ICP Air Conditioner/heat Pump(outside Unit) Manual L0522718

User Manual: ICP ICP Air conditioner/heat pump(outside unit) Manual ICP Air conditioner/heat pump(outside unit) Owner's Manual, ICP Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 12

INSTALLATION INSTRUCTIONS
Split System
Performance Line
AC & HP Condensers
These instructions must be read and understood completely before attempting installation.
Installation /Startup Information & Warranty
Installation or repairs made by unqualified
persons can result in hazards to you and others.
Installation MUST conform with local building
codes or, in the absence of local codes, with the
the National Electrical Code NFPA 70/ANSI
C1-1999 or current edition and Canadian
Electrical Code Part 1 CSA C.22.1.
The information contained in this manual is
intended for use by a qualified service technician
familiar with safety procedures and equipped
with the proper tools and test instruments.
Failure to carefully read and follow all instruc-
tions in this manual can result in equipment
malfunction, property damage, personal injury
and/or death.
After uncrating unit, inspect thoroughly for hidden damage.
If damage is found, notify the transportation company im-
mediately and file a concealed damage claim.
Locating The Outdoor Unit:
CAUTION
Improper installation, adjustment, alteration, service or
maintenance can void the warranty.
The weight of the condensing unit requires caution and
proper handling procedures when lifting or moving to avoid
personal injury. Use care to avoid contact with sharp or
pointed edges.
Safety Precautions
1. Always wear safety eye wear and work gloves when
installing equipment.
2. Never assume electrical power is disconnected. Check
with meter and disconnect.
3. Keep hands out of fan areas when power is connected
to equipment.
4. R-22 causes frost-bite burns.
5. R-22 is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instruc-
tions and Warranty are to be given to the owner or promi-
nently displayed near the indoor Furnace/Air Handler Unit.
Check local codes covering zoning, noise, platforms.
If practical, avoid locating next to fresh air intakes, vent or
bedroom windows. Noise may carry into the openings and
disturb people inside.
Placement of the unit should be in a well drained area or
unit must be supported high enough so runoff will not enter
the unit.
Do not locate where heat, lint or exhaust fumes will be dis-
charged on unit (as from dryer vents).
Roof top installations are acceptable providing the roof will
support the unit and provisions are made for water drain-
age and the noise or vibration through the structure.
Do not install the unit in a recessed or confined area where
recirculation of discharge air may occur.
Heat Pumps Only: The top surface of platform must be
above average winter snow levels to prevent coil blockage.
421 01 3002 01
Nov., 2003
_Installation Instructions Split System Condensers I
Clearances:
Nominal operating clearances, where practical, are 60
inches (150 cm) above unit for discharge air and 24 inches
(40cm) around coil for intake air on three sides. Clearance
on one side (normally between unit and structure) may be
reduced to 12 inches (30cm). Nominal clearances are
based from a solid parallel object, wall, roof overhang, etc.
Do Not install under roof overhangs without guttering. A
minimum vertical clearance of 60" is required to overhang.
The clearance may be reduced from a single object with a
small surface area, such as the end of a wall, outside cor-
ner of a wall, fence section or a post, etc. As a general rule
the width of the object should equal the minimum clearance
from the unit. For example, a 4 inch (10cm) fence post
could be 4 inches (10cm) from the unit.
Unit Support:
Inside corner locations on single story structures require
evaluation. Large overhanging soffits may cause air recir-
culation in a corner area even though recommended clear-
ances are maintained. As a guide locate the unit far enough
out so that half of the discharge grille is out from under the
soffit.
Two or more units may be spaced with 20 inches (50cm)
between units.
A service clearance of 24 inches (60cm) is desirable from
control box end or side. Control box and corner panel be-
low it can be loosened and moved out to the side to facili-
tate servicing. Internal components can be accessed
through control box corner or top only.
The unit must be level, and supported above grade by
beams, platform or a pad. Platform or pad can be of open or
solid construction but should be of permanent materials
such as concrete, bricks, blocks, steel or pressure treated
timbers approved for ground contact. Refer to Unit Clear-
ances to help determine size of supports etc. Soil condi-
tions should be considered so the platform or pad does not
shift or settle excessively and leave the unit only partially
supported.
CAUTION
Inadequate support could cause excessive vibration and
noise or binding and stress on refrigerant lines resulting in
equipment failure.
To minimize vibration or noise transmission, it is recom-
mended that supports not be in contact with the building
structure. However, slabs on grade constructions with an
extended pad are normally acceptable.
A. Ground Level Installation:
If beams or an open platform are used for support it is rec-
ommended that the soil be treated or area be graveled to
retard the growth of grasses and weeds.
B. Roof Top Installation:
This type of installation is not recommended on wood
frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If
installation is on a flat roof the unit should be 4 inches
(10cm.) above roof level. Four by four posts placed over a
load bearing wall make a suitable mounting platform.
If possible, place the unit over one or more load bearing
walls. If there are several units, mount them on platforms
that are self-supporting and span load bearing walls.
These suggestions are to minimize noise and vibration
transmission through the structure. If the structure is a
home or apartment, avoid (if practical) locating the unit
over bedrooms or study.
NOTE: When condensing unit is to be installed on a
bonded guaranteed roof, a release must be obtained from
the building owner to free the installer from all liabilities.
_J 421 01 3002 01
I Split System Condensers Installation Instructions
Figure 1 1Dimensions
FRONT
Minimum Mounting Pad Sizes with pad starting at
15" from structure for minimum clearances
Chassis #1 20" W X 20" D
Chassis #2 24" W X 26" D
"H" = Ranges from 24" to 34"
Refer to Specification Sheet
26-1/2
24-3/4 --
Chassis #1
2_, -3/4
, 21 i
-- 29-3/4
Chassis #2
Line & Low
Voltage Wiring
Ince
0
_hs G
I 2 /
IIIIIIIIIII IIIIIIIIII IIIIIIIII T7T [Tm
11/2
Figure 2 I Clearances
Recommended Clearances Mininumum Clearances Mininumum Clearances
24"
24" 36" O
24"
24"
24"
24"
Mininumum Clearances Mininumum Clearances
24' 0
6"_ _ 24"
Pipe
24"
24" 24" 24"
421 01 3002 01 3L_
jInstallation Instructions Split System Condensers J
Installing Refrigerant Lines
Component Matches
Check to see that you have the proper system compo-
nents. APPROVED MATCHED SYSTEM COMPON ENTS
MUST BE USED. Refer to the Sales Specification Sheet
or Split System Summary for match data and orifice
sizes,
The outdoor units are shipped with a refrigerant charge to
match the indoor unit and 15 ft. (4.5m) of refrigerant line. If
shorter or longer lines are used, the charge will have to be
adjusted.
TOTAL LENGTH OF REFRIGERANT LINES MUST NOT
EXCEED 50 ft. WITH A MAXIMUM VERTICAL SEPARA-
TION OF 40 ft. BETWEEN THE OUTDOOR AND IN-
DOOR UNITS.
PLEASE! UNDER NO CIRCUMSTANCES LEAVE THE
LINES OPEN TO THE ATMOSPHERE FOR ANY
PERIOD OF TIME,
Be extra careful with sharp bends. This tubing can "kink"
very easily, and if this occurs, the entire tube length will
have to be replaced. Extra care at this time will eliminate
future service problems.
Suspension And Installation Of
Refrigeration Lines
DO NOT fasten liquid or suction lines in direct contact with
the floor or ceiling joist. Use an insulated or suspension
type of hanger. Keep both lines separate, and insulate the
suction line. Both lines should be insulated in long runs in
an attic or underground in a raceway.
Restrictor Orifice
Some indoor matches use a restrictor orifice in the fitting at
the indoor coil. Some matches may require a different ori-
fice for proper system performance and it must be changed
before the refrigerant lines are connected.
Changing the Restrictor Orifice
The restrictor orifice is located in a fitting in the liquid line.
The fitting is actually the distributor end of the cap tube as-
sembly.
1. Remove the liquid line fitting and replace restrictor ori-
fice. (STANDARD RIGHT HAND THREAD)
2. Make sure the restrictor is installed with the rounded
end toward the feeder tubes. See Figure 3.
Figure 3 J Restrictor Orifice
Nut and Liquid Line
with Strainer
! RRestr 'dC_drEOd''ce
_Feeder Tubes
Refrigeration Line Sets
Ifit is necessary to add tubing in the field, use dehydrated or
dry sealed deoxidized copper refrigeration tube. DO NOT
use copper water pipe.
It is important that no tubing is cut or seals broken until
you are ready to actually make connections to the
evaporator and to the condenser section.
Do not remove rubber plugs or copper caps from the
tube ends until ready to make connections at evapora-
tor and condenser.
Do not let refrigerant lines come in direct contact with
foundation. When running refrigerant lines through the
foundation or wall, the openings should be made large
enough to allow for a sound absorbing material to be
placed or installed between the tubing and the foundation.
This will prevent noise transmission between the tubing
and the wall section (foundation) or the building.
Installation Instructions For Condensing
Units That Are Higher Than Evaporator
It is recommended that vertical suction risers not be up-
sized. Proper oil return to the compressor should be main-
tained with suction gas velocity. If velocities drop below
1500 fpm (feet per minute), oil return will be decreased. An
oil trap should be installed every 20' of vertical suction line
riser (condenser above evaporator.) Refer to line sizing
charts.
Figure 4 Oil Traps
10" Max
Min.
_8-11-1e
Line Valves
The outdoor condensing unit is supplied with straight sweat
brass service valves with copper stubs.
_J 421 01 3002 01
I Split System Condensers Installation Instructions
All line valves are positioned to seal the refrigerant in the
condensing unit with gauge ports open to connecting lines
when the Schraeder valve is depressed. Gauge ports have
Schraeder installed and require use of charging hoses with
depressors.
Brazing Connections
Fire Hazard
Refrigerant and oil mixture under pressure could
ignite as it escapes and contacts brazing torch
resulting in Fire. Make sure the refrigerant charge
is properly removed from both the high and low
sides of the system before brazing any compo-
nent or lines.
FAILURE TO DO SO COULD RESULT IN BODILY
INJURY OR DEATH.
Before making braze connections, be sure all joints are
clean. Before heat is applied for brazing, nitrogen should
be flowing through the tubing to prevent oxidation and
scale formation on the inside of the tubing.
Liquid & Suction Lines
Fully annealed refrigeration lines should be used when
installing the system.
The following is the recommended method for making
braze connections at the refrigerant line connections:
1. Clean refrigerant tube end with emery cloth or steel
brush.
2. Use a suitable brazing alloy for copper to copper joints.
3. Insert tubing into swage fitting connection.
4. Apply heat absorbing paste or heat sink product to pre-
vent damage to the service valve.
CAUTION
Do not heat valve body above 250 degrees R
5. Braze joint.
6. Quench the joint and tubing with water using a wet rag.
Leave rag on fitting body and re-wet with water to help cool
area.
Evacuating, And Charging Instructions
NOTE
Intentional release of CFC or HCFC Refrigerant to the
Atmosphere violates Federal Law, It may also violate
State and Local Codes, Check all Federal, State and
Local Codes before proceeding,
These instructions are intended for use with condensing
units that are precharged at the factory with adequate re-
frigerant to handle 15 feet.
NOTE: Do not use any portion of the charge for purging or
leak testing. It is mandatory that a thorough evacuation of
the refrigerant in the piping and evaporator be performed.
The liquid line and suction line service valves have been
closed after final testing at the factory. Do not disturb
these valves until the lines have been leak checked
and evacuated or the charge in the unit may be lost,
Recommended Method Of Evacuating A
System
1. Connect the vacuum pump to the suction and liquid line
gauge ports.
2. If the evacuation is being performed on a new system
installation, the valves should be kept in the "front seated"
(closed) position. This will allow the mechanic to evacuate
the refrigeration lines and the indoor coil, without disturbing
the factory charge in the outdoor unit.
3. Follow the vacuum pump manufacturer's instructions.
Allow the pump to operate until the system has been eva-
cuated down to 300 microns. Allow the pump to continue
running for an additional 15 minutes. Turn off the pump and
leave the connections secured to the two service valves.
After 5 minutes, if the system fails to hold 500 microns or
less, check all connections for tight fit and repeat the evac-
uation procedure.
4. Isolate the vacuum pump from the system by closing the
shutoff valves on the gauge bar. Disconnect the vacuum
pump.
Valve Actuation: Service Valves
Remove the service valve cap, if there is a male valve stem
see instructions for Ball Valves. For the standard service
valve there are two variations, but both have internal
stems. The first style uses an internal snap ring to retain the
valve stem and the second has a rolled top and also has
finer threads on the valve cap. NOTE: You may encounter
more than one type of valve on a unit,
For service valves fully insert a hex wrench into the stem. A
back-up wrench is required on the valve body to open the
valve stem. Backout counterclockwise until the valve stem
stops or just touches the retaining ring. NOTE: THIS IS
NOT A BACKSEATING VALVE. For valves with retainer
rings care must be taken to prevent dislodging them when
opening valve.
The service valve cap is a primary seal for the valve and
must be properly tightened to prevent leaks. Make sure cap
is clean and apply refrigerant oil to threads and sealing sur-
face of cap.
For valves with retaining rings: Replace service valve
cap and torque to; 8-11 ft. Ibs. on 1/4" and 3/8" valves,
12-16 ft. Ibs. on 5/8" and 3/4", 15-21 ft. Ibs on 7/8" valves. If
torque wrench is not available, tighten cap finger tight and
then tighten one (1) additional wrench flat or 1/6 of a turn.
For valves with rolled tops: Replace service valve cap
tighten cap finger tight and then tighten one (1) additional
wrench flat or 1/6 of a turn to properly seat the sealing sur-
faces. Subsequent installations will seat with 1/2 to 1
wrench flat of turning.
Gauge Ports: All Valves
Check for leaks at the schrader port and tighten valve core
if necessary. Install plastic caps finger tight.
Ball Valves
On models with ball type valves use a 6" crescent wrench
to rotate the valve stem 90°counter clockwise. Retighten
valve cap to 6-8 ft. Ibs. If torque wrench is not available,
tighten cap finger tight and then tighten one (1/2) additional
wrench flat.
421 01 3002 01 5L_
_Installation Instructions Split System Condensers I
REFRIGERATION PIPING & CHARGING
The recommended method of addition or removal of refrig-
erant is by weight.
Some matching coils may need more refrigerant than the
factory charge. If you can't determine charge by weight,
then check charge by superheat method and performance
curves. The oil charge is sufficient for 50 feet.
For oil requirements refer to Figure 5. For piping lengths
up to 75 feet refer to Figure 6 for pipe size, and Figure 7 for
refrigerant adjustment.
On applications where liquid fioodback to the compressor
is likely to occur, use of a crankcase heater is recom-
mended.
Figure 5
Distance
(Feet)
0-50
51
60
75
- Addition of Refrigeration Oil
Suction Line Size
5/8, 3/4, 7/8 1-1/8
1 oz. 2 oz.
2 oz. 4 oz.
3 oz. 6 oz.
Figure 6-LINE SIZING
Model Series
All Series
All Series
Size-ton Liquid Suction
1 1/2 to 3 3/8" 3/4"
3 1/2 to 5 3/8" 7/8"
Figure 7 Addition of Refrigeration Charge
Liquid Line Diameter oz. Per Linear Ft. *
3/8 .60
1/2 1.20
Electrical Wiring
Electrical Shock Hazard.
Shut off electric power at fuse box or service pan-
el before making any electrical connections.
Failure to shut off electric power can result in,
property damage, personal injury and/or death.
The supply voltage should be 208-230 volts (196 volt mini-
mum to 253 volts maximum) 60Hz single phase.
APPROVED FOR USE WITH COPPER CONDUCTORS
ONLY. DO NOT USE ALUMINUM WIRE.
REFER TO UNIT RATING PLATE FOR CIRCUIT
PROTECTION.
Grounding
Permanently ground unit in accordance with the National
Electrical Code and local codes or ordinances. Use a cop-
per conductor of the correct size from the grounding termi-
nal in control box to a grounded connection in the service
panel or a properly driven and electrically grounded ground
rod.
Wiring Connections
Route Low Voltage wiring through entrance into area sep-
erated by insulating paper and make ALL low voltage con-
nections to the low voltage pigtails in this area. (Two Yellow
wires, AC or W,Y,O,BL, & R for HP). The pigtail wires have
600V insulation meeting approval for use in high voltage
areas.
See Figures 8 thru 11 and Wiring Diagram on unit.
Use of Rigid Metal Conduit
It is recommended that wires be tied together or twisted to-
gether inside the conduit. This will minimize any buzzing
type sounds that could be produced with high current
loads, such as during starting. Under some conditions it
may be necessary to use a hard start kit to eliminate prob-
lem noises.
Control Box Access
Remove the four screws. Cover is notched so it will slide
out from under top edge of unit.
Figure A/C Control Box
mtactor
und Lug
Wires
Make all outdoor electrical supply (Line Voltage) connec-
tions with raintight conduit and fittings. Most codes require
a disconnect switch outdoors within sight of the unit.
Route Line Voltage wiring through entrance and up to con-
nect to Contactor and Ground Lug. Line Voltage
Entrance
Voltage
intrance
LL Low Voltage
Connections MUST be
made in this AREA
_J 421 01 3002 01
I Split System Condensers Installation Instructions I
Figure 9
Ground Lug
Line Voltage
Entrance
Heat Pump Control Box
Low Voltage
Entrance
Low Voltage area is seperated
from the high voltage area. ALL
LOW VOLTAGE CONNECTIONS
MUST BE MADE IN THIS AREA.
Defrost
Control
Contactot
Figure !0 [ VoltageA/CCondenserconnectionsTypicalLow
Indoor
Thermostat
R G BL
! I I
(Compressor i
W
!
(Co
Outdoor
Unit
ontactor)
== y --
nmon 24V)
A y -
INDOOR GAS
BLOWER OR FURNACE
COIL
Figure 11 Heat Pump Typical Low Voltage Control Connections
--®
White Rodgers 1F92 only,
field jumper required
Y1-WI.
Indoor
Thermostat
C
NOTE: White Rodgers 1F92
thermostat cannot be used
for direct staging of electric
heat. Outdoor thermostat
must be used for staging.
ELECTRIC HEAT
NO OUTDOOR THERMOSTAT
\
tti
R G BL BK GY
I I (2) (1),
W
I
INDOOR ACCESSORY
BLOWER ELECTRIC
COIL HEAT PKG.
t
Outdoor
Unit
-O DOD(Heat/Cool Relay)
-O-- Y -- (Compressor)
--QD W D(Electric Heat)
-O-- BL-- (Common 24V)
-Q__ R_ (24V-Hot)
SPLICE (WIRE NUT OR SOLDER AND TAPE)
(1) FIRST STAGE ELECTIC HEAT ALL HEATERS
(2) ADDITIONAL STAGES, ELECTRIC HEAT STAGE 2 -- BK,
STAGE 3 -- V, STAGE 4 -- BR
If electric heat is not used, discard connection shown from elecric heat package.
421 01 3002 01 7L_
_Installation Instructions Split System Condensers I
Start- Up Procedure
Start-up Procedure
1. Close electrical disconnects to energize system.
2. Energize crankcase heater on units so equipped.
3. Set Thermostat selector switch to OFF.
4. Set room thermostat at desired temperature. Be sure
setpoint is below indoor ambient temperature for cooling
and above indoor ambient for heating.
5. Set the system switch of the thermostat on COOL and
fan switch for continuous operation or AUTO, as desired.
Operate unit for 15-20 minutes, then check the system re-
frigerant charge if it was necessary to adjust.
6. After the refrigerant charge has been adjusted, the sys-
tem is now ready for continuous operation.
Final Refrigeration Charge Adjustment
Some matching coils may need more refrigerant than the
factory charge. For optimum heat pump performance at
ARI test conditions, the system should initially be charged
per cooling mode instructions (ARI "B" test conditions). A
check in heating mode (ARI "High Heat" test conditions)
should then be performed. Charge level may be adjusted
per Heating Mode Charge instructions to ensure that high
heat capacity is at or above 95% of ARI rating. ARI cooling
tests may then be performed using the adjusted operating
charge.
Airflow
Before any adjustment is made to the refrigerant charge, it
is imperative that the air flow characteristics of the indoor
blower be established.
When checking indoor air flow, it is important to remember
that the blower will deliver a higher quantity of air across a
dry coil versus a wet coil. Blower charts are calculated with
a dry coil.
Recommended air flow for installations of cooling units and
heat pumps is 350-450 CFM per ton (12,000 BTUH)
through a wet coil. Refer to indoor unit installation instruc-
tions for proper methods of determining air flow and blower
performance.
To Check System Refrigerant Charge
(Superheat Method), Cooling Only
1. Attach an accurate temperature sensing device to the
suction line approximately 4" - 6" away from the suction
line service valve. The temperature sensing device should
be clamped securely to the suction line, on a horizontal
plane (between 9 & 3 O'clock) and insulated. Record the
suction line temperature.
2. Measure and record the suction line refrigeration pres-
sure. (Measure at the suction line service valve gauge
port.) Using Temperature /Pressure Chart convert this
pressure to the saturation refrigerant temperature. The dif-
ference between actual and saturated temperatures is the
amount of superheat.
Figure 12
Temper
ature °F.
-6
-4
-2
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
-Temperature /
PSIG Temper
R-22 ature °F.
19.3 19
20.8 20
22.4 21
24.0 22
24.8 23
25.6 24
26.4 25
27.3 26
28.2 27
29.1 28
30.0 29
30.9 30
31.8 31
32.8 32
33.7 33
34.7 34
35.7 35
36.7 36
37.7 37
38.7 38
39.8 39
40.8 40
Pressure Chart
PSIG Temper
R-22 ature °R
41.9 41
43.0 42
44.1 43
45.3 44
46.4 45
47.6 46
48.8 47
49.9 48
51.2 49
52.4 50
53.6 55
54.9 60
56.2 65
57.5 70
58.8 75
60.1 80
61.5 85
62.8 90
64.2 95
65.6 100
67.1 105
68.5 110
115
PSIG
R-22
70.0
71.4
73.0
74.5
76.0
77.6
79.2
80.8
82.4
84.0
92.6
101,6
111.2
121,4
132,2
143,6
155,7
168,4
181,8
195,9
210,8
226,4
242,7
3. Measure and record the outside ambient air tempera-
ture.
4. Optimum performance will be achieved when the oper-
ating charge produces 15°-20 ° F suction superheat at
compressor with 82 ° F outdoor ambient and 80° F dry bulb
(67 ° F wet bulb) indoor temperature (ARt "B" test condi-
tions) at rated airflow. If these conditions cannot be ob-
tained, compare the calculated superheat value with the
recommended valves given in Figure 13.
Figure 13 - Recommended Superheat Values
Outside Air Superheat °F
Temp ° F Variator or Piston
65
75
85
95
105
38 -45
27 - 33
20 - 25
10- 15
2-6
L_J 421 01 3002 01
I Split System Condensers Installation Instructions
Ifthe actual superheat readings are higher than shown, the
system is most likely under-charged, and charge should
be added. Add charge in 4 ounce increments, and recalcu-
late superheat values. Continue adjusting charge until the
actual superheat approximately matches the recom-
mended values.
Ifthe actual superheat readings are lower than shown, the
system is most likely over-charged, and charge should be
removed. Remove charge in 4 to 6 ounce increments, and
recalculate superheat values. Continue adjusting charge
until the actual superheat approximately matches the rec-
ommended values.
NOTE: Each time that charge is added or removed from
the system, allow the system to run approximately 15 min-
utes before pressure and temperature readings are taken
and superheat calculations made.
NOTE: Indoor Wet Bulb Temperature ( and Relative Hu-
midity) will alter superheat values. All readings should be
at 50% humidity inside and 350 to 450 CFM per ton across
the indoor coil.
Heating Checkout (Heat Pump Only)
1. Turn thermostat heat-cool switch to OFF. Turn ther-
mostat fan switch to AUTO.
2. Turn on all power except 230 volt line to outdoor sec-
tion.
3. Turn fan switch on thermostat to ON. Blower should
run. Reset to AUTO; blower should turn off.
4. Set thermostat below room temperature. Turn selec-
tor switch to heat. Move thermostat above room tem-
perature. Blower should run on heating speed and a
click should be heard in the condensing unit outside
(contactor closing). The sequencer coils for auxiliary
heat should be energized. After approximately 30
seconds the contacts in the sequencers should close
and the electric heat elements start heating. Allow 3
minutes for all heaters to come on.
5. Set system switch to OFF> Turn the thermostat
above room temperature. Turn on the 230 volt power
to the outdoor unit. Nothing apparent will be happen-
ing, but the crankcase heater is now energized. If the
outdoor temperature is below 75 °F allow the unit to
stay in this mode at least 6 hours. This is needed to
vaporize any refrigerant that may be in the compres-
sor oil.
6. Set the thermostat above room temperature. Move
system switch to heat. Count to 5 (about 5 seconds).
Turn the electric power off at the condensing unit dis-
connect switch. Check that there is no clattering or
unusual noises. The outdoor fan blade should have
started turning and a humming noise should have
been heard from the compressor. The indoor fan
should continue to run at its normal speed and elec-
tric elements continue to heat.
7. Wait 2 minutes, then repeat the procedure and re-
check the same things in case you missed something
during the first power application.
.With the unit operating, close all doors, windows,
storm windows, and openings to the house. Set the
thermostat to the desired setting. Set outdoor ther-
mostat (if installed) to balance point of house. If tem-
perature of house is at least two degrees below
thermostat setting, heat pump and auxiliary heat not
controlled by outdoor thermostats will continue to run
until room temperature is approximately 2° below
thermostat set point. Auxiliary heat light should go
out and auxiliary heat cycle off. Heat pump should
continue to run until thermostat reaches set point.
To Check System Refrigerant Charge
(Heating Mode)
For models with an outdoor restrictor orifice, optimum heat-
ing performance will be achieved when the operating
charge produces 10° - 20° F suction superheat at com-
pressor with 47° F outdoor ambient and 70° F dry bulb in-
door temperature (ARI "High Heat" test conditions) at rated
airflow.
The recommended method of addition or removal of
charge in the heating mode is by weight. The system op-
eration may be checked against the performance charts.
Remember, indoor airflow must be approximately 400
CFM per ton to compare operation to performance charts.
Defrost System (Heat Pump Only)
The defrost system is electronic with an adjustable time in-
terval of 90, 60, or 30 minutes. It is factory set at 60 or 90
minutes. At the selected time interval with the outdoor coil
temperature at approximately 28 °F, the system will de-
frost. When the sensor sees a rise in the outdoor coil tem-
perature to approximately 10 minutes, the defrost will be
terminated.
In some areas, with high humidity, the time interval may re-
quire adjustment for complete removal of ice from the coil.
For best economy, always set to the longest interval that
will keep the coil clear of ice.
NOTE: The term ice means hard but not frost. During nor-
mal operation, the coils may become coated with frost until
they are solid white. The time interval for the defrost should
be set so the frost and ice melt off completely without hard
ice building up on the coil.
421 01 3002 01 9L_
_Installation Instructions Split System Condensers I
Maintenance
Condensate Drain
Electrical Shock Hazard.
Shut off electric power at fuse box or service pan-
el before making any electrical connections.
Failure to shut off electric power can result in,
property damage, personal injury and/or death.
Defrost Control
Time Interval Adjustment
(Except Demand Defrost)
To adjust defrost frequency, turn off all power to the Heat
Pump. Remove control box cover and locate the electronic
defrost control board.
The defrost control board has a jumper clip that fits over
two pins. To change the time interval, remove the jumper
clip and place it on pins for the desired time interval, 30, 60
or 90 minutes.
Figure14 J Adjusting Defrost Time
During the cooling season check at least monthly for free
flow of drainage and clean if necessary.
Cleanliness
These tips will help you keep your air conditioner looking
better and working more efficiently:
1. Free air flow is essential. Keep the outdoor coil clean
and free of restrictions. Keep fences, shrubs, snow
drifts and any other obstructions at least two feet from
all coil air inlets.
2. Keep the coil free of grass clippings, weeds and other
debris. BE SURE TO TURN OFF ELECTRICITY BE-
FORE CLEANING!
4.
Coils may require cleaning. The coil should al-
ways be cold when cleaning. Use an alkaline
based cleaner only. Cleaning a hot coil or using
an acid based cleaner will remove the paint from
the fins and may clog the coil.
Never use a weather cover over the outdoor unit un-
less it is a ventilated type or made of breathable fabric
that will allow moisture to evaporate rapidly. A cover
that holds moisture in the unit will cause more rust
build-up and damage than normal exposure to
weather.
l_J 421 01 3002 01
INTERNATIONAL COMFORT PRODUCTS
LIMITED WARRANTY CERTIFICATE
For Cooling & Heating Products
SAVE THIS CERTIFICATE, It gives you specific legal rights, and you may also have other rights which may vary from state to state and
province to province.
If your unit needs servicing, contact a qualified dealer or qualified service agency of your choice. When requesting service, please have the model and
serial number from each unit in your heating and/or cooling system readily available. If your dealer needs assistance, the distributor is available to
provide support and we, in turn, support its efforts.
Fill in the installation date and model and serial numbers of the unit in the space provided below and retain this Limited Warranty for your files.
GENERAL TERMS
Subject to the conditions and limitations stated herein, during the term of this Limited Warranty, we will provide a replacement for any functional
component part (as defined below) of your unit that fails due to defect in materials or workmanship. The term of this Limited Warranty is five years from
installation on Residential Products and one year from installation on Commercial Products or applications. Except as otherwise stated in the
"Additional Terms" section, this Limited Warranty covers only the original purchaser and subsequent transferees, and only while the unit remains at the
site of the original installation (except for mobile home installations), and only if the unit is installed inside the continental United States, Puerto Rico,
Alaska, Hawaii or Canada. In addition, the Limited Warranty applies only if the unit is installed and operated in accordance with the printed instructions
accompanying the unit, and in compliance with all applicable installation and building codes and good trade practices. As used in this Limited Warranty,
"installation" means the original installation of the unit.
THERE ARE EXCEPTIONS to this Limited Warranty as described on the reverse side of this page. All replacement parts will be warranted for the
unused portion of the warranty coverage period on the unit. The part to be replaced must be returned by the dealer to a distributor that sells products for
International Comfort Products, in exchange for the replacement part. In lieu of providing a replacement part, we may, at our sole option, refund to you
an amount equal to the distributor's component purchase price from us, or provide to you a credit equal to that amount to be applied toward the purchase
of any new unit that we distribute. If a credit for a new unit is given in lieu of a replacement part, the rating plate from the unit being replaced must be
submitted on a warranty claim, and your dealer must make the unit being replaced available to our distributor for disposition. As a condition to warranty
coverage, the unit must receive yearly maintenance, as described in the owner's manual, by a dealer. Satisfactory proof of yearly service by a dealer
may be required.
"Functional component parts" include only the following: blower motor, unit-mounted sensors & timers, condenser motor, evaporator coil, condenser
coil, condenser fan, capacitor, transformer, single-phase strip heat elements, expansion device, reversing valve, solenoid valve, service valve,
electronic and electro-mechanical control board, ignitor, ignition module, draft inducer assembly, burner pilot, gas valve, limit control, pressure switch,
relays and contactors, blower wheel, interlock switch, crosslighter, pilot shield, gas & oil burners, oil pure p assembly, accumulators and factory installed
driers and strainers.
This Limited Warranty DOES NOT COVER any labor, material, refractory chambers, oil nozzles, refrigerant, refrigerant inspection and refrigerant
reclaiming, freight and/or handling charges associated with any repair or replacement and such charges will be your responsibility.
To establish the installation date for any purpose under this Limited Warranty, you must retain the original records that ca n establish the installation date
ofyour unit. Ifyoudonot providesuchdocumentsthestartdateoftheterm ofthis Limited Warrantywillbe based upon thedate of unit manufacture, plus
thirty (30) days. In establishing that the required yearly service has occurred, you must furnish proof of yearly service by a qualified service agency.
This Limited Warranty does not cover: (a) failure or damages caused by accident, abuse, negligence, misuse, riot, fire, flood, or Acts of God (b)
damages caused by operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any other damaging chemicals (other
than those found in a normal residential environment) (c) damages caused by an unauthorized alteration or repair of the unit affecting its stability or
performance (d) damages caused by improper matching or application of the unit or the unit's components (e) damages caused by failing to provide
proper maintenance and service to the unit in accordance with this Limited Warranty Certificate and the printed instructions originally provided with the
unit (f) any expenses incurred for erecting, disconnecting, or dismantling the unit (g) parts or supplies used in connection with service or maintenance,
such as refrigerant, refractory chambers, oil nozzles, filters, or belts (h) damage, repairs, inoperation or inefficiency resulting from faulty installation or
application (i) electricity or fuel costs or any increase in electricity or fuel cost whatsoever including additional or unusual use of supplemental electric
heat (i) units which have not had the required yearly maintenance described elsewhere in this limited warranty.
In no event shall we be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit.
WE HAVE NOT MADE, DO NOT MAKE, AND HEREBY DISCLAIM ANY IMPLIED CONDITION OR IMPLIED
WARRANTY OF FITNESS FOR APARTICULAR USE OR PURPOSE, AND ANY IMPLIED CONDITION OR
IMPLIED WARRANTY OF MERCHANTABILITY, TO THE FULLEST EXTENT ALLOWED BY LAW. WE MAKE
NO EXPRESS OR IMPLIED WARRANTIES EXCEPT AS STATED IN THIS LIMITED WARRANTY CERTIFICATE.
No one is authorized to change this Limited Warranty or to create for us any other obligation or liability in connection with this unit. Any implied
warranties that are not disclaimable shall last only for the term of the express warranty contained herein. Some states and provinces do not allow the
exclusion or limitation of incidental or consequential damages or do not allow limitations on how long an implied warranty or condition lasts, so the a bore
limitations or exclusions may not apply to you. The provisions of this Limited Warranty are in addition to and not a modification of or subtraction from any
statutory warranties and other rights and remedies provided by law.
Please refer to reverse side of this page for additional terms.
Model No.
Serial No. Date Installed
USA: International Comfort Products, LLC 650 Hell-Quaker Avenue nO. Box 128 Lewisburg, Tennessee 37091 (931-270-4100)
CANADA: International Comfort Products division of UTC Canada Corporation 6060 Burnside Court, Unit 1, Mississauga, Ontario L5T 2T5
(905-795-8113).
Manufacturers of Airquest, Arcoaire, Clare, Comfortmaker, Dettson, Hell, Keeprite, Lincoln, Tempstar and other quality brand name private label
products.
Part No, 401 06 1010 24 (Orig. 11/03/2003)
ADDITIONAL TERMS FOR RESIDENTIAL APPLICATIONS ONLY
Tile Additional Terms for tile components listed below are in addition to, and subject to, the General Terms on tile reverse side of this page.
Warranty coverage is limited to parts that fail due to defect in materials or workmanship daring the specified term.
CENTRAL GAS & OIL FURNACE HEAT EXCHANGERS*
Gas Model Series: C9MPV, H9MPV, T9MPV, C9MPT, H9MPT, T9MPT, C9MPD, H9MPD, T9MP: Limited Lifetime Warranty on heat exchangers. If a
heat exchanger on one of these furnaces fails due to defect in the part, we will provide a replacement part or, at our option, credit toward the purchase of
a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and lasts only for as long as the original
purchaser lives in the home where the furnace is initially installed.** It is not transferable to a ny subsequent owner. If the furnace was not installed in the
home owned by the original purchaser, if the original purchaser sells the home to a subsequent owner, or if proof of original purchase cannot be
provided, then the limited warranty is only for 20 years from the date of original installation.
Gas Model Series: T8MPV. H8MPV. C8MPV. T8MPT. H8MPT. C8MPT: A replacement heat exchanger will be provided for any heat exchanger that
fails in one of these furnaces due to defect for 25 years from the original date of installation.
Gas Model Series: T8MPN. H8MPN. C8MPN. T8MPL. H8MPL. C8MPL. T8DNL. H8DNL. C8DNL N8MPN. N8MPL. N9MP1. N9MP2: A
replacement heat exchanger will be provided for any heat exchanger that fails in one of these furnaces due to defect for 20 years from original date of
installation.
Oil Model Series: OLR(105. 160. 182L OCF. OLF. OUF. NOLF. NOUE OLB. OHB. ODH. FLO. MBO. LBO. NOMF: Limited Lifetime Warranty on
heat exchangers. If a heat exc ha nger on one of these furnaces fails due to defect in the part, we will provide a replacement part or, at our option, credit
toward the purchase of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and lasts only for as
Iongastheoriginalpurchaserlivesinthehomewherethefurnaceisinitiallyinstalled.** Iris nottransferabletoanysubsequentowner. If the furnace
was not installed in the home of the original purchaser, if the original purchaser sells the home to a subsequent owner, or if proof of original purchase
cannot be provided, then the limited warranty is only for 20 years from the date of original installation.
Oil Fired Floor Furnace: NFO: A replacement heat exchanger will be provided for any heat exchanger that fails doe to defect for 10 years from
installation with the following limitation: during the sixth through tenth year, any credit toward your purchase of a component or toward the purchase of
any new unit will be in an amount equal to the distributor's purchase price reduced by 20 percent for each year after the fifth year.
ADDITIONAL TERMS FOR OIL FURNACE APPLICATIONS ONLY
1) OIL BURNERS - A replacement for 5 years from date of original installation for Oil Burner Parts.
2) OPTIONAL ACCESSORIES AND FUNCTIONAL PARTS: A replacement for 5 years from date of original installation. (Refractory and
oil nozzles not included)
GAS/ELECTRIC PACKAGED UNITS HEAT EXCHANGERS
Model series: PGAD, PGAA, PGMD, PGME, PGF, GPFM, PGC, GPCM: A replacement for 10 years from original date of installation.
COMPRESSORS:*
1) Premium Model Units: HAC0. HAC2. HAC4. CAC0. CAC2. CAC4. KAC0. TCA0. TCA2. TCA4. HHP0. HHP2. HHP4. CliP0. CliP2. CliP4.
TCH0. TCH2. TCH4.HXA2.TXA2.CXA2.HXA4.TXA4.CXA4. PGME. PYMC. PHAD. PGAD. PA95. PAPC. PAK. APK: To the original purchaser a
replacement for 10 years from original date of installation, only if the unit is installed with factory matched coils, except air conditioner condensing units
with a nominal S E E R of 10 may be matched with evaporator coils of the same nominal tonnage regardless of manufacturer and in accordance to factory
recommendations. This limited 10-year warranty is not transferable to any subsequent owner. HOWEVE R, if the unit was not installed in the home
owned by the original purchaser, if the purchaser sells the home to a subsequent owner, or if proof of original purchase cannot be provided, then the
limited warranty is only for 5 years from the original date of installation.**
2) All Other Models: Air Conditioners. Heat Pumns. & Combination Gas/Electric Units: NAC0. NAC2. NHP0. NHP2. AO. A2. HO. H2. PGF.
PGC. GPFM. GPCM. PAR APFM. PHF. HPFM. PGAA. PGMD. PA55. PH55. PAPA. PYPA. PGS. GPSM: A replacement for 5 years from date of
original installation, only if: (a) air conditioner condensing units with S E E R rating in the range of 10 to 11 S E E R are matched with evaporator coils of the
same nominal tonnage regardless of manufacturer and in accordance to factory recommendations, or (b) heat pump condensing units are used with
factory matched coils, unless written approval to do otherwise is obtained from manufacturer.
ADDITIONAL TERMS FOR COMMERCIAL PRODUCT OR APPLICATIONS ONLY
For purposes of this warranty a commercial product or application is one in which: the product has over 5 tons nominal cooling capacity, or
is designed for operation with 3 phase electrical power, or is installed in a commercial establishment such as a beauty or hair salon, hospital,
school, restaurant, church, hotel etc.,
3-Phase Models: PGF, GPFM, GPF, PGAD, PGME, PGB, PGMG, PGMF, PGS, GPSM, PGE, APE, PAE, PAB, PAMD, PAS, PAF, APFM, APE
PHB, PHE, PYMD, HPB, PHS, CAC, ACC, CAE, ACE, CHC, HCC, CHE, HCE, CHB, YA:
Tile additional Terms of tire components listed below are in addition to and subject to tire General Terms on tire reverse side of this page.
1) GAS FIRED HEAT EXCHANGERS (ALL MODELS, except PGS, GPSM 3to 5Ton):* A replacement for 10 years from date of original installation.
a) NOTE: PGS, GPSM 3 to 5 Ton Models:* A replacement for 15 years from date of original installation.
2) COMPRESSORS (ALL MODELS):* A replacement for 5 years from date of original installation.
3) OPTIONAL ACCESSORIES AND FUNCTIONAL COMPONENT PARTS (ALL MODELS):*
A replacement for 1 year from date of original installation.
4) COMMERCIAL OIL MODELS: OLR210, OLR350, OTF210, AMT3, AMT4, AMP3: Ten(10) Year Limited Warranty on heat exchangers.
*To receive advantage of your limited warranty, you must provide proof of yearly service by a qualified service agency.
**To receive advantage of your warranty, you must retain the original records that can establish the installation date and proof of purchase of the unit.
MINI SPLITS:
Summary - Mini Splits Warranted for one (1) year on all replacement parts.
Additional terms for Mini Splits:
The additional Terms of the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
1) Compressors (All Models): A replacement compressor will be provided for all compressors that fail due to defect for 5 years from date of original
installation.
2) Optional Accessories and Functional Components Parts (All Models):
A replacement part will be provided for all parts that fail due to defect for one (1) year from date of original installation.
Failure to maintain the equipment through annual maintenance by a qualified service agency shall void the warranty. Proof of service will be required
with all warranty claims. Proof of purchase and installation date must be submitted with all claims.
Page 1 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 2 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 3 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 4 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 5 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 6 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 7 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 8 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 9 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 10 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 11 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718
Page 12 of 12 - ICP  Air Conditioner/heat Pump(outside Unit) Manual L0522718

Navigation menu