ICP FSM4X6000AT User Manual FAN COILS Manuals And Guides 1209239L

User Manual: ICP FSM4X6000AT FSM4X6000AT ICP FAN COILS - Manuals and Guides View the owners manual for your ICP FAN COILS #FSM4X6000AT. Home:Heating & Cooling Parts:Icp Parts:Icp FAN COILS Manual

Open the PDF directly: View PDF PDF.
Page Count: 22

These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and
NOTE
The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manuals that may
apply to the product.
DANGER - Immediate hazards which will result in
severe personal injury or death.
WARNING - Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE - Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Introduction .................................... 2
Location ....................................... 2
Clearances and Dimensions ..................... 3
Heater Packages ............................... 4
Position Unit ................................ 4 - 8
Air Ducts ...................................... 9
Electrical Connections ...................... 9 - 13
Refrigerant Tubing ............................. 14
Refrigerant Metering Device .................... 14
Condensate Drains ............................ 15
Accessories .................................. 16
Sequence of Operation ......................... 17
Start-up Procedure ............................ 17
Care and Maintenance ......................... 17
Airflow Performance ....................... 18 - 21
R-410A Quick Reference Guide ................. 22
PERSONAL INJURY, AND/OR PROPERTY DAMAGE
HAZARD
Failure to carefully read and follow this warning could
result in equipment malfunction, property damage,
personal injury and/or death.
Installation or repairs made by unqualified persons
could result in equipment malfunction, property dam-
age, personal injury and/or death.
The information contained in this manual is intended
for use by a qualified service technician familiar with
safety procedures and equipped with the proper
tools and test instruments.
Installation must conform with local building codes
and with the National Electrical Code NFPA70 current
edition.
496 01 5402 02 April 2011
INTRODUCTION
Models FEM4X, FSM4X, and FXM4X are designed for
maximum flexibility and can be used for upflow, horizontal left
or right, and downflow applications (accessory kit required
for downflow or horizontal right).
Model FSU4X is designed for upflow installation, and can be
field modified for downflow and horizontal left or right
applications (accessory kits required for downflow or
horizontal).
FEM4X and FXM4X models are available for system sizes
1-1/2 - 5 tons (18,000 - 60,000 BTUH) nominal cooling
capacity.
FSM4X, and FSU4X models are available for system size 5
ton (60,000 BTUH) nominal cooling capacity.
FEM4X and FXM4X models use an ECM motor and have a
factory installed and appropriately sized hard shut-off TXV
metering device and are for R-410A refrigerant ONLY.
FSM4X and FSU4X models use a PSC motor and have a
factory installed and appropriately sized hard shut-off TXV
metering device and are for R-410A refrigerant ONLY.
Factory approved electric heater packages are available in
sizes 3kW through 30kW. See Product Specification
literature for available accessory kits.
LOCATION
Select the best position which suits the installation site
conditions. The location should provide adequate structural
support, space in the front of the unit for service access,
clearance for return air and supply duct connections, space
for refrigerant piping connections and condensate drain line
connections. If heaters are being installed make sure
adequate clearance is maintained from supply duct work.
See Clearances in Figure 1.
If the unit is located in an area of high humidity, nuisance
sweating of casing may occur. On these installations a wrap of
2" (51mm) fiberglass insulation with a vapor barrier is
recommended.
NOTE: Internal filter can be accessed from separate filter
door. If the filter can NOT be easily accessed, a remote filter
is recommended. Refer to ACCA Manual D for remote filter
sizing.
FIRE HAZARD
Failure to maintain proper clearances could result in per-
sonal injury, death, and/or property damage.
When heaters are installed, maintain clearances from
combustible materials as specified on unit rating plate.
Do not use plastic lined or combustible flexible ducting
within 36 inches (lm) of the supply end of the fan coil.
2 496 01 5402 02
1 / ClearancesandUnitDimensions
Figure
OPENING)
J
H
O\
L N_/J (SERVICE ACCESS)
( OPENI 38-11-82
iiii_i_i_iiii_`_i_`iiiiiiiiiiiiiiiiiiiiiiiiiiiii_`_ii__i_i_i!_i_jji!_i_i_i_i!_ii_101
No All Sides 0
Heaters From Supply Duct 0
All Sides 0
With From First 3 feet of Supply Duct to Combustibles 1
Heaters From Supply Duct to Combustibles after 3 feet 0
Model A B C D E F G H
1800 12-7/16 11 19-13/16 12-5/16 22-1/16 14-5/16 21 42-11/16
2400 15-3/4 11 19-13/16 15-5/8 22-1/16 17-5/8 21 47-5/8
3000 15-3/4 11 19-13/16 15-5/8 22-1/16 17-5/8 21 49-5/8
3500 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 53-7/16
3600 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 49-5/8
4200 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 49-5/8
4800 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 53-7/16
6000 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 53-7/16
Model A B C o I E F GI H
6000 22-3/4 11 19-13/16 22-11/16 I 22-1/8 24-11/16 24 59-3/16
m.... :
Model A B C D E F G H
1800 15-3/4 11 19-13/16 15-5/8 22-1/16 17-5/8 21 49-5/8
2400 15-3/4 11 19-13/16 15-5/8 22-1/16 17-5/8 21 49-5/8
3000 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 53-7/16
3600 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 49-5/8
4200 19-1/4 11 19-13/16 19-1/8 22-1/16 21-1/8 21 49-5/8
4800 22-3/4 11 19-13/16 22-11/16 22-1/16 24-11/16 24 53-7/16
6000 22-3/4 11 19-13/16 22-11/16 22-1/16 24-11/16 24 59-3/16
Model A B C D E F G H
1800 316 279 503 313 560 364 533 1084
2400 400 279 503 397 560 448 533 1210
3000 400 279 503 397 560 448 533 1261
3500 489 279 503 486 560 537 533 1357
3600 489 279 503 486 560 537 533 1261
4200 489 279 503 486 560 537 533 1261
4800 489 279 503 486 560 537 610 1357
6000 489 279 503 489 560 537 533 1357
....
6000 578 279 503 576 562 627
i iiliiliiliiliiiii........ :!!!!!!!:!!!!!!!!!!!!!!!!!
Model A B C D E F G H
1800 400 279 503 397 560 448 533 1261
2400 400 279 503 397 560 448 533 1261
3000 489 279 503 486 560 537 533 1357
3600 489 279 503 486 560 537 533 1261
4200 489 279 503 486 560 537 533 1261
4800 578 279 503 576 560 627 610 1357
6000 578 279 503 576 560 627 610 1503
496 01 5402 02 3
HEATER PACKAG ES
Factory approved, field installed, UL listed heater packages not factory approved could cause damage which would not
are available from the equipment supplier. See unit rating be covered under the equipment warranty.
plate for a list of factory approved heaters. Heaters that are
POSITION UNIT
Unit can stand or lie on floor, or hang from ceiling or wall.
Allow space for wiring, piping, and servicing unit.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property
damage
Afield fabricated auxiliary drain pan, with a separate
drain is REQUIRED for all installations over a fin-
ished living space or in any area that may be damaged
by overflow from a restricted main drain pan. In some
localities, local codes require an auxiliary drain pan
for ANY horizontal installation.
A. UPFLOW INSTALLATION
If return air is to be ducted through a floor, set unit on floor
over opening and use 1/8 to 1/4 inch thick (3 to 6 mm thick)
fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening
per dimensions shown in Figure 2. A field-supplied bottom
closure is required.
Figure 2 1
POWER
OPTIONS
Upflow Installation
SUPPLIED
SUPPLY DUCT
FRONT SERVICE CLEARANCE
60 model = 24" (610 mm)
UPFLOW/_
U:;_W _DARY DRA'NI_/DOWNFLOW__L_ _
PRIMA_
UPFLOW/DOWN FLOW
SECONDARY DRAIN _1
/
UPFLOW/DOWN FLOW _"
PRIMARY DRAIN
VO LT
ENTRY
OPTIONS
I
I
I
I
/
(483mm)
II FIELD MODIFIED
II A SIDERETURN
!1 2-1/2" I LOCATIONFOR
SLOPE COIL
i_ UNITS ONLY
_ FIELD SUPPLIED
RETURN PLENUM
SLOPE COIL UNITS
FEM4X
MODEL SIZE
18
24
30
35
A
12" (305mm)
17" (432mm)
17" (432mm)
19" (483mm)
SLOPE COIL UNITS
FXM4X
MODEL SIZE A
18 17" (432mm)
24 17" (432mm)
30 19" (483mm)
4 496 01 5402 02
B.DOWNFLOWINSTALLATION
PRODUCTORPROPERTYDAMAGEHAZARD
Failureto followthis cautionmayresultin productor
propertydamage
Theconversionof thefan coil to downflow requires
special procedures for the condensate drains on both
A-coil and Slope-coil units. The vertical drains have
an overflow hole between the primary and secondary
drain holes. This hole is plugged for all applications
except downflow, and must be used for downflow.
Failure to follow instructions could result in personal
injury or product and property damage.
In this application, field conversion of the evaporator coil is
required using accessory Downflow Kit along with an
accessory Base Kit. Set unit on floor over opening and use
1/8"to 1/4"thick fireproof resilient gasket between duct, unit,
and floor. Refer to installation instructions packaged with
accessory kit. See Product Specification literature for kit part
numbers.
During the conversion process, removed the plastic cap
covering the vertical drains only and discard.
Remove the plug from the overflow hole and discard.
At completion of the downflow installation, caulk around the
vertical pan fitting to door joint to retain low air leak
performance of the unit.
NOTE: Gasket kit number (EBAC01GSK) is also required for
all downflow applications to maintain low air leak/low sweat
performance.
C. HORIZONTAL INSTALLATION
Unit must NOT be installed with access panels facing up or
down. Access panels must only face to the side.
FEM4X, FSM4X, and FXM4X models are factory built for
horizontal left installation (refer to Figure 3 and Figure 4).
They can be field converted to horizontal right (accessory
Gasket Kit required, see Product Specification literature for
part number). Refer to Figure 5 and Figure 6.
FSU4X models require accessory kits for any horizontal
installation (see Product Specification literature for required
accessory kits).
NOTE: When suspending unit from ceiling, dimples in casing
indicate suitable location of screws for mounting metal
support straps.
NOTE: For optimum condensate drainage performance in
horizontal installations, unit should be leveled along its length
and width.
Figure 3 Horizontal Left Application (Slope Coil) (FXM4X factory configuration)
A-COIL
HORIZONTAL LEFT
FIELD
SUPPLIED
HANGING
STRAPS SECONDARY PRIMARY
DRAIN DRAIN
LOW VOLT
ENTRY
OPTIONS
POWER
ENTRY
OPTIONS
SECONDARY
DRAIN
PRIMARY
DRAIN
FRONT SERVICE CLEARANCE
(FULL FACE OF UNIT)
18 - 48 models = 21" (533mm)
60 model = 24" (610mm)
1-3/4"(45!_m)
FILTER ACCESS
CLEARANCE
/
496 01 5402 02 5
Figure4 J HorizontalLeftApplication(A-Coil)(FEM4X,FSM4X,and FXM4Xfactoryconfiguration)
FACTORY SHIPPED
HORIZONTAL LEFT
APPLICATION
COIL
COIL
SUPPORT
RAI L
DRAIN PAN
SUPPORT
BRACKET
COIL
HORIZONTAL
DRAIN PAN
AIR SEAL
ASSEMBLY
REFRIGERANT
CONNECTIONS
PRIMARY DRAIN
HORIZONTAL LEFT
SECONDARY DRAIN
HORIZONTALLEFT
Horizontal Right Conversion of Units With Slope Coils
1. Remove blower and coil access panel and fitting panel
(refer to Figure 5).
2. Remove coil mounting screw securing coil assembly
to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil assembly
with condensate pan down (refer to Figure 5).
5.
6.
Attach coil to casing flange using coil mounting screw
previously removed.
Align holes with tubing connections and condensate
pan connections, and reinstall access panels and
fitting panel. After brazing, make sure liquid and
suction tube grommets are in place to prevent air
leaks and cabinet sweating.
Figure 5 JHorizontal Right Conversion Applications (Slope Coil) (FXM4X)
COIL MOUNTING BLOWER
ASSEMBLY
COIL SUPPORT RAIL
SLOPE
REFRIGERANT
CONNECTIONS
SECONDARY DRAIN
6 496 01 5402 02
HorizontalRightConversionof UnitsWithA-Coils
1. Remove blower and coil access panel and fitting panel
(refer to Figure 6).
2. Remove coil mounting screw securing coil assembly
to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil unit on its right side and reinstall coil
assembly with condensate pan down (refer to
Figure 6).
5. Remove horizontal drain pan support bracket from coil
support rail on left side of unit and reinstall on coil
support rail on right side of unit.
6. Convert air-seal assembly for horizontal right (refer to
Figure 6).
a. Remove air-seal assembly from coil by removing 4
screws.
b. Remove coil drip flanges from A-coil and reinstall on
right side of coil (same side as horizontal drain pan).
c. Remove filler plate (A) and install air splitter (B) in
place of filler plate.
d.
e.
f.
7.
8.
Install filler plate (A) as shown in horizontal right
application.
Remove condensate troughs (C) and install on
opposite tube sheets.
Install hose onto plastic spout.
Install horizontal pan on right side of coil assembly.
Slide coil assembly into casing. Be sure coil bracket on
each corner of vertical pan engages coil support rails.
9. Reinstall 2 snap-in clips to correctly position and
secure coil assembly in unit. Be sure clip with large
offsets is used on right side of unit to secure horizontal
pan.
10. Remove 2 oval coil access panel plugs and reinstall
into holes on left side of coil access panel and fitting
panel.
11. Remove insulation knockouts on right side of coil
access panel
12. Reinstall access fitting panels, aligning holes with
tubing connections and condensate pan connections.
Be sure to reinstall metal clip between fitting panel and
vertical condensate pan.
13. After brazing, make sure liquid and suction tube
grommets are in place to prevent air leaks and cabinet
sweating.
Figure 6 Horizontal Right Conversion Applications (A-Coil)
SUPPORT
RAI L
CONNECTIONS ASSEMBLY HORIZONTAL
RIGHT
APPLICATION
BRACKET
DRAIN
SUPPORT
BRACKET
COIL_
SUPPORT "
RAI L
BRACKET
HORIZONTAL
DRAIN PAN
HORIZONTAL RIGHT
SECONDARY DRAIN
HORIZONTAL RIGHT
496 01 5402 02 7
D. MANUFACTUREDHOUSINGAND MOBILEHOME
APPLICATIONS
.
2.
3.
Fan coil unit must be secured to the structure using
field-supplied hardware.
Allow a minimum of 24 inches (610mm) clearance
from access panels.
Recommended method of securing for typical
applications:
a. If fan coil is away from wall, attach pipe strap to top
of fan coil using No. 10 self tapping screws. Angle
strap down and away from back of fan coil, remove
all slack, and fasten to wall stud of structure using
5/16" lag screws. Typical both sides of fan coil.
b. If fan coil is against wall, secure fan coil to wall stud
using 1/8" (3mm) wide right-angle brackets. Attach
brackets to fan coil using No. 10 self tapping screws
and to wall stud using 5/16" lag screws (refer to
Figure 7).
Mobile Home or Manufactured Hous-
Figure 7 ing Applications
4" (102mm) MAX
SECURE FAN COIL TO STRUCTURE
UNIT AWAY FROM WALL
PIPE STRAP
_°1 (TYPICAL BOTH SIDES)
!_ UNIT AGAINST WALL
1/8" (3mm) INCH THICK ANGLE
MOUNTING BRACKET
(TYPICAL BOTH SIDES)
.----....__.._
1////7 DOWN FLOW
BASE KIT
_J_ SECURE UNIT TO FLOOR
p/ ANGLE BRACKET OR PIPE STRAP
4" (102mm) MAX
NOTE: Modular units can be disassembled and
components moved separately to installation area
for reassembly. This process accommodates small
scuttle holes and limiting entrances to installation
sites (refer to Figure 8).
Removal of Brackets on
Figure 8 Modular Units
BLOWER BOX
--4 c
BRACKET _ °
2 SCREWS
COIL BOX
8 496 01 5402 02
AIR DUCTS
Connect supply-air duct over the outside of 3/4" flanges
provided on supply-air opening. Secure duct to flange using
proper fasteners for type of duct used, and seal duct-to-unit
joint.
Use flexible connectors between duct work and unit to
prevent transmission of vibration. When electric heater is
installed, use heat-resistant material for flexible connector
between duct work and unit at discharge connection. Duct
work passing through unconditioned space must be
insulated and covered with vapor barrier.
ELECTRICAL CONNECTIONS
Duct work Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and
10 feet of main duct before first branch takeoff may require
internal acoustical insulation lining. As an alternative, fibrous
duct work may be used if constructed and installed in
accordance with the latest edition of SMACNA construction
standard on fibrous glass ducts. Both acoustical lining and
fibrous duct work shall comply with National Fire Protection
Association as tested by UL Standard 181 for Class 1 air
ducts.
FEM4X (1-1/2 to 4 ton), FSM4X and FSU4X Fan Coil
models utilize an electronic fan board which has a low voltage
circuit protective fuse (5 amp), fan motor speed tap terminal
(SPT), and time-delay relay (TDR). To disable the TDR
feature, snip the jumper wire JWl (refer to Figure 9).
Make all electrical connections in accordance with the NEC
and any local codes or ordinances that may apply. Use
copper wire only. The unit must have a separate branch
electric circuit with a field-supplied disconnect switch located
within sight from and readily accessible from the unit.
FEM4X (5ton) and FXM4X Fan Coil models have a low voltage
circuit protective fuse (3 amp) inline on the wire harness. Speed
selections are made at the fan motor by selecting taps 1,2, or 3
with the Blue wire. The motor is pre-programmed with the
time-delay circuit on some of the speed taps. (See Section D)
NOTE: When a pull-out type disconnect is removed from the
unit, only the Load side of the circuit is de-energized. The
Line side remains live until the main (remote) disconnect is
turned off.
Before proceeding with electrical connections, make certain
that supply voltage, frequency, phase, and circuit ampacity are
as specified on the unit rating plate. See unit wiring label for
proper field high and low voltage wiring.
ELECTRICAL SHOCK or UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or unit damage.
If a disconnect switch is to be mounted on unit, select
a location where drill and fasteners will not contact
electrical or refrigeration components.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Turn off the main (remote) disconnect device before
working on incoming (field) wiring.
Incoming (field) wires on the line side of the discon-
nect found in the fan coil unit remain live, even when
the pull-out is removed. Service and maintenance to
incoming (field) wiring cannot be performed until the
main disconnect switch (remote to the unit) is turned
off.
Figure 9 1
FSM4X, FSU4X
II
Fan Coil Printed Circuit Board
RiO
HK61EA010
:_ i) T C (} N
®
496 01 5402 02 9
A. LINE VOLTAGE CONNECTIONS
Fan Coils installed without electric heat require the use of a
factory-authorized Power Plug Kit (accessory part number
EBAC01PLG). This kit provides the electrical connections
necessary to supply the unit with 208/230V power when
electric heat is not present. For units without electric heat:
1. Connect 208/230V power leads from field disconnect
to yellow and black stripped leads on Power Plug
(accessory part number EBAC01PLG).
2. Connect ground wire to unit ground lug.
3. When installing an electric heater, remove and discard
power plug (if equipped) from fan coil and connect
male plug from heater to female plug from unit wiring
harness. (See Electric Heater Installation
Instructions.)
B. 24V CONTROL SYSTEM
Connection to Unit
Wire low voltage in accordance with wiring label on the
blower (also refer to Figure 10 through Figure 14). Use 18
AWG color-coded, insulated (35°C minimum) wire to make
the low-voltage connections between the thermostat, the
unit, and the outdoor equipment. If the thermostat is located
more than 100 feet from the unit (as measured along the low
voltage wire), use 16 AWG color-coded, insulated (35°C
minimum) wire. All wiring must be NEC Class 1 and must be
separated from incoming power leads. Refer to outdoor unit
wiring instructions for additional wiring recommendations.
Heater Staging
The controls are factory circuited for single-stage operation
(refer to Figure 11 and Figure 12). When 2 stages are
desired, cut W3 at the W2 wire nut, strip, and reconnect
according to the thermostat kit instruction (refer to Figure 13
- outdoor thermostat optional). When 3 stages are desired,
cut the W2 wire nut off and discard. Strip W2, W3, and E, and
reconnect according to the thermostat kit instructions (refer
to Figure 14 outdoor thermostats optional).
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper
product operation.
If W2, W3, and E on any 3 stage heater (18, 20, 24, or
30kW) are individually connected - as with outdoor
thermostats or any other situation - emergency heat
relay must be used. If relay is not used, blower may
not operate when heaters are energized.
10 496 01 5402 02
/
10 | Wiring Layout -Air Conditioning
Figure IUnit (Cooling Only)
THERMOSTAT
@-
@-
(9-
RED
GRY
WHT
BLU
VlO
BRN
FANCOIL
WIRING
AIR COND.
J Wiring Layout -Air Conditioning
Figure 11 Unit (Cooling and 1-Stage Heat)
THERMOSTAT
@-
@-
FANCOIL
WIRING
RED
GRY
WHT
BLU
VIO
BRN
AIR COND.
Figure 12 Wiring Layout -Heat Pump Unit
(Cooling and 1-Stage Heat with No
Outdoor Thermostat)
THERMOSTAT FANCOIL HEAT PUMP
WIRING (CONTROL)
RED ; . ,
GRY /
BRN !
_ WriT /
BLU .
Vl°l'
Figure 13 Wiring Layout -Heat Pump Unit
(Cooling and 2-Stage Heat with
One Outdoor Thermostat)
THERMOSTAT
1:
RED
GRY
BRN
WHT
BLU
VlO
FANCOIL HEAT PUMP
WIRING (CONTROL)
Wiring Layout -Heat Pump Unit
Figure 14 (Cooling and 2-Stage Heat with
Two Outdoor Thermostats)
THERMOSTAT
RED
GRY
BRN
WHT
BLU
VlO
FANCOIL HEAT PUMP
WIRING (CONTROL)
496 01 5402 02 11
TransformerInformation
Transformer is factory wired for 230V operation. For 208V
applications, disconnect the black wire from the 230V terminal
on transformer and connect it to the 208V terminal (refer to
Figure 15).
Figure 15 JTransformer Connections
BROWN
RED
YELLOW
BLACK
C. GROUND CONNECTIONS
PRIMARY
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken
ground could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes,
the cabinet must have an uninterrupted or unbroken
ground in order to minimize potential for personal in-
jury or death if an electrical fault should occur. The
ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical
codes. If conduit connection uses reducing washers,
a separate ground wire must be used.
FEM4X (5 ton) and FXM4X models: fan speed is selected
at the motor connector. Units with or without electric heaters
require a minimum CFM. Refer to the unit wiring label to
ensure that the fan speed selected is not lower than the
minimum fan speed indicated.
Tap 1 Low 90 sec off delay
Tap 2 Medium 90 sec off delay
Tap 3 High 90 sec off delay
Tap 4 Electric Heat t 0 sec off delay
Tap 5 Max $ 0 sec off delay
t Electric heat airflow is same CFM as Tap 3, but with 0
sec off delay.
For high static applications, see Airflow Performance
Tables for max airflow.
To change motor speeds disconnect the BLUE fan lead from
motor connector terminal #2 (factory default position) and
move to desired speed-tap; 1,2, 3, or 5.
Speed-taps 1, 2, and 3 have a 90 second blower off time
delay pre-programmed into the motor. Speed tap 4 is used
for electric heat only (with 0 second blower time delay) and
the WHITE wire should remain on tap 4. Speed-tap 5 is used
for high static applications, but has a 0 second blower time
delay pre-programmed into the motor (see Airflow
Performance Tables for actual CFM for each tap). Also, see
Figure 16 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap should
be used to reduce possibility of water being blown off coil.
NOTE: Use UL listed conduit and conduit connectors for
connecting supply wire(s) to unit to obtain proper grounding.
Grounding may also be accomplished by using grounding lugs
provided in control box.
D. MINIMUM CFM AND MOTOR SPEED SELECTION
Units with or without electric heaters require a minimum CFM.
Refer to the unit wiring label to ensure that the fan speed
selected is not lower than the minimum fan speed indicated.
FEM4X models (1-1/2 to 4 ton): fan speed selection is done at
the fan motor. To change motor speeds, reposition wire at fan
motor speed terminals labeled 1-2-3 (refer to Figure 16).
FSM4X and FSU4X models: fan speed selection is done at
the fan relay on the electronic fan board. To change motor
speeds, disconnect fan lead used on relay terminal (SPT) and
replace with motor speed lead desired (refer to Figure 17).
Save insulating cap and place on motor lead removed from
relay.
NOTE: In low static applications, lower motor speed tap should
be used to reduce possibility of water being blown off coil.
All units have 2 or 3 motor speed taps. Low speed (red or 1) is
designed for mismatch outdoor unit applications. Medium
speed (blue or 2) is designed for straight matched
operations. High speed (black or 3) is used with high external
static duct situations on straight matched systems.
12 496 01 5402 02
/
16 | FEM4X and FXM4X Motor Speed
Figure ISelection
L11S018
Figure 17 FSM4X, FSU4X Fan Coil Relay and
Speed Tap Terminal
SPEED TAP _
I
COMMON YELLOW
/J_'_--FAN DECK
496 01 5402 02 13
REFRIGERANT TUBING
Size and install refrigerant lines according to information
provided with outdoor unit. Route refrigerant lines to the fan
coil in a manner that will not obstruct service access to the
unit or removal of the filter.
1. Find the liquid tube grommet in the small-parts bag
and slide it onto the liquid refrigerant line (field
line-set).
2. Remove the lower door. Remove the tubing plate (with
suction tube grommet) and slide the plate with
grommet onto the refrigerant lines (field line-set), away
from braze joints.
3. Remove rubber plugs from coil stubs using a pulling
and twisting motion. Hold coil stubs steady to avoid
bending or distorting.
4. Wrap TXV and nearby tubing with a heat-sinking
material such as a wet cloth.
REFRIGERANT METERING DEVICE
5. Fit refrigerant lines into coil stubs. Wrap a heat sinking
material such as a wet cloth behind braze joints.
6. Braze using a SiI-Fos or Phos-copper alloy.
7. After brazing, allow joints to cool. Slide tubing plate
back into place and position grommets around suction
and liquid tubes to ensure air seal.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage.
Braze with SiI-Fos or Phos-copper alloy on copper-
to-copper joints and wrap a wet cloth around rear of
fitting to prevent damage to TXV.
FEM4X, FSM4X, FSU4X, FXM4X
These Fan Coils have a factory installed hard shut-off TXV
designed only for use with R-410A refrigerant. Use only with
outdoor units designed for R-410A.
TXV is factory set and not field adjustable.
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage.
This Fan Coil has a hard shut-off TXV metering de-
vice. A compressor Hard Start Kit is REQUIRED in all
applications where the matching outdoor unit has a
single-phase reciprocating compressor.
14 496 01 5402 02
CONDENSATE DRAINS
Unit is provided with primary and secondary 3/4" (19mm)
NPT drain connections. Refer to Figures 2, 3, 4, 5, and 6 to
identify the primary and secondary locations. To prevent
property damage and achieve optimum drainage
performance, BOTH primary and secondary drain lines
should be installed and include properly sized condensate
traps (refer to Figure 18). Factory approved condensate
traps are available (accessory part number EBAC01CTK).
To connect drainlines, the drain connection knock-outs must
be removed. Use a knife to start the opening near the tab and
using pliers, pull the tab to remove the knock-out. Clean the
edge of the opening if necessary. After drain fittings are
installed, caulk the seam between the fitting and the cover to
retain the low leak rating of the unit.
It is recommended the PVC fittings be used on the plastic
condensate pan. Do not over-tighten. Finger-tighten plus
1-1/2 turns. Use pipe dope, to ensure proper seal.
Install traps in the condensate lines as close to the coil as
possible (refer to Figure 20), but avoid blocking filter access
panel.
Install drain lines below the bottom of the drain pan and pitch
the drain lines down from the coil at least ¼inch per foot of
run (6mm per 0.3m). Horizontal runs over 15 feet (5m) long
must also have an anti-siphon air vents (stand pipes),
installed ahead of the horizontal runs. Extremely long
horizontal runs may require oversized drain lines to eliminate
air trapping.
Route primary drain line to the outside or to a floor drain.
Check local codes before connecting to a waste (sewer) line.
Route the secondary drain line to a place in compliance with
local installation codes where it will be noticed when unit is
operational. Condensate flowing from secondary (overflow)
drain indicates a plugged primary drain - unit requires
service or water damage will occur.
Prime all traps, test for leaks, and insulate drain lines where
sweating could cause water damage. Consult local codes for
additional requirements or precautions.
If a gravity drain cannot be used, install a condensate pump.
Install the pump as close to the indoor section as possible.
PRODUCTorPROPERTYDAMAGE HAZARD
Failure to follow this caution may result in product or
property damage.
Use only full size P-traps in the condensate line (refer
to Figure 18). Shallow, running traps are inadequate
and DO NOT allow proper condensate drainage (refer
to Figure 19).
Figure 18 1 Recommended Condensate Trap
2 MIN (51mm)
m)
Figure 19 1 Insufficient Condensate Trap
DO NOT USE SHALLOW RUNNING TRAPS!
Figure 20 1 Condensate Drain
! o
¢q
oo o
UIRED
(USE FACTORY KIT OR
_xxFIELD-SU PPLIED TRAP)
PRIMARY TRAP REQUIRED (USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF PROPER DEPTH.
STANDARD P-TRAPS ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)
496 01 5402 02 15
ACCESSORIES
A. ELECTRONIC AIR CLEANER
The Electronic Air Cleaner may be connected to FSM4X and
FSU4X fan coils as shown in Figure 21. This method
requires a field supplied transformer. See Electronic Air
Cleaner literature for kit requirements.
Figure 21 Wiring Layout of Electronic Air
Cleaner to Fan Coil (FSM4X &
FSU4X)
CONTROL BOARD
/
/ R G C C CFAN RELAY
!
230vAoNONq I I I I I
"
.o.c /\
/ 208/230V COM /\
I_ 24MAC f }COM
CONVERSIONKITII , , , II I I/ ,,II
TOTRANSFORMER_1 I _-
BLOWER I_1 I I ¢-'_ I
MOTOR '1 I' I '1 I'
I'TO EACh' _ ; 208/230V
FROM MOLEX
PLUG AND
TRANSFORMER
(IN UNIT)
Figure 22 Wiring Layout of Humidifier to Heat
Pump
THERMOSTAT
D-
D-
Fq
D
Pq
FAN COIL
(CONTROL)
I
I
R
G
C
w2
IVV_y__ w3
/WO,E ,
IL_ I ]
FANH'IuMID,F_ I_-- RELAY I
, I I _ i I
-_--_ I--N III Lh _-t Ii
I
• b IHuMIDISTAT
HEAT PUMP
(CONTROL)
R
C
W2
o
Y
B. HUMIDIFIER
Connect humidifier and humidistat to fan coil unit as shown in
Figure 22 and Figure 23.
Figure 23 Wiring Layout of Humidifier to Fan
Coil with Electric Heat
FAN COIL
THERMOSTAT (CONTROL)
_ RED R
I l vlo
I E
IB_IN
I
I i
I I '
I
;
[--q
115V
C AIR COND.
Ca__c
I HUMIDISTAT
I
[11 -O
-O
16 496 01 5402 02
SEQUENCE OF OPERATIONS
A. CONTINUOUS FAN
Thermostat closes R to G. G energizes fan relay on
electronic fan board which completes circuit to indoor blower
motor. When G is de-energized, there is a 90 second off
delay before relay opens.
B. COOLING MODE
Thermostat energizes R to G, R to Y, and R to O (heat pump
only). G energizes fan relay on electronic fan board which
completes circuit to indoor blower motor. When G is
de-energized, there is a 90 second off delay before fan relay
opens.
C. HEAT PUMP HEATING MODE
Thermostat energizes R to G and R to Y. G energizes fan
relay on electronic fan board which completes circuit to
indoor blower motor. When G is de-energized, there is a 90
second off delay before fan relay opens.
D. HEAT PUMP HEATING WITH AUXILIARY
ELECTRIC HEAT
Thermostat energizes R to G, R to Y, and R to W. G
energizes fan relay on PCB which completes circuit to indoor
blower motor. W energizes electric heat relay(s) which
completes circuit to heater element(s). When W is
de-energized, electric heat relay(s) open, turning off heater
elements. When G is de-energized there is a 90 second off
delay before fan relay opens.
E. ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat relay(s)
which completes circuit to heater element(s). Blower motor
is energized through normally closed contacts on fan relay.
When W is de-energized, electric heat relay(s) opens.
START-UP PROCEDURE
Refer to outdoor unit Installation Instructions for system
start-up instructions and refrigerant charging method
details.
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified
service technician. Consult the servicing dealer for
recommended frequency.
Between visits, the only consumer service recommended or
required is air filter maintenance and condensate drain
operation.
Air Filter
Inspect air filters at least monthly and replace or clean as
required. Disposable type filters should be replaced.
Reusable type filters may be cleaned by soaking in mild
detergent and rinsing with cold water. Install filters with the
arrows on the side pointing in the direction of air flow.
Condensate Drain
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit
performance and/or product damage.
Never operate unit without a filter. Factory authorized
filter kits must be used when locating the filter inside
the unit. For those applications where access to an
internal filter is impractical, a field-supplied filter
must be installed in the return duct system.
During the cooling season check at least monthly for free flow
of drainage and clean if necessary.
496 01 5402 02 17
AIRFLOW PERFORMANCE TABLES
Model
FEM4X18OO
FEM4X2400
FEM4X3000
FEM4X3500
FEM4X3600
FEM4X4200
FEM4X4800
Blower Speed
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
Measured Static Pressure, inlet to outlet
0.10 0.20 I 0.30 I
ii ii ! !ili!
614 ....
823
633
1130
1033
84O
659 619
572 530
905 868
786 747
583 533
1097 1063
1000 965
802 760
1282 1238 1192
1168 1118 1067
1327
1192
iiiillliiiiil,!,iiiiiii,_ii_i_,i_iii_i,ii,!,i_iilDi....
1479
1303
1805
1652
1458
1282 1236
1151 1100
1578 1533
1437 1392
1258 1211
1772 1739
1617 1581
1418 1377
(inches water
0.40
666
578
486
83O
7O7
482
1028
928
713
1308
1142
1014
1344
1187
1039
1480
1344
1161
1704
1543
1335
column)
0.50
619
538
441
792
665
431
992
888
663
1257
1090
959
1293
1135
970
1420
1293
1108
1669
1504
1292
0.60
566
499
396
753
622
378
955
846
609
1204
1036
903
1240
1081
890
1353
1240
1054
1632
1463
1248
i iiii iiii! !i !!!!!!!!!!!!!!!!!!!!!!!!!....
Measured Static Pressure, inletto outlet(inches watercolumn)
Model Blower Speed 0.10 0.20 0.30 0.40 0.50 0.60
Tap 5 1897 1867 1836 1808 1774 1736
Tap 4 1817 1785 1757 1724 1693 1655
FEM4X6000 Tap 3 1817 1785 1757 1724 1693 1655
Tap 2 1657 1621 1589 1557 1518 1474
Tap 1 1443 1412 1377 1332 1286 1243
!ii !!!!!!! ....
Measured Static Pressure, inlet to outlet (inches water column)
Model Blower Speed 0.10 0.20 0.30 0.40 0.50 0.60
FSM4X6000 High _28 : . 1965 1875 1778 1674
Medium 1959 1898 1829 1750 1663 1566
FSU4X6000 Low 1748 1709 1659 1598 1525 1442
18 496 01 5402 02
Model
FXM4X1800
FXM4X2400
FXM4X3000
FXM4X3600
FXM4X4200
FXM4X4800
FXM4X6000
NOTES:
Blower Speed
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Tap 5
Tap 4
Tap 3
Tap 2
Tap 1
Measured Static Pressure, inlet to outlet
0.10 I 0.20 I 0.30
683 644
683 644
631 563
625 524
!!!!!!i!:
825 795
825 795
726 695
631 563
1041
1041
924
779
1237
1237
1095
1014
1519
1437
1437
1257
1237
1757
1664
1664
1459
1301
2030
1811
1811
1665
1462
998
998
876
693
1332
1206
1206
1058
885
1490
1403
1403
1226
1206
1725
1626
1626
1420
1241
1995
1775
1775
1632
1418
589
589
5OO
457
891
757
757
635
5OO
1104
944
944
817
628
1294
1160
1160
1007
773
1454
1366
1366
1191
1160
1693
1593
1593
1379
1195
1961
1740
1740
1593
1371
(inches water
0.40
66O
548
548
443
417
851
722
722
598
443
1050
886
886
752
571
1253
1121
1121
951
673
1419
1333
1333
1141
1121
1653
1552
1552
1336
1150
1927
1703
1703
1556
1327
column)
0.50
609
494
494
409
367
816
674
674
543
409
1003
837
837
7O4
526
1207
1070
1070
888
609
1379
1294
1294
1090
1070
1614
1517
1517
1298
1102
1888
1664
1664
1507
1278
0.60
572
461
461
361
319
78O
634
634
5O9
361
959
772
772
660
476
1157
1013
1013
824
549
1332
1245
1245
1033
1013
1576
1477
1477
1259
1039
1842
1613
1613
1453
1228
1. Airflow based upon dry coil at 230v with factory approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes 4200 through
6000).
2. Airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a constant torque motor. The torque doesn't drop off at the speeds the
motor operates.
3. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal
applications of 4200 - 6000 sizes must have supply static greater than 0.20 in. wc.
4. Airflow above 400 cfm/ton on 4800 - 6000 size could result in condensate blowing off coil or splashing out of drain pan.
5. Not recommended for use above 0.60 inches water column external static pressure.
6. Shading - Airflow outside 450 cfm/ton.
496 01 5402 02 19
CFM
FEM4X 400 600 800 1000 1200 1400 1600 1800 2000
1800 0.020 0.044 0.075 ......
2400 -- 0.044 0.075 0.110 .....
3000 -- -- 0.048 0.072 0.100 ....
3500 -- -- -- 0.072 0.100 0.130 -- -- --
3600
4200 .... 0.070 0.092 0.120 -- --
4800 ..... 0.092 0.120 0.152 --
6000 ...... 0.086 0.105 0.130
Airflow performance chart was developed using fan coils with DRY coils.
When taking a static reading across a WET coil, adjust the static pressure numbers by adding the values in this table (for a given
CFM, wet coil will have greater static pressure drop than dry coil).
CFM
FEM4X 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
1800 0.034 0.049 0.063 .............
2400 0.016 0.027 0.038 0.049 0.059 ...........
3000 -- -- -- 0.049 0.059 0.070 0.080 .........
3500 ..... 0.055 0.064 0.073 0.081 .......
3600 ..... 0.034 0.042 0.049 0.056 .......
4200 ....... 0.049 0.056 0.063 0.070 .....
4800 ......... 0.038 0.043 0.049 0.054 0.059 -- --
6000 ........... 0.049 0.054 0.059 0.065 0.070
! !!! ....
FSM4X CFM
FSU4X 400 600 800 I 1000 1200 I 1400 1600 1800 2000
m m
6000 ...... 0.120 0.152 0.187
Airflow performance chart was developed using fan coils with DRY coils.
When taking a static reading across a WET coil, adjust the static pressure numbers by adding the values in this table (for a given CFM, wet
coil will have greater static pressure drop than dry coil).
FSM4X CFM
so4x 16oo17oo18ooiooo1 ooo1 oo1 oo1 3oo1 4oo1 oo1 6oo1 7oo1 8oo1 ooo1 ooo
6000 ........... 0.027 0.031 0.035 0.039 0.043
20 496 01 5402 02
CFM
FXM4X I I
_oo 6oo I 8oo _oooI _oo _oo _6oo _8oo _ooo
1800 0.020 0.044 0.075 ......
2400 -- 0.022 0.048 0.072 0.100 ....
3000 -- 0.022 0.048 0.072 0.100 ....
3600 -- -- -- 0.051 0.070 0.092 0.120 0.152 --
4200 -- -- -- 0.051 0.070 0.092 0.120 0.152 --
4800 -- -- -- 0.051 0.070 0.092 0.120 0.152 --
6000 ...... 0.086 0.105 0.130
Airflowperformancechartwas developedusingfan coilswith DRY coils.
When takinga staticreadingacrossa WET coil,adjustthe staticpressurenumbersby adding the valuesinthis table (fora given CFM,wet
coil will have greaterstaticpressuredropthan dry coil).
CFM
FXM4X I I I I
500160017001800900,000,,00,200,300,400,500,600,700,800,90012000
1800 0.034 0.049 0.063 .............
2400 0.016 0.027 0.038 0.049 0.059 ...........
3000 -- -- -- 0.049 0.059 0.070 0.080 .........
3600 ..... 0.055 0.064 0.073 0.081 .......
4200 ....... 0.049 0.056 0.063 0.070 .....
4800 ......... 0.038 0.043 0.049 0.054 0.059 -- --
6000 ........... 0.027 0.031 0.035 0.039 0.043
Airflow performance chart was developed using fan coils with 10 kW electric heater (2 elements) in the 1800 - 3600 model
sizes, and 15 kW electric heaters (3 elements) in the 4200 - 6000 model sizes.
When using a different number of heater elements, adjust the static pressure numbers by adding or subtracting the values
in this table (for a given CFM, more electric heater elements create higher static pressure drop).
FEM4X
FSM4X
FSU4X
FXM4X
1800
2400
3000
3500
3600
4200
4800
6000
Heater kW
No Heater 5 8 or 10 9 or 15 I20
i
Number of Heat Elements
0
+0.02
+0.02
+0.02
+0.02
+0.02
+0.04
+0.04
+0.04
1
+0.01
+0.01
+0.01
+0.01
+0.01
2
0
0
0
0
0
+0.02
+0.02
+0.02
3
-0.02
-0.02
-0.02
-0.02
-0.02
0
0
0
4
-0.04
-0.04
-0.04
-0.04
-0.04
-0.02
-0.02
-0.02
I8, 24, or
1 30
6
-0.10
-0.10
-0.10
496 01 5402 02 21
R-410A QUICK REFERENCE GUIDE
R-410A refrigerant operates at 50% -70% higher pressures than R-22. Be sure that servicing equipment and
replacement components are designed to operate with R-410A.
R-410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
° Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard.
° Use hoses with 750 psig service pressure rating.
° Leak detectors should be designed to detect HFC refrigerant.
° R-410A, as with other HFC refrigerants, is only compatible with POE oils.
° POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
° POE oils may cause damage to certain plastics and roofing materials.
° Vacuum pumps will not remove moisture from oil.
° A liquid line filter-drier is required on every unit.
° Do not use liquid line filter-driers with rated working pressures less than 600 psig.
° Do not install a suction line filter-drier in liquid line.
° Wrap all filter-driers and service valves with wet cloth when brazing.
° Do not use with an R-22 TXV.
° If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.
° Do not use capillary tube indoor coils.
° Never open system to atmosphere while it is under a vacuum.
° When system must be opened for service, break vacuum with dry nitrogen and replace all filter-driers.
° Do not vent R-410A into the atmosphere.
° Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
International Comfort Products, LLC
22 Lewisburg, TN 37091 USA 496 01 5402 02

Navigation menu