ICP Package Units(both Units Combined) Manual L0604329
User Manual: ICP ICP Package Units(both units combined) Manual ICP Package Units(both units combined) Owner's Manual, ICP Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 21
| Download | |
| Open PDF In Browser | View PDF |
Installation Instructions
PGX3 Series
PACKAGED
GAS / ELECTRIC
UNITS
TABLEOF CONTENTS
UNITDIMENSIONS ......................................
2-3
ELECTRICALWIRtNG..................................
10
SAFEINSTALLATIONREQUIREMENTS .........................
4
DUCTWORK.........................................
11
LOCATINGTHE UNIT .......................................
5
FILTERS ............................................
11
CLEARANCES ............................................
5
AIRFLOWADJUSTMENT ...............................
12
INSTALLATION............................................
5
START-UPPROCEDURES ..............................
13
GROUNDLEVELINSTALLATION ..............................
5
GAS PRESSURES ....................................
14
HOISTING................................................
6
HEATINGSTART-UPPROCEDURES ......................
14
DOWNFLOWCONVERSION ..................................
6
OPERATION.........................................
16
HEATINGVENTASSEMBLY ..................................
6
MAINTENANCE ......................................
16
CONDENSATEDRAIN.......................................
7
INSPECTIONAND CLEANING............................
17
PRE-EXISTINGCOMMONVENTCHECK .........................
7
COMPONENTLOCATION ...............................
18
GAS SUPPLYAND PIPING ...................................
7
RIGGING ...........................................
19
ORIFICES ...............................................
8
WIRING DIAGRAMS ................................
20 - 21
CQUS
LISTED
InternationalComfortProducts,LLC
Lewisburg,TN. 37091
462 01 1201 00
Printed in U.S.A.
Code: PGX3
1-10-06
"B" CHASSIS UNIT DIMENSIONS
1. Unit Dimensions
Units
COMBINATION
GAS/
ELECTRIC
UNITS
"B" Chassis
DIM=
A
B
C
D
E
F
G
H
I
J
K
L
M
N
P
Q
R
S
in "B"
PGX324
Chassis
Configuration
- 36
(473/8 x 473/8)
INCHES
"0" _
"B"
MILLOMETERS
47-3/8
47-3/8
3-1/8
32-1/2
11-1/8
12
1203
1203
79
826
283
306
14-1/4
363
14-1/4
383
12
_
308
314 I19 28
4
_
_
"4
_
_
_1
102
4-1/4
lO8
12-1/4
311
12-1/8
14-1/4
308
363
12-1/4
318
'w'
"1''/
[ o \
//_
/
_
_..J
/
/
_
_/
;'E'_
j'G_._
_
T
'U'_'" _
_
_
/
_
"H"
'
i_--_
'_
-">,/
/
_
._--'/_
/
2-1/2"
I
A
1/2" (12.7) CONDUIT
\
_/
_i,,
(53975)
__
.-li8
_
(282.575)
'_L"_
/
_._
A
B
C
D
E
F
G
H
K*
_
_'__
(101.6)
_
_
//
_
_
_
/_
//_¢
\
..X._/_--
\
_
ROOF CURB
Unit Base shown separately to
for units in
"B" Chassis
illustrate
(473/8 x 473/8)
DIM.
_
"d"
1--1/2"
,.c,Es
42-3/4
39-3/4
18
18
3-3/4
42-3/4
Units
M.........
1086
1010
457
s
in "B"
PGX324
Chassis
95
1086
_
_x
_
_
//
_
_
_._.
_
_/
/
_
_/._..._
/_
_._
"F'_
* Roof curbs are also available in 8" (203) and 24" (610) heights (K Dimensions),
EJ
•
openings,
_.
/_
_
of duct
Configuration_
- 36
457
bottom
8o:_o:12
"C" CHASSIS UNIT DIMENSIONS
CAL
CONDUIT
('K"
1/2"
GAS
1/2"
POWER
DIM.)
VOLTAGE
(12.7)
CONDUIT
CONNECTION
(12,7)
PIPE
1/2"
COMBINATION
GAS/
ELECTRIC
UNITS
"C" Chassis
(473/8 x 73)
DIM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
P
Q
R
S
T
INCHES
36
47-3/8
73
4-5/8
15
12
18-3/4
18-3/4
12
4
1 &1-1/4
4-1/4
5-1/4
12-1/4
19
15
19
12-1/4
16-7/8
MILLOMETERS
914
1203
1354
117
361
307
476
476
306
102
25&31
108
133
311
483
381
483
318
429
,,p,,
Unit Base shown separately to
illustrate bottom of duct openings,
ROOF
CURB
for
"C" Chassis
(473/8 x 73)
_IM
A
B
C
D
E
F
G
H
I
J
K*
INCHES
67-3/4
64-3/4
23
23
2-1/2
42-3/4
39-3/4
23
12
12
14
Units in "C" Chassis Configuration
PGX342-60
MgLLIM_T_RS
1721
1645
584
584
64
1086
1010
584
305
305
356
* Roof curbs are also available in 8" (203) and 24" (610) heights (K Dimensions),
13
2. SAFE INSTALLATION
REQUIREMENTS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
components. Only trained and qualified personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance
functions of cleaning coils and filters. All other operations
should be performed by trained service personnel. When
working
on
air-conditioning
equipment,
observe
precautions in the literature, tags, and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguisher available for all brazing operations.
FIRE,
EXPLOSION,
ELECTRICAL
SHOCK,
CARBON MONOXIDE POISON HAZARD
AND
Improper installation, adjustment, alteration, service,
maintenance,
or use can cause carbon monoxide
poisoning, fire, or an explosion which could result in
personal injury or unit damage.
Consult a qualified
installer, service agency, or gas supplier for information
or assistance. The qualified installer or agency must use
only factory-authorized
kits or accessories
when
modifying this product.
FIRE,
EXPLOSION,
ELECTRICAL
SHOCK,
CARBON MONOXIDE POISON HAZARD
AND
Failure to follow this warning could result in personal
injury, death and/or property damage.
Before performing service or maintenance operations
on unit, turn off gas supply to unit. Then turn off unit main
power switch and install lockout tag.
Recogniz_ safety information. This is the safety-alert
symbol/.rX. When you see this symbol in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in serious injury or death.
WARNING signifies a hazard which could result in serious
injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
These instructions cover minimum requirements and
conform to existing national standards and safety codes. In
some instances, these instructions exceed certain local
codes and ordinances, especially those that may not have
kept up with changing residential construction practices.
We require these instructions as a minimum for a safe
installation.
141
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON
MONOXIDE POISON HAZARD
Failure to carefully read and follow all instructions in this
manual could result in furnace malfunction, property
damage, personal injury and/or death.
Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes or, in the absence of
local codes, with the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 and the National Electrical
Code NFPA70-2005 or in Canada the National Standard
CAN/CGA B149-1 and CSA C.22.1 - Canadian Electrical
Code Part 1.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test
instruments.
SAFETY CONSIDERATIONS
• Use only with type of gas approved for this unit. Refer to
unit rating plate.
• Install this unit only in a location and position as specified
in section 3 of this manual.
• Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the
detection of leaks to check all connections, as specified in
section 5.
• Always install unit to operate within the unit's intended
temperature-rise range with a duct system, which has an
external static pressure within the allowable range, as
specified in section 9. Refer to unit rating plate for the allowable external static pressures.
• All connecting ductwork to the unit (supply and return)
must be sealed to the unit casing as specified in section 7.
• Do NOT use this furnace as a construction heater.
• Check to see that filters are installed correctly and are the
proper type an size.
NOTE: It is the personal responsibility and obligation of the
customer to contact a qualified installer to ensure that the
installation is adequate and conforms to governing codes
and ordinances.
UNIT SAFETY
Failure to follow this caution may reduce unit reliability.
It is recommended that a qualified service technician
check the heat exchanger integrity every two (2) years,
after the first four (4) years of operation.
INTRODUCTION
The PGX3 unit is a fully self-contained,
combination
Category I gas heating/electric cooling unit designed for
outdoor installation (See pages 2 and 3 for unit
dimensions).
All unit sizes have return and discharge
openings for both horizontal and downflow configurations,
and are factory-shipped with all downflow duct openings
covered.
Units may be installed either on a rooftop, cement slab, or
directly on the ground if local codes permit.
Models with a'l" in the twelfth position ofthe model number
are dedicated Low NOx units designed for California
installations. The emissions ofthese models do not exceed
40 nanograms of nitrogen oxide emissions per joule of heat
output as shipped from the factory, and must be installed in
California Air Quality Management Districts or any other
regions in North America where a Low NOx rule exists.
3. LOCATING
THE UNIT
FiGuRE i
Minimum Clearances
Panels(B
Chassis and
Shown)
Access
ACCESS PANELS
I
See Figure 1 for a general view of unit and location of
access panels.
Blower Compartment
Panel
B Chassis - 2"
C Chassis - 6"
CLEARANCES
The location MUST allow for minimum clearances
and
should not be adjacent to a patio or other area where the
unit's operating sound level might be objectionable. The
combustion air inlet openings MUST not be obstructed (see
Figure 1). In addition, local codes MUST be observed.
NOTE: Units with available filter racks (3-1/2 to 5ton), need
a 26" minimum clearance at side of unit for removal of
filters. See chart below if unit is going to be placed near
combustible construction or materials.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation around
the unit for proper operation in the cooling mode. Whenever
possible, it is desirable to allow additional clearance,
especially around the condenser inlet and discharge
openings.
Do NOT install the unit in a location that will permit
discharged air from the condenser to recirculate to the
condenser inlet.
Internal Filter Access
from Burner Compartment
26" (C Chassis Units)
Side
Burner Compartment
Panel
INSTALLATION
NOTICE
Unit will NOT operate properly unless it is installed
level front to rear and side to side. The slope MUST NOT
be greater than 1/8" per foot (10mm per meter). For side
to side leveling, the drain side MUST always be lower.
Ground Level Installation
Ground level platform requirements:
- The unit MUST be situated to provide safe access for
servicing.
- Platform may be made of either concrete or pressure
treated wood and MUST be level and strong enough to
support unit weight.
UNIT DAMAGE HAZARD
- Position platform separate from building foundation.
Failure to follow this caution may result in shorten life
of unit components.
- Install in well-drained area, with top surface of platform
above grade level.
- Platform must be high enough to allow for proper
condensate
trap installation and drainage. See
FIGURE 4 and associated text for more information
about condensate drainage.
Do NOT operate unit in a corrosive atmosphere
containing chlorine, fluorine, or any other corrosive
chemicals.
Minimum
Clearances
to Combustible
Construction
Furnace Plenum .....................................
Duct Side ...........................................
Condenser Inlet ....................................
Blower Service (Side) ...............................
Control Service Side
2"
2"
30"
30"
(Front Combustion Air Inlet) ..............
Clearance between 3 Ft. Overhang
and Top of Unit .........................
Combustible Base
(Wood or Class A, B or C
roof covering material) .....................
30"
30"
0"
151
Rooftop Installation
Rooftop platform requirements:
I
FIGURE2
1
Heating Vent Assembly
Screws for
"B" Chassis
(473/8 x 473/8)
- The unit MUST be situated to provide safe access for
servicing.
I
Screw for
"C" Chassis
(473/8 x 73)
- The existing roof structure MUST be adequate to
support the weight of the unit or the roof MUST be
reinforced.
Check the weight of the unit in relation to the roof
structure and local building codes or ordinances and
reinforce roof structure if necessary. See the last page
of this manual for unit weights.
- Support for the unit MUST be level and strong enough
to carry unit weight. The support may consist of a
platform or a combination of platform and roof beams or
curb.
- See Hoisting section for hoisting instructions,
HOISTING
NOTE: All access panels MUST be secured in place before
hoisting.
The unit should be hoisted with two lifting slings. Attach the
slings to rigging shackles that have been hooked through
holes in the base rail,
Two spreader bars MUST be placed on top of the unit to
protect the unit from damage from the pressure exerted by
the slings. Make sure that all equipment is adequate to
handle the weight ofthe unit and that the slings will not allow
the unit to shift.
Refer to FIGURE 18 on the back cover of this manual for
illustrated rigging instructions and weight chart,
DOWNFLOW CONVERSION
NOTE: In downflow applications with roof curbs or jack
stands, the center rail under the unit must be removed. The
center rail is attached to the base rail with screws.
2. Install the removed plates on the horizontal return and
supply air openings.
3, Install roof curb on the building. Be sure to follow all
directions included with curb and all applicable building
codes in your installation. See page 2 or 3 for
appropriate roof curb to use.
Heating Vent Assembly
The flue cover is packed with installation screws in the
return air compartment, Refer to FIGURE 3 and assemble
as shown,
FIGURE
3
1
Heating Vent Assembly
Flue Support
(Shipped mounted to unit
Flue Cover
These units are adaptable to downflow use, To convert to
downflow use, follow these steps:
1. Remove the blockoff plates found in the return air
compartment and the supply air compartment.
NOTE: Blockoff plate in the supply air compartment only
contains one screw. If reinstalling plate, back part of plate
MUST fit into mating dimples on flange. To reinstall, slant
plate into dimples, then put plate into position and fasten
with screw.
UNIT DAMAGE
Failure to follow this caution may result in unit
damage.
Do not operate the unit without the vent assembly
installed.
161
Condensate Drain
5. GAS SUPPLY AND PIPING
The condensate drain outlet is a 3/4" (19.1 mm) female PVC
connection located atthe bottom ofthe unit to the right ofthe
filter access panel (see FIGURE 4).
NOTE: Because there are many types of liquified petroleum
(LP) gases, the term LP as used in this manual refers to
propane gas. If you intend to use any type of LP gas, proper
precautions MUST be used in the handling, piping, and use
of such gas. NOTE: In Canada, installations MUST be
performed by licensed LP installers.
The circulating blower creates a negative pressure on the
condensate drain line that can prevent the condensate from
draining properly. To combat this negative pressure, a field
supplied condensate trap that will allow a standing column
of water of at least 2" (50.8mm) MUST be installed. Top of
outlet from trap MUST be at least 1" (25.4mm) below top of
outlet from unit. Install the trap as near to the unit as
possible for proper drainage.
A 3/4" (19.1 mm) drain line MUST be installed if required by
local codes or if location of unit requires it. Run the drain line
to an open drain or other suitable disposal point.
FIGURE 4
Condensate
Drain Information*
b
25-1/2 ("B" Chassis)
32-1/4 ("C" Chassis)
The UL rating plate located on the side panel on the unit
contains the model number, type of gas, gas input rating,
and other important information.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Make certainthe unit isequipped to operate on the type of
gas available. Models designated as natural gas are to be
used with natural gas only. Models designated for use
with liquefied petroleum (LP) gas are shipped with
orifices sized for commercially pure propane gas. They
MUST not be used with butane or a mixture of butane and
propane unless properly sized orifices are installed by a
licensed LP installer.
3/4" (19,1mm)
Threaded Female
GAS PIPING
PVC Fitting
1 "
(25.4mm)
/
2" (5O.8mm)
The gas supply line MUST be of adequate size to handle the
Btu/hr requirements and length of the run for the unit being
installed. Determine the minimum pipe size for natural gas
from the table in FIGURE 5 or FIGURE 6. Base the length
of the run from the gas meter or source to the unit.
Gas Pipe Size
Btu ratings of all other gas appliances MUST be considered
for sizing of main gas line. Check gas line to installation for
compliance with local codes or, in the absence of local
codes, with the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 or in Canada the National
Standard CAN/CGA B149-1 or current editions.
80-30-27
* Condensate
4. PRE-EXISTING
trap MUST be installed,
COMMON
VENT CHECK
If the installation of this new combination gas heat/electric
cool unit involves removing an existing gas-fired furnace
from a common vent system with other gas-fired
appliances (gas-fired hot water heater, etc.), the existing
vent system must be checked and inspected by a qualified
technician. The qualified technician can determine if the
existing vent system will properly vent the flue products of
the remaining gas-fired appliances. In many cases, the
existing vent system may be oversized for the remaining
appliances.
FIGURE 5
Pipe Length
(includes
Fittings)
Gas Pipe Size, Length and Btu/hr Capacity
for Schedule 40 Iron Pipe/English/
NATURAL GAS
Btu/hr
(in thousands)
3/4"
1"
11/4"
20'
190
350
730
11/2"
1,100
2,100
2"
40'
130
245
500
760
1,450
60'
105
195
400
610
1,150
LP GAS
Pipe Length
(includes
Fittings)
Btu/hr (in thousands)
3/4"
1"
11/4"
11/2"
20'
189
1/2"
393
732
1,496
2,299
40'
129
267
504
1,039
1,559
60'
103
217
409
834
1,275
LZJ
FIGURE 6
Gas Pipe Size, Length and Btu/hr Capacity
for Schedule 40 Iron Pipe (English)
UNIT OPERATION AND COMPONENT
NATURAL GAS
Pipe Length
(includes
Fittings)
Failure to follow this caution may result in misaligned
burners, flame rollout and or unit damage.
Overtightening assembly may cause damage to the gas
valve and/or wirin_land may misali_lnthe burners.
kW**
3/4"
1"
6.1m
56
103
12.2m
38
18.3m
31
11/4 "
11/2"
2"
214
322
615
72
147
223
425
57
117
179
337
6. Use a wrench on gas valve when making connections
to prevent gas valve from turning. Do NOT use a pipe
wrench on the gas valve body.
LP GAS
Pipe Length
(includes
Fittings)
7. Provide a t/8 inch (3mm) National Pipe Thread (NPT)
plug for test gauge connection immediately upstream of
the gas supply connection to the furnace if none is
supplied with the gas valve of unit.
kW**
1/2"
3/4"
11/4 "
11/2 "
6.1m
55
115
1"
215
438
674
12.2m
38
78
148
305
457
18.3m
30
64
120
244
374
**kW (Ki!owatts) is the metric equivalent
DAMAGE HAZARD
8. Install a manual shutoff valve and tighten all joints
securely.
of Btu/hr.
LEAK CHECK/PRESSURE
PIPING
PIPING AT UNIT
TESTING OF GAS SUPPLY
Connections
NOTE: The rules listed apply to natural and LP gas pipe
installations.
1. If installation is for LP gas, have LP gas installer use
TWO-STAGE
REGULATION
and
make
all
connections from storage tank to unit.
2. Use black iron or steel pipe and fittings or other pipe
approved by local code.
3. If copper tubing is used, it MUST comply with limitation
set in Fuel Gas Code.
NOTE: If a flexible gas connector is used, it MUST be
acceptable to local authority. Connector MUST NOT be
used inside the furnace or be secured or supported by the
furnace or ductwork. Do not use a connector which has
previously serviced another gas appliance. Always use a
new listed connector.
FIRE OR EXPLOSION
HAZARD
HAZARD
Failure to follow the safety warnings could result in personal injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for
the detection of leaks to check all connections. A fire or
explosion may result causing property damage, personal injury or loss of life.
The unit and its equipment shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess
of .5 psi (3.5kPa).
The unit must be isolated from the gas supply piping system
by closing the equipment shut off valve during any pressure
testing of the gas supply piping system at test pressures
equal to or less than .5 psi (3.5 kPa).
ORIFICES
Failure to do so could result in personal injury, death
and/or property damage.
Gas connector MUST be properly installed and can NOT
be used inside the furnace.
4. Use pipe joint compound on external (male) threads
ONLY. Joint compound MUST be resistant to any
chemical action of LP gases.
Do NOT put pipe
compound on last 2 threads of pipe.
5. Use ground joint unions and install a drip leg no less
than 3 inches (76 mm) long to trap dirt and moisture
before it can enter gas valve.
TABLE 1 & 2: Equivalent
FIRE OR EXPLOSION
Orifice Sizes
Orifice sizes MUST be matched to the heating value of the
gas (see TABLE 1 & 2). Check with your gas supplier and
the National Fuel Gas Code ANSI Z223.1.
NOTE: An LP Conversion Kit MUST be used for conversion
to LP gas.
NOTE: For elevations above 2000 feet (610 meters), the
Btu input rating MUST be reduced by 4% for each 1000 feet
(305 meters) above sea level, unless the gas supplier's
Btu!ft 3 content has already been adjusted for altitude.
Check Table 1 & 2 for the proper orifice sizes.
Orifice Sizes at High Altitudes
Table1
NATURALGASORIFICESIZING
MEANELEVATIONFEETABOVESEALEVEL
0 to 2000
NominalHeatingSize
All Sizes
Orifice
Drill #
44
Kit
Number
1173863
2001to
4000
4001to
5000
5001 to
6000
6001to
7000
7001to
8000
8001to
9000
9001 to
10000
Orifice
Drill #
45
Orifice
Drill #
46
Orifice
Drill #
47
Orifice
Drill #
47
Orifice
Drill #
48
Orifice
Drill #
48
Orifice
Drill #
49
NOTE:
The orifice
sizes
above
sea level.
If converting
330732-401,
Btu/Cu.Ft.,
in the chart
from
above derate
the input rate at 4% per 1000 feet above
LP gas to Natural
Gas
at altitudes
exceeding
sea level for altitudes
2000
feet
above
exceeding
sea level,
use
2000 feet
part number
plus the required orifice size # shown in Table 1. Natural Gas data is based on 0.60 specific gravity, a heating value of 1030
and 3.5" W.C. manifold
pressure.
For fuels with different
specific
gravity, consult the National
Fuel Gas Code NFPA
54-2005/ANSI
Z223.1-2005
or National
Standard
of Canada,
Table2
Natural
Gas and Propane
Installation
Code
CSA B149.1-05.
LPGASORIFICESIZING
MEANELEVATIONFEETABOVESEA LEVEL
0 to2000
Nominal Heating
Size
Orifice
Drill #
All Sizes
55
NOTE:
The orifice
sizes
2001 to4000
Kit
Number
Orifice
Drill #
1173857
in the chart
Kit
Number
55
40011o7000
Orifice
Drill #
1173857
above derate
56
7001to9000
Kit
Number
Orifice
Drill #
1173859
56
the input rate at 4% per 1000 feet above
90011o10,000
Kit
Number
Orifice
Drill #
1173859
57
sea level for altitudes
exceeding
Kit
Number
1173861
2000 feet
above sea level. LP Gas data is based on 1.52 specific gravity, a heating value of 2500 Btu/Cu. Ft., and 10.0" W.C. manifold pressure. For
fuels with different specific gravity, consult the National Fuel Gas Code NFPA 54-2005/ANSI
Z223.1-2005
or National Standard
of
Canada,
Natural
Changing
Gas and Propane
Installation
Code
CSA B149.1-05.
Orifices
ELECTRICAL
HAZARD
FIGURE 7
SHOCK,
FIRE AND/OR
Removing
NOx Baffles
EXPLOSION
or
Failure to follow this warning could result in personal
injury, death and/or property damage.
Shut off electric power at unit disconnect or service
panel and shut off gas at manual shut off valve before
beginning the following procedure.
Changing
technician.
orifices
requires
a
qualified
service
1. Shut OFF gas at manual shut off valve.
2, Shut OFF electric power at unit disconnect or service
panel. If unit is still running, allow 3 minutes after gas
shut off before turning off power.
3, Disconnect the wires from the gas valve, sparker, and
flame sensor.
4. Remove the four screws holding the manifold to the
manifold brackets.
5. Carefully remove the manifold with the gas valve
attached.
25-22-46a
7, Remove the orifices from the manifold
end or socket wrench.
with
a 7/t6"
box
8, Check to be sure that the size of each orifice is correct
for the Btu input desired,
FIGURE8
Manifold/Orifice Measurement
Measure 13/16 " from face of orifice
back edge of manifold pipe.
6, If unit has v-shaped NOx baffles installed in the firing
tubes, they must be removed when coverting to LR
Some baffles may be attached by screws, Replace
screws after removing NOx baffles (figure 7).
CARBON MONOXIDE HAZARD.
Failure to follow this warning could result in personal injury death and/or property damage.
Install the correct orifices. Gauge the size of the orifices
with a new twist drill bit of the correct size.
NOx baffles for use with Natural Gas units ONLY. If
LP Gas is required, NOx inserts must be removed.
Make sure that the orifices go in straight so that they
form a right angle (90 °) to the manifold pipe.
Tighten the orifices so that there is a 13/t6"
distance
between the faces of the orifices to the back of the
manifold pipe.
Measure the distance with a set of calipers, If you do not
191
have a calipers, you can use an adjustable wrench and
measure between the face of the jaws.
10. Reassemble in reverse order.
6. ELECTRICAL
ELECTRICAL
WIRING
SHOCK
HAZARD.
Failure to follow this warning could result in personal
injury, death, and/or property damage,
The unit cabinet must have an uninterrupted,
unbroken electrical ground to minimize the possibility
of serious injury if an electrical fault should occur.
This ground may consist of an electrical
wire
connected to the unit ground lug in the control
compartment,
or conduit approved for electrical
ground when installed in accordance with National
Electric Code (NEC) NFPA 70, National Fuel Gas Code
NFPA 54-2005/ANSI Z223.1-2005 and local electrical
codes. In Canada, follow Canadian Electrical Code
CSA (Canadian Standards Association) C22.1 and
local electrical codes.
REDUCED EQUIPMENT
LIFE HAZARD
Failure to follow these cautions could result in damage
to the unit being installed.
1) Make all electrical connections in accordance with
National Electric code (NEC) NFPa 70, National Fuel Gas
Code NFPA 54-2005/ANSI
Z223.1-2005
and local
electrical codes governing such wiring. In Canada, all
electrical connections must be in accordance with CSA
standard C22.1, Canadian Electrical Code Part 1, and
applicable local codes. Refer to unit wiring diagram.
2) Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3) Be sure that high-voltage
power to unit is within
operating voltage range indicated on unit rating plate.
4) Do not damage internal components when drilling
through any panel to mount electrical
hardware,
conduit, etc.
Consult local power company for
correction of improper voltage and/or phase imbalance.
the electrical service panel or a properly driven and
electrically grounded ground rod. See warning above.
Line Voltage Wiring
Connections for line voltage are made in the unit control box
area. Refer to wiring diagram located on the Burner Access
panel. For access, remove the burner access panel.
1. Run the high voltage (L1, L2) and ground leads into the
control box.
2. Connect ground lead to chassis ground connection.
3. Connect L1 to pressure
compressor contactor.
lug connection
11 of the
4. Connect L2 to pressure lug connection
compressor contactor.
23 of the
Thermostat / Low Voltage Wiring
Location of the thermostat has an important effect on home
comfort. FOLLOW THE THERMOSTAT INSTRUCTION
MANUAL FOR CORRECT LOCATION, MOUNTING, AND
WIRING.
A two-stage thermostat is required for proper operation.
Thermostat should have the following terminals:
"R",
"W/W1 ", "Y1", "Y2", and "G'. Some electronicthermostats
use low voltage from the unit for power for temperature
display and programming. These electronic thermostats
will have a "C" terminal. The outdoor unit has color-coded
wires for easy connection. Using wire nuts, follow figure 10
for proper connections:
FIGURE 9
Connections
,,1_ Red
White
White
,,1_
Yellow
ed
Pink
Y_
_
Yellow
Pink
miD" Green
Typical
Mechanical
Thermostat
Subbase
THERMOSTAT
For access, remove the burner access panel. See Figure 1
for access panel location. Wiring MUST be protected from
possible mechanical damage.
Thermostat
Typical
Electronic
Thermostat
Subbase
HEAT ANTICIPATOR
The unit must have separate electrical service with a
field-supplied, waterproof, disconnect switch mounted at,
orwithin sight from, the unit. Refer tothe unit rating plate for
maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
Some thermostats have an adjustable heat anticipator. The
heat anticipator prevents temperature overshoot in heating
mode. If the heat doesn't turn off until the set point
temperature on the thermostat is exceeded, then the
anticipator setting is too low. If the heat turns off before the
thermostat reaches the set point temperature on the
thermostat, then the anticipator setting is too high. Follow
the thermostat instruction manual for proper adjustment of
the heat anticipator.
Ground Connections
Final Electrical Check
Disconnect Switch
Do NOT complete line voltage connections until unit is
permanently grounded. All line voltage connections and the
ground connection MUST be made with copper wire.
A ground lug is installed in the control box area for the
ground connection. Use a copper conductor of the
appropriate size from the unit to a grounded connection in
1. Make a final wiring check to be sure system is correctly
wired. Inspect field installed wiring and the routing to
ensure that rubbing or chafing due to vibration will not
occur.
NOTE: Wiring MUST be installed so it is protected from
possible mechanical damage.
7. DUCTWORK
Ductwork
permitted. If flexible connectors are used, they should be
protected from potential mechanical damage such as
punctures and tears.
Sizing
The maximum recommended velocity in trunk ducts is 1000
feet per minute. The maximum recommended velocity in
branch ducts is 800 feet per minute.
Ductwork sizing affects the discharge temperature, airflow
velocity, and efficiency of the system. Be sure to properly
size ductwork to the capacity of the unit and to the airflow
requirements of the conditioned space. Failure to properly
size ductwork can result in inadequate airflow and poor
efficiency. Undersized ductwork may result in tripped limit
controls and premature failure of compressors, motors and
other components.
Ductwork
Insulation
Ductwork installed outdoors must have a minimum 2" thick
fiberglass "wrap" insulation and a weatherproof vapor
barrier installed around it. The insulation and vapor barrier
must be protected against potential damage. Caulking,
flashing, and other means of providing a permanent
weather seal must be used.
Ductwork
NOTE: When connecting the supply and return plenums to
the unit, make sure that the plenums are sealed against the
side casing of the unit and do not interfere with removal of
the top of the unit.
FILTERS
All return air MUST pass through a filter before entering the
unit. An electronic air cleaner, optional filter racks, or other
accessible filter arrangement must be installed in the return
air ductwork. Minimum recommended filter sizes are listed
in FIGU RE 10 and are based on maximum face velocities of
300 ft/min for disposable filters and 600 ft/min for washable
(high velocity) filters. See figure 10 for filter sizes.
REDUCED
EQUIPMENT
LIFE
HAZARD
Failure to follow this caution may result in improper
unit operation,
Connections
The use of flexible, non-combustible connectors between
main trunk ducts and supply and return air plenums is
FIGURE 10
Do not operate the unit without
a filter,
Filter Sizes
Disposable
Filters
Nominal Size
Minimum Area
Washable
Filters"
Nominal Size
Minimum Area
(qty x w x d)
(sq. inches)
(qty x w x d)
(sq. inches)
PGX324040K ....
1 x 20" x 20"
384
1 x 10" x 20"
192
PGX324060K ....
1 x 20" x 24"
428
1 x 12" x 20"
214
PGX324080K ....
2 x 15" x 20"
576
1 x 15" x 20"
288
PGX330040K ....
1 x 20" x 24"
480
1 x 12" x 20"
240
PGX330060K ....
1 x 20" x 24"
480
1 x 12" x 20"
240
PGX330080K ....
PGX336060K ....
2 x 15" x 20"
2 x 15" x 20"
576
576
1 x 15" x 20"
1 x 15" x 20"
288
288
PGX336080K ....
2 x 15" x 20"
576
1 x 15" x 20"
288
PGX336100K ....
2 x 18"x20"
720
1 x 18" x20"
36O
PGX342080K ....
2 x 18"x20"
672
1 x 18" x20"
336
PGX342100K ....
2 x 18"x20"
720
1 x 18" x20"
36O
PGX348080K ....
2 x20" x20"
768
1 x 20" x 20"
384
PGX348120K ....
2 x 20" x 24"
854
1 x 20" x 24"
427
PGX348140K ....
2 x 24" x 24"
1008
1 x 24" x 24"
5O4
PGX360080K ....
PGX360120K ....
2 x 20" x 24"
2 x 20" x 24"
960
960
1 x 20" x 24"
1 x 20" x 24"
48O
48O
PGX360140K ....
2 x 24" x 24"
1008
1 x 24" x 24"
504
1 Washable filter size based on an allowable face velocity of 600 ft/min.
filter manufacturer's
specifications
Refer to
for allowable face velocity and required filter area.
L//J
8. AIRFLOW
ADJUSTMENT
PGX3 SERIES HEATING CHART
External Static Pressure (in H20)
.1"
Cooling
Model
PGX324040K....
PGX32406OK
....
PGX32408OK
....
PGX33O04OK
....
PGX33O06OK
....
PGX33OOSOK
....
Tuns
2
2
2
25
25
25
Hea6n0 Input Heating Hise
(8tuih0
40000
60000
80000
40000
60000
80000
Range(_F)
80000
35 65
PGF342089K....
PGX3421OOK
....
PGX34808OK
....
PGX34812OK
....
PGX34814OK
....
PGX36O08OK
....
PGX36012OK
....
3
35
35
4
4
4
5
5
100000
80000
100000
80000
120000
140000
80000
120000
.T'
8"
Heating
Heating
Rise (_F) CFM
Rise (°F)
OFM
Rise(_F)
Heating
OFM
Rise (°F)
OFM
Rise(_F)
CFM
Rise (°F)
CFM
5
1251
NA
/218
NA
1194
NA
1170
NA
1139
NA
1100
NA
1063
NA
988
NA
4
95/
NA
914
NA
883
NA
858
35
811
37
775
38
733
40
697
43
3
869
NA
842
35
809
37
768
39
736
40
684
43
650
46
599
49
2
/
71I
66/
42
45
655
4(8
45
62
623
334
48
NA
564
262
53
NA
529
219
56
NA
48I
/96
62
NA
43/
NA
NA
NA
392
NA
NA
NA
5
/251
36
/218
36
1/94
37
/170
38
1139
39
/I00
40
1063
42
988
45
4
3
951
869
47
51
9/4
842
49
58
883
809
50
55
858
768
52
58
81/
736
55
69
775
684
57
65
733
650
6/
NA
697
599
64
NA
2
711
63
655
NA
623
NA
564
NA
529
NA
48I
NA
43I
NA
892
NA
/
66/
NA
4(8
NA
334
NA
262
NA
2/9
NA
/96
NA
NA
NA
NA
NA
5
/251
47
/218
49
1/94
50
1170
5I
1/39
52
/I00
54
1083
56
988
60
4
95I
62
914
65
883
NA
858
NA
811
NA
775
NA
733
NA
697
NA
3
869
NA
842
NA
809
NA
768
NA
736
NA
684
NA
850
NA
599
NA
2
/
71I
66/
NA
NA
655
478
NA
NA
623
334
NA
NA
564
262
NA
NA
529
219
NA
NA
48I
/98
NA
NA
43/
NA
NA
NA
392
NA
NA
NA
5
/255
NA
/227
NA
/20I
NA
1164
NA
1138
NA
11/2
NA
1077
NA
/027
NA
4
1106
NA
/080
NA
1048
NA
1017
NA
992
NA
954
NA
924
NA
881
NA
3
958
NA
923
NA
894
NA
857
35
828
36
788
38
750
40
712
42
2
1
789
/54
38
39
747
/08
40
42
714
6/1
4/
44
668
618
44
48
630
584
47
51
582
524
5I
5(
542
494
55
60
495
443
60
NA
5
1255
35
1227
36
120I
37
1164
38
1138
39
/I12
40
1077
4/
/027
43
4
1106
40
1080
4I
1048
42
1017
44
992
45
954
47
924
48
88I
50
3
958
46
923
48
894
50
857
52
828
54
786
57
750
59
712
62
2
789
56
747
59
714
62
668
NA
630
NA
582
NA
542
NA
495
NA
1
/54
59
/08
63
6/I
NA
6/8
NA
584
NA
524
NA
494
NA
443
NA
5
1255
47
/227
48
120I
49
I164
5I
1138
52
/I/2
53
1077
55
/027
58
4
1106
54
/080
55
1048
57
I017
58
992
60
954
62
924
64
88I
NA
3
958
62
923
64
894
NA
857
NA
828
NA
788
NA
750
NA
712
NA
2
1
789
754
NA
NA
747
708
NA
NA
714
671
NA
NA
668
818
NA
NA
630
584
NA
NA
582
524
NA
NA
542
494
NA
NA
495
443
NA
NA
4
1630
NA
1588
NA
/528
NA
1477
NA
1415
NA
1354
NA
1287
35
/216
37
3
/276
35
/242
38
1209
37
/179
38
1150
39
/I/7
40
1086
4/
/045
43
2
1
/026
876
43
5/
994
84I
45
53
949
794
47
56
913
756
49
59
87/
894
5/
64
84I
65I
53
NA
793
598
56
NA
735
543
60
NA
4
3
1630
/276
36
46
/588
/242
37
48
1526
1209
39
49
I477
1179
40
50
14/5
1/50
42
52
/354
/I/7
44
53
1287
1086
46
55
/216
/045
49
57
2
1026
58
994
60
949
62
913
85
87I
NA
84I
NA
793
NA
735
NA
/
8/6
NA
84I
NA
/94
NA
(56
NA
694
NA
65I
NA
598
NA
543
NA
4
/630
45
/588
47
1528
49
1477
50
14/5
52
/354
55
1287
58
/216
6I
3
1276
58
1242
80
1209
6/
1179
83
1150
64
/I17
NA
1086
NA
/045
NA
2
/
1026
8/6
NA
NA
994
84I
NA
NA
949
/94
NA
NA
913
(56
NA
NA
871
694
NA
NA
84I
65I
NA
NA
793
598
NA
NA
735
543
NA
NA
5
/589
38
/537
39
1500
40
/463
4I
1423
42
/389
43
1353
44
/317
45
4
/481
40
/448
4I
1412
42
/374
43
1336
44
/298
48
1283
47
/226
48
3
1302
46
/269
47
1219
49
I179
50
1138
52
/I03
54
1060
56
/015
58
2
/
1170
/028
51
58
/I29
969
52
6I
1088
924
54
64
I050
881
58
NA
1007
838
59
NA
963
789
82
NA
912
73/
65
NA
888
680
NA
NA
5
4
/589
1481
47
50
/537
1448
48
5I
1500
1412
49
52
1463
1374
5I
54
1423
1336
52
55
/389
/298
53
57
1353
1283
55
59
/317
/226
58
60
3
2
1
1302
//70
1028
57
63
NA
1260
/I29
969
59
NA
NA
1219
/088
924
6/
NA
NA
1179
1050
881
83
NA
NA
1138
1007
836
65
NA
NA
/I03
963
/89
NA
NA
NA
1060
912
/31
NA
NA
NA
/015
886
689
NA
NA
NA
5
2103
NA
205/
NA
200I
NA
1942
NA
1878
NA
1809
NA
1723
NA
/632
36
4
183I
NA
/797
NA
1783
NA
1732
NA
1696
35
166/
38
1621
37
/559
38
3
/680
35
/850
36
1614
37
1578
38
1544
38
/507
39
1470
40
/427
42
2
1
/304
//f3
45
51
/256
112/
47
53
1218
1085
49
55
1167
/g2(
5I
58
1/26
983
53
69
/077
92f
55
64
1026
88I
58
NA
979
82I
6I
NA
5
2103
42
2051
43
200I
44
1942
48
1878
47
/809
49
1723
52
/632
54
4
/83I
49
/797
49
1783
50
/732
5I
1696
52
/66/
54
1621
55
/559
57
3
2
/680
1304
53
NA
/850
/256
54
NA
1614
1218
55
NA
/578
1167
58
NA
1544
1126
58
NA
/507
1077
59
NA
1470
1026
60
NA
/427
979
62
NA
1
1/73
NA
1127
NA
1085
NA
1027
NA
983
NA
927
NA
881
NA
821
NA
5
4
2103
/83I
49
57
205/
/797
5I
58
200I
1783
52
59
I942
1732
53
80
1878
1696
55
61
/809
/66/
57
62
1723
1621
60
64
/632
/559
64
NA
3
/680
62
/850
63
1614
64
1578
NA
1544
NA
/507
NA
1470
NA
/427
NA
2
/
1304
///3
NA
NA
1256
/I2/
NA
NA
/218
/085
NA
NA
1167
I02(
NA
NA
1126
983
NA
NA
1077
92(
NA
NA
1026
881
NA
NA
979
821
NA
NA
5
2/88
NA
2140
NA
2098
NA
2039
NA
1974
NA
1905
NA
1827
NA
/745
NA
4
2091
NA
2056
NA
2023
NA
1987
NA
1935
NA
1878
NA
1811
NA
/729
NA
3
1839
NA
/807
NA
1772
NA
1735
NA
1702
35
1667
38
1629
36
/590
37
2
/
1393
/300
43
46
/356
/263
44
4(
1313
1214
45
49
I280
/I69
48
5I
1226
1/1/
48
53
/I84
10/3
50
55
1130
1026
52
56
/086
9f5
55
6I
5
2188
41
2140
42
2098
42
2039
44
1974
45
/905
47
1827
49
/745
5I
4
2091
43
2056
43
2023
44
1987
45
1935
46
/878
47
1811
49
/729
5I
3
1839
48
1807
49
1772
50
1735
5I
1702
52
/667
53
1629
55
/590
58
2
/
1393
/300
64
NA
1356
/263
NA
NA
/313
/214
NA
NA
1280
1169
NA
NA
1226
1/I7
NA
NA
1184
1073
NA
NA
1/30
1026
NA
NA
/086
975
NA
NA
35 65
3
.6"
Heating
Rise(_F)
35 65
PGX33608OK
....
.5"
Heatln0
CFM
35 65
35 65
.4"
Heating
Rise (°F)
35 65
60000
Heatrng
CFM
35 65
3
Heating
.3"
Tap
35 65
PGX33606OK
....
PGX33610OK
....
Speed
2"
35 65
35 65
35 65
35 65
35 65
35 65
35 65
35 65
NA = Not Allowed for Heating Speed.
CIRCULATING AIR BLOWER SPEEDS
FIGURE 11
Factory-Shipped
Blower Tap Connections
Factory-Shipped
BlowerTap Connections
Coofing
Heatinglnput
Tons
(Btu/hr)
Range(°F)
(Red)
High Stage Coofing
Speed Tap (Black)
PGX32404OK....
2
40000
35-65
2
3
PGX32406OK....
PGX32408OK....
2
2
60000
80000
35-65
35-65
5
5
3
3
PGX330040K....
2.5
40000
35 - 65
2
4
PGX33006OK....
PGX33008OK....
2.5
2.5
60000
80000
35 - 65
35 - 65
5
5
4
4
PGX33606OK....
PGX336080K....
3
3
60000
80000
35-65
35-65
2
4
3
3
PGX336100K....
PGX342080K....
3
3.5
100000
80000
35-65
35-65
4
5
3
4
PGX342100K....
PGX348080K....
3.5
4
100000
80000
35-65
35-65
5
4
4
3
PGX34812OK....
PGX34814OK....
4
4
120000
140000
35-65
35-65
4
4
3
3
PGX360080K....
5
80000
35-65
3
4
PGX36012OK....
H_X3bU_4UK....
5
b
120000
]4UUUU
35-65
3b-_b
3
3
4
4
Model
ELECTRICAL
SHOCK
Heating Rise Heating SpeedTap
Low Stage Cooling
SpeedTap(Violet)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
Z
HAZARD.
Failure to follow this warning could result in personal injury, death and/or property damage.
Turn off electric power supply at disconnect switch or service panel before removing access or service panels from unit.
Verify that the proper blower speeds for heating and cooling
are selected on the blower motor by removing the blower
access panel and inspecting the blower motor. The motor
has up to 5 speeds numbered "1", "2", "3", "4", and "5". The
wires for the speed selection are as follows:
Red
=1_
Black _
Violet _
Heating
High Stage Cooling
Low Stage Cooling
Using the same speed for Heating and Cooling.
If the same speed is required for heating and high stage
cooling the following procedure must be used:
1. Set Red wire on proper speed selection on blower
motor.
2. Remove Black wire from "HI" on Blower Interface
Board. Tape end of Black lead using electrical tape.
3. Adjust thermostat setting to below room temperature.
4. Turn power ON, for approximately one minute, then
OFF. During power application check the following:
a. Contactor - Contacts Closing
b. Compressor - ON
c. Condenser fan motor - ON
d. Circulating Air Blower - ON 0 second delay
5. Turn power OFF, check the following:
a.
b.
c.
d.
Contactor contacts opening.
Compressor - OFF
Condenser fan motor - OFF
Circulating blower - OFFafter
all models.
9. START-UP
90 second delay on
PROCEDURES
3, Jumper the Red wire to both the "Heat" terminal and
"HI" terminal on the Blower Interface Board,
If the same speed is required for heating and low stage
cooling, the following procedure must be used:
1. Set Red wire on proper speed selection on blower
motor.
2. Remove Violet wire from "LO" on Blower Interface
Board. Tape end of Violet lead using electrical tape.
3. Jumper the Red wire to both the "Heat" terminal and the
"LO" terminal on the Blower Interface Board.
CONTINUOUS
FAN OPERATION
Continuous fan speed operates at the low stage cooling
speed for all models.
COOLING
1. Turn electric power OFF
2. Set thermostat Heat-Cool
FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do NOT attempt to light
flame of anv kind.
the burner with a match or
CHECK BEFORE STARTING
1. Check that the blower motor speed terminal block is
running the correct heating and cooling speeds.
2. Check to see that clean, properly sized air filters are
installed.
3, Replace
all service
access
panels,
select to COOL.
1131
NOTE: Adjustment screw cover MUST be placed on gas
valve before reading manifold pressure and operating
furnace.
FIREOR EXPLOSIONHAZARD.
Failureto follow this warning could resultin personalinjury
and/ordeath.
FIREAND/OREXPLOSIONHAZARD
TurnOFFgasat shutoffbeforeconnectingU-tubemanometer.
Failureto follow this warning couldresultin personalinjury,
deathand/or propertydamage.
FIGURE i2
[
RegulatorAdjustment
UnderCa
Honeywell
Gas Valve
DoNOTadjustmanifold
pressure
morethan+0.3incheswater
columntoobtainratedinput.
HONEYWELL
Pressure
Tap
1/8NPT
©o
Outlet
OUTLET
Inlet
Pressure
Tap 1/8NPT
25-24-98a
3. Set pressure to value shown in FIGURE 14, +_0.07kPa
(0.3 inches) water column. Pressure is also listed on
furnace rating plate. In NO case should final manifold
pressure vary more than _+0.07kPa (0.3 inches) water
column.
Check the unit's operation as outlined in the following
instructions. If any unusual sparking, odors or unusual
noises are encountered,
shut off electric power
immediately. Recheck for wiring errors, or obstructions in or
near blower motors.
1. Set thermostat Heat-Cool selector to OFF.
2. Set thermostat fan switch to AUTO.
GASPRESSURES
3. Turn electric power ON. Nothing should start running.
1. Do NOT allow gas supply pressure to fall below the
listed minimums. Doing so will decrease input to
furnace. Refer to FIGURE 13 for gas supply pressures.
2. Gas input MUST NOT exceed rated input shown on
rating plate.
3. Do NOT allow pressures to exceed the maximum limits
as listed in FIGURE 13.
Gas Pressures
Natural Gas
LP Gas
Minimum
Inlet
4.5"W.C. (1120 Pa)
11" W.C. (2740 Pa)
Recommended
Inlet
7" W.C. (1740 Pa)
11" W.C. (2740 Pa)
Maximum
Inlet
13" W.C. (3230 Pa)
13" W.C. (3230 Pa)
Manifold
Pressure
3.5" W.C. (870 Pa)
10" W.C. (2490 Pa)
Manifold Pressure Adjustment
Manifold pressures are listed in Figure 14. Check manifold
pressure using the following procedure.
1. With gas OFE Connect U-Tube manometer to tapped
opening on gas valve. Use manometer with a 0 to 12
inches water column range.
FIGURE
14
Gas Type
Manifold Pressure Settings
Manifold Pressure
Natural
3.5 Inches Water Column
(870 Pa)
Propane
10 Inches Water Column (2490 Pa)
2. Turn gas ON and remove adjustment screw cover on
gas valve. Turn counterclockwise to decrease pressure
and clockwise to increase.
1141
4. Turn manual gas valve ON.
5. Turn gas control valve ON.
6. Set thermostat fan switch to ON.
7. Reset thermostat fan switch to AUTO.
HEATING START-UP
PROCEDURE
1. Adjust thermostat setting above room temperature and
set thermostat selector to HEAT. The combustion air
blower should come ON.
2. The combustion air blower will run for 15 seconds to
purge the combustion chamber.
3, After the 15 second purge, the combustion air blower
will remain on. The sparker will turn on to ignite the gas.
Make sure the gas valve is in the "ON" position. (Refer
to Figure 14 and the instructions label located on
Burner Access Panel of unit.
NOTE: On a call for heat the sparker will remain energized
for 7 seconds or until a flame is detected by the flame
sensor. It may take several ignition attempts to purge the air
out of the gas lines at initial start-up of the unit.
4, 30 seconds after the burners
blower will begin to run,
light, the circulating
will normally be obtained when the unit is operating
input with the recommended
blower speed.
FIRE
AND/OR
EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Do NOT attempt to light the burner with a match or
flame of any kind.
HEATING INPUT RATE CHECK
The gas input to the unit is determined by measuring
the gas flow at the meter. Measuring gas flow at the
meter is recommended for natural gas units.
To
measure the heating input, perform the following
steps:
1.
Turn off all other gas appliances that use the same
meter.
2.
Turn off gas supply to unit and attach manifold
pressure gauge as instructed in the "Manifold
Pressure Adjustment" section.
3.
With gas ON to the unit and the unit operating, record
the number of seconds for the gas meter dial to make
one revolution.
4.
Divide number of seconds in Step 3 into 3600
(number of seconds in 1 hour).
5.
6,
Multiply result of Step 4 by the number of cubic feet
shown for one revolution of the meter dial to obtain the
cubic feet of gas flow per hour.
Multiply result of Step 5 by Btu heating value of gas to
obtain total measured input in Btu/hr. Compare this
with the heating value shown in figure 11. Consult
with local gas supplier ifthe heating value of gas is not
known.
1.
The temperature rise must be within the specifications
marked on the unit rating plate.
To check the temperature rise through the unit, place thermometers in the supply and return air ducts as close to the
unit as possible.
Open ALL registers
and duct dampers.
Operate
LEAST 15 minutes before taking readings.
NOTE: The blower speed MUST be set to give the correct
air temperature rise through the furnace as marked on the
rating plate. See Figure 12 for more information.
2. After 15 minutes of operation check the limit control
function by blocking the
return air grille(s).
After several minutes the main burners and pilot should
go OFE The circulating air blower should continue to
run.
Remove air restrictions. Pilot and main burners should
relight after a cool down period of a few minutes.
Adjust the thermostat setting below room temperature.
Main burners and combustion air blower should go
OFF,
The circulating air blower should continue to run for 60,
100, 140 or 180 seconds. This time is adjustable. See
FIGURE 15 for more information.
4. Set thermostat Heat-Cool selector to OFF.
FAN CONTROL CHECK
Fan Delay DIP Switch
IG#_ _IOR C0_TROL BOARD fIAT
t8¢ _
0FF
Settings
DEI_.Y DEL CT;0N
1_8
i
J_
4;
. 18¢
18/}
1.38 sec. To complete 1 revolution
2. 3600/38 = 94.7
3.94.7 x 1 = 94.7
4.94.7 x 1020 = 96,632 Btu!hr
For this example, the nameplate input is 100,000 Btu/hr, so
only a minor change in manifold pressure is required. In no
case should the final manifold pressure vary more than
+- .3 "water column from the values in figure 14.
TEMPERATURE
RISE CHECK
NOTE: Air temperature rise is the temperature difference
between supply and return air. With a properly designed
distribution system, the proper amount of temperature rise
unit AT
If the correct amount of temperature rise is not obtained
when operating on the recommended blower speed, it may
be necessary to change the blower speed. A faster blower
speed will decrease the temperature rise. A slower blower
speed will increase the temperature rise.
FIGURE i5
Example: Assume that the size of the meter dial is 1 cu. ft.,
one revolution takes 44 seconds, and the heating value of
the gas is 1020 Btu/ft3. Proceed as follows:
at rated
_
148__
100
The Fan Control has adjustable settings for the circulating
air blower to delay it "ON" and "OFF".
1. The Fan Control has a fixed "ON" delay of 30 seconds,
and a field adjustable "OFF" delay of 60, 100, 140 and
180 seconds. The "OFF" delay is factory set at 140
seconds.
Refer to FIGURE 15 for proper DIP switch settings.
2. Operate the furnace and ensure that the blower turns
ON and OFF at the appropriate time to provide the
desired comfort level.
1151
10. OPERATION
directly into the heat exchanger tubes and the turbulators
should glow orange (after about five minutes of operation).
Main burner flame should be inspected monthly.
FIGURE i6
ELECTRICAL
1
Normal
Flame
SHOCK HAZARD.
Failure to follow this warning could result in personal
injury, death and/or property damage.
Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.
COMBUSTION/INDOOR
Turbulator will glow
orange when hot.
stable and solid
blue.
Flame should be
FAN CONTROL
All functions of the combustion and indoor blower are
controlled bythe ignition control board and interface board.
On a call for heat:
The ignition control energizes the combustion blower.
Once the combustion air proving switch closes, the ignition
sequence begins. The ignition control will sense when the
main operator of gas valve has been energized thereby
firing the burners and starting the "delay on" timing
sequence of the indoor blower.
NOTE: Ifthe control senses that one of the safety limits has
opened, the combustion and indoor fans will operate until
the limit resets.
On a call for cooling:
The fan control board starts the indoor blower immediately.
Once the thermostat is satisfied, the fan control will operate
the blower for 90 additional seconds.
Using a light and mirror (as required) inspect the inside of
the vent hood and the inlet air opening in the burner
compartment. Look for soot and severe rust or corrosion
and any obstructions due to leaves, spiderwebs, etc. Clean
as required.
COOLING SEASON CHECKS (MONTHLY)
Condenser
11. MAINTENANCE
MONTHLY MAINTENANCE
CHECKS
AND INSPECTION
Keep the condenser inlet and outlet area clean and free of
leaves, grass clippings or other debris. Grass should be
kept short in front of the condenser inlet. Shrubbery MUST
be trimmed back so it is no closer than 30 inches to unit,
Condensate
Air Filters
Drain
Check for condensate drainage.
ANNUAL
REDUCED EQUIPMENT
Coil
MAINTENANCE
Clean as required.
AND INSPECTION
LIFE HAZARD
Failure to follow this cautions may result in damage to
the unit being installed.
ELECTRICAL
Do not operate the unit without
Failure to follow this warning could result in personal
injury, and/or death.
a filter,
Inspect filters at least monthly and replace or clean as
required. Washable filters may be cleaned by soaking in
mild detergent and rinsing with cold water. Replace filters
with the arrows on the side pointing in the direction of air
flow. Dirty filters are the most common cause of inadequate
heating or cooling performance,
and of compressor
failures.
HEATING SEASON CHECKS
(MONTHLY)
Main Burner Flame
Flames should be stable and solid blue, (dust may cause
orange tips or they may have wisps of yellow, but they
MUST not have solid yellow tips). They should extend
b2J
SHOCK HAZARD.
Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.
The annual inspection should include cleaning as required
to ensure efficient operation of the unit. To simplify access,
remove all access panels and the top from the unit if
possible.
Condenser
Fan Motor
Note: The condenser fan motor is permanently lubricated.
No further lubrication is required.
Do not attempt to
lubricate the condenser fan motor,
VENT ASSEMBLY
1. Disconnect electrical power to unit.
2. Turn OFF gas at manual shut off valve.
3. Remove burner access panel.
BURN HAZARD.
4. Remove the vent assembly flue pipe.
Failure to follow this caution
injury or property damage.
may result in personal
Flue cover may be hot! Allow adequate time for flue
cover to cool.
5. Disconnect gas pipe at union.
6. Disconnect wires from gas valve, note connections.
7. Remove screws that secure the flame shield and
remove gas control valve, manifold and burners as an
assembly.
Clean the surrounding area and the condenser and
evaporator coils. Use caution to avoid damage to coil fins.
8. Remove collector box, injector plate, and restrictor
plate, including gaskets.
BLOWER MOTOR ACCESS
motor and
9. Hold the burner assembly vertically and lightly tap it
against a wood block. Clean also with a stiff brush.
Severe cases of lint clogging may require washing the
burners in hot water.
2. Remove the three screws securing the blower motor
housing. If unit has a support bracket, remove the two
screws securing the bracket.
3. Remove the two red wires attached to the limit switch.
10. Clean flue gas passages by using small brushes and a
vacuum cleaner. It may be necessary to fabricate
handle extensions for the brushes to reach the areas
that require cleaning. Reinspect after cleaning and
replace the heat exchanger if defective.
Refer to Figure 17 for a view of blower
compartment.
1. Remove the blower access panel
Motor removal and replacement
This method is required to replace or repair blower wheel,
blower housing, or any unreachable components behind
blower assembly.
1. Remove all screws around rim of unit top, (except
screws which are inaccessible because of proximity to
structure).
2. Raise unit top at corner of unit closest to blower at least
2" and place a sturdy brace at least 2" thick between top
and unit corner. A 2X4 piece of wood is ideal for this.
3. Disconnect all wires from housing and slide housing out
of unit. Reverse this process to reinstall.
Circulating
11. Reinstall parts and gaskets in reverse order. On direct
spark models check the spark gap. 1/8 inch is required
between the sparker electrodes.
12. Turn gas on and check for leaks.
13. Install all access panels, turn power on and check for
normal operation.
REFRIGERANT CIRCUIT
For Qualified Service Technician Only
Annually inspect all refrigerant tubing connections and the
unit base for oil accumulations.
Detecting oil generally
indicates a refrigerant leak.
Air Blower
Visually inspect the blower wheel for accumulations of dirt
or lint. Clean the compartment and the blower wheel. If
accumulation is excessive on blower wheel, or does not
easily remove, it will be necessary to remove the blower
assembly.
Note: The blower motor is permanently lubricated.
No
further lubrication is required. Do not attempt to lubricate
the blower motor.
Burners / Heat Exchangers
/ Flue Gas Passages
To inspect the burners, heat exchanger and interior flue gas
passages, use a light and small mirror on an extension
handle.
Check the exterior of the heat exchanger and the interior
flue gas passages for any evidence of deterioration due to
corrosion, cracking or other causes. If signs of scaling or
sooting exist, remove the burners and clean the heat
exchanger, as required.
INSPECTION AND CLEANING OF BURNER
ASSEMBLY/HEAT EXCHANGERS/FLUE GAS
PASSAGES
For Qualified Service Technician
Only
See FIGURE 17 for identification of parts.
FIRE AND EXPLOSION
HAZARD.
Failure to follow this warning could result in personal
injury, death and/or property damage.
System under pressure. Relieve pressure and recover
all refrigerant before system repair or final unit
disposal to avoid serious injury or death. Use all
service ports and open all flow control devices,
including solenoid valves.
If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak
detector, halide torch, or liquid-soap solution.
FIGURE 17
Component
Locations
I Remote
Sparker
Unit I
0
Y
I GasValve
I
I Flame
I Rollout
/
_,1
IJ
/
J
i
i
f
©©
/
i
f
i
i
[ Selector
'FM and Leads
Speed
I
Switch
Primary Limit I
Switch
Sensor I
I
:D
RIGGING INSTRUCTIONS
10962_,,_-A
rn
FAILURE TO FOLLOW THESE INSTRUCTIONS
CAN RESULT IN PROPERTY DAMAGE,
BODILY INJURY OR DEATH.
QO
/K WARNING
- ALL PANELS
MUST BE IN PLACE WHEN
RIGGING
C:
i
AND LIFTING.
tQ
- HOOK RIGGING SHACKLES THROUGH
HOLES IN BASE RAIL, AS SHOWN IN DETAIL-A.
- USE SPREADER BARS, WHEN RIGGING,
TO PREVENT UNIT DAMAGE.
- BE SURE RIGGING AND SHACKLES ARE SUFFICIENT TO HANDLE WEIGHT LISTED BELOW.
i.
i
DETAIL-A
fo
m,
BARS
o
:3
____
H'_EIGHT
-OR-
r.. ilillimiili .
LENGTH _,_
WIDTH
MAX, HEIGHT
MAX. WEIGHT
i
IN
,,, ,,,,,,
r;
MAX. WIDTH'
MAX. LENGTH
CABINET
MM
IN
MM
IN
MM
LB
KG
.,_,,,
SMALL
52.00
1219
48.00
1219
38.00
965
50O
LARGE
73.00.
1854
48.00
1219
38.00
965
900
409
t_
All Models Wiring Diagram
I_PS1
IF £1iY OF Thee ORKIINA!
W RE AS SUPP HD _?I"
THai @_LIAH{Z
T _GT B I:{EFLA£ 0 wr/
TYPt: A?_NI05"C
OR NS E©S vat I/ ,
S E !_SIA IA
OR YO
l_]i
.........
--
--
like
lOW
lOW
,iT_
_,qUST8
REFLACED,
ZON bS R;CTIONS FOR PHOP[R NEA iIcG ANI} COO/IN6 (:Olq!ECI_ONS
,
_)(0,_/}'!{ Ab MOO PUGS ..... De he O scoriae{
(]i 81 ',_d
YO A{; FACTORY
vO{ AG_
VO[TAGI I-A£TOR?
v'O AO{ FK b
80£_!D St R NG
COLOP: CODE
;
[il A(}h
_K
GREEN
8t.E:
Bt
ORANG{
YflqTF
0
RED
GRA"
GY
V]OLN
V
' I f
_
All Models Wiring
Diagram
ISUL/L
b A(} AF
_, I_. /
C,_AIaG
E}<: El EC] t:_/iCiSi S_iOC!'t
L
"[
8
Wl _[F'
.....
s_,_n,_ E>]SCU,I _cC
USE COPPER_O_sUC*'
_ "OR_oS
0I_["
F][ B' SUP t¥
_P
..F!VI¢ N6
//YI
r
m ¸¸__"
0
©
"
0
t*--
r_,
Z
t ....
Cjj>
b _
..... -/
r:/S
q
r,g
f.....
L])
0
¢'S_
Om
L2
i
iLZ
i}O oEC.
"' ....
s/
230V
l _,_4
.......................................................
24V
_t_-_"h
i oo SE(},
co_c
¢
....
u
L_
_o,--
40 St(C,
_0_
-_0
O-
188 8EC,
l/t_
0
_/4
--0
L_0
--
Y_o_
i_lpS 1
?8
C
Yo_
_0-
j_
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 21 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Thu Apr 05 21:55:04 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools