Y8150 Fresh Air Ventilation System,
W8150 Fresh Air Ventilation Control
PRODUCT DATA

FEATURES
• Designed to help meet local ventilation codes and
standards, including ASHRAE 62.2-2010 standard,
“Ventilation and Acceptable Indoor Air Quality in
Low-Rise Residential Buildings.”
• Microcontroller optimizes the air delivery schedule to
make efficient use of normal HVAC run times.
• Easy-to-use input dials allow customized ventilation
for each installation.
• Test mode that includes immediate feedback to
installer to confirm that air delivery requirements of
selected ventilation standard are being met.
• Economical supply-only ventilation; works with forced
air system.
• Can be used with other equipment, such as an HRV/
ERV, for balanced ventilation.

APPLICATION
The Y8150 Fresh Air Ventilation System, W8150 Fresh Air
Ventilation Control provide fresh air to a home. The control
operates a fresh air intake damper and, when necessary,
activates the main HVAC blower to efficiently meet ASHRAE
ventilation rates.

IMPORTANT
Please read these instructions and keep them in your
records.

Put Bar Code Here

68-0282-07

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

SPECIFICATIONS
Y8150 includes:
W8150A Fresh Air Ventilation Control.
EARD6 Fresh Air Damper.
AT120B Transformer.
Mounting hardware for control.
Homeowner information label.

4-3/16 (106)

1-1/4
(32)

W8150 includes:
W8150 Fresh Air Ventilation Control.
Mounting hardware for control.
Homeowner information label.

5-3/4
(146)

Control (W8150A):
Power Supply: 20-30 Vac, 60 Hz.
Power Consumption: 3.5 VA at 24 Vac.
Thermostat Fan Load: 10 mA resistive at 24 Vac.
Thermostat Heat Load: 10 mA resistive at 24 Vac.
Remote Terminals: 10 mA resistive at 24 Vac.
Relay Contacts:
Fan: 1.5A full load, 7.5A locked rotor at 24 Vac.
Damper: 0.6A inductive, 3.1A locked rotor at 24 Vac.
Auxiliary: 0.5A inductive, 2.5A locked rotor at 24 Vac.

M19988A

W8150A Ventilation Control dimensions in in. (mm).
3-1/2 (89)

3-3/8
(86)

Damper (EARD6): 24 Vac, 12 VA, 60 Hz.
Operation: Power-open, spring-closed.
Diameter: 6 in.

1-1/2
(38)

Transformer (AT120):
Input: 120 Vac.
Output: 27 Vac open circuit, 24 Vac full load at 20 VA.
Mounting: Foot mounted.

6
(152)

Temperature: -20 °F to 160 °F (-29 °C to 71 °C).
Humidity: 5 to 90% RH, noncondensing.

8 (203)
M19989

Input Setting Ranges:
Bedrooms: 2-5.
Area: 1000-4600 sq ft.
Vent Airflow: 40-160 cfm.

EARD6 Fresh Air Damper dimensions in in. (mm).

2-13/16 (71)

Composite Setting Resolution: +/- 12% of ASHRAE
62.2-2010, recommended ventilation for single-system setup.

3/16
(5)

1-3/4
15/16 1 (44)
(24) (25)

AT120B Approvals: UL Component Recognized: Class 2,
File No. 14881.
3/16
(5)

Location: Device can be installed in unconditioned space.
Multiple devices can be installed when operating multiple
HVAC systems.

1-7/8 (48)

Dimensions: See device dimension diagrams.
1-5/8
(41)

1/16 (2)
M22022

AT120B Transformer dimensions in in. (mm).

68-0282—07

2

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

CC

4

CH

5

W

6

GT

7
8

20

C

19
18
17
16

ON

9

R
DAMPER

RC

3

XFMR

AUX

GF

2

REMOTE

1

15

10
14

11
12

BEDROOMS

AREA (SQFT)

13

VENT AIRFLOW (CFM)

M19990

W8150 QUICK GUIDE
No.

Name

Description

Function

1

GF

Equipment fan

Allows W8150 to pass thermostat calls and, when necessary, turn on
system fan for ventilation. This should be the only connection to G on the
HVAC equipment.

2

RC

24 Vac cooling system
power

Provides power to GF terminal to operate system fan, when necessary.

3

CC

24 Vac cooling system
common

Allows W8150 to monitor when system fan is energized.

4

CH

24 Vac heating system
common

Allows W8150 to monitor thermostat heat calls when W is energized.

5

W

Heating

Allows W8150 to monitor when heating is energized.

6

GT

Thermostat (or other
control) fan terminal

Allows W8150 to monitor when GT is energized. All external equipment that
controls the system fan should be wired to this terminal.

7

Switch

On (optimal ventilation)
Override
Off (Remote Only)

On (optimal ventilation) – W8150 ventilates, based on control settings.
Override – W8150 runs ventilation continuously.
Off (Remote Only) – W8150 supplies ventilation only when there is a
remote call.

8

Light

Green

Indicates device is powered and operating normally. Used in Test Mode to
signal if dial settings meet chosen standard.

9

Light

Red

Indicates the device is not operating normally. Used in Test Mode to signal
if dial settings do not meet chosen standard.

10

DIP1

Ventilation limit

Choose between 60% (default) and 100% maximum fan run time allowed
by W8150 for ventilation.

11

DIP2

Ventilation standard

Choose between ASHRAE 62.2 (default) and 62-1999 ventilation
standards.

12

BEDROOMS

Number of bedrooms

Used to calculate amount of ventilation necessary.

13

AREA
(SQ FT)

Square footage of
conditioned space

Used to calculate amount of ventilation necessary.

14

VENT
AIRFLOW
(CFM)

Air delivery rate through
fresh air duct.

Used to calculate amount of ventilation necessary.

15

Test

Test button

W8150 checks dial and switch settings, activates ventilation for up to three
minutes and provides feedback to validate if chosen standard can be met.

3

68-0282—07

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

No.

Name

Description

Function

16

REMOTE

Remote switch (two
terminals)

24 Vac powered contacts allow a remote switch closure to call for
ventilation.

17

AUX

Auxiliary (two terminals)

24 Vac dry contacts allow W8150 to control an auxiliary device, such as
exhaust fan or HRV/ERV, with a call for ventilation.

18

DAMPER

Damper (two terminals)

24 Vac powered contacts control fresh air damper.

19

XFMR C

24 Vac ventilation control Supplies power to W8150 and damper from transformer provided.
common

20

XFMR R

24 Vac ventilation control Supplies power to W8150 and damper from transformer provided.
power

INSTALLATION

Choosing a location…
When choosing locations for equipment, duct connections,
and fresh air intake, be sure to consult local code
requirements.

A fresh air duct and damper must be installed between the
outdoors and the return side of the HVAC equipment. The
W8150 control will be mounted near the HVAC system and
wired between the thermostat and the fan control.

You will need…
•
•
•
•
•
•
•
•

Device
Number

Component

1

Fresh air intake

Install away from known sources
of pollutants such as auto
exhaust, dryer vent exhaust or
chimney smoke.

2

Fresh air duct

Install between weather hood and
upstream of equipment filter and
downstream of any duct-mounted
sensor.

3

Damper

Install damper in fresh air duct,
where convenient. Optionally,
install heat recovery ventilator.

4

Control

Locate the control for convenient
access and for easy wire routing.

5

Transformer

Locate where convenient for line
voltage connection.

6

Filter

Locate filter downstream of fresh
air intake.

W8150 Fresh Air Ventilation Control.
damper.
transformer.
insulated ductwork.
outdoor weather hood.
starting collar.
access to 120 Vac power.
airflow measuring tool.

TIPS:
• To meet ASHRAE 62.2-2010, system must have at least a
MERV 6 filter installed.
• In cold climates, balanced ventilation is recommended. An
exhaust fan or heat recovery ventilator can be used.
• Humid climates may require additional dehumidification
equipment.

Location

TYPICAL ATTIC
INSTALLATION
3

4

2

5

6

1

3
1

2

1

2

3
HRV/ERV

4
TYPICAL BASEMENT
INSTALLATION

4
TYPICAL HRV/ERV
INSTALLATION

Ventilation Control
Auto
Continuous
(Remote Only)

Ventilation Contro l

6

6
M19993

68-0282—07

4

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

Installing fresh air damper, ducting,
and control…
1.
2.
3.

Wiring the control…

Disconnect power from HVAC system.
Install the weather hood, ducting, and damper following
local practices. Be sure all duct and insulation seams
are tightly sealed.
Mount the transformer and control.

TIPS:
• In general, larger ducting allows higher airflow, minimizes
additional fan run time and may be needed for larger
homes.
• Installing a damper directly to the return duct may be
convenient to support the damper and reduce ducting.
• Fresh air connection should be downstream of sensors
(such as a humidistat) in return air plenum.
• The EARD6 end stops can be used to reduce the amount
of airflow in the duct. To prevent complete opening, loosen
(but do not remove) the wing nut and move the upper lever
until the desired position is reached. Tighten the wing nut.
Keep the lower lever in the position shown.

UPPER LEVER

CAUTION

Electrical Hazard.
Can cause personal injury or equipment damage.
Disconnect power to all systems before beginning
installation.

1.
2.

Wire the control. See wiring diagrams in Fig. 1-10 as
listed below. All wiring must comply with local codes,
ordinances, and regulations.
Reapply power to system and control.

TIP:
• Control package allows wire routing through side slots and
bottom openings.
System Hookup Diagrams

LOWER LEVER
M20155

5

Page No.

Single transformer, conventional

1

10

Dual transformer, conventional

2

10

Multi-stage, conventional

3

10

Heat pump without emergency heat

4

10

Heat pump with emergency heat

5

11

Accessory Hookup Diagrams

WING NUT

Fig. No.

Fig. No. Page No.

Wiring with a PC8900 Thermostat

6

11

Wiring with a remote switch/timer

7

11

Wiring to an HRV/ERV

8

11

Wiring an exhaust fan

9

11

Wiring a fan for a steam humidifier

10

12

68-0282—07

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

Measuring airflow…
1.
2.

3.

About the control settings…

Make sure all HVAC system air filters are clean and
installed.
Push Test button:
• Control opens damper and turns on HVAC fan for
three minutes.
• A red or green light is flashing; you can now measure
airflow.
Follow instrument instructions for measuring airflow.

TIPS:
• You can exit the test mode at any time by pressing the test
button again.
• See Conversion Table (located after wiring diagrams) for
quick area and airflow setting conversions.
• For future reference, record the air flow on the inside of the
device cover.
• Pitot Tubes and flow measuring stations are commonly
used airflow measuring devices.

Dial Settings
These settings allow the installer to customize the control to
meet the ventilation requirements for the home.

Ventilation Standard
Building codes are different everywhere. The W8150
Ventilation Control can be configured to operate based on:
• ASHRAE 62.2.
• ASHRAE 62-1999
TIP:
• Clear understanding of local codes and practices is
required to make sure the ventilation system is installed
and configured correctly. Generally, ASHRAE 62.2 control
method is recommended and can meet many existing local
codes.
Code/Standard

Setting

General Ventilation
Requirements

ASHRAE 62.2

Washington State Energy
Code

ASHRAE 62.2

Canadian Building Code*

ASHRAE 62.2

Minnesota Energy Code

62-1999

2002 International
Residential Code

62-1999

*In Canada, interlocking exhaust equipment
may be required for balanced ventilation.

Ventilation Limit
This setting determines the maximum amount of time that the
fan runs for ventilation.

Ventilation Limit*
60%
ASHRAE 62.2

1
100%
2
62-1999
Ventilation
Standard

BEDROOMS

M22009

Setting ventilation limit and ventilation standard.

68-0282—07

6

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

Setting the control...

7.

Be sure power is turned on.
Set the Ventilation Standard on the control.
Set the bedrooms dial.
Set the area (sq ft) dial.
Set the airflow (cfm) dial.
Press the test button and observe the lights:
Green light is flashing.
The dial settings meet the chosen standard.
Red light is flashing.
There is not enough fresh air delivered to meet the
requirements of the selected standard. See
Troubleshooting section.
Record settings on the label inside the cover as shown
in the diagram.

W8150A 1001
GF
RC
HVAC CC
CH
W
Stat GT

R
C
DMP
DMP
AUX
AUX
REM
REM

Date installed:________________________
24 VAC
XFRM
Damper

Ventilation Limit*
60%
ASHRAE 62.2

ERV/Fan
Timer/Switch

100%
1
62-1999
2
Ventilation
Standard

_________

bedrooms

Installer
Test

_________

_________

area (sq. ft.)

airflow (cfm)

Record settings above

R
C
DMP
DMP
AUX
AUX
REM
REM

Honeywell
Golden Valley, MN 55422
50001159-001 Rev. A

1

W8150A 1001
GF
RC
HVAC CC
CH
W
Stat GT

24 VAC
XFRM
Damper

Date installed:________________________
Ventilation Limit*
60%
ASHRAE 62.2

ERV/Fan
Timer/Switch

Patent Pending

1.
2.
3.
4.
5.
6.

TIPS:
• Ventilation control reads new dial setting only when test
button is pushed or power is cycled. To ensure dial settings
are read, push test button after any changes are made.
• For single bedroom homes, set the bedrooms dial to 2 (this
may result in more ventilation than the minimum required).
• For homes having more than five bedrooms and only a
single ventilation system, set the bedrooms dial to 5 (this
may result in less ventilation than the minimum required).
• For conditioned square feet, set area (sq ft) dial to the
nearest value.
• For airflow, set airflow (cfm) dial to the nearest value.
• Vaulted ceilings do not need to be considered when setting
this control.
• For homes with multiple systems: Honeywell recommends
a ventilation control and fresh air intake for each system.
Measure ventilation airflow for each system independently.
Refer to Multi-system Setup Example for further details.

_________

bedrooms

100%
1
62-1999
2
Ventilation
Standard

Installer
Test

_________

_________

area (sq. ft.)

airflow (cfm)

Record settings above
www.honeywell.com/yourhome
or call 1-800-468-1502

Para español ver las instrucciones
*See Instructions Voir mode d'emploi en français inclus

M19991

Customizing the ventilation control.

7

68-0282—07

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

CHECKOUT
In this section, make sure the ventilation system is operating
correctly.
1.
2.
3.
4.

5.

6.
7.

On thermostat, set Fan switch to Auto and System
switch to Off.
Set any remote switches throughout the house in the
Off position.
On the W8150, set the control switch to Off (remote
only).
Press Test button for two seconds to enter test mode:
• A light on the control begins flashing.
• The HVAC system fan comes on.
• The damper moves to the Open position.
Press the Test button again to exit test mode:
• No lights on the control are on.
• The HVAC system fan turns off.
• The damper returns to the closed position.
Return the thermostat, ventilation control, and remote
switches to the original settings.
Refer to Troubleshooting section, if needed.

TIP:
• W8150 Ventilation Control automatically exits test mode
after three minutes.

TROUBLESHOOTING
Problem
Flashing red light
during test mode
(The current settings
do not meet the
selected ventilation
requirement)

Flashing red light
during normal
operation

Possible cause

What to do

Not enough airflow

• Measure airflow and check dial setting.
• See Problem: Not enough airflow.

Ventilation on-time limit
setting

• If the device is set to 60%: Set the ventilation control to 100% maximum
on time. This allows the HVAC fan to run up to 100% of the time. It may be
preferable to increase airflow.
• If the device is set to 100%: There is not enough airflow through the
fresh air duct.
• Ventilation continues to occur according to the settings but chosen
standard may not be met.

Low voltage

• Check the voltage from the transformer for at least 20 Vac. If voltage is
OK, replace W8150 Control. If voltage is not OK, disconnect damper and
remote switch connections and check again. If voltage does not return to
at least 20 Vac, replace transformer.

No light on ventilation No power to control
control when switch
set to:
• On
• Override Off/
• Remote Only and a
remote switch is on. Device malfunction

• Verify 24 volt input to R and C terminals on ventilation control.
• Check wiring connections per appropriate system diagram and replace
transformer, if necessary.

HVAC fan does not
Wiring
come on after pressing
Test button.
HVAC system does not
have power

• Check wiring connections per appropriate system diagram.

68-0282—07

• Cycle power off to control for ten seconds and recheck. If control does not
recover, replace ventilation control.

• Restore power to the HVAC system.

8

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

Problem

Possible cause

HVAC fan is running all Device is set to override
the time
Remote switch is on

What to do
• Move switch to On position to allow for automatic operation.
• Adjust remote switch to desired position.

Thermostat Fan switch is • Normal operation.
in On position

• Damper does not
open during
checkout or
• Damper does not
close.

HVAC system is running
to satisfy heating or
cooling requirements.

• Normal operation.

Ventilation limit is set to
100% ventilation limit.

• Set ventilation limit to 60%. The control may not be able to meet the
recommended ventilation requirements.
• Increase ventilation airflow through fresh air duct and adjust settings.

Low ventilation air flow.

• See Problem: Not enough airflow.

Incorrectly wired.

• Check wiring connections per appropriate wiring diagram.

Transformer output.

• Verify 24 Vac applied to actuator.

Damper actuator motor
failure or mechanical
failure.

• Manually open damper and verify free movement; damper should return
to closed position when no power is applied.
• If damper moves freely but does not operate when 24 volts is applied,
replace damper actuator.
• If damper does not move freely, replace fresh air damper.

Incorrectly wired.
Cooling compressor
comes on when there
is no cooling call from
the thermostat.

• Check wiring connections per appropriate system diagram.
• An isolation relay may be required when appliances are connected to the
GT terminals on the ventilation control. (For an example, see wiring a fan
for a steam humidifier diagram.)

Not enough airflow

•
•
•
•
•
•

Obstruction or duct size

Check for obstructions in the fresh air duct and weather hood.
Check for kinks in ductwork.
Make sure all manual dampers are fully open.
Make sure the stops on the EARD damper allow it to open fully.
Increase duct size.
Add a booster fan to the fresh air duct.

NOTE: After any changes to the ductwork, repeat the Measuring Airflow
section.

9

68-0282—07

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

WIRING DIAGRAMS
Consult thermostat Installation Instructions for alternate
terminal designations.

HVAC

HVAC

R

C

W

R

Y

C

W1 W2 Y1

Y2

G

G

GF

W8150A

RC
GF

W8150A

CC
CH

RC

W

CC

GT

CH
W
GT

R

RC

W1 W2 Y1

C

RC W

DST

Auto

G

System
Heat

AM

Room

Tue
Wake

Y

G

Fan

Room

Tue
Wake

R

Y2

System
Heat

AM

M19996

Fan

DST

Auto

Fig. 3. Multi-stage conventional system.

M19994A

Fig. 1. Single transformer, conventional system.
HVAC
HVAC
R

HEATING
R C W

R

C

Y

G

O

COOLING
C Y G

GF

W8150A

RC
GF

CC

W8150A

CH

RC

W

CC

GT

CH
W
GT

R

RC W

Y

R

RC W

System
Heat

AM

Tue
Wake

Y

Room
DST

Fan
Auto

G

Tue
Wake

NOTE:
REMOVE FACTORY
INSTALLED JUMPER
BETWEEN CC AND CH
ON W8150.

Room
DST

Fan
Auto

M19997A

Fig. 4. Wiring heat pump without emergency heat.

M19995A

Fig. 2. Dual transformer, conventional system.

68-0282—07

G O/B
System
Heat

AM

10

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

HVAC
AT120
EARD-6
R

C

Y

W2

E

G

O
XFMR

GF

W8150A

C
DAMPER

RC
Ventilation Control

CC

Auto
Continuous
Off
(Remote Only)

CH

Service

AUX

Ventilation Control

W

C

W1 Y1 W2

M22000

G O/B

System
Heat

AM

Room

Tue
Wake

E

REMOTE

GT

R

FAN TIMER

R

W8150A

DST

Fig. 7. Using a remote switch or timer.

Fan
Auto

M19998A

AT120

Fig. 5. Wiring heat pump with emergency heat.

HR150/ER150

XFMR

AT120

EARD-6

W8900

R

W8150A

DAMPER

C

Ventilation Control
Auto
Continuous
Off
(Remote Only)

XFMR

RED

BLACK

1
FAN TIMER

Service

C

REMOTE

®

RH

DAMPER

RC

AUX

HUM

REMOTE

HUM

VNT

NOTES:
– BALANCE THE HRV/ERV TO 160 CFM OR LOWER.
– SET VENTILATOR SPEED KNOB TO 0.
M22001

1 EARD DAMPER NOT USED WITH HRV/ERV.

VNT

NOTE:
CONFIGURE PC8900 SO ALL VENT PROGRAM
SETTINGS ARE OFF; THE VENT BUTTON ON THE
PC8900 THEN SERVES AS A REMOTE AND THE W8150
CONTROLS BACKGROUND VENTILATION.

Fig. 8. Wiring to an HRV/ERV.
M19999

AT120

EARD-6

Fig. 6. Wiring with a PC8900.

EXHAUST FAN
120 VAC

XFMR
R

W8150A
Ventilation Control
Auto
Continuous
Off
(Remote Only)

C
DAMPER

W8150A

R

AUX

Ventilation Control

BLUE

R8222

L1
120
VAC
L2

RED

Service

REMOTE

AUX

Ventilation Control

BLUE

AT120

BLACK

FAN TIMER

M22002

Fig. 9. Wiring an exhaust fan.

11

68-0282—07

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

• 100 cfm.
HVAC

R

C

CONVERSION TABLE

W1 W2 Y1

Y2

G
GF

W8150A

Area

RC
HE440

CC

FAN

R

RC

C

93

40

19

1300

121

50

24

GT

1600

149

60

28

1900

177

70

33

2200

204

80

38

2500

232

90

42

2800

260

100

47

3100

288

110

52

Tue
Wake

Y2

3400

316

120

57

3700

344

130

61

4000

372

140

66

4300

399

150

71

4600

427

160

76

G

System
Heat

AM

Room
DST

Fan
Auto

M22021A

Fig. 10. Wiring fan for a steam humidifier.

Multi-System Setup Example

Airflow

Total square feet and bedrooms should be proportionately
split between the ventilation controls based on sq ft served by
each system regardless of where the bedrooms are located.
Example: 5,000 sq ft, six bedrooms:
System 1:
• serves 3200 sq ft,
• two bedrooms.
• fresh air intake measured at 127 cfm.
System 2:
• serves 1800 sq ft,
• four bedrooms
• fresh air intake measured at 98 cfm.
Set W8150 for System 1:
• 3100 sq ft,
• four bedrooms
• 130 cfm.
Set W8150 for System 2:
• 1900 sq ft,
• two bedrooms

6 in. duct
(15.2 cm)
fpm

ms

fpm

ms

40

204

1.0

150

0.8

50

255

1.3

187

1.0

60

306

1.6

225

1.1

70

357

1.8

262

1.3

80

407

2.1

299

1.5

90

458

2.3

337

1.7

100

509

2.6

374

1.9

110

560

2.8

412

2.1

120

611

3.1

449

2.3

130

662

3.4

486

2.5

140

713

3.6

524

2.7

150

764

3.9

561

2.9

160

815

4.1

599

3.0

Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
customer.honeywell.com

7 in. duct
(17.8 cm)

cfm

Automation and Control Solutions

Toronto, Ontario M1V 4Z9

lps

1000

BLUE

W1 W2 Y1

cfm

W

R8222
BLUE

sq m

CH

BLACK

RED

Airflow

sq ft

® U.S. Registered Trademark
© 2011 Honeywell International Inc.
68-0282—07 T.D. Rev. 02-11
Printed in U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Copy, Extract, Assemble, Print high-res
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2011:02:09 08:49:59-06:00
Create Date                     : 2011:02:08 09:59:05-06:00
Metadata Date                   : 2011:02:09 08:49:59-06:00
Format                          : application/pdf
Title                           : 68-0282_D. Y8150 Fresh Air Ventilation System,W8150 Fresh Air Ventilation Control
Creator                         : Honeywell ECC Technical Communications
Description                     : Product Data
Producer                        : Acrobat Distiller 8.2.5 (Windows)
Document ID                     : uuid:edd5ef3b-2966-4918-81a5-1311b2ec8b15
Instance ID                     : uuid:e126ec8c-a709-451b-94b4-46a1139dbb74
Page Count                      : 12
Subject                         : Product Data
Author                          : Honeywell ECC Technical Communications
EXIF Metadata provided by EXIF.tools

Navigation menu