ICP ENA4X18C14A1 User Manual EVAP COIL Manuals And Guides 1206618L
User Manual: ICP ENA4X18C14A1 ENA4X18C14A1 ICP EVAP COIL - Manuals and Guides View the owners manual for your ICP EVAP COIL #ENA4X18C14A1. Home:Heating & Cooling Parts:Icp Parts:Icp EVAP COIL Manual
Open the PDF directly: View PDF
.
Page Count: 7
| Download | |
| Open PDF In Browser | View PDF |
NOTE: Read the entire instruction manual before starting the installation. TABLE ELECTRICALSHOCKHAZARD OF CONTENTS PAGE SAFETY CONSIDERATIONS INTRODUCTION INSTALLATION ........................ 1 ................................... 2 .................................... 2 Airflow ........................................... 2 TXV ............................................. 2 Inspect Equipment ................................ Select Installation Procedure ....................... 2 2 Installation of Furnace Coils ........................ 3 Connect Refrigerant Piping ......................... 5 Connect Refrigerant Liquid and Suction Lines ......... 5 Refrigerant Metering Device ........................ Condensate Drain Line Connection .................. 5 5 Waste Line Connection 6 ............................ Humidifier Application .............................. Model Number Identification ........................ SAFETY Failure to follow this warning could result in personal injury or death. Before installing, modifying or servicing system, always turn off main power to system. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. PERSONALINJURY HAZARD Failure to follow this caution injury. may result in personal This coil contains Nitrogen precharge of 15 PSIG. Release of this pressure through the center of the rubber lu _beforeremovin the tu s. 6 7 CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1. ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental pollution. Remove and recycle all components or materials oil, refrigerant, etc.) before unit final disposal. (i.e. CUT HAZARD Failure to follow this caution injury. may result in personal Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and loves when handlin arts. Recognize safety information. When you see this symbol Z_ on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. IMPORTANT: Nitrogen can leak out through the hole that the needle pierced in the plugs. This does not indicate a leaking coil nor warrant return of the coil. 484 01 3600 00 April 2010 iNTRODUCTiON Use this instruction manual to install indoor coils on upflow or downflow furnaces. Do not install coil in horizontal position. Coils are enclosed in a painted casing have factory-installed TXV's. These coils are used with R-410A refrigerant systems. NOTE: Models with tin-plated copper coils, "T" in the 8th position of the model number, are installed the same as standard copper coils. INSTALLATION Select These units can be installed in multiple configurations. Before installation, there are several performance requirements that must be considered because poor installation can negatively alter performance. This section wilt briefly discuss those factors. Airflow Airflow amount and distribution are vital to adequate system performance. Problems that can be experienced with incorrect airflow include: • low system performance • restricted TXV frosted coil poor humidity control water blow-off When attaching the coil and building the plenum, pay special attention to the effect these details will have on airflow. After system start-up, check the cfm to insure that it is correct. (Generally, the cfm should be 350 to 400 cfm/ton during normal cooling operation.) TXV A thermal expansion valve is utilized in this coil design to optimize performance and comfort throughout the entire operating range of the system. Special attention needs to be taken to the TXV when installing the coil Do not overheat valve. Temperatures that exceed 212°F Installation Procedure PROPERTY DAMAGE HAZARD Failure to follow damage. this caution may result in property installing coils rotated 90 ° from the front of the furnace, in upflow or downflow applications, may cause water blow-off or coil freeze-up due to the concentration of air on one slab of the coil or lack of air to a stab in the coil. it is recommended that on this type of application, a field-supplied adapter be placed between the coil and furnace to allow air to distribute properly between all slabs of the coil. NOTE: Furnace coils are not approved to be used in fan coil or "draw-through" type applications. To install cased coils in upflow applications, follow the instructions below, Upflow Cased Coil Installation. To install cased coils in downflow applications, follow the instructions below, Downflow Cased Coil installation. See Table 1 for dimensions and overhang options. Refer to instructions for placement of coil casing on furnace. (100_}0) can harm valve performance. Use a wet cloth or heat sink when brazing. Place liquid filter dryer near ID unit to reduce the risk of debris clogging the valve. Make sure TXV bulb is securely fastened and wrapped in the indentation on vapor line tube. END4X, ENW4X coils have a factory-installed hard-shutoff TXV designed only for use with R-410A refrigerant. Use only with outdoor units designed for R-410A. NOTE: AIt TXV'S have preset superheat not field-adjustable. settings and are Cabinet Sweating if this unit is installed in a garage, attic, or other unconditioned space, special attention needs to be given to the potential of cabinet sweating. A 6-in (152 mm) wide piece of insulation should be wrapped around the coil casing and supply duct connection point. Inspect Equipment File claim with shipper if equipment is damaged. 2 484 01 3600 00 Table 1 END4X, MODEL NUMBER FLUSH FIT TO FURNACE WIDTH inches (ram) TONS ENW4X COIL CONNECTION TUBE SIZE inches (ram) Liquid Suction COiL INFORMATION SHELF WIDTH (See Figure 1, Dim. A) inches (ram) END4X18(C,T) 14A 1 - 1/2 14-3/16 (360) 3/8 5/8 12-7/8 END4X19(C,T)17A 1-1/2 17-1/2 (445) 3/8 5/8 16-3/16 END4X24(C,T)14A 2 14-3/16 (360) 3/8 5/8 12-7/8 END4X24(C,T)17A 2 17-1/2 (445) 3/8 5/8 16-3/16 FITS NEXT SMALLER Equal Overhang FURNACE Overhang with Transition Offset Left (327) N/A N/A N/A (411 ) No Yes Yes (327) N/A N/A N/A (411 ) No Yes Yes (327) N/A N/A N/A (411 ) No Yes Yes Yes Yes EN D4X30(C,T) 14A 2-1/2 14-3/16 (360) 3/8 3/4 12-7/8 END4X30(C,T)17A 2-1/2 17-1/2 (445) 3/8 3/4 16-3/16 (445) 3/8 3/4 16-3/16 (411 ) No (445) 3/8 3/4 16-3/16 (411 ) No Yes Yes 3/8 3/4 19-5/8 (498) No Yes Yes END4X31(C,T)17A 2-1/2 END4X36(C,T)17A 3 END4X36(C,T)21A 3 END4X37(C,T)17A 3 END4X42(C,T)17A 3-1/2 END4X42(C,T)21A 3-1/2 END4X43(C,T)24A 3-1/2 END4X48(C,T)21A 17-1/2 17-1/2 21 (533) 17-1/2 (445) 3/8 3/4 16-3/16 (411 ) Yes No No 17-1/2 (445) 3/8 7/8 16-3/16 (411 ) No Yes Yes 3/8 7/8 19-5/8 (498) No Yes Yes 3/8 7/8 23-1/8 (587) No Yes Yes 3/8 7/8 19-5/8 (498) No Yes Yes (622) 3/8 7/8 (587) No Yes Yes 7/8 Yes Yes 21 (533) 24-1/2 4 END4X48(C,T)24A (622) 21 (533) 4 24-1/2 23-1/8 END4X60(C,T)24A 5 24-1/2 (622) 3/8 23-1/8 (587) No END4X61 (C,T)24A 5 24-1/2 (622) 3/8 7/8 23-1/8 (587) No Yes No 3 17-1/2 (445) ENW4X36 (C,T) 17A ENW4X42(C,T)21A 3-1/2 ENW4X48(C,T)21A 4 ENW4X60(C,T)24A 5 3/8 3/4 16-3/16 (411 ) Yes No No 21 (533) 3/8 7/8 19-5/8 (498) Yes No No 21 (533) 3/8 7/8 19-5/8 (498) Yes No No 3/8 7/8 (587) Yes No No 24-1/2 (622) 23-1/8 NOTES: For the model number; C = standard copper and T= tin plated copper 1. Set coil in place on upflow furnace discharge air opening. See Figure 2. 2. When coil front width matches furnace front width, the coil can be placed directly on furnace. Field-supplied Plenum 193/16" 3. Ensure coil is level for proper condensate drainage. Do not tip coil toward condensate drain. Coil enclosure need not be fastened or screwed to furnace. Coil Support Shelf Return (152) Table 1 L (57) \ Furnace A08336 Figure 1 - Correct Installation of Furnace Upflow Cased NOTE: On placed piece Orientation Coil upflow the outside \ Coils installations should of coil casing 484 01 3600 O0 on Furnace Evaporator Coil installation in an unconditioned of insulation of Coil Support Upflow Furnace Downflow Furnace where space, be applied and supply the a 6 inch and indoor coil (152 mm) wrapped duct contact around point. is Supply wide A05411 Figure 2 - Typical Coil Installation 3 NOTE: When ENW4X coils are applied to same width furnace, remove block-off plates at casing base by removing 2 screws per plate from side of casing. See Figure 3. 3. Prepare and install block-off plate. See Figure 4, Alternative C. Using field-supplied sheet metal, cut a block-off plate to be attached to bottom left side of coil casing. This plate prevents air leakage from overhanging portion of coil. Attach plate using sheet metal screws. 4. Continue with normal installation Connect Refrigerant Piping. ! __ See __ 2 1/4" (57) l Block-Off practices. l ALTERNATIVE B A05412 Figure 3 - Block-Off Plate Removal ENW4X MODEL COILS APPLIED CENTERED NARROW FURNACE ENW4X Models Only OVER 1. There is no transition required for this application. 2. Remove coil from packaging and place on top of furnace with 1 5/8 inch (41 mm) overhang on both sides. See Figure 4, Alternative A. 3. Continue with normal installation practices. See Connect Refrigerant Piping. STANDARD MODEL COILS APPLIED CENTERED OVER NARROW FURNACE REQUIRE A MINIMUM TRANSITION AS SPECIFIED IN Figure 5. 1. Prepare transition, following recommended drawing. See Figure 5. J Fabricated Block-off Plate l transition 2. Place transition on top of gas furnace. See Figure 4, Alternative B. Secure with sheet metal screws. Place coil on top of transition. Make sure coil rests evenly on top of transition and gas furnace. 3. Secure coil to transition using sheet metal screws. 4. Continue with normal installation practices. See Connect Refrigerant Piping. NOTE: If coil is not being installed in the standard orientation (front of coil matching front of furnace) then coil must be raised above furnace as specified in Figure 5. STANDARD MODEL COILS APPLIED DIRECTLY ON TOP AND OFFSET TO THE LEFT ON NARROW FURNACE 1. Notch support rail on underside of coil cabinet to provide clearances for gas furnace flange. This rail is not visible from front of coil. To locate position of notch, place coil directly on top of gas furnace with overhanging portion entirely on left side as in Figure 4, Alternative C. Mark location of gas furnace flange on coil casing. Remove coil from top of furnace. Using tin snips, make a notch in rail large enough to allow clearance for gas flow furnace flange. 2. Place coil on top of gas furnace. Make sure coil is shifted completely to left side, and notch is sufficient so coil rests on top of furnace cabinet. 4 Field ALTERNATIVE C A08337 Figure 4 - Alternative Coil Mounting Positions Downflow Cased Coil Installation 1. Place N-coil on supply duct opening. 2. When coil width matches furnace width, furnace can be placed directly on the cased coil. NOTE: In downftow installation with a 4-way multipoise furnace, break off perforated duct flanges on furnace. See Furnace Installation Instructions. 3. Coils that under-hang (narrower than furnace) must have a field-fabricated transition between furnace and N-coil casing as specified in Figure 5. 4. Coils that overhang (wider than furnace) do not require a transition in downflow application. However, a field-supplied furnace shelf should be constructed to fit furnace to coil opening. 5. Place furnace on top of field-supplied furnace shelf. N-coil casing, or 484 01 3600 00 Coil Casing Width B 3/4" Rear Bracket (19) Flanges (Where NOTE: Weld 3 places in 4 corners 19 1/2" (495) (Outside) DIMENSIONS C Front Bracket Furnace B C 12-3/4 (324) 17-1/2 (445) 2-1/4 (57) (408) 19-9/16 (497) 17-5/8 (448) 21-1/4 Outlet Inches (mm) A 16-1/16 A (InsideOpening) Shown) 21 (533) 2-1/4 (57) 24-1/2 (622) 19-3/8 (492) 2-1/4 (57) 4 (102) 23 (584) 4 (102) (540) 23 (584) 24-1/2 (622) 4 (102) A09395 Figure 5 - Recommended Connect Refrigerant Transition Piping Use accessory tubing package or field-supplied tubing of refrigerant grade. Suction tube must be insulated. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow-control device. ALWAYS evacuate the coil and field-supplied tubing before opening outdoor unit service valves. Connect Lines Refrigerant For matched recommended Liquid and Suction 6. After brazing, allow joints to coot. Slide rubber grommets over joints. Position tubing at center of each grommet to ensure an air seat around the tube. 7. Always evacuate lines and reclaim refrigerant when making connections or flaring refrigerant lines. Leak check connections before insulating entire suction line. 8. If outdoor equipment will not be installed until a later date, braze liquid and suction lines closed outside. Add a Schraeder port test fitting to the suction line outside. Refrigerant and mismatched systems, use line sizes in outdoor unit Installation Instructions. The coil can be connected to outdoor units using accessory tubing packages or field-supplied tubing of refrigerant grade. Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing. Leak check connections before insulating entire suction line. Suction Line Suction line is designed for field sweat connection. Line is plugged to keep out moisture and dirt. Remove these plugs only when ready to make connection. See Table 1 for coil connection tube size. Metering Condensate Drain Line Connection PROPERTY DAMAGE HAZARD Failure to follow damage. UNiT DAMAGE HAZARD Failure to follow damage. this caution may result in product To avoid valve damage to the refrigerant control device while brazing, valves must be wrapped with a heat_ial such as a wet cloth. 1. Remove cabinet access door. 2. Remove rubber plugs from coil stubs using a pulling and twisting motion. Hold coil stubs steady to avoid bending or distorting. 3. Wrap TXV and nearby tubing material such as a wet cloth. with a heat sinking 4. Use 1/2 psig Nitrogen purge in the suction and out the liquid line. 5. Braze using a Sil-Fos use soft solder. 484 01 3600 00 or Phos-copper alloy. Do not Device END4X, ENW4X coils have a factory-installed hard shut-off TXV designed only for use with R-410A refrigerant. Use only with outdoor units designed for R-410A. NOTE: ALL TXV'S HAVE PRESET SUPERHEAT SETTINGS AND ARE NOT FIELD-ADJUSTABLE. this caution may result in property When installing over a finished ceiling and/or living area, install a field-fabricated secondary condensate pan under the entire unit. The coil is designed to dispose of accumulated water through built-in condensate drain fittings. It is recommended that PVC fittings be used on the condensate pan. Do not over-tighten. Finger tighten plus 1-1/2 turns. Be sure to install plastic plug in unused condensate drain fitting. Two 3/4 inch female threaded pipe connections are provided in each coil condensate pan. A trap is not necessary on the condensate line. Consult local codes for additional restrictions or precautions. If local codes require a trap then the following guidelines are suggested to assure proper drainage. Install a trap in condensate line of coil as close to the coil as possible. Make trap at least 3 inches (76 mm) deep and no higher than the bottom of unit condensate drain opening (See Figure 6). 5 Pitch condensate line 1 inch (25.4 mm) for every 10 ft. of length to an open drain or sump. Make sure that the outlet of each trap is below its connection to condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps and lines if located above a living area. EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death. Provide trap with air gap in drain line when connecting to waste (sewer) line. Humidifier Application When installing a humidifier in a system which contains an N-coil, consideration must be given to location of coil slabs. See Fig. 8. 1. The humidifier should be mounted to the supply plenum or return duct whenever possible. If necessary, humidifiers can be mounted to the left side of coil casing. The right side of the coil casing must not be used to mount the humidifier. A08067X Figure 6 - Condensate Trap NOTE: If unit is located in or above a living space, where damage may result from condensate overflow, a field-supplied, external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan. Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the running of a separate 3/4 inch (19 mm) condensate line (with appropriate trap) per local code to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from secondary drain or external condensate pan, the unit requires servicing or water damage will occur. To further protect against water damage, install a float switch to shut the unit off if the water in the secondary pan gets too high. NOTE: To avoid drainage problems, test the primary drain line by slowly pouring water into the pan. Check piping for leaks and proper condensate drainage. Using the secondary drain as explained in the previous note provides further protection against overflow due to a clogged primary drain. 2. Care must be taken to prevent damage of N-coil when attaching humidifier to coil casing or plenum. 3. Ensure that humidifier has adequate airflow. Evaporator N-Coil Upflow Furnace NOTE: In applications where return air humidity levels stay at 70% or above for a prolonged period of time, condensation can form on the bottom of pan and drip. WASTE A05414 Figure 8 - Installation LINE CONNECTION If the condensate line is to be connected to a waste (sewer) line, an open trap must be installed ahead of the waste line to prevent escape of sewer gases (See Figure 7). of Humidifier in System with N=Coil Air Gap Above aid Level Condensate Line Trap I Sewer Line I A102t6 Figure 7 - Condensate 6 Drain to Waste Line 484 01 3600 00 ii Digit Position 1 2 3 4 5 6,7 8 9,10 11 12 E N D 4 X 18 C 14 A 1 E = Evaporator B = Builder D = Standard N = N Coil TYPE A = Uncased D = Cased Upflow/Downflow M = Cased Multiposition (Upflow/Downflow/Horizontal) W = Cased Upflow/Downflow H = Cased Horizontal 4 = Environmentally for narrower furnaces INSTALLATION Sound R-410A P = Piston X = TXV REFRIGERANT METERING DEVICE 18 = 18,000 BTUH = 11/2tons 19 = 18,000 BTUH = 11/2tons 24 = 24,000 BTUH = 2 tons 30 = 30,000 BTUH = 21/2tons 31 = 30,000 BTUH = 21/2tons 36 = 36,000 BTUH = 3 tons 37 = 36,000 BTUH = 3 tons 42 = 42,000 BTUH = 31/2tons 43 = 42,000 BTUH = 31/2tons 48 = 48,000 BTUH = 4 tons 60 = 60,000 BTUH = 5 tons 61 = 60,000 BTUH = 5 tons NOMINAL CAPACITY C = Plain Copper L = Aluminum T = Tin Coated Copper 14 = 14.5" HAIRPIN MATERIAL 17 = 17.5" 21 = 21" 24 = 24.5" BB = 15.5" FF = 19.1" JJ = 22.8" LL = 24.5" WIDTH Sales Digit (Major Revision) Engineering Digit (Minor Revision) 484 01 3600 00 International Comfort Products, LLC Lewisburg, TN 37091 USA 7
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 7 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Wed Jul 04 04:14:31 2012 Author : Title : Subject :EXIF Metadata provided by EXIF.tools