SHAFT

PROOF-OF-CLOSURE
SWITCH
AUXILIARY
SWITCH
2-11/16 (68.3)
RADIUS

M7322

Fig. 3. 7616BR Damper Crank Arm can be attached to
actuator shaft to drive a damper when valve is open.

WIRING

C

C

NC

NC

NO

NO

2

2
3

WARNING

Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before making wiring
connections to prevent electrical shock and equipment
damage.

Wiring must comply with all applicable electrical codes,
ordinances and regulations. Wiring to the actuator must be
NEC Class 1.

1

POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND
DISCONNECT MEANS AS REQUIRED.

2

SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN
VALVE IS SHUT (DE-ENERGIZED).

3

SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN
VALVE IS SHUT (DE-ENERGIZED).
M7334

Fig. 4. External connections to the V4055 Actuator.

7800 SERIES
RELAY
MODULE L2

Connect the power supply to terminals 1 and 2 on the V4055
terminal strip. Refer to Fig. 4 for Auxiliary Switch connections
and Fig. 5 for Max Flow Limit Switch connections. For typical
system hookups, refer to Fig. 6 and to instructions packed with
the device used to control the valve.

9
1
3

When all wiring connections are complete, replace the actuator
faceplate.

2
4

TRAVEL
LIMIT
SWITCH

CAUTION

Operation Hazard.
Improper wiring can cause improper and
dangerous operation.
Label all wires prior to disconnection when servicing
valves. Wiring errors can cause improper and
dangerous operation.

FIELD WIRING
INTERNAL WIRING

PUMP
VALVE

PUMP
MOTOR
ADJUSTABLE
NO MAX
FLOW
NC LIMIT
SWITCH
C
M12798

Fig. 5. Connecting the Max Flow
Limit Switch to the actuator.
NOTE: The Proof-of-Closure Switch is not adjustable.

NOTE: Pipe sealant is required on the conduit threads of
actuators with NEMA 4 enclosures.

Adjust Max Flow Limit Switch (If
Used)

Adjust Auxiliary Switch (If Used)

The Max Flow Limit Switch is adjustable throughout the stroke
of the actuator. With the switch installed in the actuator, turn
the adjusting screw clockwise
to cause the switch to
operate earlier in the stroke or counter-clockwise
to
cause the switch to operate later in the stroke.

The Auxiliary Switch is adjustable throughout the stroke of
the actuator. With the switch installed in the actuator, turn
the adjusting screw (see Fig. 2) clockwise
to cause the
switch to operate earlier in the stroke or counterclockwise
to cause the switch to operate later in the

60-2309—13

3

6

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

CHECKOUT AND SERVICE

7.
8.

CAUTION

9.

Equipment Damage Hazard.
Unskilled technicians can cause equipment
damage.
Only a trained, experienced, flame safeguard
technician should check out and service this control.

10.

Checkout

NOTE: When replacing the bonnet assembly on the 4inch valve, draw it evenly into the valve body.
Finger-tighten the eight bolts. Draw the bonnet
assembly into the valve by tightening, in order,
bolts 1, 5, 7 and 3 (two turns each). Repeat until
the bonnet assembly is seated. Tighten the
remaining bolts. Torque the bolts as follows:

After the installation is complete, cycle the valve several times
with the manual fuel shutoff cock closed before testing the
system in actual operation.

Service
The actuator is not field repairable except for replacing the
Auxiliary Switch, Max Flow Limit Switch or Proof-of-Closure
Switch. See Installation section for procedure. Do not
disassemble the valve actuator.

Valve Size

If the actuator fails to operate properly, replace it.
1.
2.
3.
4.
5.

Turn off the gas supply at the manual shutoff valve
located upstream from the valve(s) being serviced.
Shut off all electrical power to the valve actuator(s).
Mark and disconnect the wires from the actuator terminals. Remove conduit and disengage the damper linkage assembly (if applicable).
Loosen the two set screws from the valve to lift off the
actuator.
If the actuator is to be replaced and it did not leak
hydraulic fluid, skip to Step 11.
NOTE:

6.

If the valve bonnet assembly is in good condition and is
not replaced, replace the bonnet seal. Do not reuse the
old bonnet seal. See Table 9 below for the seal number.
Coat seals with grease provided and position in valve
body/bonnet assembly.
Carefully seat the bonnet assembly on the valve body.
Be sure the seals are in their proper position. On those
valves with a spring below the disc, be sure the spring is
centered in the indentation on the inside of the valve
body.
After positioning the bonnet assembly, replace the
screws removed earlier.

Torque

3/4 in. (19 mm) to 1-1/2 in. (38 mm)

55 in.-lb.

2 in. (51 mm) to 4 in. (102 mm)

75 in.-lb.

11.
12.
13.
14.

Remount the actuator on the bonnet assembly. Tighten
the two set screws (50-60 inch pounds).
Replace the damper crank arm assembly.
Re-attach the wires removed from the actuator terminals
and turn on the electrical power.
With the gas still off, cycle the actuator to check for
proper mechanical operation.

CAUTION

It is good practice to inspect the inside of the
valve whenever the actuator is replaced. To do
so, remove the bonnet assembly, inspect the
valve and bonnet. If all is well, proceed to Step 7.

Be sure to perform a bonnet seal and seat leak
check after installation.
Be sure to read and follow all instructions that come
with the actuators, valves, seal and bonnet kits.

If the actuator leaked hydraulic fluid onto the valve (the
fluid is red), it must be cleaned off from the valve and
bonnet assembly.
a. Wipe off the outer valve body.
b. Remove the valve bonnet bolts and lift off the bonnet.

Table 8. Replacement Bonnets for
V5055/V5097 Gas Valves.
Replacement
Bonnet

NOTE: V5055/V5097C and E Valves have additional
internal springs that will push the bonnet up as
the bolts are loosened.

133398AA

Valve
V5055A

V5097A

133417AA

c. Inspect the inside of the valve.

2, 2-1/2, 3

136911AA

(On-Off)

133398BA

V5055B

4
V5097B

IMPORTANT
If fluid is present on the inside surfaces of the valve
body or bonnet surfaces, the bonnet assembly or
entire valve must be replaced. See Table 8 below for
the bonnet assembly part number.

133417BA

d. If the inside surfaces are clear of hydraulic fluid,
clean the bonnet assembly and be sure to remove all
hydraulic fluid from the inside and outside of the
actuator mounting curb. This is the “cup-like” area
around the valve stem. Avoid using a cleaning solution as it may damage the rubber seals used in the
valve.

136911CA

(Proof of Closure)

136308AA

V5055D

3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3

136911BA

(Characterized Guide)

4

133398CA

V5055C

3/4, 1, 1-1/4, 1-1/2

V5097C

133417CA

2, 2-1/2, 3
V5097D

136307AA
136308BA
136307BA

7

Valve Size (in in.)
3/4, 1, 1-1/4, 1-1/2

4
3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3

V5055E

V5097E

3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3

60-2309—13

V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

Each replacement assembly contains the bonnet assembly,
two rubber seals, and a tube of grease. It must be used only
on the type of valve indicated above.
Table 9. Gas Valve Replacement Seals.
Replacement Seal
Assy #
133393A

Valve Size (in in.)
3/4, 1, 1-1/4, 1-1/2

133392A

2, 2-1/2, 3

137253A

4
WIRING SUBBASE TERMINAL STRIP (4)
R414OL FLAME SAFEGAURD CONTROLS

LOCKOUT
INTERLOCKS
(INCL. AIRFLOW
SWITCH)

2

3
V4055D OR E
1
BURNER
CONTROLLER

4

LIMITS

2

L1

18
C
3

9

10

ALARM

L2

10 SECOND
INTERRUPTED
PILOT/IGNITION

5

15 SECOND
INTERRUPTED
PILOT/IGNITION

6

NC
NO

17

HIGH-FIRE
12

16

7

BURNER
MOTOR

8

LOW-FIRE
SWITCH
11

COMMON

B

B

R

R

W

W

13

ALTERNATE
LOW-FIRE
SWITCH

15

F

14

MODULATE
LOW-FIRE

120V, 60 HZ
POWER
SUPPLY 1

RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL, OR INFRARED
(LEAD SULFIDE)
FLAME DETECTOR
OR

BLUE
SERIES 90
CONTROLLER

G

HIGH-FIRE
SWITCH

SERIES 90
FIRING RATE
MOTOR
L1 (HOT)

BLUE

L2
MASTER
SWITCH

C7027A, C7035A, OR
C7044A, ULTRAVIOLET
FLAME DETECTOR
OR
C7012A, C, E,F
OR C7076A
ULTRAVIOLET
FLAME DETECTOR

WHITE

YELLOW

WHITE

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

2

USE ALL NEC CLASS 1 WIRING.

3

PROOF-OF-CLOSURE SWITCH IN PREIGNITION INTERLOCK CIRCUIT;
SWITCH IS CLOSED NC-C WHEN ACTUATOR IS DE-ENERGIZED.

WHITE

L2
L1
L2

BLACK
BLACK
M7335

Fig. 6. Typical application of a V4055D/V5055C/V5097D or V4055E/V5055E/V5097E combination to meet Factory Mutual
or Underwriters Laboratories Inc. approved requirements for Proof-of-Closure Switch (valve seal overtravel interlock).
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com

® U.S. Registered Trademark
© 2010 Honeywell International Inc.
60-2309—13 E.K. Rev. 02-10
Printed in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Assemble, Print high-res
Page Mode                       : UseOutlines
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Creator Tool                    : FrameMaker 7.0
Modify Date                     : 2010:02:24 08:03:38-06:00
Create Date                     : 1999:07:07 12:30:47Z
Metadata Date                   : 2010:02:24 08:03:38-06:00
Format                          : application/pdf
Title                           : 60-2309—12 - V4055A,B,D,E On-Off Fluid Power Gas Valve Actuator
Creator                         : Honeywell ECC Technical Communications
Description                     : Product Data
Producer                        : Acrobat Distiller 8.2.0 (Windows)
Document ID                     : uuid:9808e7dc-1439-4239-93a6-1875b24b778e
Instance ID                     : uuid:8ea99814-3088-45ee-8abd-0e765dd56bf2
Page Count                      : 8
Subject                         : Product Data
Author                          : Honeywell ECC Technical Communications
EXIF Metadata provided by EXIF.tools

Navigation menu