ICP FVM2X2400A User Manual FAN COIL Manuals And Guides 1209404L
User Manual: ICP FVM2X2400A FVM2X2400A ICP FAN COIL - Manuals and Guides View the owners manual for your ICP FAN COIL #FVM2X2400A. Home:Heating & Cooling Parts:Icp Parts:Icp FAN COIL Manual
Open the PDF directly: View PDF .
Page Count: 23
Download | |
Open PDF In Browser | View PDF |
These instructions must be read and understood completely before attempting installation. Safety Labeling and Signal Words DANGER, NOTE WARNING, CAUTION, and Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product. The signal word CAUTION is used throughout this manual in the following manner: DANGER - Immediate hazards which will result in severe personal injury or death. Signal Words on Product Labeling WARNING - Hazards or unsafe practices which could result in severe personal injury or death. Signal words are used in combination with colors and/or pictures on product labels. CAUTION - Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or operation. TABLE OF CONTENTS Introduction .................................... 2 Care and Maintenance Location ....................................... 2 R-410A Quick Reference Guide ................. Heater Packages ............................... 3 - 7 Air Ducts ...................................... 7 ...................... 8 - 10 Refrigerant Tubing ............................. 10 Refrigerant Metering Device 10 .................... Condensate Drains ............................ 11 Blower Motor - CFM ....................... Accessories 12 - 13 .................................. 14 Sequence of Operation ......................... 15 Wiring Diagram ............................... 16 Fan Coil Airflow ........................... 17 - 19 ECM Motor and Control ........................ Troubleshooting ECM Motor and Controls Start-up Procedure ............................ Specifications aresubject to change without notice 22 23 3 Position Unit ................................ Electrical Connections ......................... 19 .... 19 -21 22 DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments. Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition. 496 01 5001 03 Sep 2009 INTRODUCTION Models FVM2X and FVM4X are designed for maximum flexibility and can be used for upflow, horizontal left or right, and downflow applications (accessory kit required for downflow or horizontal right). These units are designed to meet the low air leak requirements currently in effect. Because of this, the units need special attention in the condensate pan and drain connection area and when brazing tubing. Four fan coil sizes will combine with various outdoor unit sizes to offer systems ranging from 11/2- 5 tons (18,000 - 60,000 BTUH) nominal cooling capacity. All models have a factory installed and appropriately sized hard shut-off TXV metering device. Factory-authorized, field-installed electric heater packages are available in sizes 5 kW through 30 kW. See Product Specification literature for available accessory kits. LOCATION Select the best position which suits the installation site conditions. The location should provide adequate structural support, space in the front of the unit for service access, clearance for return air and supply duct connections, space for refrigerant piping connections and condensate drain line connections. If heaters are being installed make sure adequate clearance is maintained from supply duct work. Refer to Clearances in NO TAG. If the unit is located in an area of high humidity, nuisance sweating of casing may occur. On these installations a wrap of 2" fiberglass insulation with a vapor barrier is recommended. Figure 1 J Clearances and Unit Dimensions OPENING NOTE: Internal filter can be accessed from separate filter door. If the filter can NOT be easily accessed, a remote filter is recommended. Refer to ACCA Manual D for remote filter sizing. FIRE HAZARD Failure to maintain proper clearances could result in personal injury, death, and/or property damage. When heaters are installed, maintain clearances from combustible materials as specified on unit rating plate. Do not use plastic lined or combustible flexible ducting within 36 inches of the supply end of the fan coil. _R_CL_N6 No _ _ _in @; All Sides 0 With Heaters From Supply Duct All Sides From First 3 feet of Supply Duct to Combustibles From Supply Duct to Combustibles after 3 feet 0 0 1 0 Unit Size 2400 3600 4800 6000 A 153A 19¼ 19¼ 223A Heaters Unit Size 2400 3600 4800 6000 B 11 11 11 11 C 193A6 193A6 193A6 193A6 D 15% 19Y8 19Y8 221_G E 22_G 22_G 22_G 22_G F 17% 21Y8 21Y8 24_G G 21 21 21 24 H (inches) 4211AG 537A6 537A6 593A6 (SERVICE ACCESS) i ("(_OPENINGI_ 2 38-11-82 496 01 5001 03 HEATER PACKAGES Factory approved, field installed, UL listed heater packages are available from the equipment supplier. See unit rating plate for a list of factory approved heaters. POSITION Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty. UNIT Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit. A. UPFLOW INSTALLATION If return air is to be ducted through a floor, install duct flush with floor. Set unit on floor over opening. Side return is a field option on slope coil models. Cut opening per dimensions shown in Figure 2. A field-supplied bottom closure is required. PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage. A field fabricated auxiliary drain pan, with a separate drain is REQUIRED for all installations over a finished living space or in any area that may be damaged by overflow from a restricted main drain pan. In some localities, local codes require an auxiliary drain pan for ANY horizontal installation. Figure 2 [ Slope Coil Unit in Upflow Application POWER OPTIONS SUPPLIED SUPPLY DUCT VOLT ENTRY OPTIONS FRONT SERVICE CLEARANCE 24 - 48 models = 21" 60 model = 24" \ SLOPE COIL UNIT UNITS SECONDARY MODEL36SIZE 1A DRAIN I PRIMARY DRAIN II II II II A FIELD MODIFIED SIDE RETURN LOCATION FOR SLOPE COIL UNITS ONLY II 496 01 5001 03 SECONDARY DRAIN PRIMARY DRAIN FIELD SUPPLIED RETURN PLENUM 3 Figure3 J ModularUnitAssembly B. MODULAR UNITS FVM fan coil sizes 4800 and 6000 are two-piece modular units. This allows for modular units to be disassembled and components moved separately to installation area for reassembly. This process accommodates small scuttle holes and limiting entrances to installation sites (refer to Figure 3). C. HORIZONTAL INSTALLATION Unit must NOT be installed with access panels facing up or down. Access panels must only face to the side. FVM models are factory built for horizontal left installation (refer to Figure 4 and Figure 5). They can be field converted to horizontal right (accessory Gasket Kit required - EBAC01GSK). NOTE: When suspending unit from ceiling, dimples in casing indicate suitable location of screws for mounting metal support straps (refer to Figure 4). BRACKET 2SCREWS COIL BOX Figure 4 J NOTE: For optimum condensate drainage performance in horizontal installations, unit should be leveled along its length and width. Slope Coil In Horizontal Left Application (FVM factory A-COIL HORIZONTAL FIELD SUPPLIED HANGING STRAPS configuration) LEFT SECONDARY DRAIN PRIMARY DRAIN FRONT SERVICE CLEARANCE (FULL FACE OF UNIT) 24 - 48 models = 21" 60 model= 24" SECONDARY DRAIN LOW VOLT ENTRY OPTIONS 13/4_ FILTER ACCESS CLEARANCE POWER ENTRY OPTIONS 4 PRIMARY DRAIN / 496 01 5001 03 Figure5 [ A-Coil in Horizontal Left Application (FVM factory configuration) FACTORY SHIPPED HORIZONTAL LEFT APPLICATION -- COIL BRACKET COIL SUPPORT RAI L DRAIN PAN SUPPORT BRACKET COIL BRACKET HORIZONTAL DRAIN PAN PRIMARY DRAIN HORIZONTAL LEFT AIR SEAL SECONDARY DRAIN HORIZONTALLEFT REFRIGERANT CONNECTIONS Horizontal Coils Right Conversion Slope 4. 1. Remove blower and coil access panel and fitting panel (refer to Figure 6). Lay fan coil unit on its right side and reinstall coil assembly with condensate pan down (refer to Figure 6). 5. 2. Remove coil mounting screw securing assembly to right side casing flange. Attach coil to casing flange using coil mounting screw previously removed. 6. 3. Remove coil assembly. Make sure the pan cap in the fitting door is properly seated on the fitting door to retain the low air leak rating of the unit. Figure 6 [ of Units With coil Horizontal Right Conversion Applications - Slope Coil COIL MOUNTING SCREW BLOWER ASSEMBLY SLOPE COIL SKI REFRIGERANT CONNECTIONS -PRIMARY SECONDARY 496 01 5001 03 DRAIN DRAIN 5 7. Add gaskets from the Gasket Accessory EBAC01GSK. Figure 7 J Kit - 8. Align holes with tubing connections and condensate pan connections, and reinstall access panels and fitting panel. Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Conversion for Horizontal Right Applications - A-Coil CONNECTIONS ASSEMBLY HORIZONTAL RIGHT APPLICATION SUPPORT RAI L BRACKET DRAIN SUPPORT BRACKET COIL_ SUPPORT RAIL BRACKET HORIZONTAL DRAIN PAN PRIAMRY HORIZONTAL RIGHT SECONDARY HORIZONTAL DRAIN RIGHT Horizontal Right Conversion of Units With A-Coils 1. Remove blower and coil access panel and fitting panel (refer to Figure 7). 2. Remove metal clip securing fitting panel condensate pan. Remove fitting panel. to 3. Remove two (2) snap-in unit. in 4. Slide coil and pan assembly out of unit. 5. Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on coil support rail on right side of unit. 6. clips securing A-coil Convert air-seal assembly for horizontal right. a. Remove air-seal assembly from coil by removing four (4) screws (refer to Figure 7). b. Remove air splitter (B) from coil seal assembly by removing three (3) screws. (factory-shipped inset.) c. Remove filler plate (A) and install air splitter (B) in place of filler plate. d. Install filler plate (A) as shown in horizontal right application. e. Remove condensate troughs (C) and install on opposite tube sheets. f. 6 Install hose onto plastic spout. 7. Install horizontal pan on right side of coil assembly. 8. Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil support rails. 9. Reinstall two (2) snap-in clips to correctly position and secure coil assembly in unit. Be sure clip with large offsets is used on right side of unit to secure horizontal pan. 10. Remove two (2) oval fitting caps from left side of the coil, access panel, and fitting panel. 11. Remove insulation knockouts on right side of coil access panel 12. Remove two (2) oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel. 13. Install condensate pan fitting caps (from Step 10) in the right side of the coil door making sure that the cap snaps and seats cleanly on the back side of the coil door. Make sure no insulation interferes with seating of the cap. 14. Reinstall access fitting panels, aligning holes tubing connections and condensate connections. Be sure to reinstall metal between fitting panel and vertical condensate with pan clip pan. 15. After brazing, make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. 496 01 5001 03 F. DOWNFLOW INSTALLATION Recommended applications: . PRODUCT ORPROPERTY DAMAGEHAZARD Failureto follow this caution may result in product or property damage The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A-coil and Slope-coil units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, and must be used for downflow. Failure to follow instructions could result in personal injury or product and property damage. method of securing for typical a. If fan coil is away from wall, attach pipe strap to top of fan coil using No. 10 self tapping screws. Angle strap down and away from back of fan coil, remove all slack, and fasten to wall stud of structure using 5/16" lag screws. Typical both sides of fan coil. b, If fan coil is against wall, secure fan coil to wall stud using 1/8"wide right-angle brackets. Attach brackets to fan coil using No. 10 self tapping screws and to wall stud using 5/16" lag screws (refer to Figure 8). Mobile Home or Manufactured Housing Applications Figure 8 4" MAX In this application, field conversion of the evaporator coil is required using accessory Downflow Kit along with an accessory Base Kit. Set unit on floor over opening and use 1/8" to 1/4" thick fireproof resilient gasket between duct, unit, and floor. Refer to installation instructions packaged with accessory kit. See Product Specification literature for kit part numbers. / -_)_:_ SECURE FAN COIL TO STRUCTURE I UNIT STRAP AWAY PIPE _ _] _ ,---...._.. FROM WALL (TYPICAL BOTH SIDES) OR \ UNIT AGAINST WALL 1/8" INCH THICK ANGLE MOUNTING BRACKET (TYPICAL BOTH SIDES) During the conversion process, removed the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain low air leak performance of the unit. NOTE: Gasket kit number (EBAC01GSK) is also required for all downflow applications to maintain low air leak/low sweat performance. G. MANUFACTURED APPLICATIONS 1. 2. HOUSING AND MOBILE HOME Fan coil unit must be secured to the structure using field-supplied hardware. Allow a minimum of 24" clearance from access panels. 1#7 cEL--,!_ // # _ DOWN FLOW BASE KIT SECURE UNITTO FLOOR ANGLE BRACKET OR PIPE STRAP MAX AIR DUCTS Connect supply-air duct over the outside of 3/4"flanges provided on supply-air opening. Secure duct to flange using proper fasteners for type of duct used, and seal duct-to-unit joint. Duct connections flanges discharge connection. are provided on unit air When using FVM units with 20kW, 24kW, and 30kW electric heaters, maintain a 1" clearance from combustible materials to discharge plenum and ductwork for a distance of 36" from unit. Use accessory downflow base to maintain proper clearance on downflow installations. connection. Duct work passing through unconditioned space must be insulated and covered with vapor barrier. Duct work Acoustical Treatment Metal duct systems that do not have a 90 degree elbow and 10 feet of main duct before first branch takeoff may require internal acoustical insulation lining. As an alternative, fibrous duct work may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous duct work shall comply with National Fire Protection Association as tested by UL Standard 181 for Class 1 air ducts. Use flexible connectors between duct work and unit to prevent transmission of vibration. When electric heater is installed, use heat-resistant material for flexible connector between duct work and unit at discharge 496 01 5001 03 7 ELECTRICAL CONNECTIONS On units with a factory installed disconnect with pull-out removed, service and maintenance can be safely performed on only the load side of the control package. NOTE: Before proceeding with electrical connections, make certain that supply voltage, frequency, phase, and circuit ampacity are as specified on the unit rating plate. See unit wiring label for proper field high and low voltage wiring. Make all electrical connections in accordance with the NEC and any local codes or ordinances that may apply. Use copper wire only. The unit must have a separate branch electric circuit with a field-supplied disconnect switch located within sight from, and readily accessible from the unit. ELECTRICAL SHOCK or UNIT DAMAGE HAZARD B. 24V CONTROL SYSTEM Control System Connections to Fan Control Board Refer to unit wiring instructions for recommended wiring procedures. Use 18 AWG color-coded, insulated (35 ° C minimum) wires to make the low-voltage connections between the thermostat, the unit, and the outdoor equipment. If the thermostat is located more than 100 feet from the unit (as measured along the low voltage wire), use 16 AWG color-coded, insulated (35 °C minimum) wire. Fan Control Board is circuited for single-stage heater operation. When additional heater staging is desired using outdoor thermostats of Heat Staging, remove Jumper J2 on Fan Control Board to enable staging. All wiring must be NEC Class 1 and must be separated from incoming power leads. Refer to outdoor unit wiring instructions for additional wiring recommendations. Failure to follow this warning could result in personal injury or death. Connect low-voltage leads to thermostat and outdoor unit (refer to Figure 9, Figure 10, Figure 11, Figure 12). Turn off the main (remote) disconnect device before working on incoming (field) wiring. Incoming (field) wires on the line side of the disconnect found in the fan coil unit remain live, even when the pull-out is removed. Service and maintenance to incoming (field) wiring cannot be performed until the main disconnect switch (remote to the unit) is turned off. C. HEAT STAGING Heat Staging Option Heat Staging of the electric heat package is possible when the FVM is installed as a part of a single-stage heat pump system using a two-stage programmable thermostat, or capable zoning control and and one (1) of the following electric heat packages: Relay heaters EHK10AKN, EHK10AKB, EHK15AK(F,B), EHK18AHN, EHK20AK(F,B) EHK25AHCF, or EHK30AHCF. ELECTRICAL SHOCK or UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury, death, and/or unit damage. If a disconnect switch is to be mounted on unit, select a location where drill and fasteners will not contact electrical or refrigeration components. A. LINE VOLTAGE CONNECTIONS If unit contains an electric heater, remove and discard power plug from fan coil and connect male plug from heater to female plug from unit wiring harness. (Refer to Electric Heater Installation Instructions.) For units without electric heat: 1. Connect 208/230V power leads from field disconnect to yellow and black stripped leads. 2. Connect ground wire to unit ground lug. Check all factory wiring per unit wiring diagram and inspect factory wiring connections to be sure none were loosened in transit or installation. 8 Complete system low-voltage wiring as shown Figure 9, Figure 10, Figure 11, Figure 12. in NOTE: Where local codes require thermostat wiring be routed through conduit or raceways, splices can be made inside the fan coil unit. All wiring must be NEC Class 1 and must be separated from incoming power leads. A factory-authorized disconnect kit is available for installation of 5 kW through 10 kW applications. When electric heat package with circuit breakers are installed, the circuit breaker can be used as a disconnect. D. MANUFACTURED HOUSING In manufactured housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor temperatures above 40 oF. except for a heat pump defrost cycle. In some applications, an outdoor thermostat may be required. Refer to thermostat instructions for details. 496 01 5001 03 FVMFanCoilWiring Figure 9 with Air Conditioner single-stage FVM Fan Coil Wiring with single-stage Heat Pump Figure 11 FAN COIL INDOORCONTROL INDOOR CONTROL FAN COIL RVS COOLING HEAT STAGE 2 _ I F_ COOL I _ STAGE REMOVE J2 JUMPER Fq 6_ NIA HEAT STAGE ..... FOR HEAT STAGING .... FAN .... 24 VAC HOT _ 24VAC COMM _ .... _ ..... DEHUMIDIFY 24 VAC COMM --AD HUMIDIF--T_ (24 VAC) E_ HUMIDIFY __ HUMIDIFY I-_-I_ .._ __ .___ / / OUTDOOR _- E_- "-- l-_q --7_--I SENSOR OUTDOOR FVM Fan Coil wiring with two-stage Air Conditioning CONTROL __ 2 _ ..... 42_ HEAT STAGE I _ ..... 42] COOL STAGE I _ .... COOL STAGE 2 _ .... _r" --83 I I REMOVE J2 JUMPER -----Es.... HEAT/COOL STAGE1 D HEAT STAGE3 _ DEHUMIDIFY [_ ..... 24 VAC COMM _'_ ..... __ 24 VAC HOT .... _ .... ----D .... .... _, REMO_ FOR HEAT STAGING HEAT/COOL_ STAGE2 .... @] 4_ Fq 43 _ -q E_ £: FAN ----I L. DEHUMIDIFY 24 VAC COMM --HEAT q_JUMPERSTAGING FOR 43....sL[ZI | ..... 4Z_ E_ ..... __ .... q-D HUMIDIFY (24 VAC) HUMIDIFY F_- ,_.__ / HUMIDIFIER (24 VAC) t___ FAN COIL RVSCOOLING 24VAC HOTElFAN / FVM Fan Coil wiring with two-stage Heat Pump INDOORCONTROL FAN COIL HEAT STAGE _ (24 VAC) 1-_ Figure 12 Figure 10 HUMIDIFIER SENSOR OUTDOOR "-- I-_-I- OUTDOOR ,ram RVS HEATING _ N/A INDOOR ..... .... Fa DEHUMIDIFY ..... J2 JUMPER -I_ REMOVE FOR HEAT STAGING -I_ ._-___ r_] ---[] -[] .... [] G ..... HEAT STAGE 2 [2@].... HEAT/COOL .... STAGE 1 FAN I-q ..... 24 VAC HOT I-q ..... HEAT STAGE 3 ..... / RVS HEATING _ / OUTDOOR _- -__ SENSOR OUTDOOR I--_ N/A OUTDOOR -___ SENSOR OUTDOOR t-_ -I-_-- I. 496 01 5001 03 9 Figure13 J TransformerConnections BROWN R GROUND CONNECTIONS NOTE: Use UL listed conduit and conduit connectors for connecting supply wire(s) to unit to obtain proper grounding. Grounding may also be accomplished by using grounding lugs provided in control box. Use or dual or multiple supply circuits will require grounding of each circuit to ground lugs provided on unit and heaters. RED YELLOW BLACK PRIMARY E. TRANSFORMER INFORMATION Transformer is factory wired for 230V operation. For 208V applications, disconnect the black wire from the 230V terminal on transformer and connect it to the 208V terminal (refer to Figure 13). The secondary circuit of transformer is protected by a 5 amp fuse mounted on Fan Control Board. REFRIGERANT ELECTRICAL Failure to establish uninterrupted ground could result in personal death. or unbroken injury and/or According to NEC, ANSI/NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken ground in order to minimize potential for personal injury or death if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate ground wire must be used. TUBING Use accessory tubing package or field-supplied tubing of refrigerant grade. Insulate entire suction tube if field-supplied tubing is used. Tubing package has an insulated suction. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow control device. Always evacuate coil and field-supplied tubing to 500 microns before opening outdoor unit service valve. PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage. Size and install refrigerant lines according to information provided with outdoor unit. Route refrigerant lines to the fan coil in a manner that will not obstruct service access to the unit or removal of the filter. , 2. 3. METERING Cut tubing to correct length. Hold coil stubs steady to avoid bending or distorting. Fit refrigerant lines into coil stubs. Insert tube into sweat connection on unit until it bottoms. 4. Wrap TXV and nearby tubing with a heat-sinking material such as a wet cloth. 5. Wrap a heat sinking material such as a wet cloth behind braze joints. 6. Braze connection using a silver bearing or non-silver brazing materials (SiI-Fos or Phos-copper alloy). Do not use solder (matrices which melt below 800°F). Consult local code requirements. , After brazing, allow joints to cool. Evacuate coil and tubing system to 500 microns using deep vacuum method. Braze with SiI-Fos or Phos-copper alloy on copper-to-copper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV. REFRIGERANT SHOCK HAZARD DEVICE FVM fan coils have a factory installed hard shut-off TXV designed only for use with R-22 and R-410A refrigerants. Use only with outdoor units designed for corresponding refrigerants. TXV is factory set and not field adjustable. PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage. This Fan Coil has a hard shut-off TXV metering device. A compressor Hard Start Kit is REQUIRED in all applications where the matching outdoor unit has a single-phase reciprocating compressor. 10 496 01 5001 03 CONDENSATE DRAINS Units are provided with primary and secondary 3/4"NPT drain connections. Refer to Figure 2 though Figure 7 to identify the primary and secondary locations. To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include properly sized condensate traps (refer to Figure 14). Factory approved condensate traps are available (accessory part number EBAC01CTK). Figure 14 J Recommended Condensate Trap 2" MIN To connect drain lines, the drain connection knock-outs must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the knock-out. Clean the edge of the opening if necessary. After drain fittings are installed, caulk the seam between the fitting and the cover to retain the low leak rating of the unit. It is recommended the PVC fittings be used on the plastic condensate pan. Do not over-tighten. Finger-tighten plus 11/2turns. Use pipe dope, to ensure proper seal. Figure 15 J Insufficient Condensate Trap Install traps in the condensate lines as close to the coil as possible (refer to Figure 16), but avoid blocking filter access panel. Install drain lines below the bottom of the drain pan and pitch the drain lines down from the coil at least ¼ inch per foot of run. Horizontal runs over 15 feet long must also have an anti-siphon air vents (stand pipes), installed ahead of the horizontal runs. Extremely long horizontal runs may require oversized drain lines to eliminate air trapping. Route primary drain line to the outside or to a floor drain. Check local codes before connecting to a waste (sewer) line. Route the secondary drain line to a place in compliance with local installation codes where it will be noticed when unit is operational. Condensate flowing from secondary (overflow) drain indicates a plugged primary drain - unit requires service or water damage will occur. DO NOT USE SHALLOW RUNNING TRAPS! Figure 16 J Condensate ! Drain o T Prime all traps, test for leaks, and insulate drain lines where sweating could cause water damage. Consult local codes for additional requirements or precautions. o o o If a gravity drain cannot be used, install a condensate pump. Install the pump as close to the indoor section as possible. FILTER ACCESS PAN EL WITH ___(USE PRODUCT or PROPERTY DAMAGE HAZARD \ TRAP REQUIRED FACTORY KIT OR FIELD-SUPPLIED TRAP) Failure to follow this caution may result in product or property damage. PRIMARY TRAP REQUIRED (USE FACTORY KIT OR FIELD-SUPPLIED TRAP OF PROPER DEPTH. STANDARD P-TRAPS ARE NOT SUFFICIENT. SEE Use only full size P-traps in the condensate line (refer to Figure 14). Shallow, running traps are inadequate and DO NOT allow proper condensate drainage (refer to Figure 15). FIGURE OF RECOMMENDED 496 01 5001 03 CONDENSATE TRAP) 11 BLOWER MOTOR - CFM FAN CONTROL BOARD CONFIGURATION TAPS Fan Control Board taps are used by the installer to configure a system. The ECM motor uses the selected taps to modify its operation to a pre-programmed table of airflows (Refer to Table 2 and Table 3). Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such as the need for de-humidification. (Refer to Figure 17 and Figure 18). FVM fan coils must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used. Figure 17 I Fan Control Note that airflow marked is the airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized, the ECM motor will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the largest heater range approved. (Refer to Figure 17, A as indicated) Fan Control Board Wiring Arrangement Figure 18 Board i LOW VOLTAGE TERMINAL BLOCK AUX HEAT KW/CFM FAN CONTROL BOARD (Z_ SEC2 (Z) SECt AUX HEAT KW/CFM B C A AJ v-q AC/HP A D -:!S=!,o SIZE c B D B.__,,._ • SYSTEM c--_ AiJ TYPE HPC_M ...... AC/HP _FF CFM ADJUST D.__,,_ • " ON/OFF DELAY " " ZMOLEX12 I_ ? I " AUX2 HUM2 PIN CONNECTOR A. AUXILIARY HEAT KW/CFM Installer must select the auxiliary heat airflow approved for application with kW size heater installed. If no heater is installed, this step can be skipped. (Refer to Figure 17, A) The select pins are marked A, B, C, D. Heater kW ranges corresponding to each letter are listed in a chart on the unit wiring diagram. Refer to the unit wiring diagram and select the pin for the heater size being used (example wiring diagram in Figure 21). The airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe and continuous operation. (Refer to Table 4 and Table 5 for airflow delivery and minimum CFM.) 12 B. AC/HP SIZE Select System Size Installed The factory setting for air conditioner or heat pump size is the largest outdoor unit meant for application with the model of fan coil purchased. Installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes with the exception of electric heat modes. (Refer to Figure 17, B) The select pins are marked A, B, C, D. Outdoor unit sizes corresponding to each letter are listed in a chart on the unit wiring diagram. Refer to the unit wiring diagram and select the pin for the outdoor unit size being used (example wiring diagram in Figure 21). 496 01 5001 03 C.SYSTEMTYPE SelectSystemType 3. Installed AC or HP The type of system must be selected: 1. 2. 3. AC - Air Conditioner provides approximately 350 CFM per ton for greater efficiency and humidity control with the AC/HP CFM ADJUST set to the nominal (NOM) tap. (To achieve approximately 400 CFM per ton move tap to (HI) position. Refer to appropriate airflow tables for exact CFM setting.) HP-COMFORT - Heat Pump Comfort Provides approximately 315 CFM per ton for higher than normal heating air delivery temperature. Provides approximately 350 CFM per ton cooling airflow for good humidity removal with the AC/HP CFM ADJUST set to the nominal (NOM) tap. HP-EFF - Heat Pump Efficiency provides same airflow for heating and cooling modes to increase overall HP efficiency; approximately 350 CFM per ton with the AC/HP CFM ADJUST set to the nominal (NOM) tap. The factory setting is AC (Refer to Figure 17, C). D. AC/HP CFM ADJUST Select Medium, Low, or High Airflow To provide airflow at rates described above, the AC/HP ADJUST select is factory set to the nominal (NOM) tap. The adjust selections HI/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15% airflow over nominal unit size selected and LO provides 10% airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet individual installation needs for such things as noise, comfort, and humidity removal. (Refer to Figure 17, D as indicated.) E. ON/OFF DELAY Select desired time delay profile NOTE: Delay selections are active in cooling and heat pump heating modes only. Auxiliary heating modes have a one (1) minute off delay and zero (0) on delay programmed into the ECM motor that cannot be overridden. Four (4) motor operation delay profiles are provided to customize and enhance system operation. (Refer to Figure 17, E as indicated.) Selection options are: 1. 0/90: No on delay and 90 second off delay at 100% airflow (factory setting). 2. 30/90:30 second on delay with no airflow and 90 second off delay at 100% airflow profile. Used when it is desirable to allow system coils time to heat-up/cool-down in conjunction with the airflow. 496 01 5001 03 0/0: No delay option. Used for servicing unit or when a thermostat is utilized to perform delay functions. 4. ENH: enhanced selection, provides a 30 second on delay with no airflow followed by 150 seconds at 70% airflow, and no off delay for added comfort. This profile will minimize cold blow in heat pump operation and could enhance system efficiency. F. CONTINUOUS FAN Select desired fan speed when thermostat continuous fan is set on NOTE: If installed with a two-stage outdoor unit, do not select HI speed continuous fan. If HI is selected, low stage compression will also run HI fan speed possibly resulting in insufficient dehumidification. 1. LO speed - factory setting, 50% cooling mode airflow. 2. MED speed - move connector to MED, 80% cooling mode airflow. 3. HI speed - move connector to HI, 100% cooling mode airflow. (Refer to Figure 17, F as indicated.) G. LOW-VOLTAGE CIRCUIT Fusing and Reference The low-voltage circuit is fused by a board-mounted 5-amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol. H. BASIC FAN COIL CONFIGURATION The following basic configuration of the fan coil will provide ARI rated performance of an air conditioner: 1. AUX HEAT KW/CFM - Select the heater range for the size electric heater installed. 2. AC/HP SIZE - Select system size installed. 3. 4. SYSTEM TYPE - Select system type AC AC/HP CFM ADJUST - Select NOM. 5. 6. ON/OFF DELAY - Select 0/90 profile. CONTINUOUS FAN - Select desired fan speed when thermostat is set to continuous fan. The following basic configuration of the fan coil will provide ARI rated performance of a heat pump: 1. AUX HEAT KW/CFM - Select the heater range for the size electric heater installed. 2. AC/HP SIZE - Select system size installed. 3. 4. SYSTEM TYPE - Select system type HP-EFF AC/HP CFM ADJUST - Select NOM. 5. ON/OFF DELAY - Select 0/90 profile. 6. CONTINUOUS FAN - Select desired fan speed when thermostat is set to continuous fan. 13 ACCESSORIES A. ACCESSORY ELECTRIC HEATERS Electric heaters may be installed with the FVM fan coil per instructions supplied with electric heater package. See unit rating plate for factory-approved electric heater kits. B. AUXILIARY TERMINALS Figure 19 Humidifier Wiring HUMIDISTAT I HUM 1 (C) 24-VAC The AUX2 and HUM2 terminals on the Fan Control Board are tied directly to the G terminal, and provide a 24 VAC signal whenever the G terminal is energized. (Refer to Figure 17 and Figure 18) HUM 2 C. HUMIDIFIER / HUMIDISTAT CONNECTIONS Figure 20 Fan Control Board terminals HUM1 (directly connected internally to C on terminal block) and HUM2 (directly connected internally to G on terminal block) are provided for direct connections to the low-voltage control of a humidifier through a standard humidistat (refer to Figure 19). These terminals are energized with 24 VAC when G thermostat signal is present (refer to Figure 22). Alternately, the 24VAC signal may be sourced from the W1 and C terminal block connections when electric heaters are used as a primary heating source (refer to Figure 20). When using a thermostat with humidity control, the 24VAC signal may be sourced directly from humidity terminal on the thermostat. (Refer to Figure 9, Figure 10, Figure 11, or Figure 12.) 1 TO HUMIDIFIER (G) (TERMINAL BOARD CONNECTIONS) c 24-VAC Humidifier Wiring for Electric Heat Primary Heating Source H U M IDISTAT I TO HUMIDIFIER W D. DEHUMIDIFY CAPABILITY HUMIDISTAT CONNECTION WITH STANDARD Latent capacities for systems using the FVM fan coil are better than average systems. If increased latent capacity is an application requirement, the field wiring terminal block provides a connection terminal (H) for use of a standard humidy sensor/control. The FVM will detect the humidy sensor/control contact closing on increasing humidity and reduce its airflow to approximately 80% of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidity sensor/control to open its contacts. When the contacts open, the airflow will return to 100% of the selected cooling airflow. 14 496 01 5001 03 SEQUENCE OF OPERATION FVM fan coils will supply airflow in a range which is more than twice the range of a standard fan coil. Each fan coil size is designed to provide nominal cooling capacities at 50 oF evaporator temperature and the required airflow in order to match with any of four (4) different air conditioner or heat pump outdoor unit sizes. Table 1 outline the CFM range for the different FVM fan coils. F. HEAT PUMP HEATING MODE - SINGLE STAGE The blower motor is a true variable speed motor designed to deliver constant CFM. Constant CFM is valid for systems with total external static pressure between 0.1 and 0.7 inches water column. G. HEAT PUMP HEATING MODE - TWO STAGE A. CONTINUOUS FAN • Thermostat closes circuit R to G. • Blower runs at continuous fan airflow. B. COOLING MODE - SINGLE STAGE If indoor temperature is above temperature set point and humidity is below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O. NOTE: • For single stage systems, do not use the Y1 terminal. Fan coil delivers single stage cooling airflow. C. COOLING MODE - TWO STAGE • First stage (low) cooling: Thermostat closes circuits to R to G, R to O, and R to Y1. • Fan coil delivers low stage cooling airflow. • Second stage (high) cooling: Thermostat closes circuits to R to G, R to O, R to Y1 and R to Y/Y2. • Fan coil delivers high stage cooling airflow D COOLING MODE - DEHUMIDIFICATION If indoor temperature is above temperature set point and humidity is above humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O and humidistat closes R to H. • • Thermostat closes circuits R to G and R to Y/Y2. NOTE: • For single stage systems, do not use the Y1 terminal. Fan coil delivers single stage heat pump heating airflow. • First stage (low) heating: Thermostat closes circuits R to G and R to Y1. • Fan coil delivers low stage heating airflow. • Second stage (high) heating: Thermostat closes R to G, R to Y1 and R to Y/Y2. • Fan coil delivers high stage heating airflow. H. HEAT PUMP HEATING ELECTRIC HEAT • WITH AUXILIARY Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1 with R to W/W1 or W2 (and R to O in the case of defrost). If the thermostat calls for electric heat when the heat pump is operating in heating or defrost, the motor will modify the airflow if necessary. The motor will provide an airflow which is safe for the operation of the electric heat. That airflow is the greater of the heat pump heating airflow and the electric heat only airflow. ELECTRICAL SHOCK or UNIT DAMAGE HAZARD Failure to carefully read and follow this CAUTION warning could result in equipment malfunction, property damage, personal injury and/or death. Disconnect power to unit before removing or replacing connectors or servicing motor. Wait at least five (5) minutes after disconnecting power before opening motor. The fan coil delivers airflow which is approximately 80% of the nominal cooling airflow to increase the latent capacity of the system. E. ELECTRIC HEAT HEATING MODE • Thermostat closes circuit R to W/W1, or W2 • Fan coil delivers the selected electric heat airflow. 496 01 5001 03 15 Figure21 J Wiring Diagram i AIRFLOW THIS COMPARTMENT MUST BE CLOSED EXCEPT FOR SERVICING i I BLOWER MOTOR 1 i i UNIT SIZE VlO 2400 A 0-20/1100 3600 4800 6000 0-20/1225 0-30/1500 0-30/1750 i ( COOLINGONLYSCHEMATIC DIAGRAM ) -i i FIELD POWER WIRING i TABLE AUX HEAT RANGE (KW/CFM) B C D 0-15/875 0-10/675 0-5/625 0-15/1100 0-20/1250 0-20/1525 0-10/875 0-1511100 0-1511350 0-51800 0-10/975 0-1011100 DISCONNECT PER NEC i L ADJUST i i SEE RATING PLATE FOR VOLTS & HERTZ -' r_ AC/HP t BLU i SEE NOTE #1 ,_ j L2, _O]GNU 1 A SIZE B D 18 C 2400 36 30 24 3600 42 36 30 4800 48 42 36 6000 60 48 42 24 30 36 LEGEND PLUG 2 3 2 61 4 _ 3 2 61 4 RECP 2 " " / - , -. " FIELD POWERWIRING GND EQUIPMENT GROUND MARKED TERMINAL ECM FAN MOTOR PLUG AND RECEPTACLE PCB PRINTED CIRCUIT BOARD BRN mJ i PCB SEC2 SEE NOTE 8 KW AUX HEAT KW/CFM COM COMMON RECP RECEPTACLE F1 LOW VOLTAGE FUSE t- TRAN TRANSFORMER 1 B r SEC2 @ @ AC!HP SIZE ) ARRANGEMENT m]_ SEC1 t 230V t COMPONENT i i i R i O O O O W1 O O O O A/2 i C D j_i O O O SYSTEM TYPE O O O O O G O O WY2 HP-COMFORT O O AC/HP CFM ADJUST t YEL O LO HI O O O O E C ") ON/OFF DELAY IOlOlOlOlOlOlOlOlOlOlOlOl PL1 HEATER/MOTOR = i r- i 2":"['"] REDt'_ ; I ECM I _ - Ii <: :'COM , ," ' ",230 V i \ RECP 3 RECP 4 GRY 16 1. Use copperwire (75%min) only between DisconnectSwitch and unit. 2. To be wired inaccordancewith N.E.C.and bcal codes. 3. Transformerprimaryleads,blue 208v, red 230v. 4. If any offlqe originalwire, as supplied, mustbe replaced, use lhe same or equivalenttype wire. 5. Replacelow voltagefuse with no greaterthan 5 amp fuse. 6. Use 60 amp dass K fuses only,for replacement. 7. Connect R to R, G to G, etc., see outdoor instructionfor details. 8. Use tableto selectproper airflowfor aux heat size and AC/HP size. 332385-101 REV. B 496 01 5001 03 FAN COIL AIRFLOW Table 1 CFM Range Fan Coil Size Use with Outdoor Unit Size CFM Range 2400 18, 24, 30, 36 350 - 1200 3600 24, 30, 36, 42 415- 1400 4800 30, 36, 42, 48 425- 1600 6000 36, 42, 48, 60 540 - 2000 Table 2 Fan Coil Size 2400 3600 4800 6000 Fan Coil Airflow Delivery (CFM) in Cooling Outdoor Unit Size Two-Stage Single Stage Cooling Nominal Dehum 18 525 420 24 700 560 30 875 36 24 Cooling High Nominal Mode (A/C or HP) Fan Only Low Dehum Nominal Dehum Low Med Hi Two-Stage outdoor unit not offered 700 560 560 450 350 420 525 350 560 700 700 Two-Stage 440 700 875 1050 840 1050 840 840 670 525 840 1050 700 560 700 560 560 450 415 560 700 30 875 700 Two-Stage 440 700 875 36 1050 840 1050 525 840 1050 42 1225 980 Two-Stage outdoor unit not offered 615 980 1225 30 875 700 Two-Stage outdoor unit not offered 440 700 875 36 1050 840 1050 525 840 1050 42 1225 980 Two-Stage 615 980 1225 48 1400 1120 1400 1120 1120 900 700 1120 1400 36 1050 840 1050 840 840 670 540 840 1050 42 1225 980 Two-Stage 615 980 1225 48 1400 1120 1400 1120 1120 900 700 1120 1400 6O 1750 1400 1750 1400 1400 1120 875 1400 1750 outdoor unit not offered outdoor unit not offered 840 840 840 840 670 670 outdoor unit not offered outdoor unit not offered NOTES: 1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM. 2. Airflow can be adjusted +15% or -10% by selecting Hi or Lo respectively for all modes except fan only. 3. Dry coil at 230 volts and with 10kW heater and filter installed. 4. Airflows shown are valid for systems with total static pressure between 0.1 and 0.7 in wc. 496 01 5001 03 17 FanCoil Table 3 Fan Coil Size 2400 3600 4800 6000 Outdoor Unit Size Airflow Delivery (CFM) in Heat Pump Heating Mode Only Two-Stage Single Stage HP Heating HP Heating High Fan Only Low Comfort Eft 18 475 525 Comfort Eft Comfort Eft Low Med Hi outdoor unit not offered 350 38O 475 Two-Stage 24 630 700 630 350 5O5 630 3O 785 875 Two-Stage 440 63O 785 36 945 1050 945 1050 755 840 525 755 945 24 630 700 630 700 505 560 415 5O5 630 3O 785 875 Two-Stage 36 945 1050 945 440 525 63O 755 785 945 42 1100 1225 Two-Stage outdoor unit not offered 615 88O 1100 3O 785 875 Two-Stage outdoor unit not offered 440 63O 785 36 945 1050 945 525 700 505 560 outdoor unit not offered outdoor unit not offered 1050 755 1050 840 755 840 755 945 615 88O 1100 42 1100 1225 Two-Stage 48 1260 1400 1260 1400 1010 1120 700 1010 1260 36 945 1050 945 1050 755 840 540 755 945 42 1100 1225 Two-Stage 88O 48 1260 1400 1260 1400 1010 1120 615 700 1010 1100 1260 6O 1575 1750 1575 1750 1260 1400 875 1260 1575 outdoor unit not offered outdoor unit not offered NOTES: 1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM. 2. Airflow can be adjusted +15% or -10% by selecting Hi or Lo respectively for all modes except fan only. 3. Dry coil at 230 volts and with 10kW heater and filter installed. 4. Airflows shown are valid for systems with total static pressure between 0.1 and 0.7 in wc. Table 4 FVM Model Size 2400 3600 Airflow Delivery (CFM) Outdoor Unit Capacity (BTUH) Electric 0-5 NOM HI LO NOM HI 18 625 625 625 675 675 675 24 650 725 835 725 835 30 815 905 1040 * 9O5 36 980 1085 1250 980 1085 24 675 725 835 875 875 30 815 905 1040 9O5 36 980 1085 1250 875 980 42 1140 1270 1460 1140 30 6000 0-15 LO 0-10 4800 Heater kW Range 0-10 LO NOM HI LO NOM HI 1040 875 900 875 900 875 1040 1100 1100 1100 1250 980 1085 1250 1100 1100 1250 * * * 1085 1040 1250 1100 1100 1100 1100 1100 1250 1225 1225 1250 1270 1460 1140 1270 1460 1225 1270 1460 0-15 975 975 1040 1100 36 980 1085 1250 42 1140 1270 1460 48 1305 1450 36 1100 42 1140 48 60 0 - 20 0 - 20 0 - 30 1100 1100 ..... 1100 1100 1250 1250 1250 1250 * * 1140 1270 1460 1250 1270 1460 * * 1665 1305 1450 1665 1305 1450 1665 1500 1100 1250 1350 1350 1350 ..... 1270 1460 1350 1350 1460 1525 1525 1525 * 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085 1500 1665 * Airflow not recommended for heater/system size NOTE: LO, NOM, and HI refer to AC/HP CFM ADJUST selection on the control board. 18 496 01 5001 03 Table5 FVM ModelSize HeatPumpMinimumCFMfor Electric Heater Application Heater Size kW Outdoor Unit Size 5 8, 9, 10 15 18, 20 18 24 3O 625 650 800 625 725 875 .... 875 875 -1040 36 970 970 970 1040 24 675 875 .... 3O 36 800 975 875 975 1100 1100 1150 1225 42 1125 1125 1125 1225 3O 36 800 975 1125 875 975 1125 875 1100 1125 1150 1225 1225 1305 1305 1305 1305 1100 1125 1300 1100 1125 1300 1350 1350 1350 1350 1350 1465 1625 1625 1625 1750 1750 1750 18,20 24,30 2400 3600 4800 42 48 36 42 6000 48 6O A/C Minimum CFM when FVM Model Size 5 using 8,9,10 Electric 24,30 1400 Heat (CFM) Heater Size kW 15 2400 625 625 725 875 3600 4800 675 675 7OO 7OO 85O 85O 1050 1050 1400 1050 1050 1050 1050 1750 Heater Only 6000 NOTES: 1. Heater Only-Air conditioner with electric heater application. 2. These airflows are minimum acceptable airflows as UL listed. Actual airflow delivered will be per airflow delivery chart for Electric Heating Modes. ECM MOTOR AND CONTROL The ECM motor used with this product contains two parts: The control module and motor winding section. Do not assume the motor or module is defective if it will not start. Go through the steps described below before replacing control module, Fan Control Board or entire motor. The control module is available as a replacement part. TROUBLESHOOTING ECM MOTOR AND CONTROLS A. IF MOTOR TURNS SLOWLY: 1. , Replace access panel. Motor may appear to run slowly if access panel is removed. It is normal operation to run noticeable slower if G terminal is not energized in cooling or heat-pump modes. B. IF MOTOR DOES NOT RUN: Turn off power and check the following: 1. 2. , Check 5 amp fuse on Fan Control Board. Check for 24 VAC on SEC1 and SEC2. If no voltage is present, check transformer. Check all plugs and receptacles for any deformation which could cause loose connections. Be sure plugs are fully seated. 496 01 5001 03 4. Verify that approximately motor. 5. Verify low-voltage control signals to motor. The motor receives its control signals through the 12-pin plug (PL-1) on Fan Control Board and 16-pin plug on wiring harness. (Refer to Troubleshooting Example.) The combinations of pins energized will determine motor speed. (Refer to Figure 22). Refer to Table 6 for circuit board, low-voltage screw terminals energized and for voltage present at each pin on 12-pin plug (PL-1). Refer to Table 6 for pin number on 16-pin plug which should have voltage when Fan Control Board screw terminals have 24 VAC. 230 VAC is present at 19 Figure22 J CONTROLSIGNALS(FANCONTROLBOARD& 16-PinPLUG) J2JUMPER -- PULL FOR HEAT STAGING SEC1 _ __ _ SEC2 {[_) _ _FF _ _ DEHUMIDIFICATION INPUT -- 24 VAC HOT -- AUXILARY HEAT STAGE 1 Ilkh-H) l W2 -- AUXILIARY HEAT STAGE 2 -- LOW STAGE COMPRESSOR -- SINGLE OR HI STAGE COMPRESSOR _Y/Y2 AC,_Hp CFMADJUST ONOFF SCREW TERMINALS -_J_ \[[ 1 AC,H. PS_ZE____ -- _ LOW VOLTAGE ! II LH_4)I G -- FAN -- REVERSING VALVE DELAY COMMON ? PIN 12 y v ...... ........ \ oRY=_=o \ (PL 1) PIN 1 Y1 16-PtN PLUG C W 1 C A03004 C. USE THE FOLLOWING CONTROL SIGNALS: PROCEDURE TO CHECK wires from Fan Control THERMOSTAT 1. Remove Board. all thermostat 2. Jumper screw terminals (one at a time): R-G, R-Y/Y2, R-Y1, R-W1. If motor runs in all cases, thermostat is miswired, configured incorrectly or defective. If motor runs in some cases, but not others, continue to check wiring harness and circuit board. WIRING HARNESS 1. Shut off power to unit; wait five (5) minutes. 2. 3. Remove 5-pin plug from motor. Remove 16-pin from motor. 4. Replace 5-pin plug and turn power on. 5. Check for appropriate voltages on 16-pin connector with screw terminals jumpered. (Refer to Table 6 for values and refer to examples below.) If signals check correctly and motor does not run, inspect wiring harness for loose pins or damaged plastic that could cause poor connections. If connections are good, either control module or motor is defective. If proper signals are not present, check circuit board using procedure below: If proper signals are not present, replace Fan Control Board. If present at board and not at 16-pin connector, wiring harness is defective. TROUBLESHOOTING EXAMPLE: Motor is not running on a call for heat pump heating. System is a single-stage heat pump. 1. After performing checks in Thermostat section, follow Steps 1 through 5 in Wiring Harness section. Then proceed with example. 2. With all thermostat wires removed from Fan Control Board, place a jumper wire between R and Y/Y2 low-voltage screw terminals on the Fan Control Board. 3. Check Table 6 for pin number on 16-pin connector associated with the Y/Y2 signal. The correct pin is #14. The far right column shows that (-) 12 VDC should be present between pin #14 and pin #1 (common) on the 16-pin connector. 4. Set meter to read DC voltage. Place meter between pins #1 and #14 and check for (-) 12 VDC (common side of meter on pin #1). If signal is present, the problem is in the module or motor. If signal is not, problem is either in wiring harness or Fan Control Board. These steps operation. can be repeated for other modes of 12-PIN PLUG (PL-1)ON FAN CONTROL BOARD 1. Unplug harness from board. 2. Check for appropriate voltages on pins with Fan Control Board screw terminals jumpered. (Refer to Table 6 for values and refer to example below.) 20 496 01 5001 03 Table6 WiringConnectionsof FVMFanCoil WiringHarness WIRINGHARNESS CONNECTION 16-1NPLUGONWIRINGHARNESS TO MOTOR TOFANCONTROLBOARD Pinon 16-Pin Plug Pinon 12-pin plug or Set-up Selection Description 1 Common 2 W1 3 WireColor Signalon Pinwith ScrewTerminal Jumperedto R* Pin 9 on PL-1 Brown Pin 7 on PL-1 Violet Common Pin 10 on PL-1 Orange 4 On/Off Delay Selection On/Off Delay Selection White 5 AC/HP Size Selection AC/HP Size Selection Blue 6 Y1 Pin 3 on PL-1 Black 7 AC/HP CFM Adjust Selection AC/HP CFM Adjust Selection Black 8 Not Used N/A Not Used 9 System Type Selection System Type Selection Orange 10 Dehumidify Pin 12 on PL-1 Gray 11 Aux Heat Size Selection Aux Heat Size Selection Violet 12 24V AC Pin 8 on PL-1 Red 24VAC continuous 13 W2 Aux Heat Stage 2 Pin 4 on PL-1 White 24VAC** 14 Y/Y2 Single Stage AC or HP, High Speed Two-Stage AC or HP Pin 2 on PL-1 Yellow (-) 12DC** 15 G Fan Pin 1 on PL-1 Green 24VAC** 16 Not Used N/A Not Used Aux Heat Stage 1 Low Speed AC or HP 24VAC** (-) 12VDC** 0V (24VAC on no call) * Check voltages with 16-Pin Plug disconnected from motor. ** These signals will start motor. D. VERIFY MOTOR WINDING SECTION To check Fan Control Board: 1. Leave jumper wire in place between R and Y/Y2. 2. Check Table 6 under"Wiring Harness Connection to Fan Control Board" column and row for pin #14 to see pin# on Fan Control Board that should have voltage. The correct pin is #2. The column on far right will show voltage that should be present between pin #2 and #9 (or #10 common). Place meter between pins #2 and #9 and Fan Control Board and check for (-) 12 VDC 3. 4. If voltage is present, the wiring harness is bad; if not, the Fan Control Board is bad. 496 01 5001 03 Before proceeding with module replacement, check the following to ensure motor winding section is functional. With control module removed and unplugged from winding section: 1. The resistance between any 2 motor leads should be similar. 2. The resistance between any motor lead and the unpainted motor end plate should be greater than 100K ohms. If motor winding section fails one of these tests, it is defective and must be replaced. 21 START-UP PROCEDURE Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details. CARE AND MAINTENANCE For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. The system should be regularly inspected by a qualified service technician. Consult the servicing dealer for recommended frequency. Condensate Drain During the cooling season check at least monthly for free flow of drainage and clean if necessary. An inspection port is provided on all A-coil delta plates. Remove plastic plug to inspect. Between visits, the only consumer service recommended or required is air filter maintenance and condensate drain operation. Air Filter PRODUCT DAMAGE HAZARD The only required maintenance that may be performed by the consumer if filter maintenance. Failure to follow this caution may result in poor unit performance and/or product damage. Inspect air filters at least monthly and replace or clean as required. Disposable type filters should be replaced. Reusable type filters may be cleaned by soaking in mild detergent and rinsing with cold water. Install filters with the arrows on the side pointing in the direction of air flow. Never operate unit without a filter. Factory authorized filter kits must be used when locating the filter inside the unit. For those applications where access to an internal filter is impractical, a fieldsupplied filter must be installed in the return duct system. 22 496 01 5001 03 R-410A QUICK REFERENCE GUIDE ° R-410A refrigerant operates at 50% - 70% higher pressures than R-22. replacement components are designed to operate with R-410A. Be sure that servicing equipment and ° R-410A refrigerant cylinders are rose colored. ° Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. ° R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose. ° Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard. ° Use hoses with 750 psig service pressure rating. ° Leak detectors should be designed to detect HFC refrigerant. ° R-410A, as with other HFC refrigerants, is only compatible with POE oils. ° POE oils absorb moisture rapidly. Do not expose oil to atmosphere. ° POE oils may cause damage to certain plastics and roofing materials. ° Vacuum pumps will not remove moisture from oil. ° A liquid line filter-drier is required on every unit. ° Do not use liquid line filter-driers with rated working pressures less than 600 psig. ° Do not install a suction line filter-drier ° Wrap all filter-driers in liquid line. and service valves with wet cloth when brazing. ° Do not use with an R-22 TXV. ° If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV. ° Do not use capillary tube indoor coils. ° Never open system to atmosphere while it is under a vacuum. ° When system must be opened for service, break vacuum with dry nitrogen and replace all filter-driers. ° Do not vent R-410A into the atmosphere. ° Observe all WARNINGS, 496 01 5001 03 CAUTIONS, NOTES, and bold text. International Comfort Products, LLC Lewisburg, TN 37091 USA 23
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 23 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Tue Oct 02 04:14:29 2012 Author : Title : Subject :EXIF Metadata provided by EXIF.tools