ICP FSM2X2400A1 User Manual FAN COILS Manuals And Guides L0604342

ICP Evaporator Coils Manual L0604342 ICP Evaporator Coils Owner's Manual, ICP Evaporator Coils installation guides

User Manual: ICP FSM2X2400A1 FSM2X2400A1 ICP FAN COILS - Manuals and Guides View the owners manual for your ICP FAN COILS #FSM2X2400A1. Home:Heating & Cooling Parts:Icp Parts:Icp FAN COILS Manual

Open the PDF directly: View PDF PDF.
Page Count: 15

These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and
NOTE
The signal words DANGER, WARNING, CAU-
TION, and NOTE are used to identify levels of haz-
ard seriousness. The signal word DANGER is only
used on product labels to signify an immediate haz-
ard. The signal words WARNING, CAUTION, and
NOTE will be used on product labels and through-
out this manual and other manuals that may apply
to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death.
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE - Used to highlight suggestions which will
result in enhanced installation, reliability, or opera-
tion.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Introduction .................................... 2
Location ....................................... 2
Heater Packages ............................... 3
Position Unit ................................ 3 - 7
Air Ducts ...................................... 7
Electrical Connections ...................... 7 - 11
Refrigerant Tubing ............................. 11
Refrigerant Metering Device .................... 11
Condensate Drains ............................ 12
Accessories .................................. 13
Sequence of Operation ......................... 14
Start-up Procedure ............................ 14
Care and Maintenance ......................... 14
R-410A Quick Reference Guide ................. 15
DEATH, PERSONAL INJURY, AND/OR PROPERTY
DAMAGE HAZARD
Failure to carefully read and follow this warning
could result in equipment malfunction, property
damage, personal injury and/or death.
Installation or repairs made by unqualified per-
sons could result in equipment malfunction, prop-
erty damage, personal injury and/or death.
The information contained in this manual is in-
tended for use by a qualified service technician fa-
miliar with safety procedures and equipped with
the proper tools and test instruments.
Installation must conform with local building
codes and with the National Electrical Code
NFPA70 current edition.
496 01 5000 01 October 2005
INTRODUCTION
Models FEM and FSM are designed for maximum flexibil-
ity and can be used for upflow, horizontal left or right, and
downflow applications (accessory kit required for down-
flow or horizontal right).
Model FSU is designed for upflow installation, and can be
field modified for downflow and horizontal left or right ap-
plications (accessory kits required for downflow or hori-
zontal).
All models are available for system sizes 11/2- 5 tons
(18,000 - 60,000 BTUH) nominal cooling capacity.
LOCATION
All models have a factory installed and appropriately
sized hard shut-off TXV metering device. FEM2, FSM2
and FSU2 are for R-22 refrigerant ONLY. FEM4, FSM4
and FSU4 are for R-410A refrigerant ONLY.
Factory approved electric heater packages are available
in sizes 3kW through 30kW. See Product Specification lit-
erature for available accessory kits.
Select the best position which suits the installation site
conditions. The location should provide adequate struc-
tural support, space in the front of the unit for service ac-
cess, clearance for return air and supply duct
connections, space for refrigerant piping connections and
condensate drain line connections. If heaters are being
installed make sure adequate clearance is maintained
from supply duct work. See Clearances in Figure 1.
If the unit is located in an area of high humidity, nuisance
sweating of casing may occur. On these installations a
wrap of 2" fiberglass insulation with a vapor barrier is rec-
ommended.
NOTE: Internal filter can be accessed from separate filter
door. If the filter can NOT be easily accessed, a remote
filter is recommended. Refer to ACCA Manual D for re-
mote filter sizing.
FIRE HAZARD
Failure to maintain proper clearances could result
in personal injury, death, and/or property damage.
When heaters are installed, maintain clearances
from combustible materials as specified on unit
rating plate. Do not use plastic lined or combus-
tible flexible ducting within 36 inches of the supply
end of the fan coil.
Figure 1 1Clearances and Unit Dimensions
OPENING)
All Sides 0
No Heaters From Supply Duct 0
All Sides 0
With Heaters From First 3 feet of Supply Duct to Combustibles 1
From Supply Duct to Combustibles after 3 feet 0
Unit Size
1800
2400
3000
3500/3600
4200
4800
6000
C_
L(OPENING) _/_
Unit Size H (inches)
1800 421X6 421X6 421X6
2400 471Xs 471Xs 471Xs
3000 47%6 47%6 49%
3500 537/16
3600 537/16 495/8 495/8
4200 49% 49% 49%
4800 537/16 537/16 537/16
6000 593A6 593A6 593A6
(SERVICE ACCESS)
38-11-82
2 496 01 5000 01
HEATER PACKAGES
Factory approved, field installed, UL listed heater pack-
ages are available from the equipment supplier. See unit
rating plate for a list of factory approved heaters. Heaters
POSITION UNIT
Unit can stand or lie on floor, or hang from ceiling or wall.
Allow space for wiring, piping, and servicing unit.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper-
ty damage
Afield fabricated auxiliary drain pan, with a sepa-
rate drain is REQUIRED for all installations over a
finished living space or in any area that may be
damaged by overflow from a restricted main drain
pan. In some localities, local codes require an aux-
iliary drain pan for ANY horizontal installation.
OPTIONS
FRONT SERVICE CLEARANCE
18 - 48 models = 21"
60 model = 24"
UNITS
SECONDARY DRAIN
|
Figure 2 1
PRIMARY DRAIN
SECONDARY DRAIN
PRIMARY DRAIN
that are not factory approved could cause damage which
would not be covered under the equipment warranty.
A. UPFLOW INSTALLATION
If return air is to be ducted through a floor, set unit on floor
over opening and use Y8to ¼ inch thick fireproof resilient
gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut
opening per dimensions shown in Figure 2. A field-sup-
plied bottom closure is required.
Upflow Installation
FIELD SUPPLIED
SUPPLY DUCT
LOW VOLT
ENTRY
OPTIONS
11/2"
SLOPE COIL UNITS
MODEL SIZE A
18 (all) 12"
24 & 30 (all) 17"
35 (FEM) & 36 (FSU) 19"
FIELD MODIFIED
ASIDE RETURN
LOCATION FOR
SLOPE COIL
UNITS ONLY
FIELD SUPPLIED
RETURN PLENUM
B. DOWNFLOW INSTALLATION
In this application, field conversion of the evaporator coil
is required using accessory Downflow Kit along with an
accessory Base Kit. See installation instructions pack-
aged with accessory kit. See Product Specification litera-
ture for kit part numbers.
C. HORIZONTAL INSTALLATION
Unit must NOT be installed with access panels facing up
or down. Access panels must only face to the side.
FEM and FSM models are factory built for horizontal left
installation (refer to Figures 3 and 4). They can be field
converted to horizontal right (accessory Gasket Kit re-
496 01 5000 01 3
quired, see Product Specification literature for part num-
ber). Refer to Figures 5 and 6.
FSU models require accessory kits for any horizontal
installation (see Product Specification literature for re-
quired accessory kits).
Figure 3
NOTE: When suspending unit from ceiling, dimples in
casing indicate suitable location of screws for mounting
metal support straps (refer to Figure 3).
NOTE: For optimum condensate drainage performance
in horizontal installations, unit should be leveled along its
length and width.
Slope Coil In Horizontal Left Application (FEM & FSM factory configuration)
A-COIL
HORIZONTAL LEFT
LOW VOLT
ENTRY
OPTIONS
POWER
ENTRY
OPTIONS
Figure 4 1
FIELD
SUPPLIED
HANGING
STRAPS
SECONDARY PRIMARY
DRAIN DRAIN
FRONT SERVICE CLEARANCE
(FULL FACE OF UNIT)
SECONDARY 18 - 48 models = 21"
DRAIN 60 model = 24"
13/4_'
FILTER ACCESS
CLEARANCE
PRIMARY
DRAIN
A-Coil in Horizontal Left Application (FEM & FSM factory configuration)
FACTORY SHIPPED
HORIZONTAL LEFT
APPLICATION
COIL
-- BRACKET
COIL
SUPPORT
RAIL
DRAIN PAN
SUPPORT
BRACKET
COIL
BRACKET
HORIZONTAL
DRAIN PAN
AIR SEAL
REFRIGERANT
CONNECTIONS
PRIMARY DRAIN
HORIZONTAL LEFT
SECONDARY DRAIN
HORIZONTAL LEFT
4 496 01 5000 01
HorizontalRight Conversionof Units With Slope
Coils
1. Remove blower and coil access panel and fitting
panel (refer to Figure 5).
2. Remove coil mounting screw securing coil assem-
bly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil as-
sembly with condensate pan down (refer to Figure
5).
Figure 5
5,
6,
Attach coil to casing flange using coil mounting
screw previously removed.
Align holes with tubing connections and conden-
sate pan connections, and reinstall access panels
and fitting panel. After brazing, make sure liquid
and suction tube grommets are in place to prevent
air leaks and cabinet sweating.
Conversion for Horizontal Right Applications -Slope Coil
COIL MOUNTING BLOWER
SCREW ASSEMBLY
SLOPE COIL
SKI
DRAINPAN DRAIN
REFRIGERANT
CONNECTIONS
SECONDARY DRAIN
Horizontal Right Conversion of Units With A-Coils
1. Remove blower and coil access panel and fitting
panel (refer to Figure 6).
2. Remove coil mounting screw securing coil assem-
bly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil as-
sembly with condensate pan down (refer to Figure
6).
5. Remove horizontal drain pan support bracket from
coil support rail on left side of unit and reinstall on
coil support rail on right side of unit.
6. Convert air-seal assembly for horizontal right (re-
fer to Figure 6).
a. Remove air-seal assembly from coil by removing
4 screws.
b. Remove coil drip flanges from A-coil and reinstall
on right side of coil (same side as horizontal drain
pan).
c. Remove filler plate (A) and install air splitter (B)
in place of filler plate.
d, Install filler plate (A) as shown in horizontal right
application.
e. Remove condensate troughs (C) and install on
opposite tube sheets.
f, Install hose onto plastic spout.
7. Install horizontal pan on right side of coil assembly.
8. Slide coil assembly into casing. Be sure coil brack-
et on each corner of vertical pan engages coil sup-
port rails.
9, Reinstall 2 snap-in clips to correctly position and
secure coil assembly in unit. Be sure clip with large
offsets is used on right side of unit to secure hori-
zontal pan.
10, Remove 2 oval coil access panel plugs and rein-
stall into holes on left side of coil access panel and
fitting panel.
11, Remove insulation knockouts on right side of coil
access panel
496 01 5000 01 5
12. Reinstall access fitting panels, aligning holes with 13. After brazing, make sure liquid and suction tube
tubing connections and condensate pan connec- grommets are in place to prevent air leaks and cab-
tions. Be sure to reinstall metal clip between fitting inet sweating.
panel and vertical condensate pan.
Figure 6 I Conversion for Horizontal Right Applications -A-Coil
I
SUPPORT
RAIL
CONNECTIONS HORIZONTAL
RIGHT
APPLICATION
BRACKET
DRAIN
SUPPORT
BRACKET
COIL_
SUPPORT--
RAIL
BRACKET
HORIZONTAL
DRAIN PAN
PRIAMRY
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
D. MANUFACTURED HOUSING AND MOBILE HOME
APPLICATIONS
1. Fan coil unit must be secured to the structure us-
ing field-supplied hardware.
2. Allow a minimum of 24 inches clearance from ac-
cess panels.
3. Recommended method of securing for typical ap-
plications:
a. If fan coil is away from wall, attach pipe strap to
top of fan coil using No. 10 self tapping screws.
Angle strap down and away from back of fan coil,
remove all slack, and fasten to wall stud of struc-
ture using 5/_6"lag screws. Typical both sides of
fan coil.
b. If fan coil is against wall, secure fan coil to wall
stud using Ys"wide right-angle brackets. Attach
brackets to fan coil using No. 10 self tapping
screws and to wall stud using 5/_6"lag screws (re-
fer to Figure 7).
Figure 7 Mobile Home or Manufactured
Housing Applications
4" MAX
SECURE FAN COIL TO STRUCTURE
UNIT AWAY FROM WALL
PIPE STRAP
[IY _'Ib_L I_U IM blUe_b}
OR
UNIT AGAINST WALL
Y_INCH THICK ANGLE
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
I DOWN FLOW
-- BASE KIT
SECURE UNIT TO FLOOR
ANGLE BRACKET OR PIPE STRAP
4" MAX
6 496 01 5000 01
Removalof Bracketson
Figure8 ModularUnits
NOTE:Modular units can be disassembled and compo-
nents moved separately to installation area for reassemb-
ly. This process accommodates small scuttle holes and
limiting entrances to installation sites (refer to Figure 8).
-2SCREWS
BRACKET
[
BLOWER BOX
P 2 SCREWS
COIL BOX
2SCREWS
AIR DUCTS
Connect supply-air duct over the outside of %" flanges
provided on supply-air opening. Secure duct to flange us-
ing proper fasteners for type of duct used, and seal duct-
to-unit joint. If return-air flanges are required, install
factory authorized accessory kit.
Use flexible connectors between duct work and unit to
prevent transmission of vibration. When electric heater is
installed, use heat-resistant material for flexible connec-
tor between duct work and unit at discharge connection.
Duct work passing through unconditioned space must be
insulated and covered with vapor barrier.
Duct work Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow
and 10 feet of main duct before first branch takeoff may
require internal acoustical insulation lining. As an alterna-
tive, fibrous duct work may be used if constructed and
installed in accordance with the latest edition of SMACNA
construction standard on fibrous glass ducts. Both acous-
tical lining and fibrous duct work shall comply with Nation-
al Fire Protection Association as tested by UL Standard
181 for Class 1 air ducts.
ELECTRICAL CONNECTIONS
All Fan Coil models utilize an electronic fan board which
has a low voltage circuit protective fuse (5 amp), fan mo-
tor speed tap terminal (SPT), and time delay relay (TDR).
To disable the TDR feature, snip the jumper wire JW1 (re-
fer to Figure 9).
Before proceeding with electrical connections, make cer-
tain that supply voltage, frequency, phase, and circuit am-
pacity are as specified on the unit rating plate. See unit
wiring label for proper field high and low voltage wiring.
Make all electrical connections in accordance with the
NEC and any local codes or ordinances that may apply.
Use copper wire only. The unit must have a separate
branch electric circuit with a field-supplied disconnect
switch located within sight from and readily accessible
from the unit.
NOTE: When a pull-out type disconnect is removed form
the unit, only the Load side of the circuit is de-energized.
The Line side remains live until the main (remote) discon-
nect is turned off.
496 01 5000 01 7
ELECTRICAL SHOCK or UNIT DAMAGE HAZARD
Failure to follow this warning could result in per-
sonal injury, death, and/or unit damage.
If a disconnect switch is to be mounted on unit, se-
lect a location where drill and fasteners will not
contact electrical or refrigeration components.
ELECTRICALSHOCKHAZARD
Failure to follow this warning could result in per-
sonal injury or death.
Turn off the main (remote) disconnect device be-
fore working on incoming (field) wiring.
Incoming (field) wires on the line side of the dis-
connect found in the fan coil unit remain live, even
when the pull-out is removed. Service and main-
tenance to incoming (field) wiring cannot be per-
formed until the main disconnect switch (remote
to the unit) is turned off.
Figure 9lFan Coil Printed Circuit Board
FSM, FSU
CEBD4S0_4L 01B SS0LBm_ o _ _ HSGI
I
II
HI<61EAO06
R B TCCC
{
RIO
HK61 EA010
R G TCCW
A. LINE VOLTAGE CONNECTIONS
Fan Coils installed without electric heat require the use of
a factory-authorized Power Plug Kit (EBAC01 PLG). This
kit provides the electrical connections necessary to sup-
ply the unit with 208/230V power when electric heat is not
present. For units without electric heat:
1. Connect 208/230V power leads from field discon-
nect to yellow and black stripped leads on Power
Plug (EBAC01 PLG).
2. Connect ground wire to unit ground lug.
3. When installing an electric heater, remove and dis-
card power plug (if equipped) from fan coil and con-
nect male plug from heater to female plug from unit
wiring harness. (See Electric Heater Installation In-
structions.)
B. 24V CONTROL SYSTEM
Connection to Unit
Wire low voltage in accordance with wiring label on the
blower (also refer to Figures 10, 11,12, 13, and 14). Use
18 AWG color-coded, insulated (35 °C minimum) wire to
make the low-voltage connections between the thermo-
stat, the unit, and the outdoor equipment. If the thermo-
stat is located more than 100 feet from the unit (as
measured along the low voltage wire), use 16 AWG col-
or-coded, insulated (35 °C minimum) wire. All wiring
must be NEC Class 1 and must be separated from incom-
ing power leads. Refer to outdoor unit wiring instructions
for additional wiring recommendations.
Heater Staging
The controls are factory circuited for single-stage opera-
tion (refer to Figures 11 & 12). When 2 stages are de-
sired, cut W3 at the W2 wire nut, strip, and reconnect
according to the thermostat kit instruction (refer to Figure
13 - outdoor thermostat optional). When 3 stages are de-
sired, cut the W2 wire nut off and discard. Strip W2, W3,
and E, and reconnect according to the thermostat kit in-
structions (refer to Figure 14 outdoor thermostats
optional).
8 496 01 5000 01
UNIT OPERATION HAZARD
Failure to follow this caution may result in improp-
er product operation.
If W2, W3, and E on any 3 stage heater (18, 20, 24,
or 30kW) are individually connected -as with out-
door thermostats or any other situation -emer-
gency heat relay must be used. If relay is not used,
blower may not operate when heaters are ener-
gized.
Figure 10 /Wiring Layout -Air Conditioning
Unit (Cooling Only)
I
THERMOSTAT
[]
FAN COIL
'CONTROL)
_R
_G
W3
E
AIR COND.
Wiring Layout -Air Conditioning
Figure 11 Unit (Cooling and 1-Stage Heat)
THERMOSTAT FAN COIL
CONTROL)
_R
_G
W3
E
AIR COND.
Figure 12 Wiring Layout -Heat Pump Unit
(Cooling and 1-Stage Heat with
No Outdoor Thermostat)
THERMOSTAT FAN COIL
(CONTROL)
[___ RED R
[:__ BRNC
[2__ w2
/B_ W3
[] LVlO E
[]
HEATPUMP
(CONTROL)
_--R
_- C
_W2
C3_o
_y
Figure 13 Wiring Layout -Heat Pump Unit
(Cooling and 2-Stage Heat with
One Outdoor Thermostat)
THERMOSTAT FAN COIL
(CONTROL)
[]__c
[_]__ w_
I _E
[] _w3
[]
HEAT PUMP
(CONTROL)
Z__ R
_ C
ODTS
0
496 01 5000 01 9
Wiring Layout-Heat Pump Unit
Figure 14 (Cooling and 2-Stage Heat with
Two Outdoor Thermostats)
FAN COIL
THERMOSTATCONTRO_ Eo TT%
c:x
_2W
U II -T
Transformer Information
Transformer is factory wired for 230V operation. For
208V applications, disconnect the black wire from the
230V terminal on transformer and connect it to the 208V
terminal (refer to Figure 15).
Figure 15 1Transformer Connections
BROWN
RED
YELLOW
BLACK
C. GROUND CONNECTIONS
ELECTRICALSHOCKHAZARD
Failure to establish uninterrupted or unbroken
ground could result in personal injury and/or
death.
According to NEC, ANSI/NFPA 70, and local
codes, the cabinet must have an uninterrupted or
unbroken ground in order to minimize potential
for personal injury or death if an electrical fault
should occur. The ground may consist of electri-
cal wire or metal conduit when installed in accor-
dance with existing electrical codes. If conduit
connection uses reducing washers, a separate
ground wire must be used.
NOTE: Use UL listed conduit and conduit connectors for
connecting supply wire(s) to unit to obtain proper ground-
ing. Grounding may also be accomplished by using
grounding lugs provided in control box.
D. MINIMUM CFM AND MOTOR SPEED SELECTION
Units with or without electric heaters require a minimum
CFM. Refer to the unit wiring label to ensure that the fan
speed selected is not lower than the minimum fan speed
indicated.
FEM models: fan speed selection is done at the fan mo-
tor. To change motor speeds, reposition wire at fan motor
speed terminals labeled 1-2-3 (refer to Figure 16).
FSM and FSU models: fan speed selection is done at the
fan relay on the electronic fan board. To change motor
speeds, disconnect fan lead used on relay terminal (SPT)
and replace with motor speed lead desired (refer to Figure
17). Save insulating cap and place on motor lead re-
moved from relay.
NOTE: In low static applications, lower motor speed tap
should be used to reduce possibility of water being blown
off coil.
All units have 2 or 3 motor speed taps. Low speed (red or
1) is designed for mismatch outdoor unit applications.
Medium speed (blue or 2) is designed for straight
matched operations. High speed (black or 3) is used with
high external static duct situations on straight matched
systems.
10 496 01 5000 01
Figure16 1FEM Motor Speed Selection
\
I
Figure 17
FAN
iNSULATING CAP (2)
MOTOR SPEED
TAP LEADS
COMMON YELLOW
FSM & FSU Fan Coil Relay andSpeed Tap Terminal
WRAPPER -'_
FAN DECK
REFRIGERANT TUBING
Size and install refrigerant lines according to information
provided with outdoor unit. Route refrigerant lines to the
fan coil in a manner that will not obstruct service access to
the unit or removal of the filter.
1. Find the liquid tube grommet inthe small-parts bag
and slide it onto the liquid refrigerant line (field line-
set).
2. Remove the lower door. Remove the tubing plate
(with suction tube grommet) and slide the plate with
grommet onto the refrigerant lines (field line-set),
away from braze joints.
3. Remove rubber plugs from coil stubs using a pulling
and twisting motion. Hold coil stubs steady to avoid
bending or distorting.
4. Wrap TXV and nearby tubing with a heat-sinking
material such as a wet cloth.
REFRIGERANT METERING DEVICE
5. Fit refrigerant lines into coil stubs. Wrap a heat sink-
ing material such as a wet cloth behind braze joints.
6. Braze using a SiI-Fos or Phos-copper alloy.
7. After brazing, allow joints to cool. Slide tubing plate
back into place and position grommets around suc-
tion and liquid tubes to ensure air seal.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage.
Braze with SiI-Fos or Phos-copper alloy on cop-
per-to-copper joints and wrap a wet cloth around
rear of fitting to prevent damage to TXV.
FEM2, FSM2, FSU2 Models:
These Fan Coils have a factory installed hard shut-off
TXV designed only for use with R-22 refrigerant, Use
only with outdoor units designed for R-22.
FEM4, FSM4, FSU4 Models:
These Fan Coils have a factory installed hard shut-off
TXV designed only for use with R-410A refrigerant, Use
only with outdoor units designed for R-410A.
TXV is factory set and not field adjustable,
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage,
This Fan Coil has a hard shut-off TXV metering de-
vice, A compressor Hard Start Kit is REQUIRED in
all applications where the matching outdoor unit
has a single-phase reciprocating compressor.
496 01 5000 01 11
CONDENSATE DRAINS
Unit is provided withprimary and secondary 3/4"NPT drain
connections. Refer to Figures 2, 3, 4, 5, and 6 to identify
the primary and secondary locations. To prevent property
damage and achieve optimum drainage performance,
BOTH primary and secondary drain lines should be
installed and include properly sized condensate traps (re-
fer to Figure 18). Factory approved condensate traps are
available (accessory part number EBAC01CTK).
Install traps in the condensate lines as close to the coil as
possible (refer to Figure 20), but avoid blocking filter ac-
cess panel.
Install drain lines below the bottom of the drain pan and
pitch the drain lines down from the coil at least 1/4inch per
foot of run. Horizontal runs over 15 feet long must also
have an anti-siphon air vents (stand pipes), installed
ahead of the horizontal runs. Extremely long horizontal
runs may require oversized drain lines to eliminate air
trapping.
Route primary drain line to the outside or to a floor drain.
Check local codes before connecting to a waste (sewer)
line.
Route the secondary drain line to a place in compliance
with local installation codes where it will be noticed when
unit is operational. Condensate flowing from secondary
(overflow) drain indicates a plugged primary drain - unit
requires service or water damage will occur.
Prime all traps, test for leaks, and insulate drain lines
where sweating could cause water damage. Consult local
codes for additional requirements or precautions.
If a gravity drain cannot be used, install a condensate
pump. Install the pump as close to the indoor section as
possible.
Be sure to install plastic push-in plugs in unused conden-
sate drain holes.
PRODUCT or PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product
or property damage.
Use only full size P-traps in the condensate line
(refer to Figure 18). Shallow, running traps are in-
adequate and DO NOT allow proper condensate
drainage (refer to Figure 19).
Figure 18 Recommended Condensate Trap
Figure 19 1 Insufficient Condensate Trap
DO NOT USE SHALLOW RUNNING TRAPS!
Figure 20 1 Condensate Drain
o
¢-
o o o
UIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP)
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF PROPER DEPTH.
STANDARD P-TRAPS ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)
12 496 01 5000 01
ACCESSORIES
A. ELECTRONIC AIR CLEANER
The Electronic Air Cleaner may be connected to FSM and
FSU fan coils as shown in Figure 21. This method re-
quires a field supplied transformer. See Electronic Air
Cleaner literature for kit requirements,
Wiring Layout of Electronic Air
Figure 21 Cleaner to Fan Coil (FSM & FSU)
FAN RELAY /
230VAC-r2°Yq
I
SPT NO NC
CONTROL BOARD
R G T C C
¢''I'
CONVERSION KIT _ OM
TO TRANSFORMER
BLOWER
MOTOR
208/230V
TO EAC
FROM MOLEX
PLUG AND
TRANSFORMER
(IN UNIT)
B, HUMIDIFIER
Connect humidifier and humidistat to fan coil unit as
shown in Figures 22 & 23,
Figure 22 IWiring Layout of Humidifier to
Heat Pump
I
THERMOSTAT
E_
[]-
[]
[]
[]
[]
FAN COIL
(CONTROL)
_G
_o
W3
It l _LL___J
J
r
J
L
I I
FAN HU RELAY I
1!
I HUMIDISTAT
I
L....
HEAT PUMP
(CONTm..i..O L)
C:% R
C3._0
_ w2
o
Y
Wiring Layout of Humidifier to
Figure 23 Fan Coil with Electric Heat
FAN COIL
THERMOSTAT (CONTROL)
[___:q REO R
IZb_ w2
Ii _ E
i_ C AIR COND.
I I
[] i I _
I I- 1 HUMID
115V_--_ _--_
496 01 5000 01 13
SEQUENCE OF OPERATIONS
A. CONTINUOUS FAN
Thermostat closes R to G. G energizes fan relay on elec-
tronic fan board which completes circuit to indoor blower
motor. When G is de-energized, there is a 90 second
delay before relay opens.
B. COOLING MODE
Thermostat energizes R to G, R to Y, and R to O (heat
pump only). G energizes fan relay on electronic fan board
which completes circuit to indoor blower motor. When G
is de-energized, there is a 90 second delay before fan
relay opens.
C. HEAT PUMP HEATING MODE
Thermostat energizes R to G and R to Y. G energizes fan
relay on electronic fan board which completes circuit to in-
door blower motor. When G is de-energized, there is a 90
second delay before fan relay opens.
D. HEAT PUMP HEATING WITH AUXILIARY
ELECTRIC HEAT
Thermostat energizes R to G, R to Y, and R to W. G ener-
gizes fan relay on PCB which completes circuit to indoor
blower motor. W energizes electric heat relay(s) which
completes circuit to heater element(s). When W is de-
energized, electric heat relay(s) open, turning off heater
elements. When G is de-energized there is a 90 second
delay before fan relay opens.
E. ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat
relay(s) which completes circuit to heater element(s).
Blower motor is energized through normally closed con-
tacts on fan relay. When W is de-energized, electric heat
relay(s) opens.
START-UP PROCEDURE
Refer to outdoor unit Installation Instructions for system
start-up instructions and refrigerant charging method de-
tails,
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified
service technician. Consult the servicing dealer for rec-
ommended frequency.
Between visits, the only consumer service recommended
or required is air filter maintenance and condensate drain
operation.
Air Filter
Inspect air filters at least monthly and replace or clean as
required. Disposable type filters should be replaced. Re-
usable type filters may be cleaned by soaking in mild de-
tergent and rinsing with cold water. Install filters with the
arrows on the side pointing in the direction of air flow.
Condensate Drain
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor
unit performance and/or product damage.
Never operate unit without a filter. Factory autho-
rized filter kits must be used when locating the fil-
ter inside the unit. For those applications where
access to an internal filter is impractical, a field-
supplied filter must be installed in the return duct
system.
During the cooling season check at least monthly for free
flow of drainage and clean if necessary.
14 496 01 5000 01
R-410A QUICK REFERENCE GUIDE
R-410A refrigerant operates at 50% - 70% higher pressures than R-22. Be sure that servicing equipment and
replacement components are designed to operate with R-410A.
R-410A refrigerant operates at 50% - 70% higher pressures than R-22. Be sure that servicing equipment and
replacement components are designed to operate with R-410A.
R-410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard.
Use hoses with 750 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
R-410A, as with other HFC refrigerants, is only compatible with POE oils.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Vacuum pumps will not remove moisture from oil.
A liquid line filter-drier is required on every unit.
Do not use liquid line filter-driers with rated working pressures less than 600 psig.
Do not install a suction line filter-drier in liquid line.
Wrap all filter-driers and service valves with wet cloth when brazing.
Do not use with an R-22 TXV.
If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.
Do not use capillary tube indoor coils.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace all filter-driers.
Do not vent R-410A into the atmosphere.
Observe all WARNINGS, CAUTIONS, NOTES, and bold text,
496 01 5000 01 15

Navigation menu