ICP Package Units(both Units Combined) Manual L0611150

User Manual: ICP ICP Package Units(both units combined) Manual ICP Package Units(both units combined) Owner's Manual, ICP Package Units(both units combined) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 22

Installation Instructions
PGF3 Series
3 Phase ( 208/230 Volt)
PACKAGED GAS /ELECTRIC UNITS
TABLEOF CONTENTS
UNITDIMENSIONS ......................................... 2 ELECTRICALWIRING................................... 8
SAFEINSTALLATIONREQUIREMENTS ......................... 3
LOCATINGTHE UNIT ....................................... 4
CLEARANCES ............................................ 4
INSTALLATION............................................ 4
GROUNDLEVELINSTALLATION .............................. 4
HOISTING................................................ 5
DOWNFLOWCONVERSION.................................. 5
HEATINGVENTASSEMBLY .................................. 5
CONDENSATEDRAIN....................................... 5
COMBUSTIONBLOWERPIPEINSTALLATION .................... 5
PRE-EXISTINGCOMMONVENTCHECK ......................... 5
GASSUPPLYAND PIPING ................................... 6
DUCTWORK......................................... 10
FILTERS ............................................ 10
AIRFLOWADJUSTMENT ............................... 11
START-UPPROCEDURES .............................. 12
GAS PRESSURES .................................... 12
HEATINGSTART-UPPROCEDURES ...................... 13
SEQUENCEOF OPERATION- COOLING ................... 14
OPERATION......................................... 14
MAINTENANCE ...................................... 15
INSPECTIONANDCLEANING............................ 15
RIGGING ........................................... 18
ORIFICES............................................ 7 WIRINGDIAGRAMS ................................ 19 - 22
CLIS_IEDUS
internationalComfort Products,LLC
Lewisburg,TN.37091 509 01 2501 00 8-1 0-06
Printed in U.S.A.
Key: PGF3
P [IJ _11iI w]I_V_l=__"'][o] __
3 TO 5 TON I'C"
[
J
-1/4
BASE PAN - CHASSIS
L_-k
___ ©
BASE RAIL
--" 12-1/4 --
19
I
M
2-3/16
SUPPLY
/
/
/
/
/
/27 K -b_
/
/
/
/
/4-1/2" -_
/
/
/
/
/46-1 8**
/
/
/
i .,,/
/
/
/
/
/
/
/
/
/1-3/4
/
,, /
/
/--r----
3-3/4
ALL DIMENSIONSIN INCHES
Connections Detail
<_ -1/4"
AS
CONNECTION
1/2" PIPE
LOW
4_ 1-3/4, VOLTAGE
1/2" CONDUI[
N
ELECTRICAL
POWER
CONDUIT
Condensate Drain
\2-3/16
UNITSIZE A B C
3 TO 3-1/2 Ton 37-1/2 47-1/2 47-1/2
4TO5Ton* 37-1/2 47-1/2 51
** Measuredfrominsideto insideon baserails.
DEF G H I JKL M N
3-1/2 6-1/2 19 12 12 19 4-1/2 21-1/2 42-3/4 1-9/16 46-1/2
7-1/2 6-1/2 19 12 12 19 4-1/2 21-1/2 46-1/4 5-3/16 49-3/4
2. SAFE INSTALLATION REQUIREMENTS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
components. Only trained and qualified personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance
functions of cleaning coils and filters. All other operations
should be performed by trained service personnel. When
working on air-conditioning equipment, observe
precautions inthe literature, tags, and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguisher available for all brazing operations.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISON HAZARD
Improper installation, adjustment, alteration, service,
maintenance, or use can cause carbon monoxide
poisoning, fire, or an explosion which can result in
personal injury or unit damage. Consult a qualified
installer, service agency, or gas supplier for information
or assistance. The qualified installer or agency must use
only factory-authorized kits or accessories when
modifying this product.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISON HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Before performing service or maintenance operations
on unit, turn off gas supply to unit. Then turn off unit main
power switch and install lockout tag. Electrical shock or
explosion could cause serious injury or death.
[o] lJiiKe] #IRecogniz_ safety information. This is the safety-alert
symbol/.rX. When you see this symbol in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in serious injury or death.
WARNING signifies a hazard which could result in serious
injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
These instructions cover minimum requirements and
conform to existing national standards and safety codes. In
some instances, these instructions exceed certain local
codes and ordinances, especially those that may not have
kept up with changing residential construction practices.
We require these instructions as a minimum for a safe
installation.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON
MONOXIDE POISON HAZARD
Failure to carefully read and follow all instructions in this
manual could result in furnace malfunction, property
damage, personal injury and/or death.
Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes or, in the absence of
local codes, with the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 and the National Electrical
Code NFPA70-2005 or in Canada the National Standard
CAN/CGA B149-1 and CSA C.22.1 -Canadian Electrical
Code Part 1.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test
instruments.
SAFETY CONSIDERATIONS
• Use only with type of gas approved for this unit. Refer to
unit rating plate.
Install this unit only in a location and position as specified
in section 3 of this manual.
Never test for gas leaks with an open flame. Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections, as specified in
section 5.
• Always install unit to operate within the unit's intended
temperature-rise range with a duct system, which has an
external static pressure within the allowable range, as
specified in section 9. Refer to unit rating plate for the al-
lowable external static pressures.
• All connecting ductwork to the unit (supply and return)
must be sealed to the unit casing as specified in section 7.
• Do NOT use this furnace as a construction heater.
Check to see that filters are installed correctly and are the
proper type an size.
NOTE: It is the personal responsibility and obligation of the
customer to contact a qualified installer to ensure that the
installation is adequate and conforms to governing codes
and ordinances.
UNIT SAFETY
Failure to followthis caution may reduce unit tel!ability.
It is recommenaed that a quatifiea service tecnnician
check the heat exchanger integrity every two (2) years,
after the first four (4) years of operation.
INTRODUCTION
The PGF3 unit is a fully self-contained, combination
Category I gas heating/electric cooling unit designed for
outdoor installation (See page 2 for unit dimensions). All
unit sizes have return and discharge openings for both
horizontal and downflow configurations, and are
factory-shipped with all downflow duct openings covered.
Units may be installed either on a rooftop, cement slab, or
directly on the ground if local codes permit.
Models with a'l" in the twelfth position ofthe model number
are dedicated Low NOx units designed for California
installations. The emissions ofthese models do not exceed
40 nanograms of nitrogen oxide emissions per joule of heat
output as shipped from the factory, and must be installed in
California Air Quality Management Districts or any other
regions in North America where a Low NOx rule exists.
131
3. LOCATING THE UNIT
ACCESS PANELS
See FIGURE 1 for a general view of unit and location of
access panels.
CLEARANCES
The location MUST allow for minimum clearances and
should not be adjacent to a patio or other area where the
unit's operating sound level might be objectionable. The
combustion air inlet openings MUST not be obstructed (see
FIGURE 1). In addition, local codes MUST be observed.
NOTE: Units with available filter racks need a 26" minimum
clearance at side of unit for removal of filters. See chart
below if unit is going to be placed near combustible
construction or materials.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation around
the unit for proper operation inthe cooling mode. Whenever
possible, it is desirable to allow additional clearance,
especially around the condenser inlet and discharge
openings.
Do NOT install the unit in a location that will permit
discharged air from the condenser to recirculate to the
condenser inlet.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in shorten life
of unit components.
Do NOT operate unit in a corrosive atmosphere
containing chlorine, fluorine, or any other corrosive
chemicals.
Minimum Clearances to Combustible Construction
Furnace Plenum ..................................... 2"
Duct Side ........................................... 2"
Condenser Inlet .................................... 30"
Blower Service (Side) ............................... 30"
Control Service Side
(Front Combustion Air Inlet) .............. 30"
Clearance between 3 Ft, Overhang
and Top of Unit ......................... 30"
Combustible Base
(Wood or Class A, B or C
roof covering material) ..................... 0"
InternalFilter BurnerCompartment
AccessPanel Panel
INSTALLATION
NOTICE
Unit will NOT operate properly unless it is installed lev-
el front to rear and side to side. The slope MUST NOT be
greater than 1/8" per foot (10mm per meter). For side to
side leveling, the drain side MUST always be lower.
Ground Level Installation
Ground level platform requirements:
- The unit MUST be situated to provide safe access for
servicing.
- Platform may be made of either concrete or pressure
treated wood and MUST be level and strong enough to
support unit weight.
- Position platform separate from building foundation.
- Install in well-drained area, with top surface of platform
above grade level.
- Platform must be high enough to allow for proper
condensate trap installation and drainage. See
FIGURE 4 and associated text for more information
about condensate drainage.
Rooftop Installation
Rooftop platform requirements:
- The unit MUST be situated to provide safe access for
servicing.
- The existing roof structure MUST be adequate to
support the weight of the unit or the roof MUST be
reinforced.
Check the weight of the unit in relation to the roof
structure and local building codes or ordinances and
reinforce roof structure if necessary. See the last page
of this manual for unit weights.
- Support for the unit MUST be level and strong enough
to carry unit weight. The support may consist of a
platform or a combination of platform and roof beams or
curb.
- See Hoisting section for hoisting instructions.
HOISTING
NOTE:AllaccesspanelsMUSTbesecuredinplacebefore
hoisting.
Theunitshouldbehoistedwithtwoliftingslings.Attachthe
slingsto riggingshacklesthathavebeenhookedthrough
holesinthebaserail.
TwospreaderbarsMUSTbeplacedontopof theunitto
protecttheunitfromdamagefromthepressureexerted by
the slings. Make sure that all equipment is adequate to
handle the weight ofthe unit and that the slings will not allow
the unit to shift.
Refer to FIGURE 19 on the back cover of this manual for
illustrated rigging instructions and weight chart.
DOWNFLOW CONVERSION
NOTE: In downflow applications with roof curbs or jack
stands, the center rail under the unit must be removed. The
center rail is attached to the base rail with screws.
These units are adaptable to downflow use. To convert to
downflow use, follow these steps:
1. Remove the blockoff plates found in the return air
compartment and the supply air compartment.
NOTE: BIockoff plate in the supply air compartment only
contains one screw. If reinstalling plate, back part of plate
MUST fit into mating dimples on flange. To reinstall, slant
plate into dimples, then put plate into position and fasten
with screw.
2. Install the removed plates on the horizontal return and
supply air openings.
3. Install roof curb on the building. Be sure to follow all
directions included with curb and all applicable building
codes in your installation.
Combustion Blower Pipe Installation
Remove the combustion blower pipe from the right corner of
the burner compartment and position the end of the pipe
with the screw hole over the opening of the combustion
blower. The other end of the pipe should now be aligned
through the opening in the side panel of the unit. The pipe
should slightly protrude through the opening in the side
panel. See Figure 2.
Remove (1) chisel pointed #10 screw (self-drilling) taped to
the vent cap. Position the screw to the hole in the pipe and
drill through the combustion blower outlet securing the pipe
to the combustion blower.
FIGURE 2 Combustion Pipe Installation
Heating Vent Assembly
Refer to FIGURE 3 and assemble as shown.
Combustion
Pipe
FIGURE 3 Heating Vent Assembly
Attact_
Heating
Vent
UNIT DAMAGE
Failure to follow this caution may result in unit
damage.
Do not operate the unit without the vent assembly
installed.
Condensate Drain
The condensate drain outlet is a 3/4" (19.1 mm) female PVC
connection located at the bottom on the left hand side (see
FIGURE 4).
The circulating blower creates a negative pressure on the
condensate drain line that can prevent the condensate from
draining properly. To combat this negative pressure, a field
supplied condensate trap that will allow a standing column
of water of at least 2" (50.8mm) MUST be installed. Top of
outlet from trap MUST be at least 1" (25.4mm) below top of
outlet from unit. Install the trap as near to the unit as
possible for proper drainage,
A3/4" (19.1 mm) drain line MUST be installed if required by
local codes or if location of unit requires it. Run the drain line
to an open drain or other suitable disposal point.
I F,GURE Cond°nsot°O,ain,n,ormotion*
3/4" (19.1mm)
Female PVC
Fitting _
MUST be installed.
4. PRE-EXISTING COMMON VENT CHECK
If the installation of this new combination gas heat/electric
cool unit involves removing an existing gas-fired furnace
from a common vent system with other gas-fired
appliances (gas-fired hot water heater, etc.), the existing
vent system must be checked and inspected by a qualified
technician. The qualified technician can determine if the
existing vent system will properly vent the flue products of
the remaining gas-fired appliances. In many cases, the
151
existing vent system may be oversized for the remaining
appliances.
5. GAS SUPPLY AND PIPING
NOTE: Because there are many types of liquified petroleum
(LP) gases, the term LP as used in this manual refers to
propane gas. If you intend to use any type of LP gas, proper
precautions MUST be used in the handling, piping, and use
of such gas. NOTE: In Canada, installations MUST be
performed by licensed LP installers.
The UL rating plate located on the side panel on the unit
contains the model number, type of gas, gas input rating,
and other important information.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Make certainthe unit is equippedto operate onthe type of
gas available. Models designated as natural gas are to be
used with natural gas only. Models designated for use
with liquefied petroleum (LP) gas are shipped with
orifices sized for commercially pure propane gas. They
MUST not be usedwith butane or a mixture of butane and
propane unless properly sized orifices are installed by a
licensed LP installer.
GAS PIPING
The gas supply line MUST be of adequate size to handle the
Btu!hr requirements and length of the run for the unit being
installed. Determine the minimum pipe size for natural gas
from the table in FIGURE 5 or FIGURE 6. Base the length
of the run from the gas meter or source to the unit,
Gas Pipe Size
Btu ratings of all other gas appliances MUST be considered
for sizing of main gas line. Check gas line to installation for
compliance with local codes or, in the absence of local
codes, with the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 or in Canada the National
Standard CAN/CGA B149-1 or current editions.
FIGURE 5Gas Pipe Size, Length and Btu/hr Capacity
for Schedule 40 Iron Pipe/English/
NATURAL GAS
Pipe Length Btu/hr (in thousands)
(Includes
Fittings) 3/4" 1" 11/4" 11/2" 2"
20' 190 350 730 1,100 2,100
40' 130 245 500 760 1,450
60' 105 195 400 610 1,150
LP GAS
Pipe Length Btu/hr (in thousands)
(Includes
Fittings) 1/2" 3/4" 1" 11/4 "
20' 189 393 732 1,496
40' 129 267 504 1,039
60' 103 217 409 834
11/2"
2,299
1,559
1,275
Gas Pipe Size, Length and Btu/hr Capacity
FIGURE 6 for Schedule 40 Iron Pipe (English)
Pipe Length
(Includes
Fittings)
6.1m
3/4" 2"
56 615
12.2m 38 425
18.3m 31 337
Pipe Length
(Includes
Fittings) 1/2" 11/2"
6.1m 55 674
12.2m 38 457
18.3m 30 374
**kW (Kilowatts) is the metric equivalent of Btu/hr.
NATURAL GAS
kW**
1" 11/4" 11/2"
103 214 322
72 147 223
57 117 179
LP GAS
kW**
3/4" 1" 11/4"
115 215 438
78 148 305
64 120 244
PIPING AT UNIT
Connections
NOTE: The rules listed apply to natural and LP gas pipe
installations.
1, If installation is for LP gas, have LP gas installer use
TWO-STAGE REGULATION and make all
connections from storage tank to unit.
2. Use black iron or steel pipe and fittings or other pipe
approved by local code.
3. If copper tubing is used, it MUST comply with limitation
set in Fuel Gas Code.
NOTE: If a flexible gas connector is used, it MUST be
acceptable to local authority. Connector MUST NOT be
used inside the furnace or be secured or supported by the
furnace or ductwork. Do not use a connector which has
previously serviced another gas appliance. Always use a
new listed connector.
FIRE OR EXPLOSION HAZARD
Failure to do so could result in personal injury, death
and/or property damage.
Gasconnector MUST be properly installed and can NOT
be used inside the furnace.
4, Use pipe joint compound on external (male) threads
ONLY. Joint compound MUST be resistant to any
chemical action of LP gases. Do NOT put pipe
compound on last 2 threads of pipe.
5, Use ground joint unions and install a drip leg no less
than 3 inches (76 mm) long to trap dirt and moisture
before it can enter gas valve,
UNIT OPERATION AND COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in misaligned
burners, flame rollout and or unit damage.
Overtightening assembly may cause damage to the gas
valve and/or wiring and may misalign the burners.
6, Use a wrench on gas valve when making connections
to prevent gas valve from turning. Do NOT use a pipe
wrench on the gas valve body,
7,Providea t/8inch(3mm)NationalPipeThread(NPT)
plugfortestgaugeconnectionimmediatelyupstreamof
thegassupplyconnectionto thefurnaceif noneis
suppliedwiththegasvalveofunit.
8. Installa manualshutoffvalveand tightenall joints
securely,
LEAKCHECK/PRESSURETESTING OF GAS SUPPLY
PIPING
FIRE OR EXPLOSION HAZARD
Failureto follow the safetywarningsexactlycouldresultinserious
injury,deathorpropertydamage.
Never testfor gas leakswithan open flame. Use a commercially
availablesoapsolutionmadespecificallyfor thedetectionof leaks
to check all connections. A fire or explosionmay result causing
propertydamage,personalinjuryorlossof life.
The unit and its equipment shutoff valve must be
disconnected from the gas supply piping system during any
TABLE 1 & 2: Equivalent Orifice Sizes at High Altitudes
pressure testing of that system at test pressures in excess
of .5 psi (3.5kPa).
The unit must be isolated from the gas supply piping system
by closing the equipment shut off valve during any pressure
testing of the gas supply piping system at test pressures
equal to or less than ,5 psi (3,5 kPa),
ORIFICES
Orifice Sizes
Orifice sizes MUST be matched to the heating value of the
gas (see TABLE 1 & 2). Check with your gas supplier and
the National Fuel Gas Code ANSI Z223,1,
NOTE: An LP Conversion Kit MUST be used for conversion
to LP gas.
NOTE: For elevations above 2000 feet (610 meters), the
Btu input rating MUST be reduced by 4% for each 1000 feet
(305 meters) above sea level, unless the gas supplier's
Btu/ft3 content has already been adjusted for altitude.
Check Table 1 & 2 for the proper orifice sizes.
Table 1NATURAL GAS ORIFICE SIZING
MEAN ELEVATION FEET ABOVE SEA LEVEL
0 to 2000 2001 to 4001 to 5001 to 6001 to 7001 to 8001 to 9001 to
4000 5000 6000 7000 8000 9000 10000
Orifice Kit Orifice Orifice Orifice Orifice Orifice Orifice Orifice
Nominal Heating Size Drill # Number Drill # Dril! # Dri!l # Drill # Drill # Drill # Dril! #
060, 080 44 1173863 45 46 47 47 48 48 49
100 41 1173865 43 43 48 44 44 45 46
120, 140 42 1173865 43 43 44 44 45 46 47
NOTE: The orifice sizes in the chart above derate the input rate at 4% per 1000 feet above sea level for altitudes exceeding 2000 feet
above sea level. If converting from LP gas to Natural Gas at altitudes exceeding 2000 feet above sea level, use part number
330732-401, plus the required orifice size # shown in Table 1. Natural Gas data is based on 0.60 specific gravity, a heating value of 1030
Btu/Cu.Ft., and 3.5" W.C. manifold pressure. For fuels with different specific gravity, consult the National Fuel Gas Code NFPA
54-2005/ANSI Z223.1-2005 or National Standard of Canada, Natural Gas and Propane Installation Code CSA B149.1-05.
Table2 LPGASORIFICESIZING
MEANELEVATIONFEETABOVESEA LEVEL
0to2000 2001to4000 4001to 7000 70011o9000 9001to 10,000
Nominal Heating Orifice Kit Orifice Kit Orifice Kit Orifice Kit Orifice Kit
Size Drill # Number Drill # Number Drill # Number Drill # Number Drill # Number
060, 080 55 1173857 55 1173857 56 1173859 56 1173859 57 1173861
100,120,140 54 1173855 55 1173857 55 1173857 56 1173859 56 1173859
NOTE: The orifice sizes in the chart above derate the input rate at 4% per 1000 feet above sea level for altitudes exceeding 2000 feet
above sea level. LP Gas data is based on 1.52 specific gravity, a heating value of 2500 Btu/Cu. Ft., and 10.0" W.C. manifold pressure. For
fuels with different specific gravity, consult the National Fuel Gas Code NFPA 54-2005/ANSI Z223.1-2005 or National Standard of
Canada, Natural Gas and Propane Installation Code CSA B149.1-05.
171
Changing Orifices
ELECTRICAL SHOCK, FIRE AND/OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Shut off electric power at unit disconnect or service
panel and shut off gas at manual shut off valve before
beginning the following procedure.
Changing orifices requires a qualified service
technician.
1. Shut OFF gas at manual shut off valve.
2. Shut OFF electric power at unit disconnect or service
panel. If unit is still running, allow 3 minutes after gas
shut off before turning off power.
3. Disconnect the wires from the gas valve, sparker, and
flame sensor.
4. Remove the four screws holding the manifold to the
manifold brackets.
5. Carefully remove the manifold with the gas valve
attached.
6. If unit has v-shaped NOx baffles installed in the firing
tubes, they must be removed. Some baffles may be
attached by screws. When converting to LP, replace
screws after removing NOx baffles (figure 7).
7, Remove the orifices from the manifold with a 7/t6" box
end or socket wrench.
8. Check to be sure that the size of each orifice is correct
for the Btu input desired,
FIGURE 8 Manifold/Orifice Measurement
Measure 13/16" from face of orifice
back edge of manifold pipe.
9. Install the correct orifices. Gauge the size of the orifices
with a new twist drill bit of the correct size.
Make sure that the orifices go in straight so that they
form a right angle (90 °) to the manifold pipe.
Tighten the orifices so that there is a 13/t6" distance
between the faces of the orifices to the back of the
manifold pipe.
Measure the distance with a set of calipers. If you do not
have a calipers, you can use an adjustable wrench and
measure between the face of the jaws,
10. Reassemble in reverse order,
6. ELECTRICAL WIRING
CARBON MONOXIDE HAZARD.
Failure to follow this warning could result in per-
sonal injury, death and/or property damage.
NOx baffles for use with Natural Gas units ONLY. If
LP Gas is required, NOx inserts must be removed.
Removing NOx Baffles
or
25-22-46a
ELECTRICAL SHOCK HAZARD.
Failure to follow this warning could result in personal
injury, death, and/or property damage.
The unit cabinet must have an uninterrupted,
unbroken electrical ground to minimize the possibility
of serious injury if an electrical fault should occur.
This ground may consist of an electrical wire
connected to the unit ground lug in the control
compartment, or conduit approved for electrical
ground when installed in accordance with National
Electric Code (NEC) NFPA 70, National Fuel Gas Code
NFPA 54-2005/ANSI Z223.1-2005 and local electrical
codes. In Canada, follow Canadian Electrical Code
CSA (Canadian Standards Association) C22.1 and
local electrical codes. Failure to adhere to this
warning could result in serious injury or death.
181
REDUCED EQUIPMENT LIFE HAZARD
Failure to follow these precautions could result in
damage to the unit being installed.
1) Make all electrical connections in accordance with
National Electric code (NEC) NFPa 70, National Fuel Gas
Code NFPA 54-2005/ANSI Z223.1-2005 and local
electrical codes governing such wiring. In Canada, all
electrical connections must be in accordance with CSA
standard C22.1, Canadian Electrical Code Part 1, and
applicable local codes. Refer to unit wiring diagram.
2) Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3) Be sure that high-voltage power to unit i8 within
operating voltage range indicated on unit rating plate.
4) Do not damage internal components when drilling
through any panel to mount electrical hardware,
conduit, etc. Consult local power company for
correction of improper voltage and/or phase imbalance.
For access, remove the burner access panel. See
FIGURE 1 for access panel location. Wiring MUST be
protected from possible mechanical damage.
Disconnect Switch
The unit must have separate electrical service with a
field-supplied, waterproof, disconnect switch mounted at,
orwithin sight from, the unit. Refer tothe unit rating plate for
maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
Ground Connections
Do NOT complete line voltage connections until unit is
permanently grounded. All line voltage connections and the
ground connection MUST be made with copper wire.
A ground lug is installed in the control box area for the
ground connection. Use a copper conductor of the
appropriate size from the unit to a grounded connection in
the electrical service panel or a properly driven and
electrically grounded ground rod. See warning above.
Line Voltage Wiring
Connections for line voltage are made in the unit control box
area. Refer to wiring diagram located on the Burner Access
panel. For access, remove the burner access panel.
1. Run the high voltage (L1, L2 and L3) and ground leads
into the control box.
2. Connect ground lead to chassis ground connection.
3. Connect L1 to pressure lug connection 11 of the
compressor contactor.
4. Connect L2 to pressure lug connection 13 of the
compressor contactor.
5. Connect L3 to the bare Blue wire from the compressor
power plug, using a wire nut and insulate it with electric
tape.
Converting 230V Units to 208V
To convert 230V units to 208V:
1. Turn electric power OFE
2. Remove the electrical access panel.
3. Locate the 24V control transformer.
4. Remove wires from the terminal labeled "240V" on the
24V control transformer and reconnect them to the
208V terminal of the 24V control transformer.
5. Replace the electrical access panel.
Accessory Economizer Wiring
This unit has factory-routed wiring required for using an
accessory economizer. (Refer to product specification
sheets for an accessory economizer that is compatible with
this unit.)
The factory-routed economizer wiring consists of:
There are 8 wires in the low voltage connection area. These
wires must be stripped and connected to thermostat and/or
unit pigtail connections per the economizer accessory
installation instructions.
There are two gray wires with 1/4" quick connects wire-tied
to the indoor blower motor harness above the blower
housing. These two gray wires must be connected to the
mixed-air sensor shipped with the accessory economizer.
The mixed air sensor must be mounted per the economizer
accessory installation instructions.
There is a 12 pin plug connection above the return opening.
The economizer accessory comes with two wire harnesses
connected with a 12 pin plug. Unplug these two harnesses
and connect the one to the 12 pin plug connection found
above the return opening. Discard the unused harness.
Refer to the economizer accessory installation instructions
for proper installation.
Thermostat /Low Voltage Wiring
Location of the thermostat has an important effect on home
comfort. FOLLOW THE THERMOSTAT INSTRUCTION
MANUAL FOR CORRECT LOCATION, MOUNTING, AND
WIRING.
For 3 to 3-1/2 Ton Models Only:
A single stage thermostat is required for proper operation.
Thermostat must have the following terminals: "R", "W",
"Y", and "G'. Some electronic thermostats use low voltage
from the unit for power for temperature display and
programming. These electronic thermostats will have a"C"
terminal. The outdoor unit has color-coded wires for easy
connection. Using wire nuts, follow figure 9 for proper
connections:
FIGURE 9 3 to 3-1/2 Ton Thermostat Connections
@ ,,,1_ Red
,,,_ hite
Yellow
@,,,1_ Green
Typical
Mechanical
Thermostat
Subbase
For 4 to 5 Ton Models Only:
(_ -I D.- Red
White
(_ .,,1_ Yellow
@ .,,1_ Green
@-I D.- Brown
Typical
Electronic
Thermostat
Subbase
A two-stage thermostat is required for proper operation.
Thermostat should have the following terminals: "R",
"W/W1 ", "Y1", "Y2", and "G'. Some electronicthermostats
use low voltage from the unit for power for temperature
191
display and programming. These electronic thermostats
will have a "C" terminal. The outdoor unit has color-coded
wires for easy connection. Using wire nuts, follow figure 10
for proper connections:
FIGURE 10 4 to 5 Ton Thermostat Connections
,,1_ ed
White
Yellow
Pink
@,,1_ Green
Typical
Mechanical
Thermostat
Subbase
,,1_ Red
White
Y_ _Yellow
Pink
Typical
Electronic
Thermostat
Subbase
THERMOSTAT HEAT ANTICIPATOR
Some thermostats have an adjustable heat anticipator. The
heat anticipator prevents temperature overshoot in heating
mode. If the heat doesn't turn off until the set point
temperature on the thermostat is exceeded, then the
anticipator setting is too low. If the heat turns off before the
thermostat reaches the set point temperature on the
thermostat, then the anticipator setting is too high. Follow
the thermostat instruction manual for proper adjustment of
the heat anticipator.
Final Electrical Check
1. Make a final wiring check to be sure system is correctly
wired. Inspect field installed wiring and the routing to
ensure that rubbing or chafing due to vibration will not
occur.
NOTE: Wiring MUST be installed so it is protected from
possible mechanical damage.
size ductwork to the capacity of the unit and to the airflow
requirements of the conditioned space. Failure to properly
size ductwork can result in inadequate airflow and poor
efficiency. Undersized ductwork may result in tripped limit
controls and premature failure of compressors, motors and
other components.
Ductwork Insulation
Ductwork installed outdoors must have a minimum 2" thick
fiberglass "wrap" insulation and a weatherproof vapor
barrier installed around it. The insulation and vapor barrier
must be protected against potential damage. Caulking,
flashing, and other means of providing a permanent
weather seal must be used.
Ductwork Connections
The use of flexible, non-combustible connectors between
main trunk ducts and supply and return air plenums is
permitted. If flexible connectors are used, they should be
protected from potential mechanical damage such as
punctures and tears.
NOTE: When connecting the supply and return plenums to
the unit, make sure that the plenums are sealed against the
side casing of the unit and do not interfere with removal of
the top of the unit.
FILTERS
All return air MUST pass through a filter before entering the
unit. An electronic air cleaner, optional filter racks, or other
accessible filter arrangement must be installed in the return
air ductwork. Minimum recommended filter sizes are listed
in FIGURE 11and are based on maximum face velocities of
300 ft!min for disposable filters and 600 ft/min for washable
(high velocity) filters. See figure 10 for filter sizes.
7. DUCTWORK
Ductwork Sizing
The maximum recommended velocity in trunk ducts is 1000
feet per minute. The maximum recommended velocity in
branch ducts is 800 feet per minute.
REDUCED EQUIPMENT LIFE HAZARD
Failure to follow this caution may result in improper
unit operation.
Do not operate the unit without a filter.
Ductwork sizing affects the discharge temperature, airflow
velocity, and efficiency of the system. Be sure to properly
FIGURE il Filter Sizes
Model
PGF336060
PGF336080
PGF336100
PGF342080
PGF342100
PGF348080
PGF348120
PGF354100
PGF354140
Disposable Filters
Nominal Size
(qty x w x d)
2 x 15" x 20"
2 x 15" x 20"
2x18"x20"
2x18"x20"
2x18"x20"
2 x20" x20"
2 x20" x20"
2 x20" x24"
2 x24" x24"
Minimum Area
(sq. inches)
576
576
720
672
720
768
785
960
1008
Nominal Size
(qty x w x d)
1 x 15" x 20"
1 x 15" x 20"
1 x 18" x 20"
1 x 18" x 20"
1 x 18" x 20"
1 x 20" x 20"
1 x 20" x 20"
1 x 20" x 24"
1 x 24" x 24"
Washable Filters'
Minimum Area
(sq. inches)
288
288
360
336
360
384
392.5
48O
5O4
1 Washable filter size based on an allowable face velocity of 600 ft/min. Refer to
filter manufacturer's specifications for allowable face velocity and required filter area.
8. AIRFLOW ADJUSTMENT
ELECTRICAL SHOCK HAZARD.
Failure to follow this warning could result in property damage, personal injury, and/or death.
Turn off electric power supply at disconnect switch or service panel before removing access or service panels from unit.
External Static Pressure (in H20 )
.1" .2" .3" .4" .5" .6" .7" .8"
Heatin Heating
Cooling input Rise Speed Heating Heating Heating Heating Heating Heating Heating Heating
Model Tons (Btu/hr) Range(°F Tap CFM Rise(°F) CFM Rise (°F) CFM Rise(°F) CFM Rise(°F) CFM Rise (°F) CFM Rise(°F) CFM Rise (°F) CFM Rise (°F)
4 t552 NA 1607 NA 1574 NA 1541 NA t500 NA t462 30 1426 3t t384 32
3 t529 NA 1484 30 1440 31 1402 32 t364 32 1325 33 1284 34 1238 35
PGF336060 3 50000 30-60 2 t278 35 1233 36 1191 37 1149 38 t108 40 1060 42 1005 44 943 47
1 t162 38 1118 40 1062 42 1014 44 958 46 892 50 826 54 780 57
4 t552 36 1607 37 1574 38 1541 38 t500 39 1462 40 1426 41 1384 43
3 t529 39 1484 40 1440 41 1402 42 t364 43 1325 45 1284 46 1238 48
PGF336080 3 80000 35-55 2 t278 46 1233 48 1191 50 1149 51 t108 53 1060 56 1005 59 943 63
1 t162 51 1118 53 1062 55 1014 58 958 52 892 NA 826 NA 780 NA
4 t552 44 1607 45 1574 45 154t 47 t500 48 1462 50 1426 51 1384 53
3 t529 48 1484 49 1440 50 1402 52 t364 53 1325 55 1284 57 1238 59
PGF336100 3 100000 35-55 2 t278 57 1233 59 1191 61 1149 53 t108 NA 1060 NA 1005 NA 943 NA
1 t162 53 1118 55 1062 NA 1014 NA 958 NA 892 NA 826 NA 780 NA
4 t543 36 1609 37 1577 37 1541 38 t509 39 1475 40 1439 41 t402 42
3 t505 39 1467 40 1431 41 1398 42 t363 43 1324 45 1283 46 t234 48
PGF342080 35 80000 35-65 2 t240 48 1189 50 1145 52 1104 54 t053 56 t010 59 952 52 891 NA
1 1138 52 1087 54 1041 57 989 50 940 53 865 NA 806 NA 752 NA
4 t543 44 1609 45 1577 45 1541 47 t509 48 1475 49 1439 51 t402 52
3 t505 48 1467 50 1431 51 1398 52 t363 53 1324 55 1283 57 t234 59
PGF342100 35 100000 35-65 2 t240 59 1189 51 1145 63 1104 NA t063 NA 1010 NA 952 NA 891 NA
1 t138 54 1087 NA 1041 NA 989 NA 940 NA 855 NA 806 NA 752 NA
4 t908 NA 1864 NA 1819 NA 1770 NA t720 NA t578 35 1632 36 t586 37
3 t750 34 1696 35 1543 35 1592 37 t547 38 1497 40 1443 41 1400 42
PGF348080 4 80000 35-55 2 t245 48 1170 51 1110 53 1034 57 972 51 924 64 875 NA 835 NA
1 t154 51 1084 55 1005 59 940 53 880 NA 832 NA 780 NA 713 NA
4 t908 47 1864 48 1819 49 1770 50 t720 52 1578 53 1632 54 t586 55
3 t750 5t 1696 52 1543 54 1592 56 t547 57 1497 59 1443 52 t400 63
PGF348120 4 120000 40-70 2 t245 NA 1170 NA 1110 NA 1034 NA 972 NA 924 NA 875 NA 835 NA
1 t154 NA 1084 NA 1005 NA 940 NA 880 NA 832 NA 780 NA 713 NA
4 2173 34 2113 35 2067 36 2032 36 2003 37 1962 38 1904 39 t822 41
3 2109 35 2052 36 2000 37 1952 38 t899 39 1847 40 1798 41 t750 42
PGF350100 5 100000 30-60 2 t449 51 1372 54 1318 55 1258 59 t195 NA 1130 NA 1086 NA t048 NA
1 1348 55 1274 58 1218 NA 115t NA t085 NA 1032 NA 989 NA 954 NA
4 2173 48 2113 49 2067 50 2032 5t 2003 52 1962 53 1904 54 t822 57
3 2109 49 2052 51 2000 52 1952 53 t899 55 1847 55 1798 58 t750 59
PGF350140 5 140000 35-55 2 t449 NA 1372 NA 1318 NA 1256 NA t195 NA 1130 NA 1086 NA t048 NA
1 1348 NA 1274 NA 1218 NA 115t NA t085 NA 1032 NA 989 NA 954 NA
NA = Not Allowed for Heatinq Speed.
CIRCULATING AIR BLOWER SPEEDS
FIGURE 12 I Factory-Shipped Blower Tap Connections
Model
PGF336060H
PGF336080H
PGF336100H
PGF342080H
PGF342100H
PGF348080H
PGF348100H
PGF354100H
PGF354140H
Blower Speed Tap Settings
Speed Tap 2 Speed Tap 3
Speed Tap 2 Speed Tap 3
Speed Tap 2 Speed Tap 3
Speed Tap 3 Speed Tap 4
Speed Tap 3 Speed Tap 4
Speed Tap 3 (Hi); 2 (Lo) Speed Tap 4 (Hi); 3 (Lo)
Speed Tap 3 (Hi); 2 (Lo) Speed Tap 4 (Hi); 3 (Lo)
Speed Tap 3 (Hi); 2 (Lo) Speed Tap 4 (Hi); 3 (Lo)
Speed Tap 3 (Hi); 2 (Lo) Speed Tap 4 (Hi); 3 (Lo)
Verify that the proper blower speeds for heating and cooling
are selected on the blower motor by removing the blower
access panel and inspecting the blower motor. The motor
has 4 speeds numbered "1", "2", "3", and "4". The wires for
the speed selection are as follows:
Red _Heating
Black _High Stage Cooling
Violet _Low Stage Cooling (4 & 5 ton only)
Using the same speed for Heating and Cooling.
If the same speed is required for heating and high stage
cooling the following procedure must be used:
1. Set Red wire on proper speed selection on blower
motor.
2. Remove Black wire from "COOL" (3 - 3.5 Ton models)
or "HI" (4 - 5 Ton Models) on Blower Interface Board.
Tape end of Black lead using electrical tape.
3. Jumper the Red wire to both the "Heat" terminal and
either the "COOL" (3 - 3.5 Ton models) or'HI" (4 - 5Ton
Models) terminal on the Blower Interface Board.
If the same speed is required for heating and low stage
cooling (4 & 5 Ton models only), the following procedure
must be used:
1. Set Red wire on proper speed selection on blower
motor.
2. Remove Violet wire from "LO" on Blower Interface
Board. Tape end of Violet lead using electrical tape.
3. Jumper the Red wire to both the "Heat" terminal and the
"LO" terminal on the Blower Interface Board.
CONTINUOUS FAN OPERATION
Continuous fan speed operates at the cooling speed for 2
thru 3-1/2 ton models and at the low stage cooling speed for
4 and 5 ton models.
COOLING
1. Turn electric power OFF
2. Set thermostat Heat-Cool select to COOL.
3. Adjust thermostat setting to below room temperature.
4. Turn power ON, for approximately one minute, then
OFF. During power application check the following:
a. Contactor - Contacts Closing
b. Compressor - ON
c. Condenser fan motor - ON
d, Circulating Air Blower - ON 0 second delay
5. Turn power OFE check the following:
a. Contactor contacts opening.
b. Compressor - OFF
c. Condenser fan motor - OFF
d. Circulating blower - OFF after a 60 second delay for
3 thru 3-1/2 ton models and a 90 second delay for 4
and 5 ton models,
9. START-UP PROCEDURES
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do NOT attempt to light the burner with a match or
flame of any kind.
CHECK BEFORE STARTING
1. Check that the blower motor speed terminal block is
running the correct heating and cooling speeds.
2. Check to see that clean, properly sized air filters are
installed.
3. Replace all service access panels.
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners
operating.
FIRE OR EXPLOSION HAZARD.
Failure to follow this warning could result in
personal injury and/or death.
Turn OFF gas at shut off before connecting U-tube
manometer.
FIGURE i3
RegulatorAdjustment
UnderCa
Inlet
Pressure
Tap1/8NPT
Honeywell Gas Valve
HONEYWELL@
Outlet
Pressure
Tap
1/8NPT
J
OUTLET
25-24-98a
GAS PRESSURES
1. Do NOT allow gas supply pressure to fall below the
listed minimums. Doing so will decrease input to
furnace. Refer to FIGURE 14 for gas supply pressures.
2. Gas input MUST NOT exceed rated input shown on
rating plate.
3. Do NOT allow pressures to exceed the maximum limits
as listed in FIGURE 14.
b2J
FIGURE 14 Gas Pressures
Natural Gas LP Gas
Minimum 4.5"W.C. (1120 Pa) 11" W.C. (2740 Pa)
Inlet
Recommended 7" W.C. (1740 Pa) 11" W.C. (2740 Pa)
Inlet
Maximum 13" W.C. (3230 Pa) 13" W.C. (3230 Pa)
Inlet
Manifold 3.5" W.C. (870 Pa) 10" W.C. (2490 Pa)
Pressure
Manifold Pressures
Manifold pressures are covered in the startup procedure
section. See Figure 15.
1. With gas OFF, Connect U-Tube manometer to tapped
opening on gas valve. Use manometer with a 0 to 12
inches water column range.
FIGURE i5 Manifold Pressure Settings
Gas Type Manifold Pressure
Natural 3.5 Inches Water Column (870 Pa)
Propane 10 Inches Water Column (2490 Pa)
2. Turn gas ON and remove adjustment screw cover on
gas valve. Turn counterclockwise to decrease pressure
and clockwise to increase.
NOTE: Adjustment screw cover MUST be placed on gas
valve before reading manifold pressure and operating
furnace.
FIRE AND/OR EXPLOSION HAZARD
Failure to follow this warning could result in
personal injury, death and/or property damage.
Do NOT adjust manifold pressure more than _+0.3
inches water column to obtain rated input.
3. Set pressure to value shown in FIGURE 15, +_0.07kPa
(0.3 inches) water column. Pressure is also listed on
furnace rating plate. In NO case should final manifold
pressure vary more than _+0.07kPa (0.3 inches) water
column.
Check the unit's operation as outlined in the following
instructions. If any unusual sparking, odors or unusual
noises are encountered, shut off electric power
immediately. Recheck for wiring errors, or obstructions in or
near blower motors.
1. Set thermostat Heat-Cool selector to OFF.
2. Set thermostat fan switch to AUTO.
3. Turn electric power ON. Nothing should start running.
4. Turn manual gas valve ON.
5. Turn gas control valve ON.
6. Set thermostat fan switch to ON.
7. Reset thermostat fan switch to AUTO.
HEATING START-UP PROCEDURE
1. Adjust thermostat setting above room temperature and
set thermostat selector to HEAT. The combustion air
blower should come ON.
2. The combustion air blower wil run for 15 seconds to
purge the combustion chamber.
3. After the 15 second purge, the combustion air blower
will remain on. The sparker will turn on to ignite the gas.
Make sure the gas valve is in the "ON" position. (Refer
to Figure 14 and the instructions label located on
Burner Access Panel of unit.
NOTE: On a call for heat the sparker will remain energized
for 7 seconds or until a flame is detected by the flame
sensor. It may take several ignition attempts to purge the air
out of the gas lines at initial start-up of the unit.
4.30 seconds after the burners light, the circulating
blower will begin to run.
FIRE AND/OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Do NOT attempt to light the burner with a match or
flame of any kind.
HEATING INPUT RATE CHECK
The gas input to the unit is determined by measuring
the gas flow at the meter. Measuring gas flow at the
meter is recommended for natural gas units. To
measure the heating input, perform the following
steps:
1. Turn off all other gas appliances that use the same
meter.
2. Turn off gas supply to unit and attach manifold
pressure gauge as instructed in the "Manifold
Pressure Adjustment" section.
3. With gas ON to the unit and the unit operating, record
the number of seconds for the gas meter dial to make
one revolution.
4. Divide number of seconds in Step 3 into 3600
(number of seconds in 1 hour).
5. Multiply result of Step 4 by the number of cubic feet
shown for one revolution of the meter dial to obtain the
cubic feet of gas flow per hour.
6. Multiply result of Step 5 by Btu heating value of gas to
obtain total measured input in Btu!hr. Compare this
with the heating value. Consult with local gas supplier
if the heating value of gas is not known.
Example: Assume that the size of the meter dial is 1 cu. ft.,
one revolution takes 38 seconds, and the heating value of
the gas is 1020 Btu/ft3. Proceed as follows:
1.38 sec. To complete 1 revolution
2.3600/38 = 94.7
3.94.7 x 1 = 94.7
4.94.7 x 1020 = 96,632 Btu/hr
For this example, the nameplate input is 100,000 Btu/hr, so
only a minor change in manifold pressure is required. In no
1131
case should the final manifold pressure vary more than
+- .3 "water column from the values in figure 14.
Temperature Rise Check
NOTE: Air temperature rise is the temperature difference
between supply and return air. With a properly designed
distribution system, the proper amount of temperature rise
will normally be obtained when the unit is operating at rated
input with the recommended blower speed.
1. The temperature rise must be within the specifications
marked on the unit rating plate.
To check the temperature rise through the unit, place ther-
mometers in the supply and return air ducts as close to the
unit as possible.
Open ALL registers and duct dampers. Operate unit AT
LEAST 15 minutes before taking readings,
If the correct amount of temperature rise is not obtained
when operating on the recommended blower speed, it may
be necessary to change the blower speed. A faster blower
speed will decrease the temperature rise. A slower blower
speed will increase the temperature rise.
NOTE: The blower speed MUST be set to give the correct
air temperature rise through the furnace as marked on the
rating plate. See Figure 12 for more information.
2. After 15 minutes of operation check the limit control
function by blocking the
return air grille(s).
After several minutes the main burners and pilot should
go OFF. The circulating air blower should continue to
run.
Remove air restrictions. Pilot and main burners should
relight after a cool down period of a few minutes.
3, Adjust the thermostat setting below room temperature.
Main burners and combustion air blower should go
OFF.
The circulating air blower should continue to run for 60,
100, 140 or 180 seconds. This time is adjustable. See
FIGURE 16 for more information.
4. Set thermostat Heat-Cool selector to OFF.
FAN CONTROL CHECK
FIGURE i6 ]Fan Delay DIP Switch Settings
180 _,; 186 146_
_6
H_A! _£_F
The Fan Control has adjustable settings for the circulating
air blower to delay it "ON" and "OFF".
1. The Fan Control has a fixed "ON" delay of 30 seconds,
and a field adjustable "OFF" delay of 60, 100, 140 and
180 seconds. The "OFF" delay is factory set at 140
seconds.
Refer to FIGURE 16 for proper DIP switch settings.
2. Operate the furnace and ensure that the blower turns
ON and OFF at the appropriate time to provide the
desired comfort level.
10. Sequence of OPERATION
ELECTRICAL SHOCK HAZARD.
Failure to follow this warning could result in personal
injury, death and/or property damage.
Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.
Cooling Operation (036 - 042):
With a call for cooling (Y), the indoor fan energizes
immediately whereas the contactor energizes after a 5
minute time delay (incase of an initial start up) starting the
compressor and the outdoor fan motor. When the cooling
demand is met, (Y) de-energizes, shutting the compressor,
indoor fan and the outdoor fan.
Cooling Operation (048 - 054):
These units utilize a 2 stage indoor thermostat. With a first
stage call for cooling (Y1), the indoor fan (low stage)
energizes immediately whereas the contactor energizes
after a 5 minute time delay (incase of an initial start up)
starting the compressor (low stage) and the outdoor fan
motor. If the low stage operation cannot satisfy the cooling
demand, the second stage cooling (Y2) energizes
switching the compressor into high stage cooling through
energizing an internal solenoid valve inside the scroll
compressor and switching the indoor fan into high stage.
When second stage cooling is satisfied, Y2 de-energizes
switching the compressor and the indoor fan into low stage
cooling. When the low stage cooling demand is met, Y1
de-energizes shutting the compressor, indoor fan and the
outdoor fan.
11. OPERATION
ELECTRICAL SHOCK HAZARD.
Failure to follow this warning could result in personal
injury, death and/or property damage.
Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.
COMBUSTION /INDOOR FAN CONTROL
All functions of the combustion and indoor blower are
controlled by the ignition control board and interface board.
On a call for heat:
The ignition control energizes the combustion blower.
Once the combustion air proving switch closes, the ignition
bid
sequence begins. The ignition control will sense when the
main operator of gas valve has been energized thereby
firing the burners and starting the "delay on" timing
sequence of the indoor blower.
NOTE: Ifthe control senses that one of the safety limits has
opened, the combustion and indoor fans will operate until
the limit resets.
On a call for cooling:
The fan control board starts the indoor blower immediately.
Once the thermostat is satisfied, the fan control will operate
the blower for 60 additional seconds (2 to 3-1/2 ton models)
or 90 additional seconds (4 to 5 ton models).
12. MAINTENANCE
MONTHLY MAINTENANCE AND INSPECTION
CHECKS
Air Filters
REDUCED EQUIPMENT LIFE HAZARD
Normal Flame
Flame should be
Turbulator will glow stable and solid
orange when hot. blue.
Failure to follow this cautions may result in damage to
the unit being installed.
Do not operate the unit without a filter.
Inspect filters at least monthly and replace or clean as
required. Washable filters may be cleaned by soaking in
mild detergent and rinsing with cold water. Replace filters
with the arrows on the side pointing in the direction of air
flow. Dirty filters are the most common cause of inadequate
heating or cooling performance, and of compressor
failures.
HEATING SEASON CHECKS (MONTHLY)
Main Burner Flame
Flames should be stable and solid blue, (dust may cause
orange tips or they may have wisps of yellow, but they
MUST not have solid yellow tips). They should extend
directly into the heat exchanger tubes and the turbulators
should glow orange (after about five minutes of operation).
Main burner flame should be inspected monthly.
Using a light and mirror (as required) inspect the inside of
the vent hood and the inlet air opening in the burner
compartment. Look for soot and severe rust or corrosion
and any obstructions due to leaves, spiderwebs, etc. Clean
as required.
COOLING SEASON CHECKS (MONTHLY)
Condenser Coil
Keep the condenser inlet and outlet area clean and free of
leaves, grass clippings or other debris. Grass should be
kept short in front of the condenser inlet. Shrubbery MUST
be trimmed back so it is no closer than 30 inches to unit.
Condensate Drain
Check for condensate drainage. Clean as required.
ANNUAL MAINTENANCE AND INSPECTION
ELECTRICAL SHOCK HAZARD.
Failure to follow this warning could result in personal
injury, death and/or property damage.
Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.
The annual inspection should include cleaning as required
to ensure efficient operation of the unit. To simplify access,
remove all access panels and the top from the unit if
possible.
Condenser Fan Motor
Note: The condenser fan motor is permanently lubricated.
No further lubrication is required. Do not attempt to
lubricate the condenser fan motor.
VENT ASSEMBLY
BURN HAZARD.
Failure to follow this caution may result in personal
injury or property damage.
Flue cover may be hot! Allow adequate time for flue
cover to cool.
Clean the surrounding area and the condenser and
evaporator coils. Use caution to avoid damage to coil fins.
BLOWER MOTOR ACCESS
Refer to Figure 18 for a view of blower motor and
compartment.
1. Remove the blower access panel
2. Remove the three screws securing the blower motor
housing. If unit has a support bracket, remove the two
screws securing the bracket.
3. Remove the two red wires attached to the limit switch
and remove the limit switch.
Motor removal and replacement
This method is required to replace or repair blower wheel,
blower housing, or any unreachable components behind
blower assembly.
1. Remove all screws around rim of unit top, (except
screws which are inaccessible because of proximity to
structure).
2. Raise unit top at corner of unit closest to blower at least
2" and place a sturdy brace at least 2" thick between top
and unit corner. A 2X4 piece of wood is ideal for this.
3. Disconnect all wires from housing and slide housing out
of unit. Reverse this process to reinstall.
Circulating Air Blower
Visually inspect the blower wheel for accumulations of dirt
or lint. Clean the compartment and the blower wheel. If
accumulation is excessive on blower wheel, or does not
easily remove, it will be necessary to remove the blower
assembly.
Note: The blower motor is permanently lubricated. No
further lubrication is required. Do not attempt to lubricate
the blower motor.
Burners /Heat Exchangers /Flue Gas Passages
To inspect the burners, heat exchanger and interior flue gas
passages, use a light and small mirror on an extension
handle.
Check the exterior of the heat exchanger and the interior
flue gas passages for any evidence of deterioration due to
corrosion, cracking or other causes. If signs of scaling or
sooting exist, remove the burners and clean the heat
exchanger, as required.
INSPECTION AND CLEANING OF BURNER
ASSEMBLY/HEAT EXCHANGERS/FLUE GAS
PASSAGES
For Qualified Service Technician Only
See FIGURE 18 for identification of parts.
1. Disconnect electrical power to unit.
2. Turn OFF gas at manual shut off valve.
3. Remove burner access panel.
4. Remove the vent assembly flue pipe.
5. Disconnect gas pipe at union.
6. Disconnect wires from gas valve, note connections.
7. Remove screws that secure the flame shield and
remove gas control valve, manifold and burners as an
assembly.
8. Remove collector box, injector plate, and restrictor
plate, including gaskets.
9. Hold the burner assembly vertically and lightly tap it
against a wood block. Clean also with a stiff brush.
Severe cases of lint clogging may require washing the
burners in hot water.
10. Clean flue gas passages by using small brushes and a
vacuum cleaner. It may be necessary to fabricate
handle extensions for the brushes to reach the areas
that require cleaning. Reinspect after cleaning and
replace the heat exchanger if defective.
11. Reinstall parts and gaskets in reverse order. On direct
spark models check the spark gap. 1/8 inch is required
between the sparker electrodes.
12. Turn gas on and check for leaks.
13. Install all access panels, turn power on and check for
normal operation.
REFRIGERANT CIRCUIT
For Qualified Service Technician Only
Annually inspect all refrigerant tubing connections and the
unit base for oil accumulations. Detecting oil generally
indicates a refrigerant leak.
FIRE AND EXPLOSION HAZARD.
Failure to follow this warning could result in personal
injury, death and/or property damage.
System under pressure. Relieve pressure and recover
all refrigerant before system repair or final unit
disposal to avoid serious injury or death. Use all
service ports and open all flow control devices,
including solenoid valves.
If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak
detector, halide torch, or liquid-soap solution.
FiGURE18 1 Component Locations
.....'-- [ Secondary Limit Switch I
................I Primary Limit Switch I
I Burners ]
,.."-I Rollout Switch I
..... Flame Sensor I
<//{
Secondary Limit Switch I
4 & 5 Ton Models I
Secondary Limit Switch l
2 to 3-1/2 Ton Models 1
...... J J ':' 2;
I
/IlFMandSpeed ISelector Leads
..........I PrimarYswitchLimit I
Gas Valve I
L!ZJ
I; R GG NG INSTRUCTIONS __
fAiLURETOfOLLOW .STRUC-r O S
,/_ WAR\ NO CAN RESULT IN PROPERTY DAMAGE,
ALL PANELS MUST BE IN PLACE WHEN RIGGING AND
HOOK RIGGING SHACKLES THROUGH HOLES IN BASE
USE SPREADER BARS, WHEN RIGGING, TO PREVENT
BE SURE RIGGING AND SHACKLES ARE SUFFICIENT TO
_SPREADER BARS
LENGTH_ WIDTH
CABINET
SMALL
LARGE
MAX.
IN
52.00
75.00
LENGTH MAX.
MM IN
1219 48.00
1854 48.00
WIDTH
MM
1219
1219
LIFTING.
RAIL, AS SHOWN IN DETAIL-A.
UNIT DAMAGE.
HANDLE WEIGHT LISTED BELOW.
DETAIL-A
_OR _
MAX.
IN
58,00
58.00
HEIGHT
MM
965
965
MAX. WEIGHT
LB KG
500 227
900 409
C:
Ill
_D
tQ
f-
0
m.
o
:3
:D
t_
3 to 3-1/2 Ton Wiring Diagram
F
/--W
G
Y
'R
i
i (} _O £ 0
.......... 0", ()i £ i i )
...........................................<)W,OiX (ii! [ CIOI
_, i iS[ ('i i,(}i JiLl
[I [[!ii:i (}iiCi}'!
....................... i0'!I) Silii18
i)
v i {)i T
(
0
i
3 to 3-1/2 Ton Wiring Diagram
O ..............
O
O .......
(IXI4J 17¸ )
,I
;:_! ;7:
is l !
/¸ i ! _
Jl
[
II
\.1]
'I
....
_0
qs d ¸
< 07,!
i{;7
S i!
<_ <D <L¸¸
!i_iiiiii!i;,<!_<
i i01117i_ii:<i
i"i"_ •.... _<_' _<_,,
)il) ;;)ill
....d
;)
{777
t2
i
<
2
).......
<
L.............................................................................. _
._<7;................... ..................................................................................................................................................................................................................................................................................................'.........................................................................................................................
201
4 to 5 Ton Wiring Diagram
i
!i_ I
................... ;L ..........
iSEEECONOMIZER
_ _ ACCESSORY
_STALLATION
'i:_i:ii° _°
PROPERWN_ ;
: C
....................................................................................
.......................... ...................................................... I;i _ii i
©
-o &
(>-
4 to 5 Ton Wirina Diaaram
.....
) O' T ![[0 _ v _
± s I_ I :
©
(},
(-
Q?£L
.1
0
[]
(}fv" _ "<"< Y Y _"0 ' "'"'"--
(3 /----(}S_'X-- .__ _____(" )_
i0)
3
- f_ .
ut ];
003i ., O

Navigation menu