ICP Package Units(both Units Combined) Manual L0522886

PLUS LINE PLUS-E017-A/1206 L0522886

User Manual: ICP ICP Package Units(both units combined) Manual ICP Package Units(both units combined) Owner's Manual, ICP Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 20

DownloadICP  Package Units(both Units Combined) Manual L0522886
Open PDF In BrowserView PDF
Installation Instructions
I

DIRECT DRIVE BLOWER
PH55/PYPA SERIES

U SINGLE

PACKAGE HEAT
c_

PUMPS
ELECTRIC
HEAT
(OPTIONAL)
TABLEOF CONTENTS
1, SAFETY LABELING AND SIGNAL WORDS ....................

2

8. INSTALLINGELECTRICHEATACESSORY ...................

10

2. UNITDIMENSIONS ......................................

2

9. HEATERELECTRICALWIRING ...........................

11

3, SAFEINSTALLATIONREQUIREMENTS.......................

2

10. RAIN SHIELD INSTALLATION............................

15

4. LOCATINGTHE UNIT ....................................

2

11,AIR DISTRIBUTIONSYSTEM.............................

15

5, UNITELECTRICALWIRING ................................

4

12.START- UP PROCEDURES..............................

15

6, WIRING DIAGRAMS .....................................

8

13.SEQUENCE OF OPERATION ............................

17

14.OPERATION .........................................

18

7, ELECTRICNEATINSTALLATIONGENERAL INFORMATION ......

Printed in U.S.A.

10

LP-1

1/23/03

427 01 1004 01

1. Safety Labelinq and Siqnal Words
Danger, Warning

and

Caution

The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used on
product labels to signify an immediate hazard. The signal words WARNING and CAUTION

will be used on product labels and throughout

this

manual and other manuals that may apply to the product.

2. Dimensions
NOTE: DUCT COLLARS ATTACHED TO SUPPLY AND RETURN MUST BE REVERSED AT INSTALLATION. SEE INSTRUCTIONS ON PAGE 2.
ALL DIMENSIONS

IN INCHES

ROUND FLANGE
WILL
ACCOMMODATE
14" DIA.
RETURN DUCT

COIL
ACCESS
PANEL

27

3/8 DIA HOLE**

. 1 1/4 DIA.*
/ 1 1/4 DIA.*
m___
10

"

tl_

3

PRESSURE
26

--'@,--C

I
I
I
I
I
I
I
I
I
I
I
I
I
I

\

I

C,_

BK

_)

{}

Y

PRI

GND

DEFROST
CONTROL
FAN

r

TRANS

BK

G

ii

J

BK
O

SEC

O _ _/

/I

I

L_

I
I
I
I
Tq

t

//EE
/

BL
R-

I

1
I
I
I
I
I
I
I
i BLI
I I I
I I I
I I
I I
I I
I I I
I I
I
L
II

IPMC

I

I

ELECT.

L_

PACKAGE
(WHEN

HEAT

USED)

I
I

--BK

I
I
I
I
I
I
I

\
BR

OF THE ORIGINAL

REPLACED

WITH

* SEE INSTALLATION

= m

m

TYPE

WiRE

I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I

I
I

R

C

INSTRUCTIONS

^ C OR ITS
FOR

WITH

THE

O

Y

W

R-RV
I
I
J

I

Lw+

Ly

]

L O ---

(W) DEFROSTHEAT

+

(Y) COMPRESSOR

÷-

(O) HEAT/COOL

÷

(C) COMMON

I
BL ....

L

R .....................................................................
_
(R) 24 VAC

_
I
I
I

I

AS SUPPLIED

AWM-165

I
I

I
I
I
I
I
I
I
I
I
I
I
I

y--_

I

BK

IF ANY

_

DFC

I
I
I
I
I
I
I
I
I
I
I
I

I
I

L

I
I
I
I
I
I
I

G

APPLIANCE

(G) FAN

I

MUST

BE REPLACED,

AND COOLING

CONNECTIONS

IT MUST

BE

EQUIVALENT.

PROPER
COLOR

HEATING

LINE VOLTAGE

FACTORY

LINE VOLTAGE

FIELD

CODE

:

BLACK

LOW VOLTAGE

FACTORY

BROWN

LOW VOLTAGE

FIELD

GRAY

..................................................................
BLUE

8

BK

GREEN

BL

ORANGE

BR
GY

FOR

YOUR
G
O

RED

R

VIOLET

V

UNIT

WHITE

W

YELLOW

I

Y

1081364

427 01 1004 01

Wire Diagrams

(Cont'd...)
4 & 5 Ton Model
LADDER WIRING DIAGRAM

DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
O---_

L1

208/230

(OPTIONAL)

L1

CONTACTOR

CRANKCASE

II
VAC,

HEATER

GND

L2

60 HZ, 1PH

I _

|

I

T1

COMPR

T2

L2

CONTACTOR

4 CA H
DFC
O

SCO

_

C

[

FM

<

TRANS

FAN

DEFROST

CONTROLDFs

jq _ 2P2_ )

_

ZZZZ@
F

RV
R-[_R

}

_
/

()

_1_

If

O

Y

I
I
I

I

W

...............
e ...........................
(W) DEFROST HEAT

L ....
(C) COMMON

.....

_

(Y) COMPRESSOR

-e- ....

(O) HEAT/COOL

(,)

-e
4_

(R) 24 VAC
GND

(G) FAN

J

LEGEND
TRANS....TRANSFORMER

GND.......GROUND

COMPR....COMPRESSOR

LOC_.....LOSS

CAP ........ CAPACITOR
CONT......CONTACTOR
JPR ........ JUMPER

WIRE

L

..........................................
_ ............................................................................................................................

IFMC......tNDOOR
OF CHARGE

FAN MOTOR CONTROL

IFM ........ INDOOR FAN MOTOR

PRESSURE

SWITCH

RVS ........ REVERSING VALVE SOLENOID

DFS ........ DEFROST

SENSOR

OFM ........ OUTDOOR FAN MOTOR

DFC ........ DEFROST

CONTROL

TC .......... TERMINAL CONNECTOR

9

I

1081364

427 01 1004 01

7. Electric Heat Installation
Information

General

8. Installing

Electric Heat Accessory

Electrical shock hazard.

General Information

Shut OFF electric power at unit disconnect and/or service
panel before beginning the following
procedures.

Installation or repairs made by unqualified persons can result
in hazards to you and others. Installation must conform with
local building codes or, in the absence of local codes, with
National Electrical Code ANSI/NFPA 70-1990 or current
edition.
The information contained in this manual is intended for use
by a qualified service technician
familiar with safety
procedures,
equipped
with the proper tools and test
instruments.
Failure to carefully read and follow all instructions in this
manual can result in malfunction, property damage, personal
injury, and/or death.

Failure to follow this warning can result in property damage,
personal injury, and/or death.

1. Shut OFF electric power at unit disconnect switch or service panel.
2. Remove the blower access panel from unit.
NOTE: Installation
of field wiring and conduit for heaters to the
unit prior to installing the heater will simplify wiring of heaters.
3. From inside the blower compartment, remove the six screws on the
heater cover plate and save the screws. Discard the heater cover
plate.
The screws will be used later to mount the electric heat accessory
and its cover.

4. Remove the cardboard wrapper from the heater's elements.
When an electric heat accessory

is installed, two separate field power

supplies MUST be provided - one or more for the electric heat accessory
and one for the unit.

5.Insert the heater into the heater/blower
prevent damage to heater elements.
&Secure heater to heater/blower
moved in Step 3.

FIGURE 7

box. Exercise caution to

box with four of the six screws re-

The Electric Heat Accessory
FIGURE

8

Installing The Electric Heat Accessory

Breaker-

10

427 01 1004 01

9. Heater Electrical

Wirinq

Model Number

Electrical shock hazard.
Shut OFF electric power at unit disconnect
before making any electrical connections.

or service panel

Unit MUST be grounded before making line voltage connections. Do NOT fuse ground or neutral conductors.

Anticipator
Setting

AMMK05AHB/A

.18

AM MK07AH B/A

.36

AMMK10AH B/A

.36

AMMK15AH B/A

.36

AM MK20AH B/A

.54

Limit Controls
The limit controls are mounted on the face of the heater and are wired into
the supply wires to each element.

If there is not enough air flow through

the heater, the limit will open and break the power circuit. The limit will reFailure to follow this warning can result in property damage,
personal injury, and/or death.

set when the electric accessory cools down.

Time Delay Operation
NOTE: All electrical work MUST conform with the requirements of local
codes and ordinances and in the United States with National Electrical
Code ANSI/NFPA70-1990

trois which operate through the low voltage thermostat

switch (when

required) located within sight ofthe unit. Supply voltage, amperage, fuse
and disconnect switch sizes MUST conform with all technical specifications in this manual and on the unit rating plate and local codes.
Wiring MUST be protected from possible mechanical damage and MUST
NOT interfere with removal of access panels, filters, etc.
All exposed wiring or connections MUST be made with weatherproof
cable or wire unless installed in conduit.
and the ground connection

MUST be made

with copper wire.

These controls consist of a number of time delays depending on the specific heater model. An electric heat accessory

has 1,2 or 3 of these con-

trois. The first time delay is activated when the thermostat contacts close.
Approximately

1 to 20 seconds later the indoor blower and the first heater

bank are energized. Approximately

70 seconds after the first heater bank

is energized the remaining time delays and heater banks are energized.

Staging
Some electric utilities require staging on electric heaters larger than 6 kilowatts. Therefore, the heater elements are turned on in 5 or 10 kW increments under control of the sequencers.
If staging based on heat loss or demand is required, the use of accessory

The power supply wiring MUST have overcurrent protection. This can be
either fuses or circuit breakers. The maximum size for the overcurrent

outdoor thermostats

protection

or gray). Outdoor thermostats

is shown in the column

labeled "Max. Fuse or NEC HACR

Breaker (Amps)" in the Electrical Data Table in FIGURE 10 or on the unit
rating plate.

is recommended.

Grounding
Permanently ground the electric heat accessory in accordance with local
codes and ordinances and in the United States with National Electrical

The heat sequencer

wiring is de-

signed to be staged by breaking the 24V "Common" Leg (normally brown
available through your wholesale supplier

allow the control of two or four stages of electrical heat.
Some indoor electronic

Code ANSI/N FPA70-1990

circuit.

or current edition. Provide line voltage power

supply from a separate protected circuit with a disconnect

All line voltage connections

The heater elements are switched ON and OFF through one or more con-

thermostats

may provide for multiple stage of

electric heat. When this type thermostat

is used, it may be necessary to

break the 24V"Hot" leg of the sequencer

(as fed from the "W' circuit at the

thermostat).

This will require field modification

of the control wiring and

should only be done by an experienced controls technician/or

electrician.

or current edition. Use a copper conductor of

the appropriate size from the electric heat accessory to the ground lug on

Installing Wiring

the circuit breaker panel as shown in FIGURE 9.
1.Shut OFF electric power at unit disconnect or service panel.

Adjusting

Thermostat

Anticipator

Set the heat anticipator of the thermostat to the proper value. See instructions provided with the thermostat before making this adjustment.

2.Install the appropriate field supplied conduit fitting into the heater
knockout located in the rear panel of the unit. The wiring entrance
hole is sized for 1" conduit.

11

427 01 1004 01

Typical
WiringInstallation
(Breaker
StyleHeater
Shown-Pigtail
stylealsoavailable)
UnitLineVoltage
Wires

3.Connect field installed copper ground wire(s) to the ground lug(s) on
the heater mounting plate. On models with more than one circuit, a
separate copper ground wire MUST be connected to a separate
ground lug for each circuit.

4. Route the field supplied line voltage wires for the heater to the line
side of the electric heat accessory's circuit breaker(s) or high voltage
wiring harness. Leave approximately 8" of excess wire so the breaker or wiring harness may be moved to service. Make line voltage
connections to L3-L6 as appropriate.
NOTE: If heaters without
breakers are used, route field wires to inside of unit and attach to
heater wires tagged L3-L6 as appropriate using supplied wire nuts.

5. Connect the black wire with terminal from the heater wire harness to
the loose black wire at the unit blower.
NOTE: Check FIGURE 11 for heater/speed combinations that are
unacceptable.

6 Connect the red wire with terminal in the heater wire harness to the
loose red wire from the unit sequencer.
7. Connect the white wire from the heater wire harness to the white wire
from the thermostat at the field supplied low volt wire harness in the
control box.

8. Connect the grey and brown wires from the heater wire harness to
the blue wire from the unit 24V common. NOTE: If outdoor thermostats are used for staging electric heat, connect the grey and brown
wires according to the thermostat instructions.
See "Staging" in
Electrical Wiring Section of this Manual.
After completing installation of the heater, install the breaker rain shield on
the blower access panel according to the following instructions

on page

13. If using a pigtail style heater, proceed to Start-Up Procedures for Auxiliary Electric Strip Heat on page 14.
12
427 01 1004 01

FIGURE
10 Accessory
Electric
Heater
Electrical
Data
HEATER
MODEL
AMMK05AHA

AMMK20AHB

FIGURE 11

Maximum Overcurrent
ProtectiveDevice

Supply Voltage

KW Rating

Amps

Ampacity

(Amps)

240-1-60

4.8

16,382

L3-L4

20.0

25.0

3O

208-1-60

3.6

12,287

L3-L4

17.3

21.6

25

2-5 TON

2-5 TON

AMMK10AHB
AMMK15AHB

MininumCircuit

2-5 TON

AMMK07AHB
AMMK10AHA

Heater

Used With

AMMK05AHB
AMMK07AHA

Supply
Circuit No,

Nominal Heating
BTUH

21/2-5

21/2-5

TON

TON

Accessory

Electric

240-1-60

7.5

25,598

L3-L4

31.2

39.1

45

208-1-60

5.6

19,113

L3-L4

26.9

33.6

4O

240-1-60

9.6

32,765

L3-L4

40.0

50.0

6O

208-1-60

7.2

24,574

L5-L6

34.6

43.3

5O

240-1-60

14.4

49,147

L3-L4
L5-L6

40.0
20.0

50.0
25.0

6O
3O

208-1-60

10.8

36,860

L3-L4
L5-L6

34.6
17.3

43.3
21.6

5O
25

240-1-60

19.2

65,530

L3-L4
L5-L6

40.0
40.0

50.0
50.0

6O
6O

208-1-60

14.4

49,147

L3-L4
L5-L6

34.6
34.6

43.3
43.3

5O
5O

Heater Heating Data
*TemperatureRise °F @ CFM (ElectricHeat Only)

Heater
Model

Use With

AMMK05AHA

2-5 TON

AMMK20AHB**

*
**

1000

1200

1400

1600

1800

2000

19.0

15.2

12.6

10.8

9.5

8.4

7.6

2200

208-1-60

3.6

12,287

19.0

14.2

11.4

9.5

8.1

7.1

6.3

5.7

---

2-5 TON

240-1-60

7.5

25,598

39.5

29.6

23.7

19.8

16.9

14.8

13.2

11.9

10.8

208-1-60
240-1-60

5.6
9.6

19,113

29.5

22.1

2-5 TON

32,765

50.6

37.9

17.7
30.3

14.7
25.3

12.6
21.7

11.1
19.0

9.8
16.9

8.8
15.2

8.0
13.8

208-1-60

7.2

24,574

37.9

28.4

22.8

19.0

16.3

14.2

12.6

11.4

10.3

240-1-60

14.4

49,147

---

56.9

45.5

37.9

32.5

28.4

25.3

22.8

20.7

208-1-60

10.8

36.860

56.9

42.7

34.1

28.4

24.4

21.3

19.0

17.1

15.5

240-1-60
208-1-60

19.2
14.4

65,530

......

49,147

---

56.9

--45.5

50.6
37.9

43.3
32.5

37.9
28.4

33.7
25.3

30.3
22.8

27.6
20.7

AMMK10AHB
AMMK15AHB*

800

25.3

KW Rating
4.8

AMMK07AHB
AMMK10AHA

600

16,832

Supply Voltage
240-1-60

AMMK05AHB
AMMK07AHA

Total Heating
BTUR

21/2-5

21/2-5

TON
TON

15 KW HEATERNOTTO BE OPERATEDON LOW TAPFOR 21/2 TON A/C AND HE
20 KW HEATERNOTTO BE OPERATEDON LOW OR MEDIUMLOWTAP FOR3 AND3 1/2A/C AND HE

13

427 O1 1OO4 O1

---

Wire Diagrams

- Electric Heat Accessory
I WIRING

DESCRIPTION:

AM[vlK

& 15 KS! ELECTRIC

5_7.5,18

CODE_

REVISION_

[ 882£18/23_1V
HZ
1 PH

HEAT

,,J/', i\N
ELECTRICAL
SHOCK
HAZARD
DISCONNECT
ALL POWER SUPPLIES.
FAILURE
TO DO SO COULD
RESULT
SERIOUS
INJURY
OR DEATH.
LEGEND
EL .......... ELECTRIC

ELEMENT

SEQ........SEQUENCER
HTR........HEATER
GND,,,,.,,,GROUND
LS .......... LIMIT
SWITCH
[FM..,.....[NOOOR
FAN MOTOR
TRANS..,.TRANSFORMER
[FMC,.....,INDOOR
FAN MOTOR

GY

AHB
20B/24BV
USE

1PH

COPPER

60

HEATERS

ONLY

I

•

]

HZ

CONDUCTORS
TO U

ONLY

CONTACTOR

FAN
CONTROL

?_
G

s

BL

r

....
, _

:I

i

]

I

I
;

i!
, ,

]

,,

_---_

CONTROL

I
FOLLOW
LATIDN

HEATER

INSTAL

INSTRUCTIONS

ACCESSORY
HEATER
:DMMON .....

•

'

WIRE

'

WIRING

MARNESS

VOLTAGE
VOLTAGE

LOW
LINE

TO L2
COmnCTOR_

TMERMOmAT
CONNEmlONS

INTERNALNTERNAL(WHEN_WHEN
RECOMMENDED

HEATER
ABS¥
MODEL NUMBER
AMMKB5AHB
AMMK_GAHA

_"
ONO

BR
_

FOR
USE
W,TB,

ELEMENTS
1

_L3
L4
25A

AMMKO7AHB
AMMKO7AHA

[,2

40A

AMMK]OAHB
AMMK]OAHA

1,2

50A

AMMK15AHB

112.3

PA55,

PA£5

&

COLOR
BLACK

BK

24,30,36,42,48

&

60

24,30,36,42,4B

&

BO

BLUE
BROWN
GRAY
ORANGE

BL
BR
GY
0

24,30,36,42,48

&

60

RED
VIOLET
WHITE

R
V
W

YELLOW

y

3_,36,42,48

&

BO

DESCRIPTION=

WIRING

AP1P1K

28

KW ELECTRZ8

HEAT

NOTES

CODE

PH55

1 ALL WIRING MUST BE DONE IN
ACCORDANCE WITH NATIONAL
AND LOCAL
2. WIRING

BE DONE
3

CODE:

IF ANY

ELECTRICAL

THAT

CODES.

IS CIRCLED

BY

WIRE

MUST

INSTALLER

MUST

BE REPLACED,

REVISION:

PART

288/230v
HZ
1 PH

NUMBER:

1882113
B

68

......
,,

m

/-x

ELECTRICAL
SHOCK
HAZARD
DISCONNECT
ALL POWER SUPPLIES
FAILURE
TO DO SO COULD
RESULT
IN SERIOUS
INJURY
OR DEATH.
LEGEND
EL .......... ELECTRIC
SEO....,,..SEOUENCER
HTR........HEATER

ELEMENT

GND....,,..GROUND
LS .......... LIMIT SWITCH
IFN........INDOOR
FAN MOTOR
TRANS,...TRANSFORMER
IFMC.,.,...INDOOR

,
2BB/240V
i PH 6B HZ
USE COPPER
CONDUCTORS

,

÷

MOTOR

CONTROL

q
,
,

ONLY

FAN

FOLLOW
HEATER INSTAL
LATION INSTRUCTIONS.

ACCESSORY
HEATEa
WIREHARNESS

WIRING
LOW VOLTAGE
LINE VOLTAGE

L__<_

HEATER ASSY.
MODEL NUMBER

BK

COLOR

ELEMENTS
L3

AMMKO20AHB

4

L4

50A

50A

PA55
36,42,48
PAD5
36,42
PH55
36,42,48

&
&
&

60
48
80

14

NOTES

CODE

L5 L6
BLACK
BLUE
BROWN
GRAY

BK
BL
BR
GY

ORANGE
RED
VIOLET
WHITE

0
R
V
W

YELLOW

y

1. ALL

WIRING

MUST BE

DONE IN

ACCORDANCE WITH NATIONAL
AND LOCAL ELECTRICAL
CODES
2. WIRING THAT IS CIRCLED
BE DONE BY INSTALLER

MUST

3. IF ANY WIRE MUST BE REPLACED,
IT MUST BE REPLACED
WITH ITS
EQUIVALENT, MIN RATING 105°C

427 01 1004 01

10. Rain Shield Installation

connected to an existing system, the ductwork MUST be checked to make
sure it is adequate.
installed.

121

Installing The Rain Shield

Maximum

I

Extra runs or larger duct sizes may have to be

recommended

velocity in trunk ducts is 1000 feet per minute

(5.08m/s). Velocity in branches

should not exceed 800 feet per minute

(4.06m/s). Refer to the TechnicalData
requirements
RAIN SHIELD

NOTE: Ductwork sizing affects temperature
differential.

rise and cooling temperature

Be sure to properly size ductwork to the capacity and airflow

characteristics

of your unit. Failure to do so can affect limit controls, com-

pressors, motors, and other components and will lead to premature failure

S,ZE.
ADHES,VE
BAO D.

l_f_SII

Label on the unit for unit air volume

and system sizing recommendations.

of components.

I IIL_JI I _ PLACE
INSIDE

This will also adversely

affect day to day unit perfor-

mance.
Flexible Duct Kits are available from your supplier to effect proper sizing
and installation to Mobile Homes and other standard construction..

HEATER PLUGS

Refer to unit rating plate for proper Electric Heat Accessory sizing and see
the Temperature Rise Check section inthe Electric H eat Accessory Installation Section of this manual.

Ductwork Insulation

1. Removeall screwsfrom the cover plateon Blower/ElectricalAccess Panel.

It is recommended
2. Install adhesive backed gasket on Blower/Electrical

Access Panel.

that ductwork installed outdoors have a minimum of 2"

(51 mm) of fiberglass

insulation and be covered by a weatherproof

vapor

barrier that is protected against damage. Caulking and flashings, or other
3.Install lower frame of rain shield with 4 screws.

means adequate to provide a permanent weather seal, must be used.
It is recommended

4.Install rain shield hinged cover with 4 screws.

that ductwork installed in attics or other areas exposed

to outdoor temperatures
5. Install circuit breaker filler plates (2 each per unused breaker slot.)

have a minimum of 2" (51 mm) fiberglass

insula-

tion and have an indoor type vapor barrier.

Ductwork Connections
6. Re-install

Blower/Electrical

Access Panel.
The use of flexible, non-combustible

NOTE:

VERIFY ALL APPROPRIATE

SEALS ARE IN PLACE.

SEE

FIGURE 12,

11. Air Distribution

System

connectors

between main trunk

ducts and supply and return air plenums is recommended
vibration transmission.

to minimize

NOTE: Connect supply and return air plenums to unit in a manner that will
allow the top of the unit to be removed without removing plenums. Ple-

For airflow data (blower performance

data, blower speed tap settings,

etc.) see the Technical Data Sheet attached to the unit..

nums MUST be individually sealed to unit casing. Ducts MUST be terminated inside structure.

Filters

Ductwork
NOTE: The total heat gain of the structu re to be conditioned as expressed

All return air MUST pass through a field supplied filter before entering the

in total Btu/hr should be calculated by manufacturer's

unit. If used, an electronic air cleaner MUST be installed in the return air
ductwork. Minimum recommended filter areas are listed in FIGURE 13

dance with "A.S.H.R.A.E.

Guide" or "Manual J - Load Calculations"

lished by the Air Conditioning
calculated

method or in accor-

Contractors of America.

pub-

The total heat gain

should be equal to or less than the cooling capacity output

based on D.O.E. test procedures,

and are based on a velocity of 300 ft/min (1.2m/s) for disposable
and 500 ft/min (2.54m/s) for washable

steady state efficiency times input.

filters

high velocity filters.

CAUTION

Ductwork, supply registers, and return air grilles MUST be designed and
sized to handle the unit's cooling air volume requirements.
FIGURE 13
NOTE:

Recommended

If the unit is

Do NOT operate the unit without all filters

in place.

Filter Sizes

Some filters are marked with an arrow to indicate the proper direction of air flow through the filter. The air flow direction will be towards
the blower motor. Make sure filter is installed correctly.
Nominal

Tons

Air Conditioning
2

Recommended Filter Sizes
Sq. In. Surface Area/Nominal Size

Nominal Air Flow
Cubic Feet
per Minute

Disposable

Filters

Cleanable

Filters

400 or 20 x 25

246 or 15 x 20

2 1/2

900-1100

487 or 20 x 30

301 or14x25

3

1100-1300

576 or 14 x 25 (2Req.)

356 or16x25

3 1/2

1300-1500

665 or 16 x 25 (2Req.)

411 or 20 x25

4

1500-1700

753 or 20 x 25 (2 Req.)

466 or 20 x 25

5

1900-2100

960 or 20 x 30 (2 Req.)

575 or 24 x 25

700-900

15

427 01 1004 01

12. Start-up

Procedures

FIGURE 15

I

Blower Motor Speed Taps
I

Blower Speed Tap Block
Electrical shock hazard.

Yellow

Use extreme care during all of the following checks and procedures.
Make sure electric power is turned OFF as instructed
propriate steps.

in ap-

Failure to follow this warning can result in property damage,
personal injury, and/or death.

Circulating

Air Blower

Determining

Blower Speed

Auxiliary

Electric
Heat
Wire (if used)
connects
here

1.Turn electric power OFF.

B

2. From the system design, determine the total external static pressure
(ESP) for the supply ducts, return ducts and registers, diffusers,
grilles, dampers, heaters and filters.
BE SURE TO CHECK BLOWER MOTOR SPEED DATA ON THE
UNITS TECHNICAL DATA LABEL LOCATED ON THE UNIT.
3.To your system ESP determined in Step 2, add 0.05 In. W.C. for a
wet coil.

NOTE:

On Heat Pumps Electric heater blower wire must be attached to

the same speed tap required for cooling/heat
U RE 11 notes. The yellow
4.From the system design, determine the desired cooling airflow in
cubic feet per minute (CFM).

pump operation. See FIG-

lead MUST always be connected to the speed

tap block at the common quick connect terminal. The terminal is identified
as COM.
Refer to FIGURE 15 and the appropriate unit wiring diagram included in

5. Locate the unit's Blower Performance

Data table on the tech data

label for the unit's voltage. (The tech data sheet is attached to the
evaporator access panel on the unit.) From the table, determine the
speed tap required to achieve the desired airflow.

this manual.

Wire the black wire to the required speed tap terminal to

achieve required airflow determined

in Step 5.

Cooling, Heating (Heat Pump) and Auxiliary
Electric Strip Heat
6. See next section, Speed Taps, to set the blower motor speed terminal block (speed taps) to the cooling speed determined in the previous steps.

Speed Taps
After determining the required CFM andspeed tap data from the tech data
sheet, follow the steps below to change speeds if necessary.

NOTE: The cooling, heat pump and strip heat airflows are all on the same
speed tap. The refrigerant system requires the same specific CFM for
proper operation in the cooling and the heat pump mode. For this reason,
cooling and heating airflow must be the same. DO NOT SPLIT OUT INTO
A COOLING SPEED AND HEATING SPEED. If auxiliary electric heat is
installed, the auxiliary electric heat blower speed wire must be connected
to the black wire insulated quick connect terminal.

Check Before Starting
FIGURE

i4

L

Blower Speed Tap Settings

10 SEER 2 TON
10 SEER 21/2 TON
10 SEER 3 TON

MED
MED
LOW

10 SEER 31/2 TON
10 SEER 4 TON
10 SEER 5 TON

MED HI
LOW
HI

1. Check that the blower motor speed terminal block is set to the proper cooling speed. Refer to the unit wiring diagram and the various
airflow tables in this manual.

2. Check to see that clean, properly sized field supplied air filters are
installed in the return air duct.

3. Inspect the inside of the unit to be sure that all wires are in place and
all tools, etc. are removed.
4. Replace all service access panels.
Check the unit's operation as outlined in the following instructions.
unusual sparking,
power immediately.
blower motors.
16

odors or noises are encountered,

If any

shut OFF electric

Recheck for wiring errors, or obstructions

in or near

427 01 1004 01

Circulating

Air Blower

4.Set the thermostat temperature
5.Turn electric power ON.

1.Be sure electric power is OFF.

6.Operate
2.Set thermostat Heat-Cool

setting as high as it will go.

unit AT LEAST 5 minutes, then check temperature

rise.

selector to OFF.
NOTE:

The maximum

outlet air temperature

(93.350). Maximum temperature

for all models

is 200°F

rise for electric heat is 60°F (33.350)

3.Set thermostat fan switch to AUTO.
If temperature
temperature
4.Turn electric power ON. Nothing should start running.

5.Set thermostat fan switch to ON. The circulating
come ON after a 30 second delay.

rise is excessive, verify proper airflow through the unit. If
rise is inadequate,

check for proper electrical supply to the

heater and verify correct airflow.

air blower should

7.Set thermostat

to normal temperature

setting.

8.Turn electric power OFF.

6. Reset thermostat fan switch to AUTO. The circulating air blower
should go OFF after a 30 second delay. Nothing should be running.

9.Change blower speed tap if 60°F (33.3°0) TemperatureRise was exceeded
and repeat.

Cooling

10.Be sure to seal all holes in ducts if any were created during this
process.

Defrost Control Time Interval Adjustment

1. Be sure that electric power is OFF.

2. Set thermostat

Heat-Cool

select to COOL.
Electrical

3. Adjust thermostat setting to below room temperature.

4. Turn electric power ON. During power application
ing:

shock hazard.

Turn OFF electric power supply at disconnect switch or service panel before removing any access or service panel from
unit.

check the follow-

Failure to follow this warning can result in property damage,
personal injury, and/or death.

a. Contactor - Contacts closing
b. Compressor - ON
c. Condenser fan motor - ON

To adjust

d. Circulating air blower - ON (after delay)

defrost

interval:

1.Turn off all power to Heat Pump.
5. Switch the thermostat to OFF, check the following:

2. Remove control box cover.

a. Contactor contacts opening.

3. Locate electronic

b. Compressor - OFF
c. Condenser fan motor - OFF

4.The Defrost Control Board has a jumper plug that can be set at 30, 60,
90 or TEST. Remove the plug and insert on the appropriate 2 pins
indicated by ) on the board.

d. Circulating blower - OFF (after delay)

defrost control board.

6.Turn electric power OFF

Auxiliary

Heating

NOTE: Repeat circulating air blower procedure above if Auxiliary Electric
Heat is being installed after unit has been installed and checked out.

Temperature Rise Check
Temperature rise is the difference between the supply and return air temperatures. The temperature rise should be -+2°F (1.1 °C) of the temperature rise shown in FIGURE 11 .
NOTE: The temperature

rise can be adjusted by changing the heating

speed tap at the unit's blower terminal block. Refer to the unit's Installation
Instructions for airflow information.

13. Sequence

Atemperature

NOTE: If power to the unit has been interrupted, there will be a 3 minute

rise greater than 60°F (33.3°C) is not recommended.

(This

applies to electric heat only).

of Operation

delay before the compressor

1.To check the temperature rise through the unit, place thermometers
in the supply and return air ducts as close to the unit as possible.

Cooling

Mode:

Energized

starts.
(R,G,Y,

O)

De-energized

(N/A)

(a) When high and low voltage have been applied to unit
for more than 3 minutes:

2. Open ALL registers and duct dampers.

3.Set thermostat Heat-Cool

selector to HEAT.

(1)On a call for cooling ......... :
The compressor and condenser fan will energize. The evaporator
blower motor will have a delay on and will energize after 30 seconds.
17

427 01 1004 01

(2)When the cooling setpoint has been satisfied ......... :
The compressor and condenser fan will de-energize immediately.
The evaporator blower motor will have a delay off and will de-energize after 30 seconds.

NOTE: If the jumper on the defrost delay selection

(2)

Heat Mode (Heat Pump Only): Energized (R,G,Y)
De-energized (O)

(a) When high and low voltage have been applied to unit
for more than 3 minutes:
(1) On a call for heating ......... :
The compressor and condenser fan will energize (there will be a 3
minute delay on 4 Ton model with anti-cycle timer). The evaporator blower motor will have a delay on and will energize after 30 seconds. The delay on for the compressor and the condenser fan can
be by-passed by jumpering the test pins on the defrost control
board.
(2) When the heating setpoint has been satisfied ......... :
The compressor and condenser fan will de-energize immediately.
The evaporator blower motor will have a delay off and will de-energize after 30 seconds.

Defrost Mode:Energized
Sensor Closed

(1)

(R,G,Y)

De-energized

(O) Defrost

is left in the "TEST"

mode, the board will default to 90 min. delay until power is off.
When defrost has been completed .........
This condition will be maintained until the defrost sensor opens or
until the defrost mode operates for 10 minutes (or 2 seconds if test
pins are jumpered), whichever comes first.

Adding Accessories
Low/High Pressure Controls
This unit is equipped with extra !ow and high pressure ports located inside
the unit panel where the external high and low pressure ports are installed.
This allows for installation of high and low pressure controls or low ambient controls.

14. Operation
Scroll Anti-Cycle

Timer (Where Applicable)

Single phase units with scroll compressors may be equipped with an anti-

On a call for defrost .........
When the defrost sensor c!oses in the heating mode,there is a 30,
60 or 90 minute delay before the defrost mode begins. This delay
is selected by the position of a jumper on the defrost board

cycle device which delays the start of the compressor in the event of a
power interruption. This equalizes pressure throughout the system and

In normal defrost mode, the following sequence will occur after the
set delay:

vent the compressor from running backwards, so an anti-cycle
needed on these models.

1. Condenserfan
2.

prevents possible reverse rotation ofthe scroll compressor.

Later produc-

tion scroll compressors

device to pre-

off.

Reversing valve energized to cooling and auxiliary electric
heat ("W" circuit) is energized.

3. After defrost sensor opens or a maximum of 10 minutes; the
condenser fan is energized immediately.
After a 10-12 second
delay the reversing valve is then de-energized to the heat mode.
Electric strip heat is also de-energized except as required by thermostat.
To check out the defrost mode, place jumper across the two tabs
marked "DF". This simulates the defrost sensor closing. The delay
can be by- passed by jum pering the test pins on the defrost control
board (this reduces the delay from 30 minutes to 7 seconds, from
60 minutes to 14 seconds and from 90 minutes to 21 seconds). In
the defrost mode the reversing valve will energize and the condenser fan will de-energize.

are equipped with an anti-reverse

timer is not

CAUTION
Do NOT operate unit on cooling when the outdoor temperature

is be-

low 60°F. This is necessary to prevent possible damage to the compressor.

Loss of Charge Pressure Switch

Scroll compressor

bearing units are equipped with a low pressure switch

on the liquid line (high side) which has been installed to prevent system
damage due to a loss of charge. The switch will open and de- energize the
contactor if the high side pressure drops below the set point of the switch.

18

427 01 1004 01

INTERNATIONAL COMFORT PRODUCTS
LIMITED WARRANTY CERTIFICATE
For Cooling
SAVE THIS CERTIFICATE.
province

It gives you specific

& Heating Products

legal rights, and you may also have other

rights which

may vary from state to state and

to province.

If your unit needs servicing, contact a qualified dealer or qualified service technician of your choice. When requesting service, please have the model
and serial number from each unit in your heating and/or cooling system readily available. If your dealer needs assistance, the distributor is available to
provide support and we, in turn, support its efforts.
Fill in the installation date and model and serial numbers of the unit in the space provided below and retain this Limited Warranty for your files.

GENERAL TERMS
Subject to the conditions and limitations stated herein, during the term of this Limited Warranty, we will provide a replacement for any functional
component part (as defined below) of your unit found to be defective in materials or workmanship. The term of this Limited Warranty is five years from
installation on Residential Products and one year from installation on Commercial Products. Except as otherwise stated in the "Additional Terms"
section, this Limited Warranty covers only the original purchaser and subsequent transferees, and only while the unit remains at the site of the original
installation (except for mobile home installations), and onty if the unit is installed inside the continental United States, Puerto Rico, Alaska, Hawaii or
Canada. In addition, the Limited Warranty applies only if the unit is installed and operated in accordance with the printed instructions accompanying the
unit, and in compliance with alt applicable installation and building codes and good trade practices. As used in this Limited Warranty, "installation"
means the original installation of the unit.
TH ERE ARE EXCEPTIONS to this Limited Warranty as described on the reverse side of this page. All replacement parts will be warranted for the
unused portion of the warranty coverage period on the unit. The part to be replaced must be returned by the dealer to a distributor that sells products for
International Comfort Products, in exchange for the replacement part. In lieu of providing a replacement part, we may, at our sole option, refund to you
an amount equal to the distributor's component purchase price from us, or provide to you a credit equal to that amount to be applied toward the purchase
of any new unit that we distribute. If a credit for a new unit is given in tieu of a replacement part, the rating plate from the unit being replaced must be
submitted on a warranty claim, and you r dealer must make the unit being replaced available to our distributor for disposition. As a condition to warranty
coverage, the unit must receive yearly maintenance, as described in the owner's manual, by a dealer. Satisfactory proof of yearly service by a dealer
may be required.
"Functional component parts" include only the following: blower motor, unit-mounted sensors & timers, condenser motor, evaporator coil, condenser
coil, condenser fan, capacitor, transformer, single-phase strip heat elements, expansion device, reversing valve, solenoid valve, service valve,
electronic and electro-mechanical control board, ignitor, ignition module, draft inducer assembly, burner pilot, gas valve, limit control, pressure switch,
relays and contactors, blower wheel, interlock switch, crosslighter, pilot shield, gas & oil burners, oil pump assembly, accumulators and factory installed
driers and strainers.
This Limited Warranty DOES NOT COVER any labor, material, refractory chambers, oii nozzles, refrigerant, refrigerant inspection and refrigerant
reclaiming, freight and/or handling charges associated with any repair or replacement and such charges will be your responsibility.
To establish the installation date for any purpose under this Limited Warranty, you must retain the original records that can establish the installation date
ofyour unit. Ifyou donot providesuchdocumentsthe
start dateoftheterm ofthis LimitedWarrantywillbe
based uponthedate ofunit manufacture, ptus
thirty (30) days. In establishing that the required yearly service has occurred, you must furnish proof of yearly service by a qualified service technician.
This Limited Warranty does not cover: (a) failure or damages caused by accident, abuse, negligence, misuse, riot, fire, flood, or Acts of God (b)
damages caused by operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any other damaging chemicals (other
than those found in a normal residential environment) (c) damages caused by an unauthorized alteration or repair of the unit affecting its stability or
performance (d) damages caused by improper matching or application of the unit or the unit's components (e) damages caused by failing to provide
proper maintenance and service to the unit in accordance with this Limited Warranty Certificate and the printed instructions originally provided with the
unit (f) any expenses incurred for erecting, disconnecting, or dismantling the unit (g) parts or supplies used in connection with service or maintenance,
such as refrigerant, refractory chambers, oil nozzles, filters, or belts (h) damage, repairs, inoperation or inefficiency resulting from faulty installation or
application (i) electricity or fuel costs or any increase in electricity or fuel cost whatsoever including additional or unusual use of supplemental electric
heat (j) units which have not had the required yearly maintenance described elsewhere in this limited warranty.
In no event shall we be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit.
We have not made. do not make. and hereby disclaim any implied condition or implied warranty of fitness for a particular use or purpose, and
anv implied condition or implied warrantv of merchantabilitv, to the fu Ilest extent allowed bv law. We make no express or implied warranties
except as stated in this Limited Warrantv certificate.
No one is authorized to change this Limited Warranty or to create for us any other obligation or liability in connection with this unit. Any implied
warranties shall last for the term of the expressed warranty contained herein. Some states and provinces do not allow the exclusion or limitation of
incidental or consequential damages or do not allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions
may not apply to you. The provisions of this Limited Warranty are in addition to and not a modification of or subtraction from any statutory warranties and
other rights and remedies provided by law.

Please refer to reverse side of this page for additional terms.
Model No.
Serial No.

Effective

Date Installed

on units installed

After July 1, 2002,

USA: International Comfort Products Corporation (USA) • 650 Hell-Quaker Avenue * P.O. Box 128 • Lewisburg, Tennessee 37091 • (931-270-4100)
CANADA: International Comfort Products division of UTC Canada Corporation • 6060 Burnside Court, Unit 1, Mississauga, Ontario L5T 2T5
(905-795-8113).
Manufacturers of Airquest, Arcoaire, Clare, Comfortmaker, Dettson, Hell, Keeprite, Lincoln, Tempstar and other quality brand name private label
products.
Part No. 401 06 1010 19 (Orig. 9/19/2002)

ADDITIONAL

TERMS FOR RESIDENTIAL

APPLICATIONS

ONLY

The Additional Terms for the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
Warranty coverage is limited to parts that fail due to defect in materials or workmanship during the specified term.

CENTRAL GAS & OIL FURNACE HEAT EXCHANGERS*
Gas Model Series: C9MPV. HgMPV. TgMPV. CgMPT. H9MPT. T9MPT. C9MPD. HgMPD. TgMPD: Limited Lifetime Warranty on heat exchangers. If
a heat exchanger on one of these furnaces fails due to defect in the part, we will provide a replacement part or, at our option, credit toward the purchase
of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and tasts only for as tong as the originat
purchaser tives in the home where the furnace is initially installed.** It is not transferable to any subsequent owner. Ifthe furnace was not installed in the
home owned by the original purchaser, if the original purchaser setls the home to a subsequent owner, or if proof of originat purchase cannot be
provided, then the limited warranty is only for 20 years from the date of original installation.
Gas Model Series: GDL. GNL. TNE. TDE. NTC7. NDC7. NTP6. NDP6. TDE. NTV6. VNE: A replacement heat exchanger will be provided for any
heat exchanger that fails in one of these furnaces due to defect for 25 years from the originat date of installation.
Gas Model Series: NTC6. GNE. GDE. NDN6. NTG3. NDN3. FBF. NBF. NDF. NTN3. NTN6. NNE. N9MPI. N9MP2. FUH: A replacement heat
exchanger witt be provided for any heat exchanger that faits in one of these furnaces due to defect for 20 years from original date of installation.
Oil Model Series: OLR(105, 160, 182), OCF, OLE OUF, NOLE NOUF, OLB, OHB, ODH, FLO, MBO, LBO, NOMF: Limited Lifetime Warranty on
heat exchangers. Ifa heatexchangerononeofthesefurnacesfailsduetodefectinthepart,
wewitl provide a replacement part or, at our option, credit
toward the purchase of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and tasts only for as
long as the original purchaser lives in the home where the furnace is initially installed.** It is not transferable to any subsequent owner. If the furnace
was not installed in the home of the original purchaser, if the original purchaser sells the home to a subsequent owner, or if proof of original purchase
cannot be provided, then the limited warranty is only for 20 years from the date of original installation.
Oil Fired Floor Furnace: NFO: A replacement heat exchanger witl be provided for any heat exchanger that faits due to defect for 10 years from
installation with the following limitation: during the sixth through tenth year, any credit toward your purchase of a component or toward the purchase of
any new unit wilI be in an amount equal to the distributor's purchase price reduced by 20 percent for each year after the fifth year.

ADDITIONAL

TERMS FOR OIL FURNACE APPLICATIONS

ONLY

1) OIL BURNERS - A replacement for 5 years from date of original installation for Oil Burner Parts.
2) OPTIONAL ACCESSORIES AND FUNCTIONAL PARTS: A replacement for 5 years from date of original
oil nozzles not included)

GAS/ELECTRIC
Model series:

PACKAGED

installation.

(Refractory

and

UNITS HEAT EXCHANGERS

PGAD. PGAA. PGMD. PGME. PGF. GPFM. PGC. GPCM:

A replacement for 10 years from original date of installation.

COMPRESSORS:*
1) Premium Model Units: HAC0. HAC2. HAC4. CAC0. CAC2. CAC4. KAC0. TCA0. TCA2. TCA4. HHP0. HHP2. HHP4. CliP0. CliP2. CliP4.
TCH0. TCH2. TCH4. PGME. PYMC. PHAD. PGAD. PA95. PAPC. PAK. APK: To the original purchaser a replacement for 10 years from original date
of installation, only if the unit is installed with factory matched coils, except air conditioner condensing units with a nominal SEER of 10 may be matched
with evaporator coils of the same nominal tonnage regardless of manufacturer and in accordance to factory recommendations. This limited 10-year
warranty is not transferable to any subsequent owner. HOWEVER, if the unit was not installed in the home owned by the original purchaser, if the
purchaser sells the home to a subsequent owner, or if proof of original purchase cannot be provided, then the limited warranty is only for 5 years from the
original date of installation.**
2) All Other Models: Air Conditioners.
Heat PumPs. & Combination
Gas/Electric Units: NAC0. NAC2. NHP0. NHP2. AO. A2. HO. H2. PGF.
PGC, GPFM, GPCM, PAE APFM, PHE HPFM, PGAA, PGMD, PA55, PH55, PAPA, PYPA: A replacement for 5 years from date of original
installation, onty if: (a) air conditioner condensing units with SEER rating in the range of 10 to 11 SEER are matched with evaporator coils of the same
nominal tonnage regardless of manufacturer and in accordance to factory recommendations, or (b) heat pump condensing units are used with factory
matched coils, unless written approval to do otherwise is obtained from manufacturer.

ADDITIONAL

TERMS FOR COMMERCIAL

APPLICATIONS

ONLY

For purposes of this warranty a commercial application is one in which: the product has over 5 tons nominal cooling capacity, or is designed
for operation with 3 phase electrical power, or is installed in a commercial establishment such as a beauty or hair salon, hospital, school,
restaurant, church, hotel etc..
3-Phase Models: PGF, GPFM, GPF, PGAD, PGME, PGB, PGMG, PGMF, PGS, PGE, APE, PAE, PAB, PAMD, PAS, PAl=,APFM, APF, PHB, PHE,
PYMD, HPB, PHS, CAC, ACC, CAE, ACE, CHC, HCC, CHE, HCE, CHB, YA:
The additional

Terms of the components

listed below are in addition to and subject to the General Terms on the reverse side of this page.

1) GAS FIRED HEAT EXCHANGERS (ALL MODELS):* A replacement for 10 years from date of originat installation.
2) COMPRESSORS (ALL MODELS):* A replacement for 5 years from date of original installation.
3) OPTIONAL ACCESSORIES AND FUNCTIONAL COMPONENT PARTS (ALL MODELS):*
A replacement for 1 year from date of original installation.
4) COMMERCIAL OIL MODELS: OLR210, OLR350, OTF210, AMT3, AMT4, AMP3: Ten(10) Year Limited Warranty on heat exchangers.
*To receive advantage of your limited warranty, you must provide proof of yearly service by a qualified service technician.
**To receive advantage of your warranty, you must retain the original records that can establish the installation date and proof of purchase of the unit.

MINI SPLITS:
Summary - Mini Splits Warranted for one (1) year on all replacement parts.
Additional terms for Mini Splits:
The additional Terms of the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
1) Compressors
installation.

(All Models):

A replacement compressor wili be provided for atI compressors that faii due to defect for 5 years from date of original

2) Optional Accessories and Functional Components Parts (All Models):
A replacement part will be provided for alt parts that fail due to defect for one (1) year from date of original installation.
Failu re to maintain the equipment through annual maintenance by a qualified service technician shall void the warranty. Proof of service wili be required
with ati warranty claims. Proof of purchase and installation date must be submitted with ali claims.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 20
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Thu Apr 05 04:15:00 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu