Honeywell W7340 Users Manual 63 2569 4 W7340, W7345 Communicating Economizer Logic Modules

W7345 to the manual c1ff1095-ced4-484f-99e7-b3e24b1a450b

2015-01-23

: Honeywell Honeywell-W7340-Users-Manual-262638 honeywell-w7340-users-manual-262638 honeywell pdf

Open the PDF directly: View PDF PDF.
Page Count: 12

PRODUCT DATA
63-2569—04
W7340, W7345
Communicating Economizer Logic Modules
FOR VENTILATION CONTROL
APPLICATION
The W7340 Communicating Economizer Logic Module is a full
featured economizer that incorporates Demand Control
Ventilation (DCV) to provide free cooling and ventilation for
occupants in a space while saving energy.
The W7345 Communicating Economizer Logic Module is a
dry bulb only economizer that does not incorporate Demand
Control Ventilation.
The W7340 is used with both solid state temperature and
humidity or enthalpy sensors. The W7345 is used with solid
state temperature sensors only.
FEATURES
Solid state control package provides accuracy,
reliability and stability.
Housed in high-impact, glass-fiber reinforced plastic
case.
Terminals included for connecting optional S963B1136
Remote Potentiometer for remote minimum damper
position control.
Communicates using a modified Modbus protocol.
Case matches the lines of the M7215 Damper Motor.
LED indicates the status of the device input.
W7340 Only
Operates from the Modbus input, environmental
sensors, and a DCV sensor to provide a totally
integrated control system.
Combines minimum damper position potentiometer
with solid state temperature (10K NTC) and humidity or
enthalpy changeover control to provide economizer
free cooling function; this control can be overridden
by input via Modbus or DCV sensor.
W7345 Only
Operates from the Modbus input and mixed/discharge
air sensor to provide a temperature control system.
Combines the Modbus indoor and/or outdoor
temperature input with the mixed air input to provide
economizer dry bulb free cooling function.
W7340
W7345
Contents
Application.........................................................................1
Features ............................................................................1
Specifications ....................................................................2
Installation .........................................................................3
Wiring ................................................................................6
Operation...........................................................................7
Settings and Adjustment ...................................................7
Troubleshooting.................................................................11
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
63-2569—04 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
Models:
W7340: Communicating Economizer Logic Module with
minimum position potentiometer, setpoints for enthalpy or
dry-bulb, and DCV.
W7345: Communicating Economizer Logic Module with
minimum position potentiometer and setpoint for dry-bulb
temperature only.
IMPORTANT
W7340A, W7340B and W7345A:
1. Do not have the ability to set DCV minimum position
for damper position for demand control ventilation.
Damper may drive 100% open on call from CO2
sensor.
2. Do not have the E (enthalpy or dry bulb) curve
setting.
3. W7340C has the ability to set DCV minimum position
and has the E curve setting.
Dimensions: See Fig. 1.
Temperature Ratings:
Operating Ambient: -40 to +149 °F (-40 to +65 °C).
Shipping: -25 to +125 °F (-32 to +52 °C).
Humidity Ratings:
Noncondensing: 5 to 95% RH.
Condensing: 100% RH.
Inputs and Outputs: See Table 1.
Electrical Ratings:
Input Voltage: 24 Vac ±25%; 50/60 Hz (Class 2).
Nominal Power Consumption (at 24 Vac, 60 Hz): 5 VA.
Relay Contact Rating at 30 Vac (maximum power from class 2
input only): 1.5 A run, 7.5 A inrush.
Patents:
U.S. Patent 6,1,764.
Other Patents Pending.
Approvals:
cUL listed.
Underwriters Laboratories Inc. listed:
Meets UL873 plenum requirements.
Meets UL94-5VA plenum flammability requirements.
FCC Part 15 Class B.
CE.
This product complies with Title 24 Part 6 CEC standard for
Residential and Non-Residential Buildings - 2005, when
installed according to instructions.
Fig. 1. Dimensions of W7340 and W7345 in inches (mm).
Accessories:
32005191-001 Sensor, 10K ohm with 2-1/4 in. (57 mm) probe.
C7150B1046 Mixed Air Sensor, 10K ohm with mounting
bracket.
C7232 Carbon Dioxide Sensor for DCV.
C7632 Carbon Dioxide Sensor for DCV.
C7400A Solid State Enthalpy Sensor for use with W7340A
and W7340B.
C7400C Solid State Enthalpy Sensor for use with W7340C.
C7600C Relative Humidity Sensor.
S963B1136 Remote Potentiometer to provide remote control
of damper minimum position.
ST6008 Energy Management Timer for occupied/unoccupied
control.
ST7009 Electronic Programmable Timer for occupied/
unoccupied control.
M22813
1-15/16
(49)
5/8
(16)
4-1/16
(103)
4-7/16 (112)
1-3/4 (44)
1-3/8
(35)
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
363-2569—04
Table 1. Logic Module Inputs and Outputs.
a2-wire (18, 20, 22 AWG) connection.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Location and Mounting
Communicating Economizer Logic Modules
When planning the installation, allow enough clearance for
maintenance and service. Mount the device in a location
protected from rain, snow, and direct sunlight. The logic
module mounts on the side of an M7215 Damper Motor or
directly on a sheet metal duct or panel.
NOTE: Refer to Figures 4 and 5 for representative locations
of connected system devices.
CAUTION
Equipment Damage Hazard.
Mounting screws longer than 5/8 in. can damage
internal motor components.
When mounting the module to an M7215 use only the
included #6 5/8 in. thread-forming screw.
MOUNTING DIRECTLY TO THE MOTOR
1. Mount the motor.
2. Secure the W7340 or W7345 to the motor using the
supplied mounting screw (See Fig. 2).
MOUNTING SEPARATE FROM THE MOTOR
Secure the device to the sheet metal using appropriate
fasteners (not supplied)(See Fig. 3).
Fig. 2. Mounting Economizer Logic Module on Damper
Motor.
W7340 W7345
Inputs
Enthalpy 4-20 mAa
Modbus yes yes
Return Sensor optional
Mixed/Discharge Air 10K ohma10K ohma
Outdoor Sensor 10K ohma
Indoor DCV Sensor 0-10 Vdc control signal
Remote Minimum
Position Potentiometer
optional optional
Motor Feedback 2-10 Vdc
Outputs
Modbus yes yes
Exhaust One set of 24 Vac
contacts (spst)
Motor Output Signal 2-10 Vdc
M17550B
ECONOMIZER
LOGIC MODULE
M7215
DAMPER
MOTOR
5/8 INCH SCREW INCLUDED
WITH LOGIC MODULE.
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
63-2569—04 4
Fig. 3. Mounting to a Duct or Panel.
Enthalpy Sensor (W7340 only)
To measure enthalpy, the logic module accepts signals from
either:
C7600C Humidity and 10K NTC temperature sensors.
or a C7400 Enthalpy Sensor.
IMPORTANT
When using C7400 Enthalpy Sensors, connect the
enthalpy sensors to the humidity sensor terminals;
leave the temperature sensor terminals empty.
Use C7400A sensor with W7340A or W7340B.
Use C7400C sensor with W7340C.
OUTDOOR AIR SENSING
1. Mount each sensor in any orientation that exposes it to
freely circulating air and protects it from rain, snow, and
direct sunlight.
2. Connect it to the logic module.
RETURN AIR SENSING
1. For differential enthalpy or temperature control mount a
second sensor in the return air duct.
2. Connect it to the logic module.
Demand Control Ventilation (DCV) Sensor Input
(W7340 only)
The DCV sensor can be any sensor that provides a 0-10 Vdc
output over a range of 0 to 2000 ppm of CO2. The DCV signal
modulates the outdoor damper to provide ventilation based on
occupancy. Mount the sensor according to the manufacturer
specifications. If not available, mount the sensor in an area
with unobstructed air circulation.
IMPORTANT
Ensure proper polarity of sensor connections.
Incorrect polarity negates the sensor signal.
W7340B: The W7340B DCV economizer logic modules
incorporate a minimum position setting that defaults to 20%,
but can be overridden using the Modbus communication link.
The W7340B DCV maximum position sets the damper position
to a position that the damper goes to if the CO2 sensor fails. If
the minimum position set point is higher than the DCV
maximum position, on sensor failure, the damper goes to the
higher of the two DCV maximum and minimum position setting.
There is no limit on the damper position on a call from the CO2
sensor (DCV); the damper can go 100% open.
W7340C: The W7340C DCV economizer logic module has the
ability to set DCV minimum damper position and minimum
position. The DCV minimum position is set to ventilate the
building contaminants and the minimum position is set to
ventilate for the building contaminants and the building
occupants. The installer sets the damper DCV minimum
position and the minimum position based on the design
occupancy and CFM of outdoor air requirements for the space.
The damper will modulate open between the DCV minimum
damper position and the minimum position based on input
from a CO2 sensor. The damper will not drive 100% open on a
call for ventilation, but can drive 100% open on a call for
cooling. If the CO2 sensor fails the damper will drive to the
minimum position ventilating for building contaminants and
the building occupants. If the DCV minimum position has not
been set using the following procedure, the default setting will
be 50% of the minimum position setting.
DCV Min and Min Position Damper Set Up
Set up instructions for W7340C DCV damper positions:
1. Remove RAT sensor from RAT terminals.
2. Connect CO2 sensor to DCV terminals.
3. Apply power to economizer logic module.
4. Wait 10 to 15 seconds for the CO2 sensor to initialize.
Short RAT terminals.
5. Remove CO2 sensor from DCV terminals.
6. DCV LED will blink 2 times. If LED does not blink, cut
power to economizer logic and repeat steps 1-5.
7. Set DCV minimum position using MIN POS/DCV MIN
potentiometer.
8. Remove RAT short.
9. DCV minimum position is saved to memory and DCV
LED blinks 5 times.
10. Turn off power to economizer logic module.
11. Connect RAT sensor.
12. Turn power on to economizer logic module.
13. Set minimum position using MIN POS/DCV MIN
potentiometer.
IMPORTANT
Steps 3-8 must be completed within 3 minutes after
power up otherwise the configuration process will be
terminated, no changes will be saved and you will
need to repeat steps 1-13.
M17638
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
563-2569—04
Fig. 4. Representative Locations of Connected W7340 Economizer System Devices.
Fig. 5. Representative Locations of Connected W7345 Economizer System Devices.
10K NTC
DISCHARGE
AIR SENSOR
DIRECT
EXPANSION
COIL
C7400
C7232
ENTHALPY
SENSOR
C7400
ENTHALPY
SENSOR
RETURN AIR
OUTDOOR
AIR
10K
NTC
MIXED AIR
SENSOR
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400 ENTHALPY SENSORS
ARE CONNECTED TO THE ECONOMIZER MODULE—ONE IS MOUNTED
IN THE RETURN AIR DUCT, AND THE OTHER IS MOUNTED IN THE
OUTDOOR AIR DUCT. DIFFERENTIAL ENTHALPY CONTROL PROVIDES
GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY CONTROL.
USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR, NOT BOTH.
A C7600 HUMIDITY SENSOR, USED IN CONJUNCTION WITH A 10K NTC
TEMPERATURE SENSOR CAN BE USED INSTEAD OF A C7400 ENTHALPY SENSOR.
FOR DRY BULB CONTROL, USE ONLY A 10K NTC TEMPERATURE SENSOR.
M22814
INDOOR
AIR CO2
SENSOR
MODBUS
EXHAUST AIR
DISCHARGE
AIR
INDOOR
FAN
EXHAUST
FAN
M7215 MOTOR
WITH W7340
ECONOMIZER
LOGIC MODULE
1
1
2
2
2
3
3
1
3
10K NTC
DISCHARGE
AIR SENSOR
DIRECT
EXPANSION
COIL
RETURN AIR
OUTDOOR
AIR
10K
NTC
MIXED AIR
SENSOR
USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR, NOT BOTH. M22822
MODBUS
EXHAUST AIR
DISCHARGE
AIR
INDOOR
FAN
EXHAUST
FAN
M7215 MOTOR
WITH W7345
ECONOMIZER
LOGIC MODULE
1
1
1
1
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
63-2569—04 6
WIRING
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
1. All wiring must comply with applicable local codes,
ordinances and regulations.
2. Refer to Figures 6 and 7 for typical wiring diagrams.
3. All inputs and outputs to the device must be 24 Vac
Class 2.
4. Ensure proper polarity of sensor connections.
Incorrect polarity negates the sensor signal.
NOTE: All connections with label designation ending in 1
(examples: TR1, P1) are ac/dc common connections.
Fig. 6. W7340 Typical Wiring.
P1
TR1
TR1
24 VAC
TR
TR
P
EXF
M23875
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
OPTIONAL REMOTE MINIMUM POSITION POTENTIOMETER.
WHEN USING C7400 ENTHALPY SENSORS, CONNECT THE ENTHALPY SENSOR TO THE
HUMIDITY SENSOR TERMINALS. LEAVE THE TEMPERATURE SENSOR TERMINALS EMPTY.
1
2
3
3
3
3 3
2
R
B W
CCW
OPEN
MOD
BUS
CW
CLOSE
S963B
M7215
W7340
2-10 Vdc
FEEDBACK
OUTPUT
2-10 Vdc
CONTROL
SIGNAL INPUT
2-10 Vdc
FEEDBACK
INPUT
MIN POS/
DCV MIN
DCV
SETPOINT
2-10 Vdc
CONTROL
SIGNAL
OUTPUT
POWER
EXHAUST
CONTACTOR
MIXED
AIR TEMP
SENSOR
10K NTC
OUTDOOR
AIR TEMP
SENSOR
10K NTC
RETURN
AIR TEMP
SENSOR
10K NTC
C7600C
OUTDOOR
AIR
HUMIDITY
C7600C
RETURN
AIR
HUMIDITY
DCV
SENSOR
(0-10 Vdc)
MAT
OAH
OAT
RAT
RAH
DCV
AE
B
C
+–+–
+– +– +–
+
MOD BUS –
MOD BUS +
1
24 VAC
L1
L2
+
D
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
763-2569—04
Fig. 7. W7345 Typical Wiring.
OPERATION
The purpose of the economizer logic modules are to use
outdoor air for cooling, whenever possible, to reduce
compressor operation.
IMPORTANT
Use C7400A sensor with W7340A or W7340B.
Use C7400C with W7340C.
The W7340, when wired as shown in Fig. 6, responds to a
signal from the Modbus. This system uses C7400 Solid State
Enthalpy Changeover Sensor(s). The C7400 Enthalpy Sensors
respond to both dry bulb temperature and humidity, allowing
use of outdoor air at higher temperatures for free cooling when
humidity is low.
The logic module functions as a first stage of cooling and
provides maximum fuel economy during the cooling cycle. The
logic module automatically locks out free cooling during
heating. It holds the outdoor air damper at the minimum
position setting.
The W7340 operates as a basic free cooling controller. Table 2
details the input/output (I/O) logic of the W7340. The logic
module energizes the Unit Control and Indoor Fan contacts,
and operates according to Table 2.
SETTINGS AND ADJUSTMENT
W7345
Potentiometers with screwdriver adjustment slots, located on
the face of the device, provide adjustments for Minimum
Damper Position parameters (See Fig. 8 for locations on
device).
Fig. 8. Location of W7345 Potentiometers and LED.
P1
TR1
TR1
24 VAC
TR
TR
P
MOD BUS –
MOD BUS +
M23876
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
OPTIONAL REMOTE MINIMUM POSITION POTENTIOMETER.
1
1
2
2
R
B W
24 VAC
L1
L2
+
CCW
OPEN
MOD
BUS
CW
CLOSE
S963B
M7215
W7345
MINIMUM
POSITION
MIXED
AIR TEMP
SENSOR
10K NTC
MAT
+
AE
B
C
D
P P1
MBUS-
MBUS+
TR1 24V COM
TR 24V AC
-
MIN POS/
DVC MIN
OPEN
C
B
E
A
STATUS LED
DRY BULB
CHANGEOVER
SETPOINT
MINIMUM
DAMPER
POSITION
M23877
D
MAT
OAT
RAT
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
63-2569—04 8
W7340
Potentiometers with screwdriver adjustment slots, located on
the face of the device, provide adjustments for several
parameters (See Fig. 9 for locations on device):
DCV minimum and minimum damper position.
Enthalpy changeover.
DCV setpoint.
Fig. 9. Location of W7340 potentiometers and LED.
IMPORTANT
Before powering the device read the following Enthalpy
changeover setpoint guidelines:
1. Using the Enthalpy changeover setpoint, the setpoint
can be adjusted until three minutes after powering the
device. until three minutes after powering the device.
2. Through the Modbus, the Enthalpy changeover
setpoint can be modified at any time.
3. If the Enthalpy changeover potentiometer is changed
after the three minute power-up time, no change to
the Enthalpy changeover setpoint will occur unless
power is removed from the device then reapplied.
NOTES:
The DCV setpoint can be changed at anytime by
adjusting the pot.
For Enthalpy changeover setpoint see comments
above.
MIN POS can be changed anytime by adjusting
the pot.
DCV Min can be changed by procedure on page 4.
Demand Control Ventilation (DCV) Setpoint
The logic module modulates the outdoor damper to provide
ventilation based on the 2-10 Vdc DCV sensor. With no cooling
signal, DCV overrides the DCV minimum damper position
when ventilation requires outdoor air.
Table 2. W7340 Economizer I/O Logic.
aFor single enthalpy control, the module compares outdoor
enthalpy to the ABCDE setpoint.
bIf both stages of cooling are off, the system is off and the
damper is:
At DCV minimum position if DCV is below setpoint.
Modulating if DCV is above setpoint.
cModulation based on mixed air sensor signal, modulating
between DCV minimum position and 100% open.
dModulation based on DCV signal, limited by minimum
position.
eModulation based on the greater of the DCV and mixed air
sensor signals.
Adjusting Minimum Damper Position
The minimum position potentiometer maintains the minimum
outdoor air flow into the building during occupied period.
NOTE: If the mixed air temperature drops to 45° F (7° C), the
mixed air sensor overrides the DCV sensor and
closes the damper to DCV minimum position to
protect the hot or chilled water coils from freezing.
When the mixed air temperature rises to 48° F (9° C),
control reverts to normal operation.
For detailed assistance in minimum position selection,
reference the Economizer Application Guide (form 63-8594)
Ventilation section. The following provides basic guidelines for
minimum position selection and adjustment:
IMPORTANT
1. Adjust the minimum position potentiometer to allow
the amount of outdoor air, as required by local codes,
to enter the building for building contaminants and the
maximum building occupants.
2. This procedure requires use of a quality thermometer
capable of reading to 0.5° F (0.-17.5° C).
NOTE: Make minimum position adjustments with at least a
10° F (-12° C) temperature difference between
outdoor and return air.
See section on DCV setpoint set up on page 4.
PP1
+
-
+
-
ExF
MAT
OAH
OAT
RAT
RAH
DCV
2-10 VDC
DAMPER
POSITION
2-10 VDC
DAMPER
POSITION
OVERRIDE
MIN POS/
DCV MIN
OPEN
DCV
SETPOINT
1500500
STATUS LED
DEMAND
CONTROL
VENTILATION
SETPOINT
ENTHALPY
CHANGEOVER
SETPOINT
MIN POS/DCV
MIN DAMPER
POSITION
M23878
MBUS-
MBUS+
TR1 24V COM
TR 24V AC
C
B
E
A
D
+
_
+
_
INPUTS OUTPUTS
DCV
Enthalpya
Y1bY2b
Compressor
DamperOutdoor Return Stage 1 Stage 2
Below
set
High Low On On On On Minimum
position
On Off On Off
Low High On On On Off Modulatingc
On Off Off Off
Above
set
High Low On On On On Modulatingd
On Off On Off
Low High On On On Off Modulatinge
On Off Off Off
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
963-2569—04
Limit On Minimum Damper Position
On the W7340A and B models, the logic module as shipped
from the factory, limits the minimum position setpoint to 50%.
The logic module will not allow a minimum position greater
than 50% open (from fully closed).
NOTE: This setpoint limit can only be changed using a
Modbus command.
Equation 1. Formula to aid in minimum position adjustment.
or
Where:
TO = Outdoor air temperature
OA = Percent of outdoor air
TR = Return air temperature
RA = Percent of return air
TM = Resulting mixed air temperature
NOTE: The following sample calculation uses only
Fahrenheit temperature.
EXAMPLE: Assume local codes require 10% outdoor air
during occupied conditions, outdoor air is 60° F
and return air is 75° F. Under these conditions,
what is the temperature of the mixed air?
or
Mixed air will be 73.5° F when OA is 60° F and RA is 75° F with
10 percent outdoor air entering the building.
NOTE: The W7340C model min position and DCV min must
be set in the field by the installer. See Section DCV
Min and Min Position Damper Set up.
Enthalpy Changeover (W7340 only)
Outdoor Enthalpy Changeover Setpoint (Single
Enthalpy Changeover)
The outdoor enthalpy changeover setpoint returns the outdoor
air damper to minimum position when enthalpy rises above its
setpoint. Enthalpy setpoint scale markings, located on the
device, are A, B, C, D and E. See Fig. 10 for the corresponding
control point.
Differential Enthalpy Changeover Setting
Differential enthalpy control uses:
W7340A and B use two C7400A Enthalpy Sensors
connected to one logic module, or
Two 10K NTC temperature sensors and two C7600C
Humidity Sensors connected to one logic module.
W7340C uses C7400C Enthalpy Sensor(s) or
Two 10K NTC temperature sensors and two C7600C
Humidity Sensors connected to one logic module.
With outdoor and return air sensors, the logic module
compares outdoor air to return air instead of to a setpoint as it
does for single enthalpy. The logic module selects the lower
enthalpy air (return or outdoor) for cooling; for example, when
outdoor air has lower enthalpy than return air, the outdoor air
damper opens to bring in outdoor air for free cooling.
NOTE: When using the W7340 for differential enthalpy, keep
the setpoint potentiometer set at D.
Exhaust Setpoint (W7340 only)
The exhaust setpoint determines when the exhaust fan will run
based on the damper position.
The logic module, as shipped from the factory, uses an
exhaust setpoint of 25%. When the damper position is greater
than 25% open (from fully closed), relay contact for the
exhaust fan is closed. When the damper position is below 22%
open, the relay is de-energized.
Control Configuration (W7340 only)
The W7340 can be configured for humidity or enthalpy
sensors. Configuration can be performed manually or over the
Modbus.
IMPORTANT
If only a temperature sensor is connected to the
W7340, the device will operate using dry bulb
changeover control.
To configure the W7340 manually:
1. Within the first three minutes after powering the device,
short the external minimum damper position terminals
(P-P1).
NOTE: The LED will go solid within five seconds of
shorting these terminals.
2. Maintaining the short for another five seconds causes
the LED to flash quick pulses (between off periods)
indicating the sensor configuration type:
a. Two quick pulses: Humidity.
b. Three quick pulses: Enthalpy.
3. To toggle the sensor configuration type:
a. Remove the short until the LED goes solid again.
b. Reapply the short for another five seconds.
NOTE: Once the short is removed for over 10 seconds,
the device saves the most recent configuration.
TOOA×()TRRA×()+TM
=
TOTR
()OA TR
+×TM
=
0.1x6° F()0.9x75° F()+ 6.0° F 67.5° F+ 73.5° F==
60° F 75° F()0.1 75° F+×1.575° F+73.5° F==
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
63-2569—04 10
Fig. 10. W7340 Performance Characteristics for Enthalpy Changeover Settings.
Table 3. W7345 Performance Characteristics
for Temperature Changeover Settings.
CONTROL
CURVE
A
B
C
D
E
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
55 (13)
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
90
100
80
70
60
50
40
30
20
10
ENTHALPY—BTU PER POUND DRY AIR
85
(29)
90
(32)
95
(35)
100
(38)
105
(41)
110
(43)
35
(2)
35
(2)
40
(4)
40
(4)
105
(41)
110
(43)
45
(7)
45
(7)
50
(10)
50
(10)
55
(13)
55
(13)
60
(16)
60
(16)
65
(18)
65
(18)
70
(21)
70
(21)
75
(24)
75
(24)
80
(27)
80
(27)
85
(29)
90
(32)
95
(35)
100
(38)
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
A
A
B
B
C
C
D
D
M23879
RELATIVE HUMIDITY (%)
1
1
HIGH LIMIT CURVE FOR W7210D, W7212, W7213, W7214, W7340B.
E
E
Temperature
Changeover Setting
Approximate Control Point
°F °C
A7323
B7021
C6719
D6317
E5513
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
11 63-2569—04
TROUBLESHOOTING
The status LED is visible through a hole in the device cover. A
priority-based LED flash sequence indicates a detected fault.
0.25 seconds elapses between each pulse, a higher pulse
count indicates higher priority. A two-second on period
precedes each repeated sequence.
The diagnostic bit position corresponds to the Modbus
diagnostic register. The diagnostic bit resets when the
respective fault is present. To read all active faults, read the
diagnostic register via Modbus function code 8 (no flash
priority needed).
NOTES:
All pulse counts (Table 4) are based on the
number of times the light pulses off.
In the event of a Communications Failure, the LED
pulses on for 0.25 seconds every 2 seconds.
Table 4. W7340 Economizer Checkout.
Description
Pulse
count
Diagnostic
bit
Booting (0-3 min. after power-up) NA 12
Mixed air temperature sensor fault 87
Outdoor air temperature sensor fault 76
Outdoor air humidity sensor fault 65
Return air temperature sensor fault 43
Return air humidity sensor fault 32
Indoor air quality sensor fault 21
Actuator fault 10
Proper operation (outdoor air
appropriate for free cooling)
Solid
ON NA
Proper operation (NO free cooling) 2 Hz flash NA
Communications failure 1 (pulses
on) NA
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
® U.S. Registered Trademark
© 2007 Honeywell International Inc.
63-2569—04 J.I. Rev. 06-07

Navigation menu