Honeywell Visionpro Th8000 Series Installation Manual 69 2693 01 VisionPRO®

2014-12-11

: Honeywell Honeywell-Visionpro-Th8000-Series-Installation-Manual-120099 honeywell-visionpro-th8000-series-installation-manual-120099 honeywell pdf

Open the PDF directly: View PDF PDF.
Page Count: 12

DownloadHoneywell Honeywell-Visionpro-Th8000-Series-Installation-Manual- 69-2693-01 - VisionPRO® TH8000 Series  Honeywell-visionpro-th8000-series-installation-manual
Open PDF In BrowserView PDF
Installation
Guide

VisionPRO TH8000 Series
®

Touch-screen Programmable Thermostat

This manual covers the following models
•	 TH8110U: For 1 Heat/1 Cool systems
•	 TH8320U: For up to 3 Heat/2 Cool systems
•	 TH8321U: For up to 3 Heat/2 Cool systems with dehumidification
(Pull thermostat from wallplate and turn over to find model number)

System Types
•	 Gas, oil, or electric heat with air
conditioning
•	 Warm air, hot water,
highefficiency furnaces, heat
pumps, steam, gravity

•	 Heat only — two-wire systems,
power to open and close zone
valves (Series 20), and normally
open zone valves
•	 Heat only with fan
•	 Cool only
•	 750 mV heating systems

This thermostat contains a Lithium battery which may contain Perchlorate material.
Perchlorate Material—special handling may apply,
See www.dtsc.ca.gov/hazardouswaste/perchlorate

Need Help?
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502

® U.S. Registered Trademark.
Copyright © 2012 Honeywell International Inc.
All rights reserved.

69-2693-01

Installation Guide

Wallplate installation
1.	 Separate wallplate from thermostat.

Grasp top and bottom of wallplate
and pull to remove from thermostat.

2.	 Mount wallplate as shown below.

+

+
+

Drill 3/16” holes for drywall.
Drill 7/32” holes for plaster.

MCR29480

Wire hole

Mounting screws

Wall anchors

ENGLISH

MCR29481

Must be installed by a trained, experienced technician
•	 Read these instructions carefully. Failure to follow these instructions
can damage the product or cause a hazardous condition.

CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
69-2693—01

2

VisionPRO TH8000 Series
TM

Power options

NOT
USED

Insert supplied batteries for
primary or backup power.

For 24VAC primary power, connect common
side of transformer to “C” terminal.

MCR29482

Wiring
Remove factory-installed jumper
only for two-transformer systems.

Push excess wire back into the wall opening. Plug
wall opening with non-flammable insulation.

NOT
USED

MCR29483

Terminal Designations Shaded areas below apply only to TH8320/TH8321.
Heat Pump Terminal Letters:
R	
Heating power. Connect to secondary
side of heating system transformer.
Rc	 Cooling power. Connect to secondary
side of cooling system transformer.
C	
Common wire from secondary side of
cooling system transformer.
Y	
1st stage compressor contactor.
Y2	 2nd stage compressor contactor.
Aux/E	 Auxiliary/Emergency heat relay.
G	
Fan relay.
L	
Heat pump reset (powered continuously
when System is set to Em Heat; system
monitor when set to Heat, Cool or Off).
O/B	 Changeover valve for heat pumps.
S1	 Optional outdoor or remote sensor.
S2	 Optional outdoor or remote sensor.
3

69-2693—01

ENGLISH

Conventional Terminal Letters:
R	 Heating power. Connect to secondary
side of heating system transformer.
Rc	 Cooling power. Connect to secondary
side of cooling system transformer.
C	 Common wire from secondary side of
cooling transformer (if 2 transformers).
W	 1st stage heat relay.
W2	 2nd stage heat relay.
Y	 1st stage compressor contactor.
Y2	 2nd stage compressor contactor.
G	 Fan relay.
S1	 Optional outdoor or remote sensor.
S2	 Optional outdoor or remote sensor.

Installation Guide

Wiring
Wiring guide—conventional systems
Shaded areas below apply only to TH8320/TH8321.

1H/1C System (1 transformer)
Rc	
R	
W	
Y	
G	
C	
S1	
S2	

1H/1C System (2 transformers)

Power [1]
[R+Rc joined by jumper]
Heat relay
Compressor contactor
Fan relay
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

Rc	
R	
W	
Y	
G	
C	
S1	
S2	

Heat Only System
Rc	
R	
W	
C	
S1	
S2	

Heat Only System With Fan

Power [1]
[R+Rc joined by jumper]
Heat relay
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

Rc	
R	
W	
G	
C	
S1	
S2	

Heat Only System (Series 20)
Rc	
R	
W	
Y	
C	
S1	
S2	

Power [1]
[R+Rc joined by jumper]
Heat relay
Fan relay
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

Cool Only System

[R+Rc joined by jumper]
Series 20 valve terminal “R” [1]
Series 20 valve terminal “B”
Series 20 valve terminal “W”
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

Rc	
R	
Y	
G	
C	
S1	
S2	

2H/2C System (1 transformer)

ENGLISH

Y2	
W2	
Rc	
R	
W	
Y	
G	
C	
S1	
S2	

Power (cooling transformer) [1, 2]
Power (heating transformer) [1, 2]
Heat relay
Compressor contactor
Fan relay
24VAC common [3, 4]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

Power [1]
[R+Rc joined by jumper]
Compressor contactor
Fan relay
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

2H/2C System (2 transformers)

Cool relay 2
Heat relay 2
Power [1]
[R+Rc joined by jumper]
Heat relay 1
Cool relay 1
Fan relay
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

Y2	
W2	
Rc	
R	
W	
Y	
G	
C	
S1	
S2	

Cool relay 2
Heat relay 2
Power (cooling transformer) [1, 2]
Power (heating transformer) [1, 2]
Heat relay 1
Cool relay 1
Fan relay
24VAC common [3, 4]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

See [notes] below
	
	
	
	

[1]	
[2]	
[3]	
[4]	

Power supply. Provide disconnect means and overload protection as required.
Remove jumper for 2-transformer systems.
Optional 24VAC common connection.
Common connection must come from cooling transformer.

69-2693—01

4

VisionPRO TH8000 Series
TM

Wiring
Wiring guide—heat pump systems
Shaded areas below apply only to TH8320/TH8321.

1H/1C Heat Pump (no auxiliary heat)
Rc	
R	
O/B	
Y	
G	
C	
S1	
S2	

2H/2C Heat Pump (no auxiliary heat)

Power [1]
[R+Rc joined by jumper]
Changeover valve [5]
Compressor relay
Fan relay
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

Y2	
Rc	
R	
O/B	
Y	
G	
C	
S1	
S2	

2H/1C Heat Pump (with auxiliary heat)

Compressor 2 relay
Power [1]
[R+Rc joined by jumper]
Changeover valve [5]
Compressor 1 relay
Fan relay
24VAC common [3]
Optional outdoor/remote sensor
Optional outdoor/remote sensor

3H/2C Heat Pump (with auxiliary heat)

L	
Equipment monitor [6, 7]
Aux/E	 Auxiliary/Emergency heat relay (Heat 2)
Rc	
Power [1]
R	
[R+Rc joined by jumper]
O/B	 Changeover valve [5]
Y	
Compressor relay
G	
Fan relay
C	
24VAC common [3]
S1	
Optional outdoor/remote sensor
S2	
Optional outdoor/remote sensor

Y2	
Compressor 2 relay
L	
Equipment monitor [6, 7]
Aux/E	 Auxiliary/Emergency heat relay (Heat 2)
Rc	
Power [1]
R	
[R+Rc joined by jumper]
O/B	 Changeover valve [5]
Y	
Compressor 1 relay
G	
Fan relay
C	
24VAC common [3]
S1	
Optional outdoor/remote sensor
S2	
Optional outdoor/remote sensor

See [notes] below
	
	
	
	
	

5

69-2693—01

ENGLISH

[1]	 Power supply. Provide disconnect means and overload protection as required.
[3]	 Optional 24VAC common connection.
[5]	 O/B set to control as either O or B in installer setup.
[6]	If L terminal is used, 24VAC common (terminal C) must be connected.
[7]	 Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor
when set to Heat, Cool, or Off).

Installation Guide

Remove tab and mount thermostat
Remove tab.

Align pins on back of thermostat with
slots in wallplate, then push gently
until thermostat snaps into place.

MCR29484

Set date and time
Press st
to set date

Press st
to set time

TUE

Press st
to set month

TUE

15

Press st
to set year

6

2012

1:00 PM

DONE

DONE

MCR29485

Press DONE to save changes.

Press DONE to save and exit.

Installer setup
ENGLISH

Press SYSTEM.

1.	

2.	

Press and hold
these two buttons
until the display
changes.

SYSTEM
HEAT

6:00aM

TUE
FAN
AUTO

Inside

70

SYSTEM
HEAT

6:00aM
SCHED

DONE

3.	

Change settings
as required (see
pages 7-9).

CANCEL

0120

20

DONE

HOLD

MCR29486

69-2693—01

6

VisionPRO TH8000 Series
TM

Installer setup
Function

Setting

20

0120

20

0120

DONE

DONE

MCR29486

Press st to
select function

Press st to
change setting

Setup functions	

Press DONE to exit & save settings.

Settings & Options

(factory default in bold)

Shaded areas below apply only to TH8320/TH8321.
Year
(first two digits)

20	(2001-2099)
21	(2100-2178)

0130

Year
(second two digits)

12	(2012)
	
[Other options: 00-99]

0140

Month

6	 [Other options: 1-12]

0150

Date

15	 [Other options: 1-31]

0160

Schedule format

4	 7-day programming
0	Non-programmable

0170

System type

1	
2	
3	
4	
5	

0180

Fan control
(heating)

0	 Gas/Oil heat (equipment controls heating fan)
1	 Electric furnace (thermostat controls heating fan)

0190

Changeover valve
(O/B terminal)

0	 O/B terminal controls valve in cooling
1	 O/B terminal controls valve in heating

0200

Auxiliary heat

0	 Electric backup heat
1	 Fossil fuel backup heat

0210

External fossil
fuel kit

1	 External fossil fuel kit controls backup heat
0	 Thermostat controls backup heat (outdoor sensor required)

0220

1st stage compressor cycle rate

3	 Recommended for most compressors
	
[Other options: 1, 2, 4, 5 or 6 CPH]

0230

2nd stage compressor cycle rate

3	 Recommended for most compressors
	
[Other options: 1, 2, 4, 5 or 6 CPH]

1 heat/1 cool conventional
1 heat/1 cool heat pump (no aux. heat)
Heat only (2-wire systems)
Heat only with fan
Hot water Series 20 system (power to open & close zone
valves/normally open zone valves)
6	 Cool only
7	 2 heat/1 cool heat pump (with aux. heat)
8	 2 heat/2 cool multistage conventional
9	 2 heat/1 cool multistage conventional
10	 1 heat/2 cool multistage conventional
11	 2 heat/2 cool heat pump (no aux. heat)
12	 3 heat/2 cool heat pump (with aux. heat)

Continued on next page

7

69-2693—01

ENGLISH

0120

Installation Guide

Installer setup
Setup functions	

Settings & Options

(factory default in bold)

Shaded areas below apply only to TH8320/TH8321.

ENGLISH

0240

First stage heat
cycle rate (CPH=
cycles per hour)

5	
1	
3	
9	
	

Gas or oil furnaces of less than 90% efficiency
Steam or gravity systems
Hot water systems & furnaces of 90%+ efficiency
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0250

Second stage heat
cycle rate (CPH)

5	
1	
3	
9	
	

Gas or oil furnaces of less than 90% efficiency
Steam or gravity systems
Hot water systems & furnaces of 90%+ efficiency
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0260

Third stage heat
cycle rate (CPH)

9	
1	
3	
5	
	

Electric auxiliary heat or electric furnaces
Steam or gravity systems
Hot water systems & furnaces of 90%+ efficiency
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

0280

Backlight

0	 Backlight on for approx. 8 seconds after keypress
1	 Backlight always on low intensity, full bright after keypress (requires 24VAC connection)

0300

Manual/Auto
changeover

0	 Manual changeover (Heat/Cool/Off)
1	 Automatic changeover (Heat/Cool/Auto/Off)

0310

Auto changeover
deadband

3 	 Heat/cool temperature 3°F apart (1.5°C) 	** See page 11
[Other options: 2-9 (2°F to 9°F/1.5 °C to 5°C)]

0320

Temperature
display

0	Fahrenheit
1	 Celsius

0330

Daylight savings

2	 Auto-change to daylight savings time (2007 and beyond, for areas that use the new 2007 DST calendar)
1	 Auto-change to daylight savings time (through 2006, and
for areas that do not use the new 2007 DST calendar)
0	 Daylight savings time is turned off

0340

Remote sensor

0	
1	
2	
3	

0350

Heat pump
compressor lockout

0	 No heat pump compressor lockout
	
[Other options: 15, 20, 25, 30, 35, 40°F (-9.5°C to 7°C)]

0360

Heat pump
auxiliary lockout

0	 No heat pump auxiliary lockout
	
[Other options: 40, 45, 50, 55, 60°F (4.5°C to 15.5°C)]

0380

Dehumidification
control

0	 No dehumidification control
1	 Thermostat controls dehumidification with air conditioner
** See page 11

No remote sensor
Outdoor sensor (display only)
Outdoor control sensor (select heat pumps) ** See page 11
Indoor sensor

Continued on next page

69-2693—01

8

VisionPRO TH8000 Series
TM

Installer setup
Setup functions	

Settings & Options

0500

Furnace filter
change reminder

0	Off
1	 10-day run time (about 1 month)
2	 30-day run time (about 3 months)
3	 60-day run time (about 6 months)
4	 90-day run time (about 9 months)
5	 120-day run time (about 1 year)
6	 365-day run time (about 3 years)

0510

Humidifier pad
change reminder

0	Off
1	 90 calendar days
2	 180 calendar days
3	 365 calendar days

0520

UV lamp change
reminder

0	Off
1	 365 calendar days

0530

Adaptive Intelligent
Recovery™

1	On	
0	Off

0540

Program periods

4	 4 program periods (Wake, Leave, Return, Sleep)
2	 2 program periods (Wake, Sleep)

0580

Compressor
protection

5	 5 minute compressor off time	 ** See page 11
	
[Other options: 0, 1, 2, 3 or 4-minute off time]

0600

Heat temperature
range stop

90	 Max. heat temperature setting is 90°F (32°C)
	
[Other options: 40-89°F (4.5°C to 32°C)]

0610

Cool temperature
range stop

50	 Min. cool temperature setting is 50°F (10°C)
	
[Other options: 51-99°F (10.5°C to 37°C)]

0640

Clock format

12	 12-hour time (i.e., “3:30 pm”)
24	 24-hour time (i.e., “15:30”)

0650

Extended fan
timer (heat)

0	Off
90	 Fan runs for 90 seconds after call for heat ends

0660

Extended fan
timer (cool)

0	Off
90	 Fan runs for 90 seconds after call for cooling ends

0670

Keypad lock

0	 Keypad unlocked (fully functional)
1	 Partially locked (access to temperature settings only)
2	 Fully locked

0680

Heat temperature
control

2	 Standard temperature control (recommended)
1	 Choose if room is warmer than set temperature
3	 Choose if room does not reach set temperature

0690

Cool temperature
control

2	 Standard temperature control (recommended)
1	 Choose if room is cooler than set temperature
3	 Choose if room does not reach set temperature

0700

Temperature
display offset

0	
	

0710

RESET

0	 No reset
1	 Reset installer options & program schedule to factory
default (only date and time settings are retained)

(factory default in bold)

** See page 11

9

69-2693—01

ENGLISH

Thermostat displays actual room temperature
[Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)

Installation Guide

Installer system test
Test
number

During installer setup, press t
repeatedly until “Test” appears.

0120

System
status

1

20

DONE

TEST

0

DONE

MCR29488

Press st to
select test

Press st to
change status

Press DONE to terminate testing.

Shaded areas below apply only to TH8320/TH8321.
System test	

System status

1

Cooling system

0	
1	
2	

Compressor and fan turn off
Compressor and fan turn on
Second stage compressor turns on

2

Fan system

0	
1	

Fan turns off
Fan turns on

3

Heating system

0	
1	
2	
3	

Heat and fan turn off
Heat turns on (fan on if Function 0170 is set for heat pump,
or if Function 0180 is set to “1”)  ** See page 6
Second stage heat turns on
Third stage heat turns on

0	
1	

Heat and fan turn off
Heat and fan turn on

4

Emergency
heating system

ENGLISH

CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed
during testing. To prevent equipment damage, avoid cycling the compressor quickly.

69-2693—01

10

VisionPRO TH8000 Series
TM

Special functions
Shaded areas below apply only to TH8320/TH8321.
Auto Changeover (Setup Function 0300): When set to Auto, the thermostat automatically selects
heating or cooling depending on the indoor temperature. Heat and cool settings must be at least 2 degrees apart. If function 0380 is set to On, the heat and cool settings must be at least 5 degrees apart.
Remote Sensor (Setup Function 0340): If an optional outdoor sensor is installed, the thermostat can
display the outside temperature. If an optional remote indoor sensor is installed, the thermostat will
display the temperature at the sensor location (the internal sensor in the thermostat is not used).
Adaptive Intelligent Recovery (Setup Function 0530): Allows the thermostat to “learn” how long the
furnace and air conditioner take to reach programmed temperature settings, so the temperature is
reached at the scheduled time.
Compressor Protection (Setup Function 0580): Forces the compressor to wait a few minutes before
restarting, to prevent damage. During this time, the message “Wait” flashes on the display.
Dehumidification control (Setup Function 0380): TH8321 models monitor the indoor humidity level
and automatically activate the cooling system to reduce humidity by lowering the temperature by up
to 3 degrees below the current cool setting.
Heat Pump Temperature Lockout (with fossil-fuel backup): If the thermostat is installed with an
optional outdoor sensor, you can select a compressor lockout temperature (Function 0350). When
the outdoor temperature is below the lockout temperature, only the auxiliary heat operates. When the
outdoor temperature is above the lockout temperature, only the compressor operates.
Heat Pump Temperature Lockouts (with electric heat backup): If the thermostat is installed with
an optional outdoor sensor, you can select a compressor lockout temperature (Function 0350) and/
or an auxiliary heat lockout temperature (Function 0360). When the outdoor temperature is below the
compressor lockout temperature, only the auxiliary heat operates. When the outdoor temperature is
above the auxiliary lockout temperature, only the compressor operates. If the outdoor temperature is
between the compressor and auxiliary lockout temperatures, both the compressor and auxiliary heat
can operate.

Accessories & replacement parts
Please contact your distributor to order replacement parts.

11

ENGLISH

Outdoor temperature sensor............................... Part Number C7089U1006
Remote indoor temperature sensor................... Part Number C7189U1005
Cover plate*............................................................. Part Number 32003796-001
*(Use to cover marks left by old thermostats.)

69-2693—01

Installation Guide

Specifications
Temperature Ranges
•	 Heat: 40° to 90°F (4.5° to 32°C)
•	 Cool: 50° to 99°F (10° to 37°C)

Electrical Ratings
W Heating	

20-30 Vac	

0.02-1.0 A

Operating Ambient Temperature
•	 0° to 120°F (-18° to 48.9°C)

(Powerpile)	

750 mV DC	

100 mA DC

W2 Heating	

20-30 Vac	

0.02-0.6 A

Shipping Temperature
•	 -30° to 150°F (-34° to 66°C)

Y Cooling	

20-30 Vac	

0.02-1.0 A

Y2 Cooling	

20-30 Vac	

0.02-0.6 A

Operating Relative Humidity
•	 5% to 90% (non-condensing)

Aux/E Aux. heat	
Emergency heat

20-30 Vac	

0.02-1.0 A

Physical Dimensions
•	 4-9/16” H x 6” W x 1-3/8” D
•	 116 mm H x 152 mm W x 35 mm D

O/B Changeover	

20-30 Vac	

0.02-0.6 A

L Heat pump reset	

20-30 Vac	

0.02-0.6 A

Terminal	

Voltage (50/60Hz)	

Running Current

Need Help?
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502

Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN  55422
http://customer.honeywell.com

® U.S. Registered Trademark.
© 2012 Honeywell International Inc.
69-2693—01   M.S. 01-12
Printed in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Assemble, Print high-res
Author                          : Honeywell ECC Technical Communications
Create Date                     : 2012:01:05 11:51:14-06:00
Modify Date                     : 2014:12:07 14:56:45+08:00
Subject                         : Installation Guide
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03
Metadata Date                   : 2014:12:07 14:56:45+08:00
Creator Tool                    : Adobe InDesign CS5 (7.0.4)
Page Image Page Number          : 1, 2
Page Image Format               : JPEG, JPEG
Page Image Width                : 256, 256
Page Image Height               : 256, 256
Page Image                      : (Binary data 7773 bytes, use -b option to extract), (Binary data 9941 bytes, use -b option to extract)
Instance ID                     : uuid:8ea38e1c-4ddb-4b45-a135-1a96a2f08318
Original Document ID            : adobe:docid:indd:95e35ca7-4752-11de-9666-909008c4f253
Document ID                     : xmp.did:9EB8831D7614E111987AA4B2A1E37D29
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:A6247F1D7614E111987AA4B2A1E37D29
Derived From Document ID        : adobe:docid:indd:95e35ca7-4752-11de-9666-909008c4f253
Derived From Original Document ID: adobe:docid:indd:95e35ca7-4752-11de-9666-909008c4f253
Derived From Rendition Class    : default
History Action                  : saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved
History Instance ID             : xmp.iid:7FAB9FBCBE1DE011A19998760E4D156D, xmp.iid:80AB9FBCBE1DE011A19998760E4D156D, xmp.iid:B7327B24BF1DE011A19998760E4D156D, xmp.iid:B28726F6541EE011B59FA94457B1DA93, xmp.iid:ADD08B936D14E11198E7BDD67FDD0E18, xmp.iid:D6E3E0C27314E11198E7BDD67FDD0E18, xmp.iid:AD5F2ACE7514E111AE77D6983273FB40, xmp.iid:A6247F1D7614E111987AA4B2A1E37D29, xmp.iid:9EB8831D7614E111987AA4B2A1E37D29, xmp.iid:B03309737614E111AC26D6489E074434, xmp.iid:A2188CB87614E111AC26D6489E074434, xmp.iid:78F9BCC47614E111AC26D6489E074434, xmp.iid:92EF56CB7B14E111A11BAB906EAD8779, xmp.iid:B574CE0A7C14E1119E22E6B3568E5909, xmp.iid:B674CE0A7C14E1119E22E6B3568E5909, xmp.iid:0376A934AD14E111BCA78C394584775D, xmp.iid:B8273D83AF14E111BCA78C394584775D, xmp.iid:E0F8369FAF14E111BCA78C394584775D, xmp.iid:4E6107AAAF14E111BCA78C394584775D, xmp.iid:06838670B014E111BCA78C394584775D, xmp.iid:BB15B2EFB014E111BCA78C394584775D, xmp.iid:E5FC26DB4F15E111B6EDB54FF669CF86, xmp.iid:2168B86E5015E111B6EDB54FF669CF86, xmp.iid:B0986B005115E111B6EDB54FF669CF86, xmp.iid:6322BE975A15E111B6EDB54FF669CF86, xmp.iid:459FAFE47215E111BBB4C2602E0C87ED, xmp.iid:09EAAE820725E111AC9DB370CAC2AE3B, xmp.iid:59796B640825E111ADB3C23FA2DCCB7B, xmp.iid:FE3B87375825E11181FDEED6D36A89D0, xmp.iid:06C47CC5BC37E11184ACC8C8E98C7F6E, xmp.iid:089D2361BE37E11184ACC8C8E98C7F6E, xmp.iid:03BCA7D5C537E11184ACC8C8E98C7F6E
History When                    : 2011:01:11 14:09:46-06:00, 2011:01:11 14:09:46-06:00, 2011:01:11 14:12:40-06:00, 2011:01:12 08:05:07-06:00, 2011:11:21 12:21:05-06:00, 2011:11:21 13:05:22-06:00, 2011:11:21 13:20-06:00, 2011:11:21 13:22:13-06:00, 2011:11:21 13:22:13-06:00, 2011:11:21 13:24:36-06:00, 2011:11:21 13:26:33-06:00, 2011:11:21 13:26:53-06:00, 2011:11:21 14:02:52-06:00, 2011:11:21 14:04:38-06:00, 2011:11:21 14:04:38-06:00, 2011:11:21 19:56:34-06:00, 2011:11:21 20:13:05-06:00, 2011:11:21 20:13:52-06:00, 2011:11:21 20:14:10-06:00, 2011:11:21 20:19:43-06:00, 2011:11:21 20:23:16-06:00, 2011:11:22 15:20:52-06:00, 2011:11:22 15:24:59-06:00, 2011:11:22 15:29:04-06:00, 2011:11:22 16:37:43-06:00, 2011:11:22 19:31:40-06:00, 2011:12:12 15:23:18-06:00, 2011:12:12 15:29:37-06:00, 2011:12:13 01:01:01-06:00, 2012:01:05 10:46:10-06:00, 2012:01:05 10:57:41-06:00, 2012:01:05 11:51:03-06:00
History Software Agent          : Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0
History Changed                 : /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata
Format                          : application/pdf
Title                           : 69-2693-01 - VisionPRO® TH8000 Series
Description                     : Installation Guide
Creator                         : Honeywell ECC Technical Communications
Startup Profile                 : Print
Doc Change Count                : 399
Producer                        : Adobe PDF Library 9.9
Trapped                         : False
Page Count                      : 12
EXIF Metadata provided by EXIF.tools

Navigation menu