Installation
Instructions
Contents
1. Unit Dimensions
1. Safety Labeling

...................
And Signal Words

2. Safe Installation
the Unit

4. Electrical

Wiring

6. Economizer
7. Start-up

c@@

System

3

7

.............

9

...........

10

..............

11

.......................

13

.....................

Instructions

.. 3

4

...................

Procedures

9. Maintenance
10. Rigging

.....

..................

Accessory

8. Operation

80-30-04

Requirements

3. Locating

5. Air Distribution

2

14

............

16

I

I DIRECT
DRIVEBLOWER

I,o ,

SINGLE
PACKAGE
AIRCONDITIONER
ELECTRIC
HEAT(OPTIONAL)
Printed in U.S.A.

513 01 1005 00

10/23/01

I Installation Instructions

Single Package Air Conditioners

1. Unit Dimensions

UNIT DIMENSIONS

ALL MODELS

D_M

INCHES

MILL METERS

A

36"

B

47 3/8 'r

/ 203

C

73"

/854

D

4 58"

/ 17

E

15"

381

F

12"

307

G

/8 3_4"

476

H

/8 3_4"

476

E2"

305

J

9/4

J

/02

K

N/A

L

4 I '4"

/ 08

M

5P4"

E33

N

12 1'4"

3/ /

P

E9"

483

Q

15"

381

R

19"

483

S

/2 //4"

3/1

•

/6 78"

429

I
I
I

LOW VOLTAGE
1/2" CONDU_T

UNIT

BASE

SHOWN

TO ILLUSTRATE
DUCT

ELECTRIC HEAT POWER
1", 1-1/2", 2" CONDUIT

SEPARATELY

BOTTOM

OPENINGS

UNIT ELECTRICAL POWER
3/4", 1", 1-1/4" CONDUIT

Note: Above dimensions are ininches

ROOF CURB
ALL MODELS
DiM

INCHES

MILLIMETERS

A

67 34"

/721

B

64 34"

1645

C

23"

584

D

23"

584

E

2 //2"

F

42 3_4"

1086

64

G

39 34"

/010

H

23"

584

I

/2"

305

J

12"

305

_÷

/4"

356

,,÷j

pJ

80 10 14

* Roof curbs are also available in 8" (203mm) and 24" (610mm) heights (K dimension).

I

I Single Package Air Conditioners

Installation

Instructions

1. Safety Labeling And Signal Words
DANGER,

WARNING

AND

CAUTION

CAUTION

- Hazards or unsafe practices which COULD

result in minor personal injury or product or property damThe signal words DANGER, WARNING and CAUTION are
used to identify levels of hazard seriousness. The signal
word DANGER is only used on product labels to signify an
immediate hazard. The signal words WARNING and CAU-

age.

Signal Words

in Manuals

TION will be used on product labels and throughout this

The signal word WARNING is used throughout this manual

manual and other manuals that may apply to the product.

in the following manner:

SIGNAL WORDS
DANGER - Immediate hazards which WILL result in severe personal injury or death.
The signal word CAUTION is used throughout this manual
in the following manner:
WARNING - Hazards or unsafe practices which COULD
result in severe personal injury or death.

CAUTION

2. Safe Installation Requirements
• Seal supply and return air ducts.
Installation or repairs made by unqualified persons can result in hazards to you and others.
Installation MUST conform with local building
codes or, in the absence of local codes, with the
National Electrical Code NFPA70-1990 or current
edition or in Canada CSA C22.1 - Canadian Electrical Code Part 1 or current edition.
The information

• Check to see that filters are installed correctly and
are the proper type and size.
NOTE: It is the personal responsibility and obligation of the
customer to contact a qualified installer to ensure that the
installation is adequate and conforms to governing codes
and ordinances.

contained in this manual is in-

tended for use by a qualified service technician
familiar with safety procedures and equipped
with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in unit malfunction,
property damage, personal injury and/or death.

131

I Installation Instructions

Single Package Air Conditioners I

3. Locating the Unit
The unit is designed for outdoor installation
may be installed on a concrete slab (or other
form) at ground level, or on a rooftop with an
form or a roof curb. Typical installations
NO TAG through NO TAG.
FIGURE 1 [

only. The unit
adequate platadequate platare shown in

CAUTION
Do NOT operate unit in a corrosive atmosphere containing chlorine, fluorine, or any other corrosive chemicals.

Minimum Clearances
Construction

Minimum Clearances

to Combustible

Supply and Return Air Ducts ......................

0"

Duct Connection Side (no economizer)
...........

2" (50mm)

on

Duct Connection Side (with economizer)

61/3 ton models
. 48" (1220mm)

Condenser Access Panel Side ..........

30" (762mm)

Blower Access Panel Side ..............

30" (762mm)

Electrical Access Panel Side ............

30" (762mm)

Clearance between 3 Ft. Overhang
and Top of Unit

............

30" (762mm)

Combustible Base
(Wood or Class A, B or C
roof covering material) .................

0"

Access Panels
CAUTION

Clearances
The location MUST allow for minimum clearances

and

should not be adjacent to a patio or other area where the
unit's operating sound level might be objectionable. Local
codes MUST be observed.
Minimum clearances, as specified belowand in FIGURE 1,
MUST be maintained from adjacent structures to provide
adequate air circulation and room for service personnel.

Unit will NOT operate properly without all access panels in place.
See FIGURE 2 below for a general view of unit and location
of access panels.
FIGURE 2

I

Compressor
Panel

Access
__

While minimum clearances are acceptable for safety reasons, they may not allow adequate air circulation around
the unit for proper operation in the cooling mode. Whenever possible, it is desirable to allow additional clearance, especially around the condenser inlet and discharge

Blower _-eess

openings.
Do NOT install the unit in a location that will permit discharged air from the condenser to recirculate to the condenser inlet.
Electrical Access
Panel

4L_!J

Access Panels

[

Panel

I Single Package Air Conditioners

Installation

Rooftop
CAUTION

Unit will NOT operate properly unless it is installed level front to rear and side to side.
The slope MUST NOT be greater than 1/8" per foot
(10mm per meter). For side to side leveling, the control
box side MUST always be lower.

Ground

Installation

Level Installation

Ground level platform requirements:
The unit MUST be situated to provide safe access for
servicing.
Platform may be made of either concrete or pressure
treated wood and MUST be level and strong enough
to support unit weight.
Position platform separate from building foundation.
Install in well-drained area, with top surface of platform above grade level.
Platform MUST be high enough to allow for proper
condensate trap installation and drainage. See
FIGURE 4 and associated text for more information
about condensate drainage.

Instructions

Installation

Rooftop platform requirements:

The unit MUST be situated to provide safe access for
servicing.
The existing roof structure MUST be adequate to
support the weight of the unit or the roof MUST be reinforced.
Check the weight of the unit in relation to the roof
structure and local building codes or ordinances and
reinforce roof structure if necessary. See FIGURE 11
on the back cover of this manual for unit weights and
corner weights.
Support for the unit MUST be level and strong
enough to carry unit weight. The support may consist
of a platform or a combination of platform and roof
beams or curb.
The platform may be constructed of pressure treated
wood and may be covered with Class A, B or C roof
covering.
Platform MUST allow for proper condensate trap
installation and drainage. See FIGURE4
and
associated text for more information about condensate drainage.
See Hoisting section below for hoisting instructions.
NOTE: Cardboard covers on horizontal supply and return duct openings MUST be removed before starting
unit.

Hoisting
NOTE: All access panels MUST be secured in place before
hoisting.
The unit should be hoisted with two lifting slings. Attach the
slings to rigging shackles that have been hooked through
holes in the base rail.

Two spreader bars MUST be placed on top of the unit to
protect the unit from damage from the pressure exerted by
the slings. Make sure that all equipment is adequate to
handle the weight of the unit and that the slings will not allow the unit to shift.
Refer to FIGURE 11 on the back cover of this manual for
illustrated rigging instructions and weight chart.

ISl

_ Installation Instructions

Downflow

Single Package Air Conditioners

Conversion

These units are shipped ready for horizontal operation but
are adaptable to downflow use. To convert to downflow
use, follow these steps:
1.

Remove the blockoff plates found in the return air
compartment and the supply air compartment (see
FIGURE 3.

NOTE: Blockoff plate in the supply air compartment only
contains one screw. If reinstalling plate, back part of plate
MUST fit into mating dimples on flange. To reinstall, slant
plate into dimples, then put plate into position and fasten
with screw.

Condensate

I

Drain

The condensate drain outlet is

a 3/4"

(19.1mm) threaded

female PVC connection located at the bottom of the unit to
the left of the electrical access panel (see FIGURE 4). Condensate drain outlet MUST be held with wrench when
installing trap and drain line.
The circulating blower and the condenser fan create a negative pressure on the condensate drain line that will prevent the condensate from draining properly without a trap.
To combat this negative pressure, a field supplied condensate trap that will allow a standing column of water of at
least 2" (50.8mm) MUST be installed. Top of outlet from

2.

Install the removed plates on the horizontal return
and supply air openings.

NOTE: It is the installer's personal responsibility to follow
all local codes and ordinances and instructions contained
herein, as well as instructions included with accessory
items when installing unit. It is the installer's personal responsibility to locate directions for installation of this unit
and any or all accessories. Manufacturer is NOT responsible for improper installation practices.
3.

Install unit on the appropriate roof curb.

FIGURE 3

trap MUST be at least 1" (25.4mm) below top of outlet from
unit. Install the trap as near to the unit as possible

for

proper drainage.
A

3/4"

(19.1 mm) drain line MUST be installed if required by

local codes or if location of unit requires it. Run the drain
line to an open drain or other suitable disposal point.

FIGURE 4 I Condensate

Drain Information*

Blockoff Plate
(Return Air Compartment)

Access Panel

80-30-27

* Condensate

trap MUST be installed.

I Single Package Air Conditioners

Installation Instructions

4. Electrical Wiring
connections. If an economizer is installed, see the following section, Low Voltage Wiring With Economizer Option.
Electrical shock hazard.
Disconnect power at fuse box or service panel
before making any electrical connections.
Unit MUST be grounded to electrical service panel.
Failure to follow this warning can result in property damage, personal injury, and/or death.
NOTE: All electrical work MUST conform with the requirements of local codes and ordinances and in the United
States with National Electrical Code ANSI/NFPA 70-1990
(or current edition) and in Canada with CSA C22.1 - Cana-

Low Voltage
Option

Wiring

With

Economizer

Same as the above Low Voltage Wiring section except refer to the connection wiring diagram supplied with the
economizer. Also, a pre-wired plug for the economizer is
located just inside the return air opening.

Thermostat
The location of the thermostat has an important effect on
the operation of the unit. FOLLOW THE INSTRUCTIONS
INCLUDED WITH THE THERMOSTAT FOR CORRECT
LOCATION, MOUNTING AND WIRING.

Unit Without

Economizer

dian Electrical Code Part 1 (or current edition). Provide line
voltage power supply from a separate fused circuit with a
disconnect switch (when required) located within sight of
the unit. Supply voltage, amperage, wire, fuse and disconnect switch sizes MUST conform with specifications in the

A field supplied single stage thermostat is required.

Unit With

Economizer

Wiring MUST be protected from possible mechanical dam-

A field supplied two stage thermostat is recommended for
use with an economizer. If a single stage thermostat is
used, the compressor will not start if the economizer can
not satisfy the demand for cooling.

age and MUST NOT interfere with removal of access panels, filters, etc.

Ground Connections

Technical Support Manual and on the unit rating plate.

All exposed wiring and connections MUST be made with
weatherproof cable or wire unless installed in conduit.

Low Voltage Wiring
Low voltage connections are made on the low voltage terminal board inside the electrical compartment (see
FIGURE 5). For access, remove the electrical access panel (see FIGURE 2).

A ground lug is installed on the electrical control plate for
the ground connection (see FIGURE 5). Use a copper conductor of the appropriate size from the unit to a grounded
connection in the electrical service panel or to a properly
driven and electrically grounded ground rod. See WARNING above.

Line Voltage Wiring

Refer to the Technical Support Manual for the connection
wiring diagram for the applicable model and to the instructions included with the thermostat.

Do NOT complete line voltage connections until unit is permanently grounded. All line voltage connections and the
ground connection MUST be made with copper wire.

Route low voltage wires through the port located at the bottom left corner of the blower access panel side of the unit.

Connections for line voltage are made on the unit electrical
control plate (see FIGURE 5). For access, remove the
electrical access panel (see FIGURE 2).

Route low voltage wires behind unit cornerpost, through
the wire clip provided, and up to the low voltage terminal
board.
NOTE: If an Electric Heat Accessory is installed, see the
Electric Heat Accessory Installation Manual for low voltage

Refer to applicable wiring diagram in the TechnicalSupport
Manual. Complete the line service connections to the con-

171

_ Installation Instructions

tactor 'L' terminals on the unit electrical control plate.
Check all screw terminals to ensure they are tight.

Single Package Air Conditioners

5.

Replace the electrical access panel.

Field Installed
NOTE: If an Electric Heat Accessory is installed, refer to
the Electric Heat Accessory Installation Manual to determine line voltage connections. The Electric Heat Accessory mounts inside the unit. Field supplied line voltage wires
for the Electric Heat Accessory (separate from the field
supplied line voltage wires to the unit) connect to the circuit
breaker(s) in the Electric Heat Accessory.

Equipment

Wiring to be done in the field between the unit and other devices, or between separate devices which are field
installed and located, MUST NOT exceed the temperature
limitations for type T wire and MUST be installed according
to the manufacturer's instructions for the devices.

Final Electrical
Converting

I

Check

230V Units to 208V
Make a final wiring check to be sure system is correctly

To convert 230V units to 208V:

wired. Inspect field installed wiring and the routing to en-

1.

Turn electric power OFF.

sure that rubbing or chafing due to vibration will not occur.

2.

Remove the electrical access panel.

NOTE: Wiring MUST be installed so it is protected from

3.

Locate the 24V control transformer.

possible mechanical damage.

4.

Remove wires from the terminal labeled "240V" on
the 24V control transformer and reconnect them to
the 208V terminal of the 24V control transformer.

FIGURE 5

I Typical Wiring Installation

Electrical Control
Plate
Low Voltage Terminal Board
Contactor 'L' Terminals
Ground lug
Carefully route low
voltage wires behind
unit cornerpost
through wire clip
Field supplied line
voltage wires
Knockout for Electric Heat Accessory
field supplied line
voltage wires

8L2J

I Single Package Air Conditioners

5. Air Distribution

Installation

Instructions

System

For airflow data (blower performance data, blower speed
tap settings, filter sizes, etc.) see the Technical Support
Manual.

Ductwork
NOTE: The total heat gain from the structure as expressed
in total Btu/hr MUST be calculated by manufacturer's
method or in accordance with "A.S.H.R.A.E. Guide" or
"Manual J - Load Calculations" published by the Air Conditioning Contractors of America or in Canada "H. R.A.I. Residential Heating and Cooling Load Calculation Manual."
The total heat gain calculated should be equal to or less
than the cooling capacity. Output based on D.O.E. test procedures, steady state efficiency times input.
Ductwork, supply registers, and return air grilles MUST be
designed and sized to handle the unit's cooling air volume
requirements. If the unit is connected to an existing system,
the ductwork MUST be checked to make sure it is adequate. Extra runs or larger duct sizes may have to be
installed.
Maximum recommended velocity in trunk ducts is 1000
feet per minute (5.08m/s). Velocity in branches should not
exceed 800 feet per minute (4.06m/s). Refer to the Technical Support Manual for unit air volume requirements and
system sizing recommendations.
NOTE: Ductwork sizing affects temperature rise and cooling temperature differential. Be sure to properly size ductwork to the capacity and airflow characteristics of your unit.
Failure to do so can affect limit controls, compressors, motors, and other components and will lead to premature failure of components. This will also adversely affect day to
day unit performance.

Ductwork

Insulation

It is recommended that ductwork installed outdoors have a
minimum of 2" (51 mm) of fiberglass insulation and be covered by a weatherproof vapor barrier that is protected
against damage. Caulking and flashings, or other means
adequate to provide a permanent weather seal, must be
used.
It is recommended that ductwork installed in attics or other
areas exposed to outdoor temperatures be installed with a
minimum of 2" (51mm) fiberglass insulation and have an
indoor type vapor barrier.

Ductwork

Connections

The use of flexible, non-combustible
connectors between main trunk ducts and supply and return air plenums
is recommended to minimize vibration transmission.
NOTE: Connect supply and return air plenums to unit in a
manner that will allowthe top of the unit to be removed without removing plenums. Plenums MUST be individually
sealed to unit casing. Ducts MUST be terminated inside
structure.

Filters
All return air MUST pass through a filter before entering the
unit. An electronic air cleaner, optional filter racks or other
accessible filter arrangements MUST be installed in the return air ductwork. Minimum recommended filter areas are
listed in the Technical Support Manual and are based on a
velocity of 300 ft/min (1.2m/s) for disposable filters and 500
ft/min (2.54m/s) for washable high velocity filters.

CAUTION
Do NOT operate the unit without

Refer to unit rating plate for proper Electric Heat Accessory
sizing and see the Temperature Rise Check section in the
Electric Heat Accessory Installation Instructions.

all filters

in place.

_ Installation Instructions

Single Package Air Conditioners

I

6. Economizer Accessory
The purpose of an economizer is to:
•

•

Sequence

Provide cool outdoor air to the conditioned space
during the cooling cycle to minimize the use of compressors.
Bring outdoor air into the conditioned space to meet
minimum ventilation air requirements whenever the
circulation blower is running.

Theory of Operation

NOTE: For correct wiring to the low voltage terminal board,
see the connection wiring diagram in the economizer's
documentation.

When a field supplied two stage thermostat is in the FAN
ON position:
The outdoor air dampers will open to the minimum
position for outdoor air.

1.

The economizer has two sets of dampers that are mechanically linked together. The outdoor air dampers regulate the
intake of outdoor air and the return air dampers regulate
the flow of return air (see FIGURE 6). When the outdoor air
dampers modulate open, the linkage causes the return air
dampers to modulate closed. A barometric relief damper is
installed in the return air side of the system. It relieves any
positive pressure in the unit created by the economizer.

2.

NOTE: All circuits have a low voltage safety circuit
consisting of a high pressure switch, a low pressure
switch and an anti-cycle delay timer.
.

[

On the thermostat's call for cooling, the thermostat
completes Circuit 1 between thermostat terminals R
and G and Y1 for first stage cooling.
If the economizer's enthalpy sensor determines that
the outdoor air conditions are below the setting for
economizer operation, the outdoor air dampers will
modulate open and the return air dampers will modulate closed.

The economizer is controlled by a logic module which field
connects to the unit controls through a harness plug. The
logic module also controls the compressor staging based
on the thermostat input.
FIGURE 6

of Operation

Typical Downflow Economizer
Outdoor Air
Dampers
Mixed Air
Sensor

The mixed air sensor at the blower inlet modulates
the economizer dampers to prevent the mixed air
from falling below 56°F (13.3°C). (Mixed air refers to
return air after it combines with outdoor air from the
economizer.) The mixed air sensor modulates the
outdoor air dampers between the full open and minimum outdoor air positions.
If the mixed air is not cold enough to maintain the
conditioned space at the selected temperature, the
thermostat will make Y2 and call for second stage
cooling by energizing the economizer logic module.
This energizes the Y1 anti-cycle delay timer and
contactor Cl which energizes the condenser fan and
the compressor.

Actuator Motor and
Logic Module

4,

Return Air
Dampers

If the thermostat is still calling for cooling and the
economizer's enthalpy sensor determines that the
outdoor air conditions have risen above the setting
for economizer operation:
a. The economizer dampers will close to the minimum position for outdoor air and remain there.
b. Contactor Cl will remain energized and the compressor will continue to run.

I Single Package Air Conditioners

Installation Instructions

7. Start-up Procedures
cess panel and is also published in the Technical Support
Manual. Wire the speed tap as required.
Electrical shock hazard.
Use extreme care during
checks and procedures.

Cooling
all of the following

Make sure electric power is turned
instructed in appropriate steps.

OFF as

Failure to follow this warning can result in property damage, personal injury, and/or death.

Circulating

Air Blower

Determining

Blower Speed

If an Electric Heat Accessory is used, see its Installation
Manualfor proper heating speed tap settings. If it has been
determined that cooling and heating speeds are needed on
the same speed tap, remove the red heating lead from the
speed tap block and connect it to the insulated male terminal on the black cooling lead. Then place the insulated
black female quick connect to the required speed tap.

Check Before Starting
1,

1.

Turn electric power OFF.

2,

From the system design, determine the external static pressure (ESP) for the supply ducts, return ducts
and registers, diffusers, grilles, dampers, heaters
and special filters (if any).

3.

To your system ESP determined in Step 2, add 0.05
inches of Water Column for a wet coil and 0.08 inches
of Water Column for the unit filter.
From the system design, determine the desired cooling airflow in cubic feet per minute (CFM).

4,

5.

Locate the unit's Blower Performance Data table in
the tech data sheet for the unit's voltage. (The tech
data sheet is attached to the inside of the electrical
access panel and is also published in the Technical
Support Manual.) From the table, determine the
speed tap the desired airflow requires.
,

See next section, Speed Taps, to set the blower motor speed terminal block (speed taps) to the cooling
speed determined in the previous steps.

Speed Taps
After determining the required CFM and speed tap data
from the tech data sheet, follow the steps below to change
speeds if necessary.
NOTE: The yellow lead MUST always be connected to the
speed tap block at the common quick connect terminal.
The terminal is identified as COM. Also, this is the only lead
which is 3/16" wide. All other quick connects are 1/4" wide.

Cooling

Only

and Heating

2,

Check that the blower motor speed terminal block is
set to the proper cooling speed. Refer to the unit wiring diagram and the various airflow tables in the
Technical Support Manual.
Check to see that clean, properly sized field supplied
air filters are installed in the return air duct.

3.

Inspect the inside of the unit to be sure that all wires
are in place and all tools, etc. are removed.

4.

Replace all service access panels.

Check the unit's operation as outlined in the following
instructions. If any unusual sparking, odors or noises are
encountered, shut OFF electric power immediately. Recheck for wiring errors or obstructions in or near blower motors.

Reverse Rotation (Scroll Compressors
Only)
Three phase scroll compressors CAN run in reverse if improperly wired. If the compressor makes an unusually loud
noise, or if high and low side pressures are nearly identical,
this indicates reverse rotation. To correct, reverse any two
wires at line voltage connections ONLY. Do NOT rewire
any circuits inside the unit to attempt correction of reverse
rotation.

Circulating

Air Blower

1.

Be sure electric power is OFF.

2.

Set thermostat Heat-Cool selector to OFF.

3.

Set thermostat fan switch to AUTO.

Refer to FIGURE 7 on Page13 and the unit's wiring diagram, which is attached to the inside of the electrical ac-

illl

Single Package Air Conditioners I

_ Installation Instructions
4,

Turn electric power ON. Nothing should start running.

5.

Set thermostat fan switch to ON. The circulating air
blower should come ON.

,

Resset thermostat fan switch to AUTO. The circulating air blower should go OFF. Nothing should be running.

I Single Package Air Conditioners

Installation Instructions
c. Condenser fan motor - ON

Cooling

d. Circulating air blower - ON
1.

Be sure that electric power is OFF

2,

Set thermostat Heat-Cool

3.

4,

Adjust thermostat
ture.

select to COOL.

Turn electric power OFF, check the following:

setting to below room tempera-

Turn electric power ON for approximately one minute, then OFF. During power application check the
following:
a. Contactor - Contacts closing
b. Compressor - ON

FIGURE 7

5.

Blower Motor Speed Taps (3-Speed

a. Contactor contacts opening.
b. Compressor - OFF
c. Condenser fan motor - OFF
d. Circulating blower - OFF

Heating
If an Electric Heat Accessory is used, see its Installation
Manual for proper heater operation.
and 4-Speed Motors)

)TOR

SPEED DATA IN THE
I BE TECHNICAL
SURE TO CHECK
BLOWER
MOTOR I
SUPPORT
MANUAL.

1131

_ Installation Instructions

Single Package Air Conditioners I

8. Operation
Starting Unit After Shutdown

Thermostat

Cooling

With the thermostat fan switch in the ON position, the circulating air blower will run continuously at the speed used for
cooling.

Adjust thermostat setting to desired temperature and set
Heat-Cool selector switch to COOL. The unit will come on
and operate automatically under control of the thermostat.
Close all doors and windows. The unit may run continuously for several hours or longer on the initial run because of
residual heat and moisture in the house. This is normal for
any air conditioning system.
CAUTION
Do NOT operate unit on cooling when the outdoor temperature is below 40°F (4.4°C) unless an optional low
ambient kit is used. This is necessary to prevent possible damage to the compressor.

Fan Switch Operation

With the thermostat fan switch in the AUTO position, the
circulating air blower will only run during each cooling cycle
(or heating cycle if Electric Heat Accessory is installed).

Adjusting

Room Temperatures

If the temperature in individual rooms is not as desired, balance the system by adjusting the dampers in the branch
ducts. Adjust a little at a time and wait a day after each
change to judge the effect. Once the dampers are adjusted
for normal weather conditions, it is best to leave them that
way. Compensate for temporary weather changes by adjusting the thermostat setting.

Heating
If the unit has an Electric Heat Accessory installed, see the
Electric Heat Accessory Installation Instructions for starting procedure.

Turning The Unit Off
1.

2.

Set the thermostat selector switch to OFF and set the
thermostat fan switch to AUTO. To restart in cooling
mode, adjust the thermostat to the desired temperature and set the thermostat Heat-Cool selector
switch to COOL. To restart in heating mode if Electric
Heat Accessory is installed, adjust the thermostat to
the desired temperature and set the thermostat
Heat-Cool selector switch to HEAT.
To shut the unit down completely, turn electric power
OFF.

b2J

FIGURE 8

Typical Branch Duct Dampers

I Single Package Air Conditioners

Installation Instructions

9. Maintenance
Monthly
Checks

Maintenance

and Inspection

be trimmed back so it is no closer than 30 inches (762mm)
to unit.

Condensate

Drain

Air Filters
Check for condensate drainage. Clean as required.

CAUTION
Do NOT operate unit without air filters.
Inspect filters at least monthly and replace or clean as required. Washable filters may be cleaned by soaking in mild
detergent and rinsing with cold water. Replace filters with
the arrows on the side pointing in the direction of air flow.
Dirty filters are the most common cause of inadequate
heating or cooling performance, and of compressor failures.

Refrigeration

Access Ports

This unit is equipped with refrigeration access ports
mounted on the side of the unit. Refer to FIGURE 9 for

Annual Maintenance

and Inspection

Electrical shock hazard.
Turn OFF electric power supply at disconnect
switch or service panel before removing any access or service panel from unit.
Failure to follow this warning can result in property damage, personal injury, and/or death.

identification of ports.
The annual inspection

MUST include

lubrication

and

cleaning as required to ensure efficient operation of the
FIGURE 9

Typical Access Ports

unit. To simplify access, remove all access panels and the
top from the unit if possible.

Condenser

Fan Motor
CAUTION

Do not use 3 in 1 oil, penetrating oil, WD40 or similar
oils to oil motor bearings.
Oil the condenser fan motor after five years of operation
and every five years thereafter.
Use SAE 10W30 motor oil. To oil, remove the hole plugs
from the motor end bells and add several drops (approximately 1/2 teaspoonful) of oil with a squeeze type, flexible
tube oiler. Replace hole plugs after oiling. Do NOT over oil.

Cooling Season Checks (Monthly)
Condenser

Coil

Keep the condenser inlet and outlet area clean and free of
leaves, grass clippings or other debris. Grass should be
kept short in front of the condenser inlet. Shrubbery MUST

Clean the surrounding area and the condenser and evaporator coils. Use caution to avoid damage to coil fins.

_ Installation Instructions

Single Package Air Conditioners

Blower Motor Access

2,

Remove the blower access panel.

3.

Remove four screws securing blower housing to
blower deck. If the unit has a support bracket, remove
the two screws securing the support bracket to the
blower housing.

To access the blower motor follow the following steps. To
remove the blower motor and/or the blower motor housing
assembly, refer to Method 1 and Method 2 below.

Slide entire housing toward you.

4,
1.

Turn electric power OFF.

2.

Remove the blower access panel.

3.

Remove the four screws securing the blower motor
housing. If unit has a support bracket, remove the two
screws securing the bracket.

4,

5.

5.

Refer to NO TAG for a view of blower motor and blower

Remove screws securing corner and front of unit top
(see FIGURE 10).

CAUTION
Do NOT place fingers
,

Slide entire housing toward you. This will allow easier
access to the speed tap block, motor, and wires.
When finished, reassemble in reverse order.

I

7.

8.

between unit top and unit.

Raise corner of unit top at least 2" (50.8mm). Place a
sturdy brace at least 2" (50.8mm) thick between corner and unit top. A 2X4 piece of wood is ideal for this.
Disconnect all wires from blower housing and slide
blower housing out of unit.
When finished, reassemble in reverse order.

compartment.

Method

1 and Method

FIGURE 10

2

Blower Access Showing
Lid Propped with 2X4

Method 1 allows the motor to be removed without removing the entire blower housing assembly. If it is desirable to
remove the entire blower housing assembly to work on the
motor, use Method 2.
With Method 2, the top of the unit is lifted up so that the entire blower housing assembly can be removed. Use Method 2 to replace or repair blower wheel, blower housing, or
any unreachable components behind blower assembly.

Blower Motor Removal

Using Method

1

1.

Turn electric power OFF.

2.

Remove the blower access panel.

3.

Remove the four screws securing the blower housing
to blower deck. If the unit has a support bracket, remove the two screws securing the support bracket to
the blower housing.

4.

Slide entire housing toward you. This will allow easier
access to the speed tap block, motor, and wires.

5.

Reach behind blower housing and locate blower
wheel set nut. Loosen blower wheel set nut.

6.

Disconnect all wires from motor and remove the four
pins securing the blower motor mounting cradle to
blower housing.

Circulating

Air Blower

Visually inspect the blower wheel for accumulations of dirt
or lint. Clean the compartment and the blower wheel. If accumulation is excessive on blower wheel, or does not easily remove,

it will be necessary

to remove the blower

assembly.

CAUTION

7.

Pull motor towards you and remove.

Do NOT use 3 in 1 oil, penetrating oil, WD40 or similar
oils to oil motor bearings.

8.

When finished, reassemble in reverse order.

The blower motor should be oiled after five years of opera-

Blower Motor and Blower Housing
Using Method 2
1.

Turn electric power OFF.

Removal

tion and every five years thereafter. Oil the blower motor by
adding t/2 teaspoonful (lcc) of SAE 10W30 to each motor
bearing.

I Single Package Air Conditioners

10. Rigging
FIGURE

11

Installation

Instructions
_

Rigging

Instructions

RIGGING
INSTRUCTIONS
,&WARNING
PROPERTY

-

DAMAGE,

PERSONAL

INJURY

C

AND/OR

DEATH.

All panels MUST be in place when rigging and lifting.
Hook rigging shackles through holes in base rail, as shown in DetaiI-A.
Use spreader bars, when rigging, to prevent unit damage.
Be sure rigging and shackles are sufficient to handle weight listed below.

SARS

CABINET

Instructions

DETAIL

A

COOLING
CAPACITY
RANGE

IN

MM

IN

MM

IN

MM

LB

KG

3 - 6.3 TONS

73.00

1854

48.00

1219

36.50

927

670

303

LENGTH

CORNER

WIDTH

WEIGHTS

HEIGHT

MAX. WEIGHT

in LBS. (KG)
CORNER WEIGHTS

MODEL NUMBER

OPERATING WEIGHT

A

B

C

D

3 TON

560 (254)

117 (53)

128 (58)

164 (74)

151 (68)

31/2 TON

570 (259)

119 (54)

130 (59)

167 (76)

154 (70)

4 TON

590 (268)

124 (56)

134 (61)

173 (78)

159 (72)

5TON

610 (277)

128 (58)

139 (63)

179 (81)

164 (74)

61/3 TON

710 (322)

149 (68)

162 (73)

208 (94)

191 (87)

1171

INTERNATIONAL COMFORT PRODUCTS
LIMITED WARRANTY CERTIFICATE
For Cooling
SAVE THIS CERTIFICATE.
province

It gives you specific

& Heating Products

legal rights, and you may also have other

rights which

may vary from state to state and

to province.

If your unit needs servicing, contact a qualified dealer or qualified service technician of your choice. When requesting service, please have the model
and serial number from each unit in your heating and/or cooling system readily available. If your dealer needs assistance, the distributor is available to
provide support and we, in turn, support its efforts.
Fill in the installation date and model and serial numbers of the unit in the space provided below and retain this Limited Warranty for your files.

GENERAL TERMS
Subject to the conditions and limitations stated herein, during the term of this Limited Warranty, we will provide a replacement for any functional
component part (as defined below) of your unit found to be defective in materials or workmanship. The term of this Limited Warranty is five years from
installation on Residential Products and one year from installation on Commercial Products. Except as otherwise stated in the "Additional Terms"
section, this Limited Warranty covers only the original purchaser and subsequent transferees, and only while the unit remains at the site of the original
installation (except for mobile home installations), and onty if the unit is installed inside the continental United States, Puerto Rico, Alaska, Hawaii or
Canada. In addition, the Limited Warranty applies only if the unit is installed and operated in accordance with the printed instructions accompanying the
unit, and in compliance with alt applicable installation and building codes and good trade practices. As used in this Limited Warranty, "installation"
means the original installation of the unit.
TH ERE ARE EXCEPTIONS to this Limited Warranty as described on the reverse side of this page. All replacement parts will be warranted for the
unused portion of the warranty coverage period on the unit. The part to be replaced must be returned by the dealer to a distributor that sells products for
International Comfort Products, in exchange for the replacement part. In lieu of providing a replacement part, we may, at our sole option, refund to you
an amount equal to the distributor's component purchase price from us, or provide to you a credit equal to that amount to be applied toward the purchase
of any new unit that we distribute. If a credit for a new unit is given in tieu of a replacement part, the rating plate from the unit being replaced must be
submitted on a warranty claim, and you r dealer must make the unit being replaced available to our distributor for disposition. As a condition to warranty
coverage, the unit must receive yearly maintenance, as described in the owner's manual, by a dealer. Satisfactory proof of yearly service by a dealer
may be required.
"Functional component parts" include only the following: blower motor, unit-mounted sensors & timers, condenser motor, evaporator coil, condenser
coil, condenser fan, capacitor, transformer, single-phase strip heat elements, expansion device, reversing valve, solenoid valve, service valve,
electronic and electro-mechanical control board, ignitor, ignition module, draft inducer assembly, burner pilot, gas valve, limit control, pressure switch,
relays and contactors, blower wheel, interlock switch, crosslighter, pilot shield, gas & oil burners, oil pump assembly, accumulators and factory installed
driers and strainers.
This Limited Warranty DOES NOT COVER any labor, material, refractory chambers, oii nozzles, refrigerant, refrigerant inspection and refrigerant
reclaiming, freight and/or handling charges associated with any repair or replacement and such charges will be your responsibility.
To establish the installation date for any purpose under this Limited Warranty, you must retain the original records that can establish the installation date
ofyour unit. Ifyou donot providesuchdocumentsthe
start dateoftheterm ofthis LimitedWarrantywillbe
based uponthedate ofunit manufacture, ptus
thirty (30) days. In establishing that the required yearly service has occurred, you must furnish proof of yearly service by a qualified service technician.
This Limited Warranty does not cover: (a) failure or damages caused by accident, abuse, negligence, misuse, riot, fire, flood, or Acts of God (b)
damages caused by operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any other damaging chemicals (other
than those found in a normal residential environment) (c) damages caused by an unauthorized alteration or repair of the unit affecting its stability or
performance (d) damages caused by improper matching or application of the unit or the unit's components (e) damages caused by failing to provide
proper maintenance and service to the unit in accordance with this Limited Warranty Certificate and the printed instructions originally provided with the
unit (f) any expenses incurred for erecting, disconnecting, or dismantling the unit (g) parts or supplies used in connection with service or maintenance,
such as refrigerant, refractory chambers, oil nozzles, filters, or belts (h) damage, repairs, inoperation or inefficiency resulting from faulty installation or
application (i) electricity or fuel costs or any increase in electricity or fuel cost whatsoever including additional or unusual use of supplemental electric
heat (j) units which have not had the required yearly maintenance described elsewhere in this limited warranty.
In no event shall we be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit.
We have not made. do not make. and hereby disclaim any implied condition or implied warranty of fitness for a particular use or purpose, and
anv implied condition or implied warrantv of merchantabilitv, to the fu Ilest extent allowed bv law. We make no express or implied warranties
except as stated in this Limited Warrantv certificate.
No one is authorized to change this Limited Warranty or to create for us any other obligation or liability in connection with this unit. Any implied
warranties shall last for the term of the expressed warranty contained herein. Some states and provinces do not allow the exclusion or limitation of
incidental or consequential damages or do not allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions
may not apply to you. The provisions of this Limited Warranty are in addition to and not a modification of or subtraction from any statutory warranties and
other rights and remedies provided by law.

Please refer to reverse side of this page for additional terms.
Model No.
Serial No.

Effective

Date Installed

on units installed

After July 1, 2002,

USA: International Comfort Products Corporation (USA) • 650 Hell-Quaker Avenue * P.O. Box 128 • Lewisburg, Tennessee 37091 • (931-270-4100)
CANADA: International Comfort Products division of UTC Canada Corporation • 6060 Burnside Court, Unit 1, Mississauga, Ontario L5T 2T5
(905-795-8113).
Manufacturers of Airquest, Arcoaire, Clare, Comfortmaker, Dettson, Hell, Keeprite, Lincoln, Tempstar and other quality brand name private label
products.
Part No. 401 06 1010 18 (Orig. 8/9/2002)

ADDITIONAL

TERMS FOR RESIDENTIAL

APPLICATIONS

ONLY

The Additional Terms for the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
Warranty coverage is limited to parts that fail due to defect in materials or workmanship during the specified term.

CENTRAL GAS & OIL FURNACE HEAT EXCHANGERS*
Gas Model Series: C9MPV. HgMPV. TgMPV. CgMPT. H9MPT. T9MPT. C9MPD. HgMPD. TgMPD: Limited Lifetime Warranty on heat exchangers. If
a heat exchanger on one of these furnaces fails due to defect in the part, we will provide a replacement part or, at our option, credit toward the purchase
of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and tasts only for as tong as the originat
purchaser tives in the home where the furnace is initially installed.** It is not transferable to any subsequent owner. Ifthe furnace was not installed in the
home owned by the original purchaser, if the original purchaser setls the home to a subsequent owner, or if proof of originat purchase cannot be
provided, then the limited warranty is only for 20 years from the date of original installation.
Gas Model Series: GDL. GNL. TNE. TDE. NTC7. NDC7. NTP6. NDP6. TDE. NTV6. VNE: A replacement heat exchanger will be provided for any
heat exchanger that fails in one of these furnaces due to defect for 25 years from the originat date of installation.
Gas Model Series: NTC6. GNE. GDE. NDN6. NTG3. NDN3. FBF. NBF. NDF. NTN3. NTN6. NNE. N9MPI. N9MP2. FUH: A replacement heat
exchanger witt be provided for any heat exchanger that faits in one of these furnaces due to defect for 20 years from original date of installation.
Oil Model Series: OLR(105, 160, 182), OCF, OLE OUF, NOLE NOUF, OLB, OHB, ODH, FLO, MBO, LBO, NOMF: Limited Lifetime Warranty on
heat exchangers. Ifa heatexchangerononeofthesefurnacesfailsduetodefectinthepart,
wewitl provide a replacement part or, at our option, credit
toward the purchase of a new furnace manufactured by us. This additional Limited Warranty runs only to the original purchaser, and tasts only for as
long as the original purchaser lives in the home where the furnace is initially installed.** It is not transferable to any subsequent owner. If the furnace
was not installed in the home of the original purchaser, if the original purchaser sells the home to a subsequent owner, or if proof of original purchase
cannot be provided, then the limited warranty is only for 20 years from the date of original installation.
Oil Fired Floor Furnace: NFO: A replacement heat exchanger witl be provided for any heat exchanger that faits due to defect for 10 years from
installation with the following limitation: during the sixth through tenth year, any credit toward your purchase of a component or toward the purchase of
any new unit wilI be in an amount equal to the distributor's purchase price reduced by 20 percent for each year after the fifth year.

ADDITIONAL

TERMS FOR OIL FURNACE APPLICATIONS

ONLY

1) OIL BURNERS - A replacement for 5 years from date of original installation for Oil Burner Parts.
2) OPTIONAL ACCESSORIES AND FUNCTIONAL PARTS: A replacement for 5 years from date of original
oil nozzles not included)

GAS/ELECTRIC
Model series:

PACKAGED

installation.

(Refractory

and

UNITS HEAT EXCHANGERS

PGAD. PGAA. PGMD. PGME. PGF. GPFM. PGC. GPCM:

A replacement for 10 years from original date of installation.

COMPRESSORS:*
1) Premium Model Units: HAC0. HAC2. HAC4. CAC0. CAC2. CAC4. KAC0. TCA0. TCA2. TCA4. HHP0. HHP2. HHP4. CliP0. CliP2. CliP4.
TCH0. TCH2. TCH4. PGME. PYMC. PHAD. PGAD. PA95. PAPC. PAK. APK: To the original purchaser a replacement for 10 years from original date
of installation, only if the unit is installed with factory matched coils, except air conditioner condensing units with a nominal SEER of 10 may be matched
with evaporator coils of the same nominal tonnage regardless of manufacturer and in accordance to factory recommendations. This limited 10-year
warranty is not transferable to any subsequent owner. HOWEVER, if the unit was not installed in the home owned by the original purchaser, if the
purchaser sells the home to a subsequent owner, or if proof of original purchase cannot be provided, then the limited warranty is only for 5 years from the
original date of installation.**
2) All Other Models: Air Conditioners.
Heat PumPs. & Combination
Gas/Electric Units: NAC0. NAC2. NHP0. NHP2. AO. A2. HO. H2. PGF.
PGC, GPFM, GPCM, PAE APFM, PHE HPFM, PGAA, PGMD, PA55, PH55, PAPA, PYPA: A replacement for 5 years from date of original
installation, onty if: (a) air conditioner condensing units with SEER rating in the range of 10 to 11 SEER are matched with evaporator coils of the same
nominal tonnage regardless of manufacturer and in accordance to factory recommendations, or (b) heat pump condensing units are used with factory
matched coils, unless written approval to do otherwise is obtained from manufacturer.

ADDITIONAL

TERMS FOR COMMERCIAL

APPLICATIONS

ONLY

For purposes of this warranty a commercial application is one in which: the product has over 5 tons nominal cooling capacity, or is designed
for operation with 3 phase electrical power, or is installed in a commercial establishment such as a beauty or hair salon, hospital, school,
restaurant, church, hotel etc..
3-Phase Models: PGF, GPFM, GPF, PGAD, PGME, PGB, PGMG, PGMF, PGS, PGE, APE, PAE, PAB, PAMD, PAS, PAl=,APFM, APF, PHB, PHE,
PYMD, HPB, PHS, CAC, ACC, CAE, ACE, CHC, HCC, CHE, HCE:
The additional

Terms of the components

listed below are in addition to and subject to the General Terms on the reverse side of this page.

1) GAS FIRED HEAT EXCHANGERS (ALL MODELS):* A replacement for 10 years from date of originat installation.
2) COMPRESSORS (ALL MODELS):* A replacement for 5 years from date of original installation.
3) OPTIONAL ACCESSORIES AND FUNCTIONAL COMPONENT PARTS (ALL MODELS):*
A replacement for 1 year from date of original installation.
4) COMMERCIAL OIL MODELS: OLR210, OLR350, OTF210, AMT3, AMT4, AMP3: Ten(10) Year Limited Warranty on heat exchangers.
*To receive advantage of your limited warranty, you must provide proof of yearly service by a qualified service technician.
**To receive advantage of your warranty, you must retain the original records that can establish the installation date and proof of purchase of the unit.

MINI SPLITS:
Summary - Mini Splits Warranted for one (1) year on all replacement parts.
Additional terms for Mini Splits:
The additional Terms of the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page.
1) Compressors
installation.

(All Models):

A replacement compressor wili be provided for atI compressors that faii due to defect for 5 years from date of original

2) Optional Accessories and Functional Components Parts (All Models):
A replacement part will be provided for alt parts that fail due to defect for one (1) year from date of original installation.
Failu re to maintain the equipment through annual maintenance by a qualified service technician shall void the warranty. Proof of service wili be required
with ati warranty claims. Proof of purchase and installation date must be submitted with ali claims.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 19
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Apr 20 13:25:57 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu