ICP Package Units(both Units Combined) Manual L0909100
User Manual: ICP ICP Package Units(both units combined) Manual ICP Package Units(both units combined) Owner's Manual, ICP Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 37
Download | |
Open PDF In Browser | View PDF |
Installation Instructions PGD3 / PGS3 /WPG3 PACKAGED Series GAS/ELECTRIC International ComfortProducts,LLC Lewisburg, TN.37091 UNIT 509 01 3402 01 04-09-09 TABLE OF CONTENTS PAGE 1 2 2-13 2 2 2 2 2 2 2 6 6 6 6 9 9 9 10 SAFETY CONSIDERATIONS ............................ INTRODUCTION ....................................... RECEIVING AND INSTALLATION ..................... Check Equipment ..................................... Identify Unit ........................................ Inspect Shipment ................................... Provide Unit Support .................................. Roof Curb ......................................... Slab Mount ........................................ Field Fabricate Ductwork .............................. Provide Clearances ................................... Rig and Place Unit .................................... Inspection ......................................... Rigging/Lifting ...................................... Connect Condensate Drain ............................ Install Flue Hood ..................................... Install Gas Piping ..................................... Install Duct Connections .............................. Configuring Units for Downflow (Vertical) Discharge ........................................ 10 Install Electrical Connections .......................... 10 High-Voltage Connections .......................... 12 Special Procedures for 208-V Operation .............. 12 Control Voltage Connections ........................ 12 Standard Connection ............................... 12 Heat Anticipator Setting ............................. 13 Transformer Protection ............................. 13 PRE-START-UP ...................................... 13 START-UP ....................................... 13-20 Check for Refrigerant Leaks ........................... 13 Start-Up Heating & Make Adjustments .................. 14 Check Heating Control ............................. 14 Check Gas Input ................................... 14 Adjust Gas Input ................................... 15 Check Burner Flame ............................... 15 Normal Operation .................................. 19 Airflow and Temperature Rise ........................ 19 Heating Sequence of Operation ...................... 19 Limit Switches ..................................... 19 Rollout Switch ..................................... 19 Start-Up Cooling & Make Adjustments .................. 19 Checking Cooling Control Operation .................. 19 Checking & Adjusting Refrigerant Charge ............. 19 Indoor Airflow and Airflow Adjustments ................ 20 Continuous Fan Operation .......................... 20 Cooling Sequence of Operation ...................... 20 MAINTENANCE ................................... 28-30 Air Filter .......................................... 28 Indoor Blower and Motor ............................ 28 Induced Draft (Combustion Air) Blower ................ 29 Flue Gas Passageways ............................ 29 Limit Switch ....................................... 29 Burner Ignition ..................................... 29 Main Burners ...................................... 29 Removal of Gas Train .............................. 29 Outdoor Coil, Indoor Coil, & Condensate Drain Pan ..... 29 Outdoor Fan ...................................... 30 Electrical Controls and Wiring ........................ 31 Refrigerant Circuit .................................. 31 Gas Input ......................................... 31 Evaporator Airflow ................................. 31 R-410A Items ..................................... 32 TROUBLESHOOTING ................................. 32 START-UP CHECKLIST ............................... 32 1 NOTE: Read the entire instruction manual before starting the installation. NOTE: Installer: Make sure the Owner's Manual and Service Instructions are left with the unit after installation. Fig. 1 - Unit PGD3/PGS3/WPG3 SAFETY (Low NOx models available) CONSIDERATIONS Improper installation, adjustment, alteration, service maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70. In Canada refer to the current editions of the National Standards of Canada CAN/CSA-B149.1 and .2 Natural Gas and Propane Installation codes, and Canadian Electrical Code CSA O22.1 Recognize safety information. This is the safety-alert symbol/_ When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. ELECTRICALSHOCKHAZARD Failure to follow this warning could result in personal injury or death. Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable. 509 01 3402 01 FIRE, EXPLOSION, ELECTRICAL MONOXIDE POISONING HAZARD SHOCK AND CARBON For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate if required. Roof Curb CUT HAZARD Install accessory roof curb in accordance with instructions shipped with curb (See Fig. 5). Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb. IMPORTANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb. Improperly applied gasketing also can result in air leaks and poor unit performance. Curb should be level to within 1/4 in. (6 mm). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required. Failure to follow this caution may result in personal injury. Slab Mount When removing access panels or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit. Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102 mm) thick with 2 in. (51 mm) above grade. The slab should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit. (See Fig. 2.) Do not secure the unit to the slab except when required by local codes. Failure to follow this warning could result in personal injury or unit damage. A qualified installer or agency must use only factory-authorized kits or accessories when modifying this product. INTRODUCTION Fig. 2 - Slab Mounting Details The PGD3/PGS3/WPG3 units (see Fig. 1) are a fully self-contained, combination Category I gas heating/electric cooling unit designed for outdoor installation (See Fig. 3 and 4 for unit dimensions). All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered. Units may be installed either on a rooftop or on a cement slab. (See Fig. 5 for roof curb dimensions). Models with the number "1" in the 13th position of the model number are dedicated Low NOx units designed for California installations. These models meet the California maximum oxides of nitrogen (NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory and must be installed in California Air Quality Management Districts or any other regions in North America where a Low NOx rule exists. NOTE: Low installations. NOx requirements RECEIVING Step 1 m Check AND apply only to natural gas INSTALLATION Equipment Identify Unit The unit model number and serial number are stamped on the unit information plate. Check this information against shipping papers. Inspect Shipment Inspect for shipping damage before removing packaging materials. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation. Step 2 m Provide in 2" I I Illll Illll lT dJJJ.[J (50.8mm) l ±,, L Step 3 _ EVAR COIL COND. COIL Field Fabricate Ductwork Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned insulated and covered with a vapor barrier. space must be If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. Read unit rating plate for any required clearances around ductwork. Cabinet return-air static shall not exceed -.25 IN. W.C. Unit Support IMPORTANT: The unit must be secured to the curb by installing screws through the bottom of the curb flange and into the unit base rails. When installing large base units onto the common curb, the screws must be installed before allowing the full weight of the unit to rest on the curb. A minimum of six screws are required for large base units. Failure to secure unit properly could result in an unstable unit. See Warning near Rigging/Lifting information and accessory curb instructions for more details. 509 01 3402 01 2 Fig. 3 - PGD3/PGS3/WPG324-36 Unit Dimensions © © • I I_1_1_1_ ............. __o I_1__1__1©1_ ==1 I_,l&l-°l-= !!!!! :: ...... =1 I-_1-_1-_1_ _- :: _z_ :.....: : : : _ _ _ z ..... o ...... ...... _1 I£1_1_1£ ::: E .= _ T --i -=_ _ z " _i E co i © o < m _ t . o ? r_ o_ _z _x 3 509 01 3402 01 Fig. 4 - PGD3/PGS3/WPG342-60 Unit Dimensions ,© o I t c_J ° ° Lr) CO © __ 509 01 3402 01 4 Fig. 5 - Roof Curb Dimensions Dashed Lines show cross suppori location for barge basepan units. COMMON CURB A09096 ROOF CURB DETAIL SMALL BASE UNiT F LARGE BASE UNIT UNIT PLACEMENT ON COMMON CURB A09094 / LARGE CURB UNIT SIZE Small or Large CATALOG NUMBER A IN. (mm) CPRFCURB010A00 11 (279) CPRFCURB011A00 14 (356) CPRFCURB012A00 Large SMALL OR LARGE BASE UNIT A09095 B (small base) IN. (mm)* C IN. (mm) D IN. (mm) 14 (356) 16 (406) 47.8 (1214) 10 (254) 11 (279) CPRFCURB013A00 B (large base) IN. (mm)* N/A 14 (356) * Part Numbers CPRFCURB010A00 and CPRFCURB011A00 unit is a small basepan or a large basepan. NOTES: E IN. (mm) F IN. (mm) 32.4 (822) 2.7 (69) 43.9 (1116) can be used on both small and large basepan units. The cross supports must be located based on whether the 1. Roof curb must be set up for unit being installed. 2. Seal strip must be applied, as required, to unit being installed. 3. Roof curb is made of 16-gauge steel. 4. Attach ductwork to curb (flanges of duct rest on curb). 5. Insulated panels: 1-in. 5 (25.4 mm) thick fiberglass 1 Ib. density. 509 01 3402 01 Step 4 m Provide Clearances The required minimum operating and service clearances are shown in Fig. 3 and 4. Adequate combustion, ventilation and condenser air must be provided. IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor-air inlet or the fan discharge may be detrimental to compressor life. The condenser fan pulls air through the condenser coil and discharges it through the top grille. Be sure that the fan discharge does not recirculate to the condenser coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48-in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48-in. (1219 mm). Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab-mounted units should be at least 4 in. (102 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water. Step 5 m Rig and Place Unit Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.). Only trained, qualified crane operators and ground support staff should handle and install this equipment. When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply. Training for operators of the lifting equipment should include, but not be limited to, the following: Follow atl applicable safety codes. Wear safety shoes and work gloves. 1. Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads. 2. Instruction in any special operation or precaution. 3. Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc. Inspection Prior to initial use, and at monthly intervals, atl rigging shackles, clevis pins, and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Materials showing any kind of wear in these areas must not be used and should be discarded. UNIT FALLING HAZARD Failure to follow this warning could result in personal injury or death. Never stand beneath rigged units or lift over people. PROPERTY DAMAGE HAZARD Failure to follow this warning injury/death or property damage. could result in personal When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above the unit top cover. Rigging/Lifting of Unit (See Fig. 6) UNIT FALLING HAZARD Failure to follow this warning could result in personal injury or death. Large base units must be secured to common curb before allowing full weight of unit to rest on curb. Install screws through curb into unit base rails while rigging crane is still supporting unit. Lifting holes are provided in base rails as shown in Fig. 3 and 4. 1. Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging the unit. If the skid is not available, use a spreader bar of sufficient length to protect the unit from damage. 2. Attach shackles, clevis pins, and straps to the base rails of the unit. Be sure materials are rated to hold the weight of the unit. (See Fig. 6). 3. Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground. After the unit is placed on the roof curb or mounting pad, remove the top skid. 509 01 3402 01 d Fig. 6 - PGD3/PGS3/WPG3 Unit Suggested Rigging 50CY502286 SMALL CABINET 24 30 Unit * Rigging Weight 36 Unit * Ib kg Ib kg Ib kg 311 141 316 143 326 148 Rigging Weight 2,0 LARGE CABINET 42 48 Ib 420 kg 191 Ib 428 60 kg 194 Ib 450 kg 204 * For 460 volt units add 14 Ib (6.35 kg) to the rigging weight. NOTE: See dimensional drawing for corner weights. ? 509 01 3402 01 Table 1 - Physical Data - Unit PGD3/PGS3/WPG3 UNIT SIZE NOMINAL SHIPPING SHIPPING CAPACITY WEIGHT** WEIGHT** (ton) lb. (kg) 24040 24060 2 2 311 141 311 141 30040 30060 36060 36090 42060 42090 2-1/2 2-1/2 3 3 3-1/2 3-1/2 316 143 316 143 326 148 326 148 420 191 420 191 6.4 2.9 6.4 2.9 6.1 2.7 6.1 2.7 Scroll COMPRESSORS Quantity REFRIGERANT Quantity lb. Quantity (kg) REFRIGERANT 1 (R-410A) 4.8 2.2 METERING (Cfm) Propane Gas HIGH-PRESSURE SWITCH (psig) Cut-out Reset (Auto) LOSS-OF-CHARGE / LOW-PRESSURE SWITCH (Liquid Line) (psig) cut-out Reset (auto) RETURN-AIR FILTERSt$ Throwaway Size in. (mm) 1..21 10.2 1...21 10.2 1...21 11.9 1...21 11.9 1...21 15.4 1...21 15.4 1...21 13.6 1...21 13.6 2800 24 609.6 1/5 (810) 2800 24 609.6 1/5 (810) 3000 24 609.6 1/5 (810) 3000 24 609.6 1/5 (810) 3200 24 609.6 1/5 (810) 3200 24 609.6 1/5 (810) 3600 26 660.4 1/5 (810 3600 26 660.4 1/5 (810) 2...17 3.7 2...17 3.7 3...17 3.7 3...17 3.7 3...17 3.7 3...17 3.7 3...17 4.7 3...17 4.7 800 10x10 254x254 1/2 (1050) 800 10x10 254x254 1/2 (1050) 1000 10x10 254x254 1/2 (1050) 1000 10x10 254x254 1/2 (1050) 1200 1 lx10 279,4x254 3/4 (1000) 1200 1 lx10 279,4x254 3/4 (1000) 1400 1lx10 279,4x254 3/4 (1075) 1400 1 lx10 279,4x254 3/4 (1075) 2.. ,44 2...55 2.. ,38 2...53 2.. ,44 2...55 2.. ,38 2...53 2.. ,38 2...53 3...38 3...53 2.. ,38 2...53 3...38 3...53 650 ,._- 15 420 ,. _- 25 20 -.__ 5 45 ,._- 10 20x20x1 508x508x25 Table llphysical UNIT SIZE CAPACITY WEIGHT** WEIGHT** 6.2 2.8 TXV Burner Orifice No. (Qty...Drill Size) Natural Gas NOMINAL SHIPPING SHIPPING 6.2 2.8 DEVICE OUTDOOR COIL Rows...Fins/in. Face Area (sq ft) OUTDOOR FAN Nominal CFM Diameter in. Diameter (mm) Motor Hp (Rpm) INDOOR COIL Rows...Fins/in. Face Area (sq ft) INDOOR BLOWER Nominal Cooling Airflow Size in. Size (mm.) Motor HP (RPM) FURNACE SECTION* 4.8 2.2 (ton) Ib kg 20x24x1 508x610x25 24x30x1 610x762x25 Data Con't - Unit PGD3/PGS3/WPG3 48090 48115 48130 60090 60115 4 4 4 5 5 5 428 194 428 194 428 194 450 204 450 204 450 204 10,0 4.5 10,0 4.5 10,0 4.5 Scroll 1 COMPRESSORS Quantity REFRIGERANT (R-410A) Quantity Ib Quantity (kg,) REFRIGERANT METERING 6.4 2.9 1...21 15.5 1...21 15.5 1...21 15.5 2...21 15.5 2...21 15.5 2...21 15.5 4000 26 660.4 1/5 (810) 4000 26 660.4 1/5 (810) 4000 26 660.4 1/5 (810) 3200 26 660.4 1/5 (810) 3200 26 660.4 1/5 (810) 3200 26 660.4 1/5 (810) 3...17 4.7 3...17 4.7 3...17 4.7 3...17 5.7 3...17 5.7 3...17 5.7 1600 11x10 279.4x254 1600 11x10 279.4x254 1600 11x10 279.4x254 1750 11x10 279.4x254 1750 11x10 279.4x254 1.0 (1075) 1.0 (1075) 1.0 (1075) 1.0 (1040) 1.0 (1040) 1750 11x10 279.4x254 1.0 (1040) 3...38 3...53 3...33 3...51 3...31 3...49 3...38 3...53 3...33 3...51 3...31 3...49 SWITCH (psig) Cut-out Reset (Auto) LOSS-OF-CHARGE / LOW-PRESSURE SWITCH (Liquid Line) (psig) cut-out Reset (auto) FILTERS 6.4 2.9 TXV OUTDOOR FAN Nominal Cfm Diameter in. Diameter (mm) Motor Hp (Rpm) INDOOR COIL Rows...Fins/in. Face Area (sq ft) INDOOR BLOWER Nominal Cooling Airflow (Cfm) Size in. Size (mm) Motor HP (RPM) FURNACE SECTION* Burner Orifice No. (Qty._Drill Size) Natural Gas Propane Gas HIGH-PRESSURE 6.4 2.9 DEVICE OUTDOOR COIL Rows...Fins/in. Face Area (sq ft) RETURN-AIR (mm) 60130 Throwawayt$ in. 650 +/- 15 420 +/- 25 20 +/- 5 45 +/- 10 24x36x1 610x914x25 *Based on altitude of 0 to 2000 ft (0-610 m). 1- Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type. Air filter pressure drop for non-standard filters must not exceed 0.08 IN. W.C. $ If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity. ** For 460 volt units, add 14 Ibs (6.35 kg) to the shipping weight. 509 01 3402 01 8 Step 6 m Connect Condensate Drain Step 8 _ NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions. Unit disposes of condensate water through a 3/4 in. NPT fitting which exits through the base on the evaporator coil access side. See Fig. 3 & 4 for location. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied 2-in. (51 mm) condensate trap at the end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the drain-pan condensate connection to prevent the pan from overflowing (See Fig. 7). Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit. Connect a drain tube using a minimum of 3/4-in. PVC or 3/4-in. copper pipe (all field-supplied) at the outlet end of the 2-in. (51 mm) trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1-in. (25 mm) for every 10 ft (3.1 m) of horizontal run. Be sure to check the drain tube for leaks. Fig. 7 - Condensate Trap TRAP t-in. (25 ram) rain. OUTLET ram) rain. Step 7 m Install Flue Hood The flue assembly is secured and shipped in the return air duct. Remove duct cover to locate the assembly (See Fig. 9). NOTE: Dedicated low NOx models MUST be installed in California Air Quality Management Districts where a Low NOx rule exists. These models meet the California maximum oxides of nitrogen (NOx) emissions requirements of 40 nanograms/joule or less as shipped from the factory. NOTE: Low NOx requirements apply only to natural gas installations. CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death. The venting system is designed to ensure proper venting. The flue hood assembly must be installed as indicted in this section of the unit installation instructions. Install the flue hood as follows: 1. This installation must conform with local building codes and with NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC), (in Canada, CAN/CGA B149.1, and B149.2) latest revision. Refer to Provincial and local plumbing or wastewater codes and other applicable local codes. Install Gas Piping The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/2-in. (12.7 mm) FPT gas inlet on the gas valve. Install a gas supply line that runs to the heating section. Refer to the NFGC for gas pipe sizing. Do not use cast-iron pipe. It is recommended that a black iron pipe is used. Check the local utility for recommendations concerning existing lines. Size gas supply piping for 0.5 in. wc maximum pressure drop. Never use pipe smaller than the 1/2-in. (12.7 mm) FPT gas inlet on the unit gas valve. For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wc or greater than 13 in. wc while the unit is operating. For propane applications, the gas pressure must not be less than 11.0 in. wc or greater than 13 in. wc at the unit connection. A 1/8-in. (3.2 mm) NPT plugged tapping, accessible for test gauge connection, must be installed immediately upstream of the gas supply connection to the gas valve. When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 latest edition (in Canada, CAN/CGA B149.1). NOTE: In the state of Massachusetts: 1. Gas supply connections MUST be performed by a licensed plumber or gas fitter. 2. When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm). 3. When lever handle type manual equipment shutoff valves are used, they shall be T-handle valves. 4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts. In the absence of local building codes, adhere to the following pertinent recommendations: 1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. (6.35 mm) for every 15 ft (4.6 m) of length to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter. 2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 ft (1.8 m). For pipe sizes larger than 1/2 in., follow recommendations of national codes. 3. Apply joint compound (pipe dope) male threads of joint when making only pipe dope that is resistant petroleum gases as specified by codes. Never use Teflon tape. sparingly and only to pipe connections. Use to action of liquefied local and/or national 4. Install sediment trap in riser leading to heating section (See Fig. 8). This drip leg functions as a trap for dirt and condensate. 5. Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft (1.8 m) of heating section. 6. Install ground-joint union close to heating section between unit manual shutoff and external manual main shut-off valve. 7. Pressure test all gas piping in accordance with local and national plumbing and gas codes before connecting piping to unit. 2. Remove flue hood from shipping location (inside the return section of the blower compartment-see Fig. 9 & 10). Remove the return duct cover to locate the flue hood. Place flue hood assembly over flue panel. Orient screw holes in flue hood with holes in the flue panel. 3. Secure flue hood to flue panel by inserting a single screw on the top flange and the bottom flange of the hood. 509 01 3402 01 Table 2 - Maximum NOMINAL IRONPIPE SIZE (IN,) INTERNAL DIAMETER (IN,) 10 (3) 20 (6) 30 (9) 40 (12) 1/2 3/4 .622 .824 175 360 120 250 97 200 Gas Flow Capacity* 50 (15) LENGTHOF PIPE FT (m)f 60 70 80 90 (18) (21) (24) (27) 100 (30) 125 (38) 150 (46) 175 (53) 200 (61) 82 170 73 151 66 138 61 125 57 118 53 110 50 103 44 93 40 84 -77 -72 1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 1-1/4 1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280 1-1/2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430 *Capacity of pipe in cuft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of O.5-in. wc (based on a 0.60 specific gravity gas). Refer to Table, National Fire Protection Association NFPA 54. This length includes an ordinary number of fittings. Step 9 m Install Fig. 8 - Sediment Trap Duct Connections The unit has duct flanges on the supplyand return-air openings on the side and bottom of the unit. For downshot applications, the ductwork connects to the roof curb (See Fig. 3 and 4 for connection sizes and locations). IN Configuring Units for Downflow (Vertical) Discharge TEE ELECTRICAL NIPPLE CAP NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union. FIRE OR EXPLOSION HAZARD SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. 1. Open all electrical disconnects before starting any service work. 2. Remove horizontal (metal) duct covers to access vertical (downflow) discharge duct knockouts in unit basepan. 3. Starting in a corner as shown in Fig. 10, score the panel in both directions from the corner. Tap the panel out from the scored corner using a small hammer. Be careful and not damage any other part of the unit. 4. If unit ductwork is to be attached to vertical opening flanges on the unit base (jackstand applications only), do so at this time. Failure to follow this warning could result in personal injury, death and/or property damage. -Connect gas pipe to unit using a backup wrench to avoid damaging gas controls. -Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. -Use proper length of pipe to avoid stress on gas control manifold. -If a flexible connector is authority having jurisdiction, installed at furnace gas valve 2 in. (51 mm) outside furnace required or allowed by black iron pipe shall be and extend a minimum of casing. -If codes allow a flexible connector, always use a new connector, do not use a connector which has previously serviced another gas appliance. 8. Check for gas leaks at the field-installed and factory-installed gas lines after all piping connections have been completed. Use a commercially available soap solution (or method specified by local codes and/or regulations). 509 01 3402 01 PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage. Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur. 5. It is recommended that the base insulation around the perimeter of the vertical return-air opening be secured to the base with aluminum tape. Applicable local codes may require aluminum tape to prevent exposed fiberglass. 6. Reinstall both horizontal air- and watertight. duct covers. Ensure opening is 7. After completing unit conversion, perform all safety checks and power up unit. NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or local codes and ordinances. 10 4. All units must have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1. Fig. 9 - Supply and Return Duct Opening 5. Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected. 6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure. 7. Flash, weatherproof, and vibration isolate all openings in building structure in accordance with local codes and good building practices. Horizontal Duct Covers Step 10 m Install Basepan Downflow Electrical Connections ELECTRICALSHOCKHAZARD (Vertical) Basepan Downflow Supply _ Knockout J (Vertical) Return Knockout Failure to follow this warning could result in personal injury or death. The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NFPA 70 (NEC) (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes. Fig. 10- Vertical (Downflow) Discharge Duct Knockouts i ..... UNIT COMPONENT p .................. INSTRUCTIONS FOR REMOVING DOWNSHOT 1 Score groove in corner 1 in both directions as far 2 Starting in corner 1 tap out atl sides with a smatl not to damage any other part of unit 3. If side from corner 3 to 4 is not accessible due to pivot panel up and down by hand until remaining Failure to follow this caution may result in damage to the unit being installed. 1. Make atl electrical connections in accordance withh NFPA 70 (NEC) (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram. 2. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE. PANELS as you can reach hammer, Be careful heat exchanger. side breaks off A09054 Adhere to the following criteria when selecting, sizing, and installing the duct system: 1. Units are shipped for horizontal duct installation (by removing duct covers). 2. Select and size ductwork, supply-air registers, and return-air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations. 3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure weather-tight and airtight seat. 11 DAMAGE HAZARD 3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance. 4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are in same conduit as high-voltage wires. 5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. 509 01 3402 01 High-Voltage Connections Control When routing power leads into unit, use only copper wire between disconnect and unit. The high voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight. The unit must have a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used (See Fig. 3 and 4 for acceptable location). See unit wiring label (Fig. 15, 16 and 17) and Fig. 11 for reference when making high voltage connections. Proceed as follows to complete the high-voltage connections to the unit. Single phase units: 1. Run the high-voltage (L1, L2) and ground lead into the control box. 2. Connect ground lead to chassis ground connection. 3. Locate the black and yellow wires connected to the line side of the contactor (if equipped). 4. Connect field L1 to black wire on connection 11 of the compressor contactor. 5. Connect field wire L2 to yellow wire on connection the compressor contactor. Three-phase units: 1. Run the high-voltage control box. 23 of Voltage Connections Do not use any type of power-stealing problems may result. 2. Connect ground lead to chassis ground connection. Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box. Locate six (seven for 3-phase) 18-gage wires leaving control box. These low-voltage connection leads can be identified by the colors red, green, yellow, brown, blue, and white (See Fig. 11). A gray wire is standard on 3-phase units for connection to an economizer. Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Route leads through hole in bottom of control box and make low-voltage connections (See Fig. 11). Secure all cut wires, so that they do not interfere with operation of unit. Fig. 11 - High- and Control-Voltage Connections l HIGH VOLTAGE POWER LEADS _c= (SEE UNIT WIRtNG 1 LABEL) _:_ 1-PHASE USES TWO POWER LEADS CONTROL = = SHOWN L_ EQUIP GR FIELD-SUPPLiED FUSED DISCONNECT BOX 3. Locate the black and yellow wires connected to the line side of the contactor (if equipped). 4. Connect field L1 to black wire on connection 11 of the o= dHTLVV--1 )'D=@ =Y&LLYL _= Q o= compressor contactor. 5. Connect field wire L3 to yellow wire on connection the compressor contactor. 6. Connect field wire L2 to blue wire from compressor. Special Procedures 13 of LOW-VO LTAG E POWER LEADS (SEE UNIT WIRING LABEL) @ o= o =. o= for 208-v Operation BR_C.Z.p. BLU.(.D H),p._-Ph_e Dnly SPLICE BOX Heat Anticipator Setting (Electro-Mechanical ELECTRICAL Make sure the power supply to the unit is switched OFF and install lockout tag. before making any wiring changes. With disconnect switch open, move black wire from transformer (3/16 in. [4.8 mm]) terminal marked 230 to terminal marked 208. This retaps transformer to primary voltage of 208 vac. SHOCK FIRE/EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death and property damage. Before making any wiring changes, make sure the gas supply is switched off first. Then switch off the power supply to the unit and install lockout tag. 509 01 3402 01 Thermostats on__eLv3 SHOCK HAZARD Failure to follow this warning could result in personal injury or death. ELECTRICAL Unit control Use no. 18 American Wire Gage (AWG) color-coded, insulated (35°C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35°C minimum) wires. Standard Connection 3-PHASE (L1, L2, L3) and ground lead into the thermostat. The room thermostat heat anticipator must be properly adjusted to ensure proper heating performance. Set the heat anticipator, using an ammeter between the W and R terminals to determine the exact required setting. NOTE: For thermostat selection purposes, use 0.18 amp for the approximate required setting. Failure to make a proper heat anticipator adjustment will result in improper operation, discomfort to the occupants of the conditioned space, and inefficient energy utilization; however, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation. Transformer Protection The transformer is of the energy-limiting type, however short will likely blow a secondary fuse. If an overload or present, correct overload condition and check for blown Indoor Fan board or Integrated Gas Controller. Replace required with correct size and rating. a direct short is fuse on fuse as 12 PRE-START-UP FIRE, EXPLOSION ENVIRONMENTAL, SHOCK HAZARD FIRE, EXPLOSION, ELECTRICAL Failure to follow this warning could result in personal injury or death. 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor plug is in place and secured. 3. Do not remove ccompressor plug until all electrical sources are disconnected and tagged. 4. Relieve and recover all refrigerant from system before touching or disturbing compressor plug if refrigerant leak is suspected around compressor terminals. 5. Never attempt to repair soldered connection while refrigerant system is under pressure. 6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows: a. Shut off electrical power to unit and install lockout tag. b. Relieve and reclaim all refrigerant from system using both high- and low-pressure ports. c. Cut component connecting tubing with tubing cutter and remove component from unit. d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame. Use the Start-Up Checklist supplied at the end of this book and proceed as follows to inspect and prepare the unit for initial start-up: 1. Remove access panels. 2. Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with unit. 3. Make the following inspections: a. Inspect for shipping and handling damage, such as broken lines, loose parts, disconnected wires, etc. b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. c. Leak-test all refrigerant tubing connections using electronic leak detector, or liquid-soap solution. If a refrigerant leak is detected, see following Check for Refrigerant Leaks section. d. Inspect all field- and factory-wiring connections. sure that connections are completed and tight. Be e. Ensure wires do not touch refrigerant tubing or sharp sheet metal edges. f. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb. 13 HAZARD Failure to follow this warning could result in personal injury, death or property damage. Do not purge gas not use a match or Use a commercially for the detection of supply into the combustion chamber. Do other open flame to check for gas leaks. available soap solution made specifically leaks to check all connections. 4. Verify the following conditions: a. Make sure gas line is free of air. Before lighting the unit for the first time, perform the following with the gas valve in the OFF position: NOTE: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the ground joint union be loosened, and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines into a combustion chamber. Immediately upon detection of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit. b. Ensure fan hub is positioned correctly with respect to motor housing. c. Make sure that air filter(s) is in place. d. Make sure that condensate drain trap is filled with water to ensure proper drainage. e. Make sure that all tools and miscellaneous loose parts have been removed. START-UP Step 1 m Check for Refrigerant Leaks Proceed as follows to locate and repair a refrigerant leak and to charge the unit: 1. Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both highand low-pressure ports. 2. Repair leak following accepted practices. NOTE: Install a filter drier whenever the system has been opened for repair. 3. Add a small charge of R-410A refrigerant vapor to system and leak-test unit. 4. Recover refrigerant from refrigerant system and evacuate to 500 microns if no additional leaks are found. 5. Charge unit with R-410A refrigerant, using an accurate scale. Refer to unit rating plate for required charge. Step 2 m Start-up Heating and Make Adjustments Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Make sure that burner orifices are properly aligned. Unstable operation my occur when the burner orifices in the manifold are misaligned. Follow the lighting instructions on the heating section operation label (located on the inside of the control access panel) to start the heating section. NOTE: Make sure that gas supply has been purged, and that all gas piping has been checked for leaks. 509 01 3402 01 0.60 specific gravity, or propane gas with a heating value of Fig. 12 - Burner Assembly 2500 Btu/ft 3 at 1.5 specific gravity. IN THE U.S.A.: The input rating for altitudes above 2,000 ft (610 m) must be reduced by 4% for each 1,000 ft (305 m) above see level. For installations below 2,000 ft (610 m), refer to the unit rating plate. For installations above 2,000 ft (610 m). multiply the input by on the rating plate by the derate multiplier in Table 3 for correct input rate. Table 3 - Altitude Derate Multiplier for U.S.A.* DERATEMULTIPLIER "Manifold Fig. 13 - Monoport Burner BURNER FLAME BURNER MANIFOLD ALTITUDEFT (M) PERCENTOF DERATE FACTOR1" 0-2000 (0-610) 0 1.00 2001-3000* (610-914) 8-12 0.90 3001-4000 (915-1219) 12-16 0.86 4001-5000 (1220-1524) 16-20 0.82 5001-6000 (1524-1829) 20-24 0.78 6001-7000 (1829-2134) 24-28 0.74 7001-8000 (2134-2438) 28-32 0.70 8001-9000 (2439-2743) 32-36 0.66 36-40 0.62 9001-10,000 (2744-3048) *In Canada 1-Derate range. Check Heatinq Control Start and check the unit for proper heating control operation as follows (see furnace lighting instructions located on the inside of the control access panel): 1. Place room thermostat SYSTEM switch in the HEAT position and the fan switch is placed in AUTO position. 2. Set the heating temperature control of the thermostat above room temperature. 3. The induced-draft motor will start. 4. On a call for heating, the main burner should light within 5 sec. of the spark being energized. If the burners do not light, there is a 22-sec. delay before another 5-sec. try. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break the 24-v power to W. 5. The evaporator fan will turn on 45 sec. after the flame has been established. The evaporator fan wilt turn off 45 sec. after the thermostat has been satisfied. Please note that the integrated gas unit controller (IGC) has the capability to automatically reduce the evaporator "ON" delay and increase the evaporator "OFF" delay in the event of high duct static and/or partially-clogged filter. see Canadian multiplier factors Altitude are based Adjustment. on midpoint altitude for altitude IN CANADA: The input rating for altitudes from 2,000 (610 m) to 4,500 ft (1372 m) above sea level must be derated 10% by an authorized Gas Conversion Station or Dealer. EXAMPLE: 90,000 Btu/hr Input Furnace Installed at 4300 ft. FurnaceInputRateat Sea X DerateMultiplier Level Factor 90,000 X 0.90 = FurnaceInputRateatInstallationAltitude = 81,000 When the gas supply being used has a different heating value or specific gravity, refer to national and local codes, or contact your distributor to determine the required orifice size. Check Gas Input Check gas input and manifold pressure after unit start-up (See Table 4). If adjustment is required proceed as follows: • The rated gas inputs shown in Table 4 are for altitudes from sea level to 2000 ft (610 m) above sea level. These inputs are based on natural gas with a heating value of 1025 Btu/ft 3 at 509 01 3402 01 14 Table HEATING INPUT 4 - Heating Inputs GAS SUPPLYPRESSURE(IN. W.C.) NaturallPropane*lMax Min MANIFOLDPRESSURE NUMBEROF ORIFICES Min 2 4.0 13.0 11.0 13.0 Natural13.2-3.8 60,000 2 4.0 13.0 11.0 13.0 3.2-3.8 10,0-11.0 90,000 3 4.0 13.0 11.0 13.0 3.2-3.8 10,0-11.0 115,000 130,000 3 3 4.0 4.0 13.0 13.0 11.0 11.0 13.0 13.0 3.2-3.8 3.2-3.8 10,0-11.0 (BTUH) 40,000 (IN. W.C.) Max Propane*f 10.0-1 l.O 10,0-11.0 *When a unit is converted to propane, different size orifices must be used. See separate, natural-to-propane conversion kit instructions. 1-Based on altitudes from sea level to 2000 ft (610 m) above sea level. For altitudes above 2000 ft (610 m), reduce input rating 4 percent for each additional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent. UNIT DAMAGE HAZARD Failure to follow this caution may result in reduced unit and/or component life. Do Not redrill an orifice. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise and misdirection of burner flame. If orifice hole appears damaged or it is suspected to have been redrilted, check orifice hole with a numbered drill bit of correct size. Adjust Gas Input The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The manifold pressure must be measured to determine the input of propane gas units. Measure Gas Flow (Natural Gas Units) Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be maintained between 3.2 and 3.8 IN. W.C. Fig. 14 - Single-Stage Gas Valve REGULATOR 5. Multiply result of Step 4 by the number of cubic feet (cu ft) shown for one revolution of test dial to obtain cubic feet (cu ft) of gas flow per hour. 6. Multiply result of Step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value with heating input shown in Table 4 (Consult the local gas supplier if the heating value of gas is not known). EXAMPLE: Assume that the size of test dial is 1 cu ft, one revolution takes 32 sec, and the heating value of the gas is 1050 Btu/ft 3. Proceed as follows: 1. 32 sec. to complete one revolution. 2. 3600 + 32 = 112.5. 3. 112.5 x 1 =112.5 ft 3 of gas flow/hr. 4. 112.5 x 1050 = 118,125 Btuh input. If the desired gas input is 115,000 Btuh, only a minor change in the manifold pressure is required. Observe manifold pressure and proceed as follows to adjust gas input: 1. Remove regulator cover screw over plastic screw on gas valve (See Fig. 14). adjustment 2. Turn plastic adjustment screw clockwise to increase gas input, or turn plastic adjustment screw counterclockwise to decrease input (See Fig. 14). Manifold pressure must be between 3.2 and 3.8 IN. WC. _COVERSCREW PLASTIC ADJUSTMENT SCREM/ ON/OFF FIRE AND UNIT DAMAGE HAZARD SWITCH (PROPANE - WHITE) (NATURAL- SILVER) Failure to follow this warning could result in personal injury or death and/or property damage. Unsafe operation of the unit may result if manifold pressure is outside this range. 3. Replace regulator cover screw on gas valve (See Fig. 14). 4. Turn off gas supply to unit. Remove manometer pressure tap and replace pipe plug on gas valve. Fig. 12.) Turn on gas to unit and check for leaks. from (See Measure Manifold Pressure (Propane Units) If larger adjustments are required, change main burner orifices following the recommendations of national and local codes. NOTE: All other appliances that use the same meter must be turned off when gas flow is measured at the meter. Proceed as follows: 1. Turn off gas supply to unit. 2. Remove pipe plug on manifold (See Fig. 12) and connect manometer. Turn on gas supply to unit. 3. Record number of seconds for gas meter test dial to make one revolution. 4. Divide number of seconds in Step 3 into 3600 (number of seconds in one hr). 15 Refer to propane kit installation instructions for properly checking gas input. NOTE: For installations below 2,000 ft (610 m), refer to the unit rating plate for proper propane conversion kit. For installations above 2,000 ft (610 m), contact your distributor for proper propane conversion kit. Check Burner Flame With control access panel removed, observe the unit heating operation. Watch the burner flames to see if they are light blue and soft in appearance, and that the flames are approximately the same for each burner. Propane will have blue flame (See Fig. 13). Refer to the Maintenance section for information on burner removal. 509 01 3402 01 Fig. 15 - 208/230-1-60 Wiring Diagram I Z < O < N F O z f-% < q9 z C3 > k_ c_ 0 E, ..... < _r LI 0 CO Z z 0 CP c/9 C} Z _q < _P L_ GO 0 Z Z 8 < CO CP k_ k_ "ii!ii ii!:i iilSi!;i k_ _0 z i .......... 509 01 3402 01 _o°'°llil I _._H=.= 16 Fig. 16- 208/230-3-60 Wiring Diagram ........................ _F_................... Z _D z _ L i _ _............................................... / ¢ , 4 Z C_ ,- _9 ,_ T = z S £.P ............................. ;7 o 509 01 3402 01 Fig. 17- 460-3-60 Wiring Diagram o _/JI z L_J CL_ z z z 509 01 3402 01 ;8 Normal Operation Rollout Switch An LED (light-emitting diode) indicator is provided on the integrated gas unit controller (IGC) to monitor operation. The IGC is located by removing the control access panel. During normal operation, the LED is continuously on (See Table 5 for error codes). The function of the rollout switch is to close the main gas valve in the event of flame rollout. The switch is located above the main burners. When the temperature at the rollout switch reaches the maximum allowable temperature, the control circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor (evaporator) fan motor (IFM) and induced draft motor continue to run until switch is reset. The IGC LED will display FAULT CODE 7. Airflow and Temperature Rise The heating section for each size unit is designed and approved for heating operation within the temperature-rise range stamped on the unit rating plate. Table 9 shows the approved temperature rise range for each heating input, and the air delivery cfm at various temperature rises for a given external static pressure. The heating operation airflow must produce a temperature rise that falls within the approved range. Refer to Indoor Airflow and Airflow Adjustments section to adjust heating airflow when required. Heating Sequence (See Fig. 15-17 and unit wiring label.) On a call for heating, terminal W of the thermostat is energized, starting the induced-draft motor. When the pressure switch senses that the induced-draft motor is moving sufficient combustion air, the burner sequence begins. This function is performed by the integrated gas unit controller (IGC). The indoor (evaporator)-fan motor is energized 45 sec after flame is established. When the thermostat is satisfied and W is de-energized, the burners stop firing and the indoor (evaporator) fan motor shuts off after a 45-sec time-off delay. Please note that the IGC has the capability to automatically reduce the indoor fan motor on delay and increase the indoor fan motor off delay in the event of high duct static and/or partially-clogged filter. Limit Switches Normally closed limit switch (LS) completes the control circuit. Should the leaving-air temperature rise above the maximum allowable temperature, the limit switch opens and the control circuit "breaks." Any interruption in the control circuit instantly closes the gas valve and stops gas flow to the burners and pilot. The blower motor continues to run until LS resets. When the air temperature at the limit switch drops to the low-temperature setting of the limit switch, the switch closes and completes the control circuit. The direct-spark ignition system cycles and the unit returns to normal heating operation. Table 5 - LED Indications STATUS CODE LED INDICATION Normal Operation 2 No Power or Hardware Failure Fault 2 Flashes Flame Sense Fault Four Consecutive Limit Switch 3 Flashes Faults Ignition Lockout Fault Pressure Switch Fault Rollout Internal Temporary On Off 4 Flashes 5 Flashes 6 Flashes Switch Fault 7 Flashes Control 8 Flashes Fault 1 hr auto reset I 9 Flashes Cooling and Make Adjustments Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature is below 40°F (4.4°0) (unless accessory low-ambient kit is installed). Do not rapid-cycle the compressor. Allow 5 minutes between on cycles to prevent compressor damage. Checking of Operation Limit Switch Step 3 m Start-up Cooling Control Operation Start and check the unit for proper cooling control operation as follows: 1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position. 2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evaporator fan will continue to run for 90 sec. IMPORTANT: Three-phase, scroll compressors are direction oriented. Unit must be checked to ensure proper compressor 3-phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, the difference between compressor suction and discharge pressures will be minimal. Checkinq and Adjustinq Refriqerant Charge The refrigerant system is fully charged with R-410A refrigerant and is tested and factory sealed. Allow system to operate a minimum of 15 minutes before checking or adjusting charge. NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R-410A charge. The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label is attached to the inside of the compressor access panel. The chart includes the required liquid line temperature at given discharge line pressures and outdoor ambient temperatures. An accurate thermocoupleor thermistor-type thermometer, and a gauge manifold are required when using the subcooling charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement. NOTES: 1 .This code indicates an internal processor fault that will reset itself in one hr. Fault can be caused by stray RF signals in the structure or nearby. This is a UL requirement. 2. LED indicates acceptable operation. Do not change ignition control board. 3. When W is energized the burners will remain on for a minimum of 60 sec. 4. If more than one error code exists they will be displayed on the LED in sequence. 19 UNIT DAMAGE HAZARD Failure to follow this caution may result in unit damage. When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils. 509 01 3402 01 Proceed as follows: 1. Remove fittings. caps from low- and high-pressure service 2. Using hoses with valve core depressors, attach tow- and high-pressure gauge hoses to low- and high-pressure service fittings, respectively. 3. Start unit in Cooling Mode and let unit run until system pressures stabilize. 4. Measure and record the following: a. Outdoor ambient-air temperature (°F [°C] db). b. Liquid line temperature (°F [°C]). c. Discharge (high-side) pressure (psig). d. Suction (low-side) pressure (psig) (for reference only). 5. Using "Cooling Charging Charts," compare outdoor-air temperature(°F [°C] db) with the discharge line pressure (psig) to determine desired system operating liquid line temperature (See Table 7). 6. Compare actual liquid line temperature with desired liquid line temperature. Using a tolerance of _+2°F (_+1.1°C), add refrigerant if actual temperature is more than 2°F (1.1°C) higher than proper liquid line temperature, or remove refrigerant if actual temperature is more than 2°F (1.1°C) lower than required liquid line temperature. NOTE: If the problem causing the inaccurate readings is a refrigerant leak, refer to the Check for Refrigerant Leaks section. Indoor Airflow and Airflow Adjustments UNIT OPERATION HAZARD Failure to follow this caution may result in unit damage. For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate. NOTE: Be sure that all supply-and return-air free from obstructions, and adjusted properly. ELECTRICAL grilles are open, SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect electrical power to the unit and install lockout tag before changing blower speed. This unit has independent fan speeds for gas heating and cooling. In addition, this unit has the field-selectable capability to run two different cooling fan speeds: A normal cooling fan speed (350-400 CFM/Ton) and an enhanced dehumidification fan speed (As low as 320 CFM/Ton) for use with either a dehumidistat or a thermostat that supports dehumidification. This unit is factory-set up for use with a single cooling fan speed. The cooling speed is marked "LOW" on the interface fan board (IFB) (Fig. 18). The factory-shipped settings are noted in Table 9. There are 3 additional speed tap wires available for use in either gas heating or cooling (For color coding on the indoor fan motor leads, see Table 6). The additional 3 speed tap wires are shipped loose with vinyl caps and are located in the control box, near the interface fan board (IFB) (Fig. 18). Gas Heatinq Fan Speed Set-up To change the gas heating speed: 509 01 3402 01 1. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Table 9 shows the temperature rise associated with each fan speed for a given static pressure. Make sure that the speed chosen delivers a temperature rise within the rise range listed on the unit rating plate. 2. Remove the current speed tap wire from the "GAS HEAT" terminal on the interface fan board (IFB) (Fig.18) and place vinyl cap over the connector on the wire. 3. Connect the desired speed tap wire to the "GAS HEAT" terminal on the interface fan board (IFB). Single Cooling Fan Speed Set-up (Dehumidification feature not used) To change cooling speed: 1. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding). Add the wet coil pressure drop in Table 10 to the system static to determine the correct cooling airflow speed in Table 9 that will deliver the nominal cooling airflow as listed in Table 1 for each size. 2. Remove the current speed tap wire from the "LOW" terminal on the interface fan board (IFB) (Fig. 18) and place vinyl cap over the connector on the wire. 3. Connect the desired speed tap wire to the "LOW" terminal on the interface fan board (IFB). Two Cooling Fan Speeds Set-up (Dehumidification feature) IMPORTANT: Dehumidification control must open control circuit on humidity rise above set point. Use of the dehumidification cooling fan speed requires use of either a 24 VAC dehumidistat or a thermostat which includes control of a 24 VAC dehumidistat connection. In either case, the dehumidification control must open the control circuit on humidity rise above the dehumidification set point. Dehumidification controls are available with the reverse logic; these must not be used. 1. Remove fan speed tap wire from the "LOW" terminal on the interface fan board (IFB) (Fig. 18). 2. Determine correct normal cooling fan speed for unit and application. Add the wet coil pressure drop in Table 10 to the system static to determine the correct cooling airflow speed in Table 9 that will deliver the nominal cooling airflow as listed in Table 1 for each size. 3. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the normal cooling fan speed and place desired speed tap wire on "HIGH" on the interface board. 4. Refer to airflow tables (Table 9) to determine allowable speeds for the dehumidification cooling fan speed. In Table 9, speeds that are not allowed for dehumidification cooling are shaded. 5. Remove the vinyl cap off of the desired speed tap wire (Refer to Table 6 for color coding) for the dehumidification cooling fan speed and place desired speed tap wire on the "LOW" connection on the interface board (IFB). Verify that static pressure is in the acceptable range for the speed tap to be used for dehumidification cooling. 6. Use any spare vinyl plugs to cap any unused speed tap wires. NOTE: For cooling operation, the recommended airflow is 350 to 450 CFM for each 12,000 Btuh of rated cooling capacity. Continuous Fan Operation When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB "LOW" speed when the DH control lead is not energized, or IFB "HIGH" speed when the DH lead is energized. (See Figure 18). 20 Fig. 18- Interface Fan Board (IFB) GAS HEAT HIGH LOW Table 6 - Color QC7 CQM QC4 for Indoor Fan Motor Leads Black = High Speed Orange = Med-High Speed GCCo QC6 Coding Red = Med Speed Pink = Med-Low Speed QC3 Blue = Low Speed RL3 C8 R1L Q1 D2 c ....0 00004nr-] q3 F u [ W2 21 Y2/ DH G of Operation With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, the cooling sequence of operation is as follows: 1. When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. .o000 SSTZ-8 Cooling Sequence _1/ c R 2. The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OFM). Both motors start instantly. 3. The set of normally open contacts on the interface fan board (IFB) are closed which energizes a circuit to the indoor fan motor (IFM). NOTE: Once the compressor has started and then stopped, it should not be started again until 5 minutes have elapsed. The cooling cycle remains on until the room temperature drops to a point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat breaks the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C. The condenser and compressor motors stop. After a 90-sec. delay, the blower motor stops. The unit is in a standby condition, waiting for the next call for cooling from the room thermostat. 509 01 3402 01 50901340201 22 Table 8 - Filter Pressure Drop Table (IN. W.C.) CFM FILTER SIZE in. (ram) 20X20X1 (508X508X25) 20X24X1 (508X610)(25) 24X30X1 (610X762x25) 24X36X1 (610X914X25) 500 600 700 800 900 1000 1100 1200 0.05 0.07 0.08 O.1 O.12 O.13 O.14 O.15 0.09 O.10 O.11 O.13 0.05 0.06 0.07 .... -- -- -- 0.04 ....... Table 9 - Dry Coil Air Delivery* UNIT Size HEATING RISERANGE OF(oc) MOTOR WIRE SPEED COLOR Low Med-Low 24040 30 - 60 Medium2 Blue Pink Red (17 - 33) Med-High1 High Low Ned-Low 24060 25 - 55 Medium2 Orange Black Blue Pink Red (14 - 31) Ned-High High1 23 Orange Black 1400 1500 1600 O.14 O.15 O.16 ..... 0.07 0.08 0.09 O.1 ........ 0.06 0.07 0.07 0.08 - Horizontal 1300 1700 1800 1900 2000 2100 2200 2300 0.09 O.10 O.11 O.12 O.13 O.14 O.14 ........ and Downflow 0.09 Discharge - Unit PGD3/PGS3/WPG3 EXTERNALSTATICPRESSURE(IN, W.C.) 0.1 0.2 CFM 754 650 0.3 0.4 0.5 0.6 0.7 0.8 0.9 Heating Rise (°F) 40 46 56 NA NA NA NA NA NA Heating Rise (°C) CFM 22 26 31 NA NA NA NA NA NA Heating Rise (°F) 36 777 675 39 45 51 NA NA NA NA NA Heating Rise (°C) CFM 20 22 25 28 NA NA NA NA NA 774 684 Heating Rise (°F) 32 36 39 44 52 NA NA NA NA Heating Rise (°C) CFM 18 20 22 25 29 NA NA NA NA !009: ! 91 _ 840: ! _75:: _ 759 667 Heating Rise (°F) 30 33 36 40 45 52 NA NA NA Heating Rise (°C) CFM 17 18 20 22 25 29 NA NA NA Heating Rise (°F) NA NA NA NA 31 34 37 41 47 Heating Rise (°C) CFM NA NA NA NA 17 19 21 23 26 754 650 Heating Rise (°F) NA NA NA NA NA NA NA NA NA Heating Rise (°C) CFM NA NA NA NA NA NA NA NA NA 851 : : 777 675 Heating Rise (°F) 52 NA NA NA NA NA NA NA NA Heating Rise (°C) CFM 29 NA NA NA NA NA NA NA NA 851 : 774 684 Heating Rise (°F) 9_! _::: 47 52 NA NA NA NA NA NA NA Heating Rise (°C) CFM 26 29 NA NA NA NA NA NA NA 759 667 Heating Rise (°F) !00_: 44 ,_i7 48 53 NA NA NA NA NA NA Heating Rise (°C) 24 27 29 NA NA NA NA NA NA Heating Rise (°F) 36 38 40 43 46 50 54 NA NA Heating Rise (°C) 20 21 22 24 25 28 30 NA NA 509 01 3402 01 Table 9 - Dry Coil Air Delivery* - Horizontal and Downflow Discharge - Unit PGD3/PGS3/WPG3 HEATING RISERANGE UNIT OF(oc) MOTOR SPEED WIRE COLOR Low Blue Ned-Low1 30040 30 - 60 (17 - 33) Medium Ned-High2 High Low Ned-Low 30060 25 - 55 (14 - 31) Medium Ned-High2 High1 Low1 Ned-Low 36060 25 - 55 (14 - 31) 509 O1 3402 O1 Medium2 Pink Red Orange Black Blue Pink Red Orange Black Blue Pink Red Ned-High Orange High Black EXTERNALSTATICPRESSURE(IN, W.C.) 0.1 CFM Heating 41 Rise (°F) Heating 23 Rise (°C) CFM 973 Heating 31 Rise (°F) Heating 17 Rise (°C) CFM _888 Heating NA Rise (°F) Heating NA Rise (°C) CFM 11'46' Heating NA Rise (°F) Heating NA Rise (°C) CFM Heating NA Rise (°F) Heating NA Rise (°C) CFM Heating NA Rise (°F) Heating NA Rise (°C) CFM 973 Heating 46 Rise (°F) Heating 25 Rise (°C) CFM _888 Heating 41 Rise (°F) Heating 23 Rise (°C) CFM Heating 39 Rise (°F) Heating 22 Rise (°C) CFM Heating 37 Rise (°F) Heating 21 Rise (°C) CFM _234 Heating 36 Rise (°F) Heating 20 Rise (°C) CFM _29_ Heating 34 Rise (°F) Heating 19 Rise (°C) CFM 35_ Heating 33 Rise (°F) Heating 18 Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 47 55 NA NA NA NA NA NA NA NA NA NA NA NA 26 31 887 823 34 37 41 45 56 NA NA NA 19 20 23 25 31 NA NA NA , _023 _73_;_._`_6_:_538_:_1_._1_` 954 881 800 30 32 34 38 42 46 54 NA 16 18 19 21 23 26 30 NA , _06_ !!!!i!i!!!!i',!'i!723!i11!,!i!!!!!!!,!!!i!i!!!!i',!'i!!658;!;;!;!!;i;i!i,!!!ii! !!!!!!!!i',!'!!S631ii!!i!!i!!!!i!!i!i:!,iiiiiiiiii',i'ili_6i_iiil,ii_i 996 915 840 NA 30 33 36 !!!!i!_!!!!i``!`_!758!;_!;!!:_:_!__!!!_i!_!!!!i!!!!i``!`_!!68!!!!`i`!!i!!i!!!!i!! !!!!!!!!!i',!'!!'564!!!!!i,!!!i!i,!!!!!,iiiiiiiiii',i'ili_iSO_i:iiil,i 40 44 54 NA NA 17 18 20 22 24 30 NA NA NA 30 31 34 37 41 48 NA NA 17 17 19 21 23 27 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 887 823 50 54 NA NA NA NA NA NA 28 30 NA NA NA NA NA NA 954 881 800 47 50 NA NA NA NA NA , _023 43 24 _73_._`_6_:_5__:_`_1_1_ ' !!!!i!i!!!!i',!'i!723!i11!,!i!!!!!!!,!!!i!i!!!!i',!'i!!_58;!;;!;!!;i;i!i,!!!ii! !!!!!!!!i``!`!!_5_3_i_!!i!!i!!!!i!!i!i:!`iiii_iiiii``i`i_i_i_ii_ NA NA NA NA 26 28 NA 996 915 840 42 45 49 53 NA NA NA NA 23 25 27 29 NA NA NA NA 39 41 44 46 50 55 NA NA 22 23 24 26 28 30 NA NA 1168 1093 1021 961 38 41 44 46 50 54 NA NA NA NA 21 iiii_iiiii``i`i_i_!ii!iiiiii`!`i!;_i`_iiiiiiiii``i`i_i48Q_i_iii_ !' 23 24 26 28 1154 1090 1027 977 36 39 41 43 45 50 54 NA 20 21 23 24 25 28 30 NA 53 , _'2_8 _2_, _,2_'6 30 89_ _28:62 1158 1102 1046 981 34 36 38 40 42 45 48 19 20 21 22 24 25 27 24 Table 9 - Dry Coil Air Delivery* UNIT HEATING RISE RANGE OF(OC) - Horizontal MOTOR SPEED Low Med-Low 36090 35 - 65 (19 - 36) Medium2 Med-High High1 Low1 Med-Low 42060 25 - 55 (14 - 31) Medium Med-High2 High Low Med-Low 42090 35 - 65 (19 - 36) Medium1 Med-High2 and Downflow Pink Red Orange Black Blue Pink Red Orange Black Blue Pink Red Orange - Unit PGD3/PGS3/WPG EXTERNALSTATICPRESSURE(IN, W.C.) WIRE COLOR Blue Discharge 0.1 CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) _234 55 0.2 0.3 0.4 0.5 0.6 1168 1093 1021 961 58 62 NA NA 89_; NA 0.7 ,_25 : NA 31 32 35 NA NA NA NA _90, _223 1154 1090 1027 977 89_ 53 56 59 62 NA NA 29 31 33 35 NA 1158 50 53 55 59 28 29 31 42 44 24 42 0.8 0.9 ,759 ; NA ,68 : NA NA NA NA NA NA NA NA NA NA 1102 1046 981 9!8 _3 62 65 NA NA NA 33 34 36 NA NA NA 46 48 50 52 54 56 60 24 25 26 28 29 30 31 33 43 45 46 48 51 53 56 60 27 28 30 31 33 iiiiiiiii ',i'_i_i31ii6i_i_i_i_fii_;iiill 1140 23 24 25 26 1295 1234 1182 1126 34 36 38 39 41 44 47 49 52 19 20 21 22 23 24 26 27 29 1345 1282 1235 1194 1140 33 35 36 37 39 41 43 46 48 18 19 20 21 22 23 24 25 27 1358 1323 1282 1234 1169 1130 30 31 31 33 34 35 36 38 39 16 17 17 18 !!!i!i!!!!i_!!_i!O_iSi!!!!i,!!!ii!i iiiiiiiii_i_ii_iiOi_iii6iiiiiiiiiii!;iiill iiiiiiiii_,i_,i!i_955!i!ili!iii_iii!i!iiiiiiiii_,i_,li,898ii!iii!:_ii!i!:iiii! iiiiiiiiiiii_,i_,li,_Ti_!i!,ii_iiiiill !!!i!i!!!!i_!!_i!09 _;!iii!!,!!!ii!i; iiiiiiiiiiii_,i_,i_i_:;_!iii_ii!ii_iill 19 19 20 21 22 1362 1313 1278 1231 1188 29 30 31 31 33 34 35 36 37 16 17 17 17 18 19 19 20 21 _7o5', _. _. _ _s_s, _s_ _4_3 _,_,_s _4o_ _6o 26 27 28 28 29 30 31 32 33 14 15 15 16 16 17 17 18 18 1295 1234 1182 1126 53 55 58 60 63 NA NA NA NA 29 31 32 34 35 NA NA NA NA 1345 1282 1235 1194 1140 51 53 55 57 60 62 NA NA NA 28 29 31 32 33 35 NA NA NA 1358 1323 1282 1234 1169 1130 45 47 48 50 51 53 55 58 60 25 26 27 28 29 29 31 32 33 1362 1313 1278 1231 1188 44 46 47 48 50 52 53 55 57 24 25 26 27 28 29 30 31 32 40 41 42 43 45 46 47 48 50 22 23 24 24 25 25 26 27 28 !!!!f!!!!!i_:!_i_i!;_75!i!!!!_!_!!i!!_!! iiiiiiiiii_i_ii_il;_i_ii_i_i_i_i_ili!!_!_! _ _85!_i!i!li!!lii!ii !!!!!!!!!!ii:!ii_i!;_9_!!!!i!i!!i!!i!!; CFM High Black Heating Rise (°F) Heating Rise (°C) 25 509 01 3402 01 Table 9 - Dry Coil Air Delivery* - Horizontal and Downflow Discharge - Unit PGD3/PGS3/WPG3 UNIT HEATING RISE RANGE MOTOR WIRE SPEED COLOR EXTERNALSTATICPRESSURE(IN, W.C.) OF(oc) Low1 Blue 48090 35 - 65 Medium2 (19 - 36) Med-High High Low Med-Low 48115 30 - 60 (17 - 33) Medium 2 MedHigh 1 High Low Med-Low 48130 35 - 65 (19 - 36) Medium 2 MedHigh 1 High 509 01 3402 01 Pink Red Orange Black Blue Pink Red Orange Black Blue Pink Red Orange Black 0.2 0.3 0.4 0.5 0.6 CFM 1402 1351 1311 _6_. _22_ 1172 Heating Rise (OF) 49 50 52 54 56 58 Heating Rise (°C) CFM 27 28 29 30 31 1457 1404 1367 1318 1284 47 48 50 52 53 26 27 28 29 39 40 41 42 22 22 23 24 Heating Med-Low 0.1 Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (OF) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) _2)4).2),2082 0.8 0.9 )))))','I;)36)))); )X:! ))) ','1080))), ) 60 63 65 33 35 I_:_ I_'4_ 55 57 59 62 29 31 32 33 34 1553 1512 1465 1427 1381 44 45 46 48 49 24 25 26 26 27 ,_2026.!)80 32 0.7 _23_ !))_ ))),,I)0): 18_ 36 1104 1793 _ NA NA NA NA NA 35 36 36 38 NA NA NA NA NA 19 20 20 21 _234_, _230_, 225_, 220_, 199_ 1902 NA NA NA NA NA NA NA 36 38 NA NA NA NA 20 21 NA NA NA NA NA NA NA NA NA NA NA 1402 1351 1311 NA NA NA 2_I NA NA NA NA NA 1457 1404 1367 1318 1284 60 NA NA NA NA 33 NA NA _ 36, _69_:, 64_, _D NA NA NA _!'97 _!4_ NA NA 1803 NA NA NA NA NA NA NA _60_ 1553 1512 1465 1427 1381 50 51 53 54 56 57 59 NA NA 28 28 29 30 31 32 33 NA NA 40 41 42 43 44 45 46 47 48 22 23 23 24 24 25 25 26 27 _79_ !!!!i!i!!!2344_!i!ii!!i!!i!' !!!i!i!!i!2306!!i!!i!!!i!i' !!!!!i!!i!2259!i!i!i!i!!i!i!i!!i!' !!!!i!!_i!22_3!i!!i!!!i!' !!!!!i!!!!i_i!_!i_!!!!i!!!!i_i!_i'!, !!!i!i!!!!i_i!20_O_X_X_!!i!ii!ill ))i)iiiii,ii_)))8D_ii)i 37 38 38 39 41 42 44 46 48 21 21 21 22 23 23 24 25 27 1402 1351 1311 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 1457 1404 1367 1318 1284 NA NA NA NA NA NA NA NA NA !!!!i!i!!_!!!26_i!i!!i!!!i!,!!!!!i!!!!i_i!_i_!!!224ii_!ii!!!!!i ,!!!i!i!!!!i_i!_i_!!!_!!!_!ii)X!!i!i,!_ )))!)!!!!)_)!_)_)))_)))_!!!!!!i!!!!!,)Di)i ))i)iiiii,ii_)))Q_)))i) )))))!))!!!)0!!)))23_!)!))!!!)!)) i)))i)iii,iil)))_)))Q_i NA NA NA NA NA NA NA NA NA 1553 1512 1465 1427 1381 55 57 59 60 62 64 NA NA NA 31 32 33 33 34 35 NA NA NA 45 46 47 48 49 50 51 52 54 25 25 26 26 27 28 28 29 30 !!!!i!i!!!2344_!i!ii!!i!!i!' !!!i!i!!i!2306!!i!!i!!!i!i' !!!!!i!!i!2258!i!i!i!i!!i!i!i!!i!' !!!!i!!_i!22_3!i!!i!!!i!' !!!!!i!!!!i_i!_!i_!!!!i!!!!i_i!_i'!, !!!i!i!!!!i_i!201_O_X_X_!!i!ii!ill ))i)iiiii,ii_)))8_ii)i) 41 42 43 44 45 47 48 51 53 23 23 24 24 25 26 27 28 30 2d Table 9 - Dry Coil Air Delivery* - Horizontal and Downflow Discharge - Unit PGD3/PGS3/WPG3 UNIT HEATING RISE RANGE OF (oc) MOTOR SPEED 0.1 Low 1 Med-Low 60090 35 - 65 (19 - 36) Medium 2 Med-High High Low Med-Low 60115 30 - 60 (17 - 33) Medium 2 MedHigh1 High Low Ned-Low 60130 Blue Pink Red Orange Black Blue Pink Red Orange Black Blue Pink 35 - 65 (19 - 36) EXTERNAL STATIC PRESSURE WIRE COLOR Medium 2 Ned-High 1 Red Orange CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Heating Rise (°F) Heating Rise (°C) CFM Black 49 0.3 51 0.4 0.5 0.6 53 55 57 60 63 NA 29 31 32 33 35 NA 26 27 28 1678 1635 1602 41 42 42 44 45 46 47 48 50 23 23 24 24 25 26 26 27 28 !!!i!i!!!_!!_i!ii;ii!iiiiil;,!!!i!!!!i'i!'i_!!_i_iii!ii!;ii;i_H iiiiiiiiii'ii'i_i_i;i;iiiiiilJ;i;; iiiiiiiii,ii_i4_Si!!i;i!iiii:iSiii,ii_i40_;_i_"_34_;;il iiiii_iii_ii_6_ii;_;_i_i_i_.!!!_!!!!_!!_i_iii!ii_.!!!i!_!!!_88_i!i!i!i!iii_i;i.!!!!_!!!!_84_i_i_i_i_i_ii!ii!ii{.iiii_iiiiiiii`i_ii_9_`!`i_ii_;iii_ii_;_; iii}iiiiiiiii'i_ii_!i!!i!!i!ili_;i 1711 1675 1628 35 36 36 37 38 39 40 41 42 19 20 20 20 21 22 22 23 23 NA NA NA NA NA 35 36 37 38 NA NA NA NA NA 19 20 20 21 NA NA NA NA NA NA NA 35 36 NA NA NA NA NA NA NA 19 20 !!!i!_!!!_!_ii_ii_iii_!!!i!_!!!_!!_89_i_i_;iiii_i1i_ii_ii3¢_iiiiiiii_i_ii_i_iiiii_iii_ii_i_iiiiiiii_i_ii_i_!!!i!_!!!!_!_!_236iii_;_i_i_iii:i iiiiiiiii_i'_iiii!,89!;i;i_!i;!iiiii iiiiiiii,_,i',_iiii_ii_iiiiiiiii:_i iiiiiiii,_,i',_iii_;!;ii:iiii!;ii:i! iiiiiliiii,_,i',_iiiO_;_iiiii!,ii;ili;iii 60 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 33 NA NA 1678 1635 1602 52 53 54 56 57 59 60 NA NA 29 30 30 31 32 33 34 NA NA _6_ , _15 , _880 !!!i!i!!!_!!_i!ii;ii!iiiiiii,!!!i!!!!i_i!_i_!!51i_iii!ii!iiiii_il i[iiiiiiii_ii_i_i_i;i;iiiiiilJ;il; iiiiiiiii,ii_i438i!!i!i!iiii:iSiii,ii_i4041_i_ _34_iiii 1711 1675 1628 44 45 46 , _84_ 47 , _ 9_ 48 50 51 52 53 25 25 26 26 27 28 28 29 30 !!!!!_!_i_!_!_!_!_!_iii!iiii_!_'!!!!_!_iH_o_8_i_i_i_i_!i_iii!i!ii_'!!!!_!_iH_o_6_!!!H!_!_iH'!!!!_!_iH_!_!_!_!Hi_!_i_'!!!!_!_i_!!_!_98_!_!!;!;!;!_!_ iiiiiiliiiiii_94i_iiiiiiiiiiiiiiiii _i_i_{;ii_i_i8_i_i_i_i_ii!_i_ii;i_!iii_i_i_{_ixi_i86:8_iiii_i_:;_:; iiiiiiiii{iiiii_ii78_i;i;ii;iiii:ii:il;ii 41 42 42 43 44 45 46 47 49 23 23 23 24 24 25 26 26 27 !!!i!_!!!246!_!!!!_!_!!!_!_!!!i!_!!!2489!_!_!_!_!!i!i!i!!_!!_!!!_!!_i!2389!_!_!_!_!!i!i!i!!_!!_!!!_!!_i!2286_i_i_!!!!!_!!_!!!!_!!!!_!_!_!_i_i_!!_!_!_ iii}iiiiii_ii_ii_0_i_i_i_i_iiiil;il;:i iiiiiiiii,i2062iiii!ii!!iiiii iiiiiiiii,ii_iii968iii!;ii!iiili iiiiiiiiiiii,ii_iii8g4iiii!iliiiii 35 36 37 38 40 41 42 44 46 20 20 21 21 22 23 23 25 26 iiiii_iiiii_;i44_!!!!_!_!!_!!!!!!!!!i!_Xa_!!!_!!!_!_!_!!!_!!!!i!_!_!_!!!!!_!_!!!i!_!!!!i_!!!_!_!!!!_!_!!!!!!!!! ii;iiiiiii',i'_i_iii;ii!i!i,!!! iiiiiiiiiii;,,i,,i_!!:o2_iii_;li_i_, NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 1678 1635 1602 Heating Rise (°F) Heating Rise (°C) CFM 57 59 60 62 64 65 NA NA NA 32 33 33 34 35 36 NA NA NA 1711 1675 1628 Heating Rise (°F) Heating Rise (°C) CFM 49 50 51 52 54 55 56 57 59 27 28 28 29 30 31 31 32 33 45 46 47 48 49 50 51 52 54 25 26 26 27 27 28 28 29 30 Heating Rise (°F) Heating Rise (°C) CFM High 47 0.2 (IN. W.C.) Heating Rise (°F) Heating !!!!!!!!!!i_i!_58!!!!'!!_i_!_i!!!!!!!!!!!i_;!_:_i!_!_!i!i!i!i!!!!!_! ! iiiiiiiiii_i_ii_ii47i_ii_iii:liiii ii;iiiiiii ',i'_i_;_iii_iiiiiilil !!!i!_!!_6_!_!!!!i!!!!_!_!!!!!!!!_!!!_!!!_!_!_!!!!!_233_!!!_!!!_!_!_!!!!!_22_6!!!_!_!!_!_!_!!!i!_!!!!i_i!_!92!!!!_!!!!_!!_ iiiiiiiiii_i_i_i_i!_i8_liiii,!!!! iiiiiii:_,i_206_iiiiiiii,i_,li,i:iiiiiiiii:_,i_,i_!_6_i,i,i_,li,i,i_,_i_i iiiiiiiiiii:_,i_,i_!_!i_ii!:li!iii 39 40 41 42 44 45 47 49 51 22 22 23 23 24 25 26 27 29 Rise (°C) *Air delivery values are without air filter and are for dry coil (See Table 10 - PGD3/PGS3/WPG3 Wet Coil Pressure Drop table). 1 Factory-shipped heating speed 2 Factory-shipped cooling speed "NA" = Not allowed for heating speed Note: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting. Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed. 27 509 01 3402 01 Table 10 - PGD3/PGS3/WPG3 UNIT SIZE 24 30 36 42 48 60 600 0.030 700 0.037 0,037 800 0.044 0,044 - 900 0.053 0,053 0,055 - 1000 0.063 0,063 0,060 0,045 1100 0,072 0,090 0,050 Wet Coil Pressure Drop (IN. W.C.) STANDARDCFM (S.C.EM) 1200 1300 1400 0,081 0,100 0,060 0,041 0,105 0,110 0,065 0,063 0,140 0,075 0,085 1500 0,080 0,100 0,060 1600 0,090 0,104 0,065 1700 0,094 0,110 0,072 1800 1900 2000 0,110 0,120 0,077 0,130 0,085 0,100 Table 11 - Wet Coil Air Delivery -- Downflow Discharge -- High Speed UNIT SIZE 0.1 36 42 48 60 0.2 1333 1612 2166 0.3 1289 1569 2085 1256 1527 2002 0.4 EXTERNAL STATICPRESSURE (in. W.C.) 0.5 0.6 0.7 1214 1481 1919 1152 1451 1798 1118 1393 1709 0.8 1076 1351 1582 0.9 1035 1317 1467 997 1278 1270 1.0 950 1242 988 MAINTENANCE To ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This unit should be inspected at least once each year by a qualified service person. To troubleshoot unit, refer to Table 12-14, Troubleshooting Chart. NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract. ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental pollution. Remove and re-cycle all components or materials (i.e. oil, refrigerant, etc) before unit final disposal. The minimum maintenance as follows: PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death and unit component damage. The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the Owner's Manual. ELECTRICAL SHOCK HAZARD Failure to follow these warnings injury or death: could result in personal 1. Turn off electrical power to the unit and install lock out tag before performing any maintenance or service on this unit. 2. Use extreme caution parts. 3. Never place anything contact with the unit. when removing combustible panels and either on or in UNIT OPERATION HAZARD Failure to follow operation. this caution may result in improper Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing. 509 01 3402 01 requirements for this equipment are 1. Inspect air filter(s) each month. Clean or replace when necessary. 2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary. 3. Inspect blower motor and wheel for cleanliness at the beginning of each heating and cooling season. Clean when necessary. For first heating and cooling season, inspect blower wheel bi-monthly to determine proper cleaning frequency. 4. Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary. 5. Ensure electric wires are not in contact with refrigerant tubing or sharp metal edges. 6. Check and inspect heating section before each heating season. Clean and adjust when necessary. 7. Check flue necessary. Air Filter hood and remove any obstructions, if IMPORTANT: Never operate the unit without a suitable air filter in the return-air duct system. Always replace the filter with the same dimensional size and type as originally installed. See Table 1 for recommended filter sizes. Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice during each cooling season and twice during the heating season, or whenever the filter becomes clogged with dust and lint. Indoor Blower and Motor NOTE: All motors are pre-lubricated. these motors. Do not attempt to lubricate For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually. 28 Flue Gas Passageways ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect and tag electrical power cleaning the blower motor and wheel. to the unit before To clean the blower motor and wheel: 1. Remove and disassemble blower assembly as follows: a. Remove blower access panel. b. Disconnect 5 pin plug and 4 pin plug from indoor blower motor. Remove capacitor if required. c. On all units remove blower assembly from unit. Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment. d. Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly. e. Loosen setscrew(s) that secures wheel to motor shaft, remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing. 2. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel orientation. b. Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes. c. Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent. d. Reassemble wheel into housing. e. Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of shaft. Reinstall blower into unit. Reinstall capacitor. f. Connect 5 pin plug and 4 pin plug to indoor blower motor. g. Reinstall blower access panel. 3. Restore electrical power to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles. Induced Draft (combustion air) Blower Assembly The induced-draft blower assembly consists of the inducer motor, the blower housing, and the induced-draft blower wheel. Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during the heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency. To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove induced-draft blower assembly as follows: 1. Remove control access panel. 2. Remove the 5 screws that attach induced-draft blower assembly to the flue collector box cover. 3. Slide the assembly out of the unit. Clean the blower wheel. If additional cleaning is required, continue with Steps 4 and 5. 4. To remove blower wheel, remove 2 setscrews. 5. To remove inducer motor, remove screws that hold the inducer motor to the blower housing. 6. To reinstall, reverse the procedure outlined above. 29 To inspect the flue collector box and upper areas of the heat exchanger: 1. Remove the induced draft blower assembly according to directions in the Induced Draft Blower Assembly section. 2. Remove the 11 screws holding the flue collector box cover (See 19) to the heat exchanger assembly. Inspect the heat exchangers. 3. Clean all surfaces, as required, using a wire brush. Limit Switch Remove blower access panel. Limit switch is located on the fan partition. Burner Ignition Unit is equipped with a direct spark ignition 100 percent lockout system. Ignition module (IGC) is located in the control box (See 19). Module contains a self-diagnostic LED. During servicing, refer to label diagram or Table 5 in these instructions for LED interpretation. If lockout occurs, unit may be reset by either momentarily interrupting power supply to unit or by turning selector switch to OFF position at the thermostat. Main Burners At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary. Removal of Gas Train To remove the gas train for servicing: 1. Shut off main gas valve. 2. Shut off power to unit and install lockout tag. 3. Remove control access panel (See Fig. 20). 4. Disconnect gas piping at unit gas valve. 5. Remove fan partition mounting bracket (2 screws located on the left side of the control compartment on the fan partition panel). Slide bracket forward, bottom first, to remove (See Fig. 19 & 20). 6. Remove wires connected to gas valve. Mark each wire. 7. Remove ignitor and sensor wires at the ignitor module. 8. Remove the mounting screw that attaches the burner rack to the unit base (See Fig. 19). 9. Slide the burner rack out of the unit (See Fig. 19 and 22). 10. To reinstall, reverse the procedure outlined above. Outdoor Coil, Indoor Coil, and Condensate Inspect the condenser coil, evaporator drain pan at least once each year. Drain Pan coil, and condensate The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base. Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a "plumbers snake" or similar probe device. 509 01 3402 01 Fig. 19 - Blower Housing and Flue Collector Box Fig. 21 - Removal of Motor and Blower Wheel FanPartitionMountingBracket integrated Gas Unit BLOWER HOUSING dGC) Auto Transformer fuses used on 460 ty. (Hidden) Board (IFB) Induced Draft Motor 2 SETSCREWS (HIDDEN) Flue Collector Box Blower Burner Rack Mounting Screw Rollout Switch Housing Fig. 20 - Unit Access Panels Fig. 22 - Burner Rack Removed t Outdoor Fan UNIT OPERATION HAZARD Failure to follow this caution may result in damage to unit components. Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit. 1. Remove 6 screws holding outdoor grille and motor to top cover. 2. Turn motor/grille assembly expose fan blade. upside down on top cover to 3. Inspect the fan blades for cracks or bends. 4. If fan needs to be removed, loosen setscrew and slide fan off motor shaft. 5. When replacing fan blade, position blade as shown in Fig. 23. 6. Ensure that setscrew engages the flat area on the motor shaft when tightening. 7. Replace grille. 509 01 3402 01 30 Fig. 23 - Fan Blade Position MOTOR FAN GRILLE T / A X MOTOR SHAFT MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE "A" SIZE IN. MM 24 7.3 30 7.3 185 185 36 7.3 185 42 7.6 7.6 7.6 193 48 60 Electrical Controls and Wiring Remove access panels to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, re-strip the wire end and reassemble the connection properly and securely. After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checks. Refriqerant Circuit Annually inspect all refrigerant tubing connections and the unit base for oil accumulations. Detecting oil generally indicates a refrigerant leak. SAFETY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury, death or property damage. System under pressure. Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves. If oil is detected or if low cooling performance is suspected, leak-test all refrigerant tubing using an electronic leak-detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, refer to the Check for Refrigerant Leaks section. If no refrigerant leaks are found and low cooling performance is suspected, refer to the Checking and Adjusting Refrigerant Charge section. 31 193 Gas Input Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit. EXPLOSION, 193 The gas input does not require checking unless improper heating performance is suspected. If a problem exists, refer to the Start-Up section. Evaporator Airflow The heating and/or cooling airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all supply- and return-air grilles are open and free from obstructions, and that the air filter is clean. When necessary, refer to the Indoor Airflow and Airflow Adjustments section to check the system airflow. R-410A Items Metering Device (Thermostatic Expansion Valve ) This metering device is a hard shutoff, balance port TXV. The TXV maintains a constant superheat at the evaporator exit resulting in higher overall system efficiency. Pressure Switches Pressure switches are protective devices wired into control circuit (low voltage). They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit. These pressure switches are specifically designed to operate with R-410A systems. R-22 pressure switches must not be used as replacements for the R-410A system. Loss of Charqe Switch This switch is located on the liquid line and protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 20 psig. If system pressure is above this, switch should be closed. To check switch: 1. Turn off all power to unit. 2. Disconnect leads on switch. 3. Apply ohm meter leads across switch. You should have continuity on a good switch. NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover 509 01 3402 01 all system charge so that pressure gauges read 0 psig. Never open system without breaking vacuum with dry nitrogen. necessary precautions atmosphere. High-Pressure Servicing Systems on Roofs with Synthetic Materials Switch The high-pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at 650 psig. High pressure may be caused by a dirty outdoor coil, failed fan motor, or outdoor air recirculation. To check switch: 1. Turn off all power to unit. 2. Disconnect leads on switch. 3. Apply ohm meter leads across switch. You should have continuity on a good switch. Copeland Scroll Compressor (R-410A Refrigerant) The compressor used in this product is specifically designed to operate with R-410A refrigerant and cannot be interchanged. The compressor is an electrical (as well as mechanical) device. Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most troubleshooting techniques. Refrigerants present additional safety hazards. FIRE/EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death and/or property damage. Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils. The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with a noise reducing shutdown device and an internal pressure relief port. The pressure relief port is a safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550 (26.34 kPa) and 625 psi (29.93 kPa) differential pressure. EXPLOSION, ENVIRONMENTAL SAFETY HAZARD Failure to follow this warning could result in personal injury, death or equipment damage. This system uses R-410A refrigerant which has higher operating pressures than R-22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Refrigerant to avoid exposure of the oil to the POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials. Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take appropriate precautions to protect roofing. Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device, coil, accumulator, or reversing valve. Synthetic Roof Precautionary Procedure 1. Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10 X 10 ft. (3.1 m X 3.1 m) area. 2. Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills and prevent run-offs, and protect drop cloth from tears caused by tools or components. 3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run-offs through the Iouvered openings in the unit base. 4. Perform required service. 5. Remove and dispose of any oil contaminated local codes. material per Liquid Line Filter Drier This filter drier is specifically designed to operate with R-410A. Use only factory-authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system. R-410A Refriqerant Charqinq Refer to unit information plate and charging chart. Some R-410A refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position. For cylinders equipped with a dip tube, charge R-410A units with cylinder in upright position and a commercial metering device in manifold hose. Charge refrigerant into suction-line. TROUBLESHOOTING Use the Troubleshooting occur with these units. Guides (See Tables 12-14) if problems START-UP Use Start-Up followed. CHECKLIST checklist to ensure proper start-up procedures are System This information covers the refrigerant system of the PGD3/PGS3/WPG3, including the compressor oil needed, servicing systems on roofs containing synthetic materials, the filter drier and refrigerant charging. Compressor Oil The Copeland scroll compressor uses 3MAF POE oil. If additional oil is needed, use Uniqema RL32-3MAF. If this oil is not available, use Copeland Ultra 32 CC or Mobil Arctic EAL22 CC. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all 509 01 3402 01 32 R-410A • QUICK REFERENCE GUIDE R-410A refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A • R-410A refrigerant cylinders are rose colored. • Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400. • R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating • Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low-side • Use hoses with minimum 700 psig service pressure rating. • Leak detectors should be designed to detect HFC refrigerant. • R-410A, as with other HFCs, is only compatible with POE oils. retard. • Vacuum pumps will not remove moisture from oil. • Do not use liquid-line • Do not leave R-410A suction line filter driers in line longer than 72 hrs. filter driers with rated working pressures less than 600 psig. • Do not install a suction-line • POE oils absorb moisture rapidly. Do not expose oil to atmosphere. • POE oils may cause damage to certain plastics and roofing materials. filter drier in liquid line. • Wrap all filter driers and service valves with wet cloth when brazing. • A factory approved liquid-line • Do NOT use an R-22 TXV. • filter drier is required on every unit. Never open system to atmosphere while it is under a vacuum. • When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers. Evacuate to 500 microns prior to recharging. • Do not vent R-410A into the atmosphere. • Observe all warnings, cautions, and bold text. • All indoor coils must be installed with a hard shutoff R-410A TXV metering device. 33 509 01 3402 01 Table 12- Troubleshooting SYMPTOM Chart CAUSE REMEDY Power failure Call power company Replace fuse or reset circuit breaker Fuse blown or circuit breaker tripped Compressor and condenser fan will not start. Defective contactor, transformer, or high-pressure, of-charge or low-pressure switch Insufficient loss- Incorrect or faulty wiring Thermostat Check wiring diagram and rewire correctly Lower thermostat temperature setting below room temperature setting too high Faulty wiring or loose connections in compressor Compressor motor burned out, seized, or Compressor runs will not start but condenser fan internal overload open Defective run/start capacitor, overload, One leg of 3-phase circuit start relay Scroll compressor Refrigerant is rotating in the wrong direction overcharge Replace and determine cause Determine cause and correct Determine cause and correct Defective run/start capacitor Faulty outdoor fan motor or capacitor in refrigerant Dirty air filter Unit undersized Compressor Determine cause and replace Replace Locate restriction and remove system Replace filter Decrease load or increase unit size for load Thermostat temperature Low refrigerant charge operates continuously Reset thermostat set too low Locate leak, repair, and recharge Air in system Recover refrigerant, evacuate system, and recharge Clean coil or remove restriction Outdoor coil dirty or restricted Dirty air filter Replace filter Clean coil Dirty condenser coil Refrigerant overcharged Excessive head pressure Recover excess refrigerant Air in system Head pressure Recover refrigerant, evacuate system, and recharge Determine cause and correct Condenser air restricted or air short-cycling Low refrigerant charge too low Check for leaks, repair, and recharge. Remove restriction Restriction in liquid tube Refrigerant overcharged Excessive suction pressure Recover excess refrigerant Dirty air filter Replace filter Low refrigerant charge Metering device or low side restricted Check for leaks, repair and recharge Remove source of restriction Insufficient Suction pressure too low evaporator Temperature Increase air quantity Check filter-replace if necessary Reset thermostat airflow too low in conditioned area Install low-ambient Outdoor ambient below 55°F (13°C) Filter drier restricted Table 13- Troubleshooting SYMPTOM Burners will not ignite heating 509 01 3402 01 Guide-Heating REMEDY Water in gas line Drain. Install drip leg. No power to furnace Check power supply fuses, wiring or circuit breaker. Check transformer. No 24-v NOTE: Some transformers have internal over-current requires a cool-down period to reset. power supply to control circuit Mis-wired or loose connections spark electrodes Check all wiring and wire nut connections Check flame ignition and sense electrode Adjust as necessary. protection that positioning. No gas at main burners 1. Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate before attempting to light unit. 2. Check gas valve. Dirty air filter Clean or replace filter as necessary Gas input to furnace too low Unit undersized for application Restricted airflow Check gas pressure at manifold match with that on unit nameplate Replace with proper unit or add additional unit Limit switch cycles main burners Poor flame characteristics kit Replace filter CAUSE Misaligned Inadequate Correct the direction of rotation by reversing the 3-phase power leads to the unit. Shut down unit to allow pressures to equalize. Recover refrigerant, evacuate system, and recharge to capacities shown on rating plate or undercharge Insufficient line voltage Blocked outdoor coil Restriction Replace compressor Determine cause and replace Determine cause and correct Defective compressor Compressor cycles (other than normally satisfying thermostat) Check wiring and repair or replace Determine cause Replace fuse or reset circuit breaker Determine cause power dead Low input voltage Three-phase scroll compressor makes excessive noise, and there may be a low pressure differential. Replace component Determine cause and correct line voltage Incomplete combustion results in: Aldehyde odors, carbon monoxide, sooting flame, floating flame Clean or replace filter. Remove any restriction. Check rotation of blower, temperature rise of unit. Adjust as necessary. 1. Tighten all screws around burner compartment 2. Cracked heat exchanger. Replace. 3. Unit over-fired. Reduce input (change orifices or adjust gas line or manifold pressure). 4. Check burner alignment. 5. Inspect heat exchanger for blockage. Clean as necessary. 34 Table 14- Troubleshooting SYMPTOM No Power or Hardware (LED OFF) Limit switch Guide-LED CAUSE failure Loss of power to control module (IGC)*. faults Status Codes REMEDY Check 5-amp fuse son IGC*, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset. Check the operation of the indoor (evaporator) High temperature Flame sense fault (LED 3 flashes) The IGC* sensed flame that should not be present. Reset unit. If problem persists, replace control board. Inadequate airflow to unit. Check the operation of the indoor (evaporator) fan motor and that supply-air temperature rise agrees with range on unit nameplate information. 4 consecutive limit switch (LED 4 flashes) Ignition lockout (LED 5 flashes) fault Pressure switch (LED 6 flashes) fault limit switch is open. fan motor. Ensure that (LED 2 flashes) faults Unit unsuccessfully attempted ignition for 15 minutes, Rollout switch fault (LED 7 flashes) Rollout switch has opened, Internal control (LED 8 flashes) Microprocessor hardware. Temporary 1 hr auto reset fault I (LED 9 flashes) Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that fame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas. Verify wiring connections to pressure switch and inducer motor. Verify pressure switch hose is tightly connected to both inducer housing and pressure switch. Verify inducer wheel is properly attached to inducer motor shaft. Verify inducer motor shaft is turning. Open pressure switch, fault the supply-air temperature rise is in accordance with the range on the unit nameplate. Clean or replace filters. Rollout switch will automatically reset, but IGC* will continue to lockout unit. Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Inspect heat exchanger. Reset unit at unit disconnect. has sensed an error in the software or Electrical interference If error code is not cleared by resetting unit power, replace the IGC*. impeding IGC software Reset 24-v. to control board or turn thermostat off, then on again. Fault will automatically reset itself in one (1) hour. *WARNING /_ : If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that my be present before handling new control board. The IGC is sensitive to static electricity and my be damaged if the necessary precautions are not taken. IMPORTANT: Refer to Table 12-Troubleshooting Guide-Heating for additional troubleshooting analysis. LEGEND IGC--Integrated Gas Unit Controller LED--Light-Emitting Diode 35 509 01 3402 01 START-UP CHECKLIST (Remove and Store in Job Files) I. PRELIMINARY INFORMATION MODEL NO.: SERIAL NO.: DATE: TECHNICIAN: II. PRESTART-UP (Insert check mark in box as each item is completed) () VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT ( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION ( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS INSTRUCTIONS ( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE) ( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE () VERIFY THAT UNIT INSTALLATION IS LEVEL ( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS COMPRESSOR AMPS III. START-UP ELECTRICAL INDOOR (EVAPORATOR) TEMPERATURES FAN AMPS SUPPLY VOLTAGE OUTDOOR (CONDENSER) AIR TEMPERATURE_DB RETURN-AIR TEMPERATURE DB COOLING SUPPLY AIR GAS HEAT SUPPLY AIR PRESSURES DB GAS INLET PRESSURE WB WB IN. W.C. GAS MANIFOLD PRESSURE IN. W.C. REFRIGERANT SUCTIONPSIG, SUCTION LINE TEMP* REFRIGERANT DISCHARGE_PSIG, LIQUID TEMPT ( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS GAS HEAT TEMPERATURE RISE TEMPERATURE RISE (See Literature) RANGE MEASURED TEMPERATURE RISE * Measuredat suction inlet to compressor 1- Measuredat liquid line leaving condenser. 509 01 3402 01 3d
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 37 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Sun Oct 04 04:21:12 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools