ICP Air Handler (indoor Blower&evap) Manual L0502498

User Manual: ICP ICP Air Handler (indoor blower&evap) Manual ICP Air Handler (indoor blower&evap) Owner's Manual, ICP Air Handler (indoor blower&evap) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 14

DownloadICP  Air Handler (indoor Blower&evap) Manual L0502498
Open PDF In BrowserView PDF
INSTALLATION
INSTRUCTIONS
Models
FCV2400C2
FCV3600C2

FCV4800C2
FCV6000C2
Requires
AMF001NHA
Accessory
No Heat Kit

Use ONLY factory listed electric heaters.

General Information / Installation ............
Upflow Installations
........................
Horizontal Installations .....................
Ductwork Connections
.....................
Filter Installation ...........................
Condensate Drain ..........................

2
3
3
3
4
5

Refrigerant Lines ...........................
Electrical Connections ......................

5
6

Motor Speeds and Airflow ...................
Blower Performance ........................
Checks and Maintenance ...................

7
9
10

Wiring Diagram ............................
Replacement Parts .........................

11
12

Variable Speed Fan Coils
Safety Labelingand Signal Words
Danger,Warning and Caution
The signal words DANGER, WARNING and CAUTION
are used to identify levels of hazard seriousness. The
signal word DANGER is only used on product labels to
signify an immediate hazard. The signal words WARNING and CAUTION will be used on product labels and
throughout this manual and other manuals that may apply to the product.
DANGER - immediate hazards which WILL result in severe personal injury or death.
WARNING
- Hazards or unsafe practices which
COULD result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which COULD
result in minor personal injury or product or property
damage.

Printedin U.S.A.

Signal Words in Manuals
The signal word WARNING is used throughout
manual in the following manner:

this

The signal word CAUTION is used throughout
manual in the following manner:

this

CAUTION
Product Labeling
Signal words are used in combination with colors and/or
pictures on product labels.

496 01 4109 02
June 2002

Fan Coils ]

_ Installation Instructions

FigUre

Dimensions

and Clearances

14-3/8"
17-7/8"
/8"

(2 Ton)
(3 Ton)
(4 / 5 Ton)

CLEARANCES
NO HEATERS
All Sides ..................................
From Supply Duct ..........................
Recommended Service From Front ..........
(Service for blower, filter if installed)

8 1/2"

42"

WITH HEATERS
All Sides ..................................
From First Three
Feet of Supply Duct to Combustibles
........
From Duct after Three Feet .................
Recommended Service From Front ..........
(Service for blower, filter, heaters if installed)

(2&3 Ton)
52"
(4-5

Ton)

0"
0"
20"

0"
1"
0"
20"

Filter Door

Fire Hazard
_F

16-3/8

./

21

1/2"

W

(2 Ton)_

19-7/8 '' (3 Ton)
27-1/8 '' (4 / 5 Ton)

BottomReturnAir Opening
14 1/2X20
2Ton
18X20
3Ton
251/4X20
4-5 Ton

When heaters are installed maintain clearances from combustible materials as specified on unit rating plate. Do not use plastic
lined or combustible flexible ducting within 36
inches of the supply end of the air handler.
Failure to do so can result in fire, property
damage, personal injury and/or death.

38-20-17

GeneralInformation

Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes and with the
National Electrical Code NFPA70 current edition.
The information contained in this manual is intended
for use by a qualified service technician familiar with
safety procedures and equipped with the proper tools
and test instruments.
Failure to carefully read and follow all instructions in
this manual can result in equipment malfunction,
property damage, personal injury and/or death.
The blower cabinet may be used for cooling or heat pump operation with or without
electric heat. Installations
without electric
heat, require a No Heat Kit.The cabinet can be installed in an upflow or horizontal
position (Figure
2, 3). Horizontal
installations

_J

require a horizontal
kit. Some models are shipped with the horizontal kit already installed .These units are not shipped with air filters installed.
Filter must be field supplied,
either washable
or
disposal type. Washable
filters are available as an accessory.

Location
Select the best position which suits the installation site conditions.
The location should provide adequate structural support, space in
the front of the unit for service access, clearance
for return air and
supply duct connections,
space for refrigerant piping connections
and condensate
drain line connections.
If heaters
are being
installed make sure adequate
clearance
is maintained
from supply ductwork,
See Clearances
and Warning
in Figure 1.
NOTE: Internal filter can be accessed from separate filter door. If
the filter can NOT be easily accessed,
a remote filter is recommended.
Refer to ACCA Manual D for remote filter sizing.
If the unit is located in an area of high humidity, nuisance sweating
of casing may occur. On these installations
a wrap of 2" fiberglass
insulation
with a vapor barrier should be used.

496 01 4109 02

Fan Coils

Installation Instructions ]

Upflow Installations
The unit is ready to install in the upflow position without modifications.

Figure 3

Airflow Positions

HORIZONTAL LEFT POSITION

The unit MUST be supported
on the bottom ONLY and set on a
supporting
frame or shelf. Use screws through the bottom to anchor to supporting
frame.

,,=,

Figule 2

I

Airflow Positions

UPFLOW POSITION
HORIZONTAL RIGHT POSITION
HEAll_R

,,=,
m

38-20-19

3. Position side of coil drain pan into horizontal
drain
trough on deep end of pan on right side of coil.
o

4

O_
38-20-19

RLTER

Remove coil drip flanges from A-coil
side of coil (same side as horizontal

and reinstall
drain pan).

pan

on right

5. Remove the coil support
bracket from the left side of the
cabinet and reinstall bracket on the right side of the cabinet.
6. Install drain plugs as required in back side of horizontal
drain pan. Install plugs in A col! drain pan to prevent air
leaks.

Non-Ducted Return Air Closet Installation
The cabinet

can be installed

in a closet with a false bottom

to form

7. Slide coil assembly
sulation.

into cabinet

being careful

not to tear in-

a return air plenum, or mounted
on an open platform
inside the
closet. Platform should be high enough to provide a free (open)
area for adequate
return airflow into the bottom of the cabinet.
The open area can be on the front side or a combination
of front
and sides, providing there is clearance
on the sides between cabinet and closet. Refer to ACCA Manual D for sizing and free
area recommendations.

NOTE: Be sure A coil pan fits into the support bracket on the back
side of the cabinet and that pan is under the flange of the bracket
on the right side. The brackets fit over the top edge of the A coil
drain pan to hold it when it's put into the horizontal
position.

NOTE: Local codes may limit application of systems without a
ducted return to single story dwellings.

Cabinet

Horizontal Left and Right Installations
Units that are shipped with the horizontal
drain pan installed are
set up for horizontal
left hand airflow. They must have the drain
pan repositioned
for right hand airflow. All other units must have
the horizontal
drain pan kit installed for either left or right hand applications.
For installation
of the drain pan, refer to the installation
instructions
included with the horizontal
drain pan kit, and the fo!lowing.

CAUTION
Afield-fabricated
auxiliary drain pan, with a seperate
drain is
REQUIRED
for all installations
over a finished living space or
in any area that may be damaged
by overflow from the main
drain pan. In some localities,
local codes require an auxiliary
drain pan for ANY horizontal
installation.

Drain Pan Installation / Conversion for Right Hand Airflow
See Figure 4

8. Refer to Restrictor Orifice Selection and change
necessary,
then install
coil access panel.
can now be placed

on it's side for horizontal

if

airflow.

SuspendedCabinetInstallation
1. The cabinet may be supported
be suspended.

on a frame or shelf, or it may

2. Use metal strapping
or threaded
rod with angle iron supports under the auxiliary
drain pan to suspend
cabinet.
These supports
MUST run parallel with the length of the
cabinet (Figure 5 ).
3. Ensure
access

that there is adequate
panels after installing

4. Place Styrofoam
cabinet.

blocks

room to remove service
supporting
brackets.

in auxiliary

drain

and

pan to support

Duct Connections
SupplyDuct
Supply duct must be attached to the outside of flange on outlet
end of unit. Flexible connectors
may be used if desired. Maintain
clearances
from supply duct to combustibles
when heaters are
installed.
See Figure
1 and unit rating plate.

1. Remove coil access panel and carefully pull Coil/Horizontal Drain Pan Assembly out.

ReturnDuct

2. Separate horizontal drain pan from coil drain pan. The coil
drain pan fits snuggly inside the horizontal pan.

Return duct should be attached
al screws or other fasteners.

496 01 4109 02

restrictor

to bottom

of unit using

sheet met-

3L_

Fan Coils I

_ Installation Instructions
FigUre 4

Horizontal Drain Pan

Drip Flange mounts to
top two holes in coil plate
Horizontal Drain Pan
(Left Hand Airflow)

Coil Support Bracket
(Right

Hand

Airflow)
\

il Support

Bracket

Filter Door

Coil Support Bracket

Coil Access Panel

(Left Hand Airflow)
--_

Drip Flanges
(Left Hand Airflow)

Plug drains
on back side

Horizontal Drain Pan
(Right Hand Airflow)
Drip Flanges
(Right Hand Airflow)

Filter Installation

38-20-06

Figure 5

Horizontal Installation

Filters must be field supplied. The blower cabinet is set up for an
internal filter or a remote filter grille or other means may be provided. Refer to ACCA Manual D for remote filter sizing.
To install an internal filter, remove screw securing filter door and
slide filter into unit. Some filters are marked for airflow direction,
make sure arrow points towards blower if marked. Washable
filters are offered as an accessory.
Disposable
filter sizes are listed
in Filter Static Pressure
Drop Table.

S

MUST
upports

_J

runpara

II I
h Field'FabricatedDrain
Pan
e wit
blowercabinet

=_-o=

496 01 4109 02

I Fan Coils

Installation

Instructions

CondensateDrain Connections
The unit is provided with 3/4" National Pipe Thread (NPT) condensate drains. (Figure 1). Any drain can be used as a primary or
secondary
drain depending
on the fitting used. Condensate
drain
lines should be installed in a manner that does not obstruct access to the filter.
There is a secondary
drain fitting supplied with the unit that will
convert any of the primary condensate
drain connections
into a
secondary
drain connection.
This fitting should be installed in any
of the primary drain connections
to convert it to a secondary
drain.

Figule

6

Condensate

3. Routetotheoutsideor
line (sewer).
Check
sewer line.

toafloor
drain, laundrytrayorwaste
local codes before connecting
to a

4. Insulate
damage.

where

drain

lines

sweating

could

cause

water

5. If a gravity drain cannot be used, install a condensate
pump. Install the pump as close to the indoor section as
possible.

Waste Line Connection

Drain Fittings

If the condensate
line is to be connected
to a waste line, an open
trap must be installed ahead of the waste line to prevent escape of
sewer gases. NEVER CONNECT
THE DRAIN LINE DIRECTLY
TO A WASTE
LINE. ALWAYS
INCLUDE
AN AIR GAP AND
TRAP, (Figure
7). Be sure to keep the trap filled with water during
the winter or off season.

,oureJ
Secondary
Drain Fitting
(small hole)

Primary Drain
Fitting

Condensate Drain to Waste Line
Air Gap Above
uid Level

Condensate
Line

1. Connect the drain lines to the appropriate
drain fittings. 3/4"
PVC or other type of drain line may be used. The drain line
must not be smaller than the drain fitting.

Trap

2. Install a trap in the drain line below the bottom of the drain
pan and pitch the drain lines down from the coil at least I/4"
per foot of run. Horizontal
runs over 15 feet long must also
have an anti-siphon
air vent (stand pipe), installed ahead
of the horizontal
run. An extremely
long horizontal
run may
require an oversized
drain line to eliminate air trapping.

Sewer Li_

RefrigerantLine Connections
Size refrigerant
lines according
to information
provided with outdoor condensing
unit. Route the refrigerant
lines to the coil in a
manner that wil! not obstruct service access to the unit or removal
of the filter.
1. Remove rubber plugs from refrigerant
connections
using a
pulling and twisting motion. Hold refrigerant
lines to avoid
bending or distorting.
2. Remove the coil door before brazing refrigerant
tions to prevent damage to paint finish.

I

Gasket

Refrigerant

Lines

,,_
j

Tubing Plate

connec-

3. Fit refrigerant
lines into coil connections
and remove the
tubing plate and slide plate over the refrigerant
lines to assure sufficient
room for brazing.
4. Reinstall tubing plate and door and install the gasket, provided with the unit, over the suction and liquid lines into the
tubing plate recess to ensure an air seal around the coil.
See Figure 8.

496 01 4109 02

Figule8

Refrigerant

k_n
e_s__

"

Recessed
Area
For Gasket

.%

5[_

I Installation

Fan Coils I

Instructions

ElectricalConnections
Connect field wiring to appropriate
terminals on electric
lugs on the No Heat Kit. All line voltage connections
made with copper wire.

Electrical shock hazard.

heater or
must be

LineVoltageConnection
Turn OFF electric power at fuse box or service
panel before making any electrical connections
and ensure a proper ground connection is made
before connecting line voltage.

1. Provide
separate

line voltage power supply (208V-240V)
circuit(s). Size per table or table in heater

from a
manual.

2. Connect line voltage to the lugs on the No Heat Kit., or to
circuit breakers or wire leads from heaters. Refer to Figure
9 and wiring diagram.

Failure to do so can result in property damage,
personal injury and/or death.

Grounding Connection

All electrical work MUST conform with the requirements
of local
codes and ordinances
and the National Electrical Code NFPA 70
current edition.

Use a copper conductor(s)
from the ground lug on the No Heat Kit
or ground lugs on the electric heater to a grounded connection
in
the electric
service panel or a properly
driven and electrically
grounded
ground rod.

The low voltage transformer
and the fan control are standard on
all models
and are prewired
at the factory.
Line voltage
connections
are made to the heater accessory or the lugs on the
No Heat Kit.

Overcurrent Protection
Figure
The power supply wiring to the
overcurrent
protection.
Governing
fuses ONLY or circuit breakers.
For blower
used.

cabinets

without

unit MUST be provided
with
codes may require this to be

heaters,

a 15 amp

circuit

9

Electrical

Controls

Low Voltage _

Matching Receptacle

may be

or Electric Heater

No Heat Kit Installation
Connections __
If electric

heat is not used,

1. Locate
adapter
package.
2. Attach adapter
match cabinet,
3. Secure

install

and

accessory

filler

plates,

with

screws

plate and filler plate to bracket
Refer to Figure 9.

the No Heat Kit accessory

if required

Filler Plate
(4-5 Ton)

to

Adapter
(3 Ton)

with four screws.

Plate _

.oHeat
_:_!

CAUTION
to force

For No Heat Kit

inside

4. Connect
the plug from No Heat Kit wiring
into the
receptacle
on the control board on the side of the cabinet.

Do not attempt

_

No Heat Kit.

....

plug as it only fits one way.

Line Voltage Connections

Lugs for
Line Voltage
and Ground
Connections

Line voltage wiring may be brought into the unit through the top
right-hand
corner or the right-hand
side panel. The correct hole
size required by the conduit fitting must be punched at the pilot
hole location. Plug the un used pilot hole with a hole plug (supplied
with unit).

Maximum

Recommended

Overcurrent

Supply Circuit

Supply

Nominal

Branch

Protective

Circuit

Motor

Motor

Total

Circuit

Device

Maximum

SupplyWire
Ground

75ec, Copper
Max.

Wire

Volts

Phase

Hertz

No,

H.P,

AMPB.

AMP8,

Ampacity*

(AMPB,)

No,

Size

Length (Ft)

No.

Size

240

1

60

Single

1/2

33

33

3.8

15

2

14

104

1

14

208

1

60

Single

1/2

33

33

3.8

15

2

14

90

1

14

240

1

60

Single

1

66

66

6.9

15

2

14

104

1

14

208

1

60

Single

1

66

66

6.9

15

2

14

90

1

14

* Based on maximum ampacity allowed by Magellan control program.

496 01 4109 02

I Fan

Coils

Installation

LowVoltage Control Connections

Adjusting ThermostatAnticipator

The 24 volt power supply is provided
by an internally wired low
voltage transformer
which is standard
on all models. If power
supply is 208 volt, the low voltage transformer
must be rewired to
the 208 volt tap. See the unit wiring label.

Set the heat anticipator
instructions
provided
adjustment.

Field supplied low voltage wiring can enter the unit on the top left
hand corner* or the left hand side panel. When using the left hand
side panel entrance,
the low voltage wiring must be fed through
the entrance hole in the bottom of the blower deck into the control
area.

Install the strain relief bushing (supplied with unit) in the selected
hole and a hole plug (supplied
with unit) in the unused hole.
Connect
the field wiring at the screw
board. Refer to Figure 9.
Keep the low voltage
box.

wiring

terminals

as short as possible

of the

Size

of the thermostat
to the proper value.
with the thermostat
before making

- KW

Anticipator

05

.24

07, 10

.32

See
this

Setting

Adding Humidistat or Outdoor Thermostat

control

inside the control

Complete connections between indoor blower, outdoor section,
indoor thermostat and electronic outdoor thermostat (accessory)
according to instruction provided with the Condenser Installation
Instructions or those provided with the accessory and refer to
Figure 9.

Figure i0

Heater

Instructions

Adding a humidistat
or outdoor thermostat
allows the airflow to be
reduced
to 80% of normal
allowing
greater
humidity
control.
Humidistats
are preferred but an outdoor thermostat
can be used
but can only be set based on temperature.
Suggested
starting
point is 85 F, but this will vary depending
on several factors.
The control must be wired
pumps. On air conditioners
ref Figure 10.

differently
on air conditioners
and heat
connect to Y and Dehum terminals H,

HEAT PUMPS ONLY: Heat pumps must use only the outdoor
thermostat, because it is powered instead of just performing a
switching function. This allows it to be out of the circuit when
continuous circulation is desired, which is required for the system
to operate on Fan Only for circulation, which is 60% airflow. On
heat pumps connect to Y and Dehum terminals H, and C and O to
power the outdoor thermostat, ref Figure 11.

[ Typical Low Voltage Schematic

Cooling Only

ElectricHeater Staging

Thermostat

Outdoor

R

Unit

The heater
G

Y
Y

Y
W

are turned

on in increments.

Refer to Heater

A control signal (24V) from Wl on the Indoor T'stat to Wl on the
control board energizes
the 1st stage of heat. A control signal
(24V) to W2 on the control board energizes
the second stage of
electric heat. To turn ON both stages at the same time, using one
control signal, W1 and W2 are jumpered
together.

OO
W2 W 1

elements

Staging Table in the Heater Installation
Manual. In addition on
heaters larger than 5KW, the heat can be staged (1 st & 2nd) either
through an indoor thermostat
or by using an outdoor thermostat.
This satisfies
staging requirements
imposed
by some electric
utilities on heaters larger than 6 kilowatts.

--

G

Y
Indoor

O

H

If the indoor
thermostat
does not have staging
capabilities,
accessory
electronic
outdoor thermostats
are available that will
control two stages of electric heat.

Blower

Motor Speeds and Airflow
Air Conditioner - Adding Control for 80% Airflow

See

Figure

12 and

Page

8.

The motor speed can be set on one of eight speeds and the air
flow will adjust between
60%, 80% and 100% depending
on
settings. Time ON / OFF settings can also be adjusted.

0bo

W 2 W 1

G

Y
Indoor

oO

Blower

H

C
oo

R

Determine
coil static pressure
drop,
measure
duct system static pressure,
speed setting from blower charts.

consult
coil manual and
then determine
required

For Cooling - Set switches 6, 7, and 8 on the motor end bell to
position 0 (off) or 1 (on) as specified on blower charts.
For Heating - Set switches 3, 4, and 5 on the motor end bell to
position 0 (off) or 1 (on) as specified on blower charts.
Humidistat or Outdoor Thermostat

Set switches
1 and 2 to position 0 (off) or 1 (on) as specified
Figure 12 to control Fan delay ON - OFF.
NOTE:
switch

496 01 4109 02

in

Power must be completely
OFF to unit any time
settings are changed or settings will not take effect.

7L_J

_ Installation Instructions

Figure

1i I

Fan Coils I

Typical Low Voltage Control Schematic

L

Staging
_ermostat
R

Cooling with Electric Heat
Thermostat

R
G

R

G

Heat Pump with Electric Heat

BL

c

-Y

W

o
--

Y

y

Y

Outdoor Unit

O

w1

Outdoor Unit

w2

t

C
r

R

w

Air Conditioner - Adding Control for 80% Airflow

o oooo

W2 W 1

G

Y

Indoor

O

H

C

Heat Pump - Adding Control for 80% Airflow

R

Blower

©©
W2 Wl

G

Y
Indoor

O

H

C

R

Blower

Humidistat or Outdoor Thermostat
Outdoor Thermostat

Figure

12[

Motor Speeds
See next page for switch positions and CFM range
Heat
CFM
Select

Time
Delay Select

=1

Cool
CFM
Select

=

II

=

I
1 Positions

1

2

3

4

5

6

7

8

0

(on)

Switch (off)

Available Selections:
Time Delays:
00 0 sec. on/60 sec. off (default)
01 0 sec. on/90 sec. off

Motor Controller mounted to blower housing

_J

10 0 sec. on/30
11 0 sec. on/0

sec. off
sec. off

496 01 4109 02

I Fan Coils

Installation

Instructions

NOTE:
Both sets of
switches must be set
FCV24
Dip Switch Settings
are set at switches
6, 7 and 8 for
Cooling, 3, 4, and 5
for Heating.

1400,

1200,

1000,

IJ_

Dip Switch Settings

800,

0

000 Highest Speed
111 Lowest Speed

600,

400,

200
0.1

0.2

0.3

I

I

I

I

0.4

0.5

0.6

0.7

EXTERNAL

For Heat Pumps both
sets of switches should
be set the same.
08

For electric heat the
heat switches can be set
to obtain a comfort level
within the specified heat
rise of the unit.

STATIC

Dip Switch Settings - 000 Highest Speed 111 Lowest Speed
Dip Switch Settings are set at switches on the motor controller.
"0" is OFF Position, "1" is ON Position
FCV36
1600 o
I
I
I
I

I
I
I
I

I
I
I
I

I
I
I
I

I
I
I
I

I
I
I
I

0.3

0.4

0.5

0.6

0.7

0.8

1400,

1200,

1000,
LL

L)

800,

600,

400,

200

i

0.1

0.2

0.9

ExternalStatic

496 01 4109 02

9L_

_ Installation Instructions

Fan Coils ]

NOTE:
Both sets of
switches must be set

FCV48
2200,

Dip Switch Settings
are set at switches
6, 7 and 8 for
Cooling, 3, 4, and 5
for Heating.

2000,

1800,

000

1600_

001

1400,

010

Dip Switch Settings

LI.

0
u)

1200q

000 Highest Speed
111 Lowest Speed

011

1000_

100

For Heat Pumps both
sets of switches should
101 be set the same.

800,

110 For electric heat the

600,

400

_
0.1

0.2

0.3

_
w

_

i

0.4

0.5

0.6

External

0.7

heat switches can be set
to obtain a comfort level
within the specified heat
rise of the unit.

0.8

Static

Dip Switch Settings - 000 Highest Speed 111 Lowest Speed
Dip Switch Settings are set at switches on the motor controller.
"0" is OFF Position, "1" is ON Position
FCV60

2200,
I
I

I
I

I
I

I
I

2000,

1800,

000
001

I

1600,

I
I

I

I

I

1400,

010

LL

L_
u)

1200,

011
1000,

100
800,

101
110

600,

400

111

w

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

External Static

l_J

496 01 4109 02

I Fan Coils

Installation
FILTER

STATIC

PRESSURE

DROP*

*WASHABLE
FILTER SIZE

DISPOSABLE
FILTER SIZE

FCV24

14 1/4 X 20 1/4

14 X 20

FCV36

17 31/4 X 20 1/4

18X20

.......

25

.......

MODEL

FCV48/FCV60

24 3/4

X 20

1/4

X 20

Air Flow Check

CFM
600

800

1000

1200

.05

.09

.13

.19

0.09

0.12

1400

1600

1800

0.17

0.22

......

0.09

0.11

0.14

2000

............

......

0.18

TemperatureRise Check

For proper system operation, the air flow through the indoor coil
should be between 350 and 450 cfm per ton of cooling capacity.
The air flow through the unit can be determined by measuring the
external static pressure to the unit and selecting the motor speed
tap that will most closely provide the required air flow.
1. Set up to measure external static pressure at the supply
and return duct connections (Figure13).
2. Drill holes in the ducts for pressure taps, pitot tubes, or
other accurate pressure sensing devices.

Temperature
rise is the difference
air temperatures.
NOTE:
heating

A temperature
recommended.

rise

greater

ALL registers

than

60

and return

by changing
block.

OF (33.3

°C)

5. Turn electric

power

NOTE:

is

not

8. Turn electric

LEAST

5

as high as it wil! go.

minutes,

air temperature

to normal
power

to HEAT.

setting

ON.

The maximum
outlet
is 200 OF (93.3 °C).

7. Set thermostat

selector

temperature

6. Operate
unit
AT
temperature
rise.

temperature

then

check

for all models
setting.

OFE

9. Be sure to seal al! holes in ducts if any were created
this process.

/nedt I°rn

the

and duct dampers.

Heat-Coo!

4. Set the thermostat

s.pply ___¢
)

the supply

1. To check the temperature
rise through
the unit, place
thermometers
in the supply and return air ducts as close to
the unit as possible.

3. Set thermostat

static Pressure Check

between

The temperature
rise can be adjusted
speed tap at the unit's blower terminal

2. Open

Figure

Instructions

during

Maintenance
Filters
3. Connect
gauge.

these taps to a level inclined

4. Ensure the coil and filter are clean,
open.
5. Determine
operating.

the

external

static

manometer

or draft

and all the registers

pressure

with

the

are

8. Recheck the external static pressure
and confirm speed switch selection.

496 01 4109 02

must be cleaned when they become dirty. Inspect at least
per month. The frequency
of cleaning depends
upon the
of operation
and the local atmospheric
conditions.
Clean
keep unit efficiency
high.

Lubrication

blower

The bearings of the blower motor are permanently

6. Refer to the Air Flow Charts, pages 9 & 10 to find the Dip
Switch Speed setting that will most closely provide the
required air flow for the system.
7. Refer to Motor Speeds and Airflow
the speed is to be changed.

Filters
once
hours
filters

in these

instructions

with the new setting,

if

lubricated.

Condensate Drains
During the cooling season check the condensate
drain lines to be
sure that condensate
is flowing from the primary drain but not
from the secondary
drain. If condensate
ever flows from the
secondary
drain the unit should be promptly
shut off and the
condensate
pan and drains cleaned
to insure a free flowing
primary drain.

1_

I Installation Instructions

Fan Coils I

BASE LIMIT OPTIONAL
NO-HEAT
KIT AMF001NH
INSTALLED
*SEE INSTALLATION
MANUAL
FOR PROPER
HEATING
AND COOLING
FACTORY
PRF-RFT
RPFFI3
CC)NNFCTIC)NR
FOR YC)I JR I JNIT

AMFK20AH

r

B

It-

o...g,'.o _

II
D_3_r
_

_I_BL

_L1

1,
II

L-_I
B____,

BL

IR_ ,/

5 Kw

- Y
AMFK05AH

BL_I_--

ELECTRIC

_

I"

al_

Y

0

I_I-_-2-___ IIIC
..=-1q-¢l

w_., L--H-_,_

F"_ - -I

BKJ

_i

,i_i", II _P_°=_ol
rhu_o

b,_if.vb ,_i_,

I

BL

Y

._ilit;

! 4_,_o_
__-,__7.5&

r

Y

_Y

--_h
_.i.i_'-_", B_T-"I I III _°
.r7_-q-F_---f-__
I I Il=-H-m

0*.

--1

- ! "1

/

_!_LIMIT
_

i!l
__i:-F-._ / IIII
;tl P-_-_IF_ P_L I II1_ -m

HEATER

LIMIT

-X

5 Kw

B_HI

_,

-_
_I_BL

I

'----"_L,M,T
IV _-T_

HEATER

p/_

_//_Y

I

GRD

BKF

--_LIMIT

ELECTRIC

Gy I

10 Kw

_____L____L_____,_

_o"
BKI

..

IY

AMFK25AHL
R

ELECTRIC

f
' _

r

HEATER

\

%

BYKB_Y
" "

LIMIT
O

B

\
'_
--

AMFK07AH

/ AM FK10AH

,

L

ELECTRIC

7

HEATER

LIMIT

_

H

BLI

--'--I

--_r

_--

I

-_ ,___L

,,
_y_2_'O

' 1130
I

//_=
,y

BI"

BK_
BK

AMFK14AH
*AMFK15AH

ELECTRIC
ELECTRIC

HEATER
HEATER

(2 LIMITS)

AMFK30AH

ELECTRIC

HEATER

1087574

496 01 4109 01

I Fan Coils

Installation

Instructions

ReplacemaentParts

Z2
w

X

\

13

12

11

GG
A

\

BB
8

FF

H

AA

GG
CC

JJ

38-11-25

496 01 4109 01

I Installation

Fan Coils I

Instructions

ReplacemaentParts
O4

KEY

DESCRIPTION

NO,

PART
NUMBER

(j
o
,_
>N
(J
LL

1
1
1

Coil, Evap EXA24B15A
EXA36F19A1
EXA48N26A1

........
.......
.......

1

EXA60N26A1

.......

€'4

_j
o
{o
>_
(J
It.

rj
o
o
>_°
(J

LL

LL

KEY
NO.

DESCRIPTION

L
O
O
O
P
P
P

Bracket, Colt Hold Down
Panel, Rear Blower Deck

Q
Q
Q
R
S
S
S

Panel,Side Blower Deck

Panel, Top

1

V
V
V
W
W
W

Housing, Blower

X
X
X

Panel, Blower Cutoff

1
1
1

Manifold, Evaporator Suction

4
4
4

Valve, Expansion

6
7
7

Distributor Assembly
Pan, Drain, 15"
19"

.......
1082775
1082776

1

7
8
8

26"
Pan, Drain Horizontal

1085353
1082619
1082621

1

9
10

Control, Fan Timer
Transformer

1085914
1082611

1
1

1
1

11
11

Motor, Blower

1012478
1012479

1

1

12
12
12

Mount, Blower Motor

1050254
1066700
1057955

1

13
13
13

Wheel, Blower

600585
600587
96839

1

14
14

Control, Motor

1012476
1012477

1

A
A

Baffle, Top

1082955
1082956

1

B
B
B

Plate, Triangular

1082779
1082924
1082782

2

C
D
F
F
F

Plug, Drain Pan
Plug, Drain Pan
Wrapper

1083241
1082965
1082601
1082825
1082827

4
1
1

H
K
K

Plate, Tubing
Grommet, Tubing Plate

1085601
1085603
1085602

1
1

1_

N

(j
o
co
_
(J

1

2
2
2
2
3

Distributor

O4

1083246
1083253
1083310
1083258
1062727

1

1

1

1082871
1082873
1087341

1

1

1
1
1

1
1

1
1

1
1

1

1

1

1
1

1
1

1

1

LL

1

1

1

1

1

1

1082622
1082847
1082849
1085371
1082609
1082927
1082929

2
2
1

2
1

1

1

1082610
1082835
1082837

1
1

1

1087343
1087193
1087194

1
1

1

1082607
1082616
1082949

1
1

1

1085504
1085521
1085189
t085t90
1085192

1
1
1

1
1

1
1

1

1

1085301
1082838
1082840

1
1

1

1085194
1085195
1085197

1

1

Door, Filter Access

2

2

4
1

4
1

DD
EE

Plate, Heater Adapter
Plate, Heater Filler

1084606
1084608

FF
GG

Clamp. Tube
Shield, Condensate

1063118
1083333

1

1

1

1

JJ
)(
)(
)(

Adapter,
Harness,
Harness,
Harness,

1085010
1087518
1087519
1087049

1

1

)(

Manual, Installation

1

1
1

1

2

1
1
1

LL

1

CC
CC
CC

1
1

Mate (Drain)
Wire
Wire
Wire

O
O
o
o

LL

Door, Blower Access

1

IN

O
O
o
co
_

1
1

BB
BB
BB

1

IN

O
O
o
_
0_

LL

Rail, Blower R.H.
Rail, Blower L.H.
Door, Coil Access

1

4
1

Bracket, Control Fan
Bracket, Drain Pan

1_1

O
O
o
v
_

1082602
1082604
1082844
1082846
1086694
1085372
1085374

Zl
Z2
AA
AA
AA

1

1

Panel, Front Blower Deck

PART
NUMBER

1_1

49601410900

1
1
1

2
1
1

1
1

1

1

1
1
1
1

1

1
1

1

1

1
1

1
1

1
2

1
2

1
2

1
2

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1

1

1

1

496 01 4109 01



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 14
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Apr 20 16:22:39 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu